REPORT
1.0 INTRODUCTION
The purpose of the report is to provide all the relevant information and engineering assumptions involved in
the Design of Franklin County Corrections Centre Structure by using RAM STRUCTURAL and RAM
CONCEPT.This report covers the detailed procedure of Franklin County Corrections Centre Structure
calculations.
Location of the Building
2551 FISHER ROAD, COLUMBUS, OH-43204

Elevation

Typical Plan
Client :PrimeAE Date : 11.22.2023
Project : FCCC Designed by :
Project No :01 Checked by :

Section View

Section View
Client :PrimeAE Date : 11.22.2023
Project : FCCC Designed by :
Project No :01 Checked by :

1.1 CODES, STANDARDS AND PROJECT SPECIFICATIONS


All the members have been designed in accordance with the relevant following Codes of Practice.
S.NO: DESCRIPTION CODE
1 Structural Steel AISC 360-10 - 14TH EDITION
2 Structural Concrete ACI 318-11
3 Design Loads ASCE 7- 16
4 Load Combinations ASCE 7- 16

Structural steel
S.NO: DESCRIPTION GRADE OF STEEL
1 Wide Flange,WT ,HSS,Rectangular and Square Shapes ASTM A992
2 Pipe Steel ASTM A53,GR.B
3 S shapes, channels, angles, & plates ASTM A36
4 High strength bolts ASTM A325
5 Anchor Bolts ASTM F1554

Masonry
S.NO: DESCRIPTION SPECIFICATION
1 Hollow Concrete Masonry ASTM C90
2 Mortar ASTM C270

Concrete
S.NO: Description Compressive strength Units
1 Foundation Walls and pedastals 4000 psi Phase 2A structural
2 Columns and slabs 5000 psi drawing
3 Floor Slabs & Mat Foundations 4000 psi

2.0 STRUCTURAL DESIGN LOADS


THE STRUCTURE HAS BEEN DESIGNED FOR THE FOLLOWING LOADS:

2.1 DEAD LOADS:


S.NO: Description Unit Weight
1 Concrete (Normal Weight) 150 pcf
2 Metal Stud Wall 12 psf
3 CMU 6" (Full Grout) 62 psf
ASCE 7-16
4 CMU 8" (Full Grout) 83 psf
5 CMU 10" (Full Grout) 105 psf
6 CMU 12" (Full Grout) 127 psf

2.2 LIVE LOADS:


S.NO: Description Loads
1 Roof 20 psf
2 Cell Living space 40 psf
3 Corridors & walkways 100 psf
4 Sub-Dayrooms 50 psf Phase 2A structural
5 Penthouse 40 psf drawing & ASCE 7-16
6 Multipurpose 75 psf
7 Storage 150 psf
8 Day Rooms 100 psf
Client :PrimeAE Date : 11.22.2023
Project : FCCC Designed by :
Project No :01 Checked by :

2.3 WIND PARAMETERS:


S.NO: Description
1 Basic Wind Speed 120 mph
2 ASD wind speed 93 mph Phase 2A structural
3 Risk category III drawing & ASCE 7-16
4 Exposure C

2.4 SEISMIC PARAMETERS:


S.NO: Description
1 Importance Factor 1.25
2 Risk category III
3 Ss 0.121
4 S1 0.062
5 SDd 0.097
6 SD1 0.07
Phase 2A structural
7 Site class C
drawing & ASCE 7-16
8 Seismic Design Category B
Basic Seismic Force Ordinary Precast Shear
9
Resisting system walls
10 Cs 0.03
11 Respose reduction factor 4
12 Analysis Procedure EQLF

3.0 DESIGN SOFTWARE USED


1 RAM STRUCTURAL
2 RAM CONCEPT
3 Design Spreadsheets

4.0 ENGINEERING ASSUMPTIONS

4.1 Modeling of Precast Inslutated wall panel

1
While modelling the Precast shear walls in Ram structures, the length of the wall is considered as 16' as
two individual wallpanels of 8' will be connected through connections to act as a single wall of 16' length.

To capture the actual stiffness of the precast panels, only the thicknesses of the concrete portions of the
2
walls is modelled (5" + 3" = 8") neglecting the insulation portion.

3 To capture the actual stiffnesses of the concrete elements, all the elements are assumed to be cracked
under the application of loads and corresponding cracked stiffnesses are used in the design calculations.

4
The composite action between concrete and metal sheet is assmed to have achieved an efficiency of 75%.