Professional Documents
Culture Documents
1
Current Transformers .
2
Current Transformers contd.
• The wound primary is used for smaller currents, but it can only be applied on
low fault level installations due to thermal limitation
• For currents greater than 100 A, the bar primary type ( is used.
3
CT Terminologies
CT Errors
The primary current contains two components:
• An exciting current, which magnetizes the core and supplies the eddy current
and hysteresis losses, etc.
The exciting current is not being transformed and is therefore the cause of
transformer errors
4
CT Terminologies contd.
CT Burden
• The burden of a CT is the maximum load (in VA) that can be applied to the CT
secondary.
• The CT secondary load = Sum of the VA’s of all the loads (ammeter,
wattmeter, transducer etc.) connected in series to the CT secondary circuit +
the CT secondary circuit cable burden
• The CT secondary circuit load should not be more than the CT VA rating. If the
load is less than the CT burden, all meters connected to the measuring CT
should provide correct reading.
5
CT Protection
Since CTs normally have much more turns in secondary compared to
the primary, hence a high voltage on the secondary side
6
Voltage Transformers
There are basically, two types of voltage transformers used for protection
equipment
Electromagnetic type (commonly referred to as a VT)
Capacitor type (referred to as a CVT).
7
Voltage Transformers
The electromagnetic type is a step down transformer whose primary (HV) and
secondary (LV) windings are connected as below
8
Voltage Transformers Protection
Protection and earthing of PTs Voltage Transformers can be protected by HRC fuses on
the primary side for voltages up to 66kV.
Fuses do not usually have a sufficient interrupting capacity for use with higher voltages.
Practice varies, and in some cases protection on the primary is omitted
.
The secondary of a VT should always be protected by fuses or a miniature circuit
breaker (MCB). The device should be located as near to the transformer as possible.
A short circuit on the secondary circuit wiring will produce a current of many times the
rated output and cause excessive heating.
Even where primary fuses can be fitted, these will usually not clear a secondary side
short circuit because of the low value of primary current and the minimum practicable
fuse rating.
9
Relays
Relays are devices which monitor the conditions (such as voltage levels, current
levels and frequency) of a circuit and give instructions to open a circuit under
unhealthy conditions
They detect conditions such as short circuit or overloading ,then supplies signal to
circuit breakers for circuit interruption.
10
Classification According to Construction
According to construction they are classified as Electromechanical, Static and
Digital relays
Static or Solid State relay uses electronic circuit to open and close relay contact
Digital or Microprocessor based relay uses digital signals to open and close
contact
11
Classification according to Time Characteristics
According to time characteristics they are classified as instantaneous , inverse
time, Definite time lag,
Definite Minimum time lag/Time delay; It operates after certain time regardless of
the value of the current
The mechanical force is generated through current flow in one or more windings
on a magnetic core or cores, hence the term electromechanical relay
13
Electromechanical Relays
However, only attracted armature types have significant application at this time, all other types
having been superseded by more modern equivalents.
These generally consist of an iron-cored electromagnet that attracts a hinged armature when
energised.
A restoring force is provided by means of a spring or gravity so that the armature will return to its
original position when the electromagnet is de-energised
14
Relays
Static Relays
In a protection relay, the term ‘static’ refers to the absence of moving parts to create the relay
characteristic.
Their design is based on the use of analogue electronic devices instead of coils and magnets to
create the relay characteristic.
Compared to static relays, digital relays introduce A/D conversion of all measured analogue
quantities and use a microprocessor to implement the protection algorithm
15
Numerical relays
The distinction between digital and numerical relay rests on points of fine technical detail,
and is rarely found in areas other than Protection.
16
Overcurrent protection Scheme
Overcurrent protection is based on a very simple premise that in most instances of a fault, the
level of fault current dramatically increases from the pre-fault value
Overcurrent protection is that protection in which the relay picks up when the magnitude of the
current exceeds the pickup value
If on establishes a threshold well above the nominal load current, as soon as the current exceeds
the threshold, it may be assumed that a fault has occurred and a trip signal may be issued.
it is in wide use for protection of radial low-voltage distribution lines, ground protection of high-
voltage transmission lines, and protection of machines (motors and generators)
17
Overcurrent/Overload protection
Overcurrent protection , include short circuit protection and overload protection
Short circuits could be due to phase faults, earth faults, or winding faults
Short-circuit currents are generally several times (5-20) full load current
19
Relay coordination
. The basic rules for correct relay co-ordination can generally be stated as
follows:
• whenever possible, use relays with the same operating characteristic in series
with each other
• make sure that the relay farthest from the source has current settings equal to
or less than the relays behind it, that is, that the primary current required to
operate the relay in front is always equal to or less than the primary current
required to operate the relay behind it.
