You are on page 1of 1

Hinge

85

85
85
-H1 -H2 -H3

-H4

-PM
380 V
Swing
Handle
Key
-S1

Live Busbar Behind

Back Cover

800 800 800 800


800 800

FRONT VIEW REAR VIEW REAR VIEW


W/O COVER
Swing Out

Mounting Plate

85
85

35
LIST MATERIAL (LV MDB-102) :

55
-Q1 = ACB 3P 3200A NW32H1
-Q2- Q4 = MCCB 3P 630A NSX630N C63N42D630
-QC = MCB 2P 2A IC60N A9F74202
-QC = MCB 1P 2A IC60N A9F74102
-PM = POWER METER PM5330 METSEPM5330
-H1 = PILOT LAMP (Red) XB5AVM4 230/240V AC/DC - PHASE R
800

-H2 = PILOT LAMP (Orange) XB5AVM5 230/240V AC/DC - PHASE S


-H3 = PILOT LAMP (Green) XB5AVM3 230/240V AC/DC - PHASE T
-H4 = PILOT LAMP (White) XB5AVM1 230/240V AC/DC - FAN ON
-S1 = EMERGENCY PUSH BUTTON XB5AS8442
-F1-X = HOLDER & CYLINDRICAL FUSE 2A
-V10 = THERMOSTAT TYPE. KTO - 10A (1NC) KTS 011-F
1090

-FAN = FAN 10" (2 Unit) & FILTER (4 Unit)


-H100 = TL LAMP 10W 220VAC
1600 -X3 = TERMINAL BLOCK CONTROL
TOP VIEW

Plate Alluminium 4mm


Fixing from Inside

NOTE :
Earthing bar Panel Size = H1200xW1600xD800mm
Protection Category = IP55
100 55

Material Panel = Aluminium


Plate Type = Aluminium
Quantity = 1
800

750

1600 750
FRONT VIEW
800
W/O DOOR
SECTION VIEW

FOR APROVAL
130 540 130 130 540 130 PT. LINTECH DUTA PRATAMA
800 800

BOTTOM VIEW CLIENT :


PT.FREEPORT INDONESIA
PROJECT :
COAL FIRED POWER PLANT REPLACEMENT
& LNG SUPPLY PROJECT LNGPP EARLY WORK
DRAWING TITLE :
MDB-100

SCALE : 1:20 DATE DRAWING NO. REV.


DESIGNED :
A
DRAWING BY : ANA 12-12-2023
CHECKED BY : - -
-
APP. BY : ISO-A

You might also like