GEA BOCK HG SEMI-HERMETIC COMPRESSORS · 25

OPERATING LIMITS

R513A Operating limits

tC (°C) HGX12P, HGX22e, HGX34e, HGX44e, HGX56e tC (°C) HGX66e, HGX88e

90 90
80 80
0K
70 70 <2
∆t 0h
∆t0h<20K
60 60
50 50
∆t0h≥20K ∆t0h≥20K
40 40
30 30
t0h+20 °C t0h+20 °C
20 20
10 10
–30 –20 –10 0 10 20 30 t0 (°C) –30 –20 –10 0 10 20 30 t0 (°C)

t0 Evaporating temperature (°C) Unlimited application range


tC Condensing temperature (°C) Motor version -S- (more powerful motor)
∆t0h Suction gas superheat (K) Supplementary cooling or reduced suction gas temperature
t0h Suction gas temperature (°C) Required minimum superheating ∆t0h=20K

Max. permissible operating pressure (LP/HP) 1): 19/28 bar


LP = low pressure, HP = high pressure
1)

NOTES
R513A Notes

Operating limits Performance data


Compressor operation is possible within the limits shown on the The performance data for R513A are based on European
application diagrams. Please note the colored areas. Compressor Standard EN 12900 with a 50 Hz power supply frequency.
application limits should not be chosen for design purposes or This signifies: 20 °C suction gas temperature without liquid subcooling.
continuous operation.
This results in significant differences compared to specifications with
Restrictions to operating limits may occur when using a frequency liquid undercooling and/or suction-gas temperatures.
converter. A comprehensive modification to 20 °C suction gas temperature will
For further explanations consult www.gea.com. follow at a later date.

Conversion factor for 60 Hz = 1.2


Performance data for other operating points, see GEA VAP software
(vap.gea.com).