20
Directional Relay
Directional relay or protection are relay that will only trip in the direction of power
flow.
21
Distance Relay
Distance relay or protection are those in which the operation is governed by the
ratio of applied voltage to the current
Distance relays has the ability to detect fault within a pre-set distance along the
transmission line from its location
Distance relay therefore looks at the current and voltage and compares these
two on the basis of ohms law
Hence distance relay is designed to operate only for faults occurring between
the relay location and the selected reach point, thus giving discrimination for
faults that may occur in different line sections
22
Distance Relay
Operating principle
The basic principle of distance protection involves the division of the voltage at
the relaying point by the measured current.
In normal operating condition the restoring torque is greater than the deflecting
torque.
However under fault condition the deflecting torque becomes greater than the
restoring torque due to high current during fault condition
23
Distance Relay
The apparent impedance so calculated is compared with the reach point
impedance.
If the measured impedance is less than the reach point impedance, it is assumed
that a fault exists on the line between the relay and the reach point
Distant relays are widely used for the protection of transmission line by measuring
the impedance between the fault location and the relays
They provide primary and backup protection for transmission and distribution
lines against 3phase, phase to phase faults
24
Differential Relay
Differential relays is one that operates when a phasor
difference(magnitude, angle) of two or more similar electrical
quantities(current ,voltage )exceeds a pre-determined value
This type of protection can be divided into two types, namely: balanced current
and balanced voltage differential relays
Under normal operating conditions the two currents are equal hence no current
flow through the relays
25
Differential Relay
Under fault conditions the excess current flows through the relay hence causes
the relay to trip the circuit breaker
The balanced or circulating current systems are invariably used for generator,
transformer and switchgear main protection where it is convenient to readily
access the midpoint of the pilots
The balanced voltage systems are used mainly on feeder protection where the
CTs are mounted in different substations, which are some distance apart
26
Signalling
Protection schemes formed by a number of relays located remotely from each
other, and some distance protection schemes ; require some form of
communication between each location in order to achieve a unit protection
function.
27
Signalling
• Various types of communication links are available for protection
signalling, for example.
• private pilot wires installed by the power authority
• pilot wires or channels rented from a communications company
• carrier channels at high frequencies over the power lines
• radio channels at very high or ultra high frequencies
• optical fibres
28
Signalling
• Pilot wires are continuous copper connections between signalling stations,
while pilot channels are discontinuous pilot wires with isolation transformers or
repeaters along the route between signalling stations
29
Signalling
Whether or not a particular link is used depends on factors such as:
30
Autoreclosers
Faults on overhead lines can be categorized into transient (or temporary) faults and permanent
faults
80-90% of faults on any overhead line network are transient in nature. The remaining 10%-20% of
faults are either semi-permanent or permanent.
Use of an auto-reclose scheme to re-energise the line after a fault trip permits successful re-
energisation of the line.
Sufficient time must be allowed after tripping for the fault arc to de-energise prior to reclosing
otherwise the arc will re-strike
As 80% of overhead line faults are transient, elimination of loss of supply from this cause by the
introduction of auto-reclosing gives obvious benefits through:
• improved supply continuity
• reduction of substation visits
Sample Question
1. Mention five advantages that numerical relays have over electromechanical ones
2. Mention five links available for communication in power systems.
3. What factors influence the choice of a communication link?
4. Apart from one-line diagram of system and impedances of system components, what other
data is required for the proper setting of overcurrent relays.
5. Mention three ways of achieving discrimination in overcurrent relays.
Equipment Protection
The primary function of power system protection is to limit damage to power system apparatus
Whether the fault or abnormal condition exposes the equipment to excessive voltages or
excessive currents, shorter fault times will limit the amount of stress or damage that occurs
Lightning impose higher voltages on transmission lines which can lead to flashover or puncture of
insulators
Earth (sky) wires are provided on transmission lines to intercept direct strokes of lightning and thus
keep them off the phase conductors thereby reducing the surge current and hence the
overvoltage on the phase conductors
Transmission line protection
Protection of transmission line insulators from damage due to flashovers
Overvoltages on transmission lines, due to lightning strikes, or electrical faults, can cause arcs
across insulators (flashovers) that can damage them.
Arcing horns (arc-horns) which are projecting conductors are used to protect insulators on high
voltage electric power transmission systems from damage during flashover.
Horns are normally paired on either side of the insulator, one connected to the high voltage part
and the other to ground.
They encourage the flashover to occur between themselves rather than across the surface of the
insulator they protect
Busbar protection
Busbars are the nerve-centres of power systems; various circuits are connected together at the
busbars.
A fault on a busbar though rare (because of their location), causes enormous damage
When protective relays operate to isolate a busbar from a system, there is a large disruption in
supply.
However, with increasing system voltage and short-circuit capacities, it is no longer advisable to
leave busbars without primary protection.
A number of busbar protection systems have been devised
• system protection used to cover busbars
• frame-earth protection
• differential protection
Generator protection
Several faults occur in generators. These include:
• Stator insulation failure
• Overload
• Overvoltage
• Unbalanced load
• Rotor faults
• Loss of excitation
• Loss of synchronism
Generator protection
Stator protection
Stator faults result from insulation breakdown that causes an arc to develop, either from phase to
phase or from the phase conductor to the grounded magnetic steel laminations of the stator.
The cause of the insulation breakdown may be due to overvoltage, overheating, or mechanical
damage of the winding insulation due to faults.
The overvoltage that may cause an insulation failure might be due to lightning or switching
surges, which are usually protected against by surge protective devices.
There are many different types of stator protection. Phase fault and ground fault protections
schemes have been explained below.
The standard method of protection against phase faults is the differential method, and usually the
percentage differential type of relay is used
Generator protection
Rotor Protection
The rotor has a DC supply fed onto its winding which sets up a standing flux.
When this flux is rotated by the prime mover, it cuts the stator winding to induce current and
voltage therein.
This DC supply from the exciter need not be earthed. If an earth fault occurs, no fault current will
flow and the machine can continue to run indefinitely, however, one would be unaware of this
condition
There are several methods of detecting a rotor circuit ground. The three most common ones are:
(i) Potentiometer method,
(ii) AC injection method and
(ii) DC injection method.
Generator protection
Other protection
Overload protection
Overcurrent protection
Overvoltage protection
Transformer protection
Types of transformer faults The following are the types of faults that can occur in a power
transformer:
Differential protection schemes are used to protect transformers against internal fault.
Differential protection, as its name implies, compares currents entering and leaving the protected
zone and operates when the differential current between these currents exceeds a pre-
determined level
Buchholz protection
The Buchholz relay can detect both gas and oil surges as it is mounted in the pipe to the
conservator.
Transformer protection
Restricted earth fault protection
A simple overcurrent and earth fault relay will not provide adequate protection for winding earth
faults. In these circumstances, it is often necessary to add some form of separate earth fault
protection.
The degree of earth fault protection is very much improved by the application of unit differential
or restricted earth fault systems
For example, the starting and stalling currents/times must be known when applying overload
protection, and furthermore the thermal withstand of the machine under balanced and
unbalanced loading must be clearly defined.
The conditions for which motor protection is required can be divided into two broad categories:
imposed external conditions and internal faults
Overcurrent protection is required to protect personnel, the motor branch circuit conductors,
control equipment, and motor from these high currents
One of the most important relays for the detection of abnormal conditions is the overload relay
which is applied to the protection of motors. Overload is a condition caused by an increase in
the mechanical load to the motor
Motor protection
Protection schemes for motors
The overload relay differs from the overcurrent relay in the following ways. Whereas overcurrent
relay must operate quickly in times of around or less than 1s, the overload relay is associated with
times of tens of seconds to several minutes.
However, the overload relay must be capable of measuring accurately current which is only
slightly greater than the nominal full-load current, compared to the overcurrent relay, which
under fault conditions is required to detect a current which is many times the normal current.
Other protection
Differential protection
Building protection
Two protection systems are used to eliminate or limit overvoltages due to lightning:
They are known as the building protection system (for the outside of buildings) and the electrical
installation protection system (for the inside of buildings).
Building protection system The role of the building protection system is to protect it against direct
lightning strokes. The system consists of:
• the capture device(arrester);
• down-conductors designed to convey the lightning current to earth;
• earth leads (earth electrodes);
• links between all metallic frames (equipotential bonding) and earth leads
Building protection
There are three types of building protection systems:
The simple lightning rod
The lightning rod is a metallic capture tip placed at the top of the building. It is earthed by one or
more conductors (often copper strips)
Each circuit is protected by an overcurrent protection device which is either a fuse or a circuit
breaker
A special type of circuit breaker known as earth leakage circuit breaker (ELCB) which has an
inbuilt relay is employed to detect current leaking to earth from an installation and cut of power.
An ELCB may be voltage operated or current operated.