Professional Documents
Culture Documents
CONTENTS
3
SPECIFICATION
1 Technical Specifications
1.1 SCOPE
Location Indoor
Cell life cycle 5000 cycles at rated capacity at 80% Depth of Discharge (DoD) at
25°C
4
SPECIFICATION
Rated Grid 50 Hz
Frequency
Operating 47 to 52 Hz
Frequency
When the distribution system frequency deviates outside the
Range
specified limits (52 Hz on higher side and 47 Hz on lower side) up to
0.2 sec, the system shall automatically disconnect from the grid.
Harmonics Individual harmonic voltage distortion limits for odd harmonics shall
not exceed 2% and in the case of even harmonics shall not exceed
1%; Total Harmonic Voltage Distortion shall not exceed 3% at the
point of connection (POC) as specified in IEEE 519.
DC Injection The system shall not inject DC current greater than 0.5% of full rated
and Ripple output at the interconnection point or 1% rated inverter output
current into the grid under any operating conditions.
DC voltage ripple content shall be not more than 1%
Flicker Operation of BESS should not cause voltage flicker in excess of the
limits stated in IEC 61000
Power factor The system shall be able to operate in a range 0 - 1.0 leading or
lagging power factor. The system shall be capable of supplying
reactive power as per grid requirement (automatically or manual
intervention through EMS/ remote control) during normal operation
Protection DC isolator2
AC isolator3
..............................
1 3-phase 400 V AC voltage shall also be the input voltage for the charging
2 DC isolator should be easily accessible and allow disconnection of the entire battery storage system
3 AC isolator must be provided to isolate the entire system from grid through MCCB located in a separate
standalone panel
5
SPECIFICATION
Islanding and In the event of loss of supply from the grid, the system must be
Disconnection disconnected within 2 seconds according to IEC 61727
Overload and The system should have the facility to automatically switch off in
Overheat case of overload or overheat and should automatically restart when
normal conditions are restored
6
SPECIFICATION
The EMS/BESS control system shall support at least the above BESS
operations. The operation modes can be selected from the control
panel/ remote command from the utility
7
SPECIFICATION
Ingress IP 54 (minimum)
Protection
Dimension Max. 4m x 2m x 3m
(Width x Depth
x Hight)
The battery module/cell shall conform to all applicable IEC or equivalent standards. As a
minimum requirement, the following standards as applicable shall be complied with:
IEC-61427 Secondary cells and batteries for renewable energy storage for on-grid
applications. Non-chemistry specific (applicable to all secondarybattery
types)
IEC 62619 Safety requirements for secondary lithium cells and batteries, for use
in industrial applications
IEC 62281 Safety of primary and secondary lithium cells and batteries during
transport: Applicable for storage systems using Lithium Ion chemistries
A) The battery storage system may consist of one or more battery packs to meet the
application requirement. Battery packs shall be electrically interconnected in any
desirable series and parallel configuration to achieve the overall system storage and
power rating requirements.
B) The modular configuration shall have provision for connecting additional battery
modules in the future.
..............................
4 The manufacturer shall provide Windows-based software for reading and downloading the battery data of
8
SPECIFICATION
C) If required, the modular design should have more than one battery rack to distribute
the weight of the battery on the floor.
F) Cells/modules, wiring, switch gear, and all DC electrical components shall be insulated
for the maximum expected voltages with adequate safety margin.
G) All DC cables and busbars within the storage system or connection to the inverters
should have a current rating of 1.5 times the short circuit rating of the respective
connection.
A) The BMS shall be integrated with BESS to provide for automatic, unattended
operation of the battery storage system.
• Charge control: - BMS shall automatically control the charge and discharge of the
individual cell/module.
C) History - (Log Book Function):- Monitoring and storing the battery's parameters and
communicating the same to the energy management system(EMS)/ inverter. The past
9
SPECIFICATION
D) Alarm and fault generation in the event of undesirable battery operation and
communicating the same to EMS/ Inverter. The information shall be displayed on the
display as an alarm
The inverter is the interface between the DC battery system and the AC system, which
also provides charging and discharging of the battery. It may consist of one or more
parallel units. The inverter shall be bi-directional inverters with four quadrant operations.
The inverter shall be capable of adjusting the output voltage and frequency to suit the
grid condition.
The inverter shall conform to all applicable IEC or equivalent standards. As a minimum
requirement, the following standards as applicable shall be complied with:
IEC-61683 Efficiency Measurements
IEC 61000 Emission/ Immunity requirement Harmonics
IEC 60068 / Environmental Testing
IEC 62093
IEC 62116/ Protection against Islanding of Grid
IEEE 1547
IEC 62109 Safety of power converters for use in powersystems
IEEE 1547 Standard for interconnecting distributedresources with electrical
power systems.
A) The inverter, in conjunction with the control system, shall be capable of completely
automatic, unattended operation, including self-protection, synchronizing and
paralleling with the utility, and disconnecting.
B) Each inverter should have the AC and DC isolator to disconnect the respective battery
module and inverter for maintenance purposes
D) The inverter shall have anti-islanding protection as per IEC 62116 or equivalent
international standard.
10
SPECIFICATION
F) The incoming DC feeder of the inverter shall have a suitably rated fuse.
G) The system shall have the provision of connecting an additional inverter with battery
for future expansion
H) Internal Surge Protection Device (SPD) shall be provided in the inverter on DC and AC
side. It shall consist of Metal Oxide Varister (MOV) type arrestors. The Surge
Protective Device shall be of Type 2 as per IEC 61643-11 or better. During earth fault
and failure of MOV, the SPD shall safely disconnect the healthy system.
The Energy Management System (EMS) system should have the functionality for real time
monitoring, operation, control, and optimization of the performance of the BESS system.
The EMS shall have the following functions,
A) Real-time acquisition and display of data, status, alarms and trends on the control
panel display as mentioned in section 1.2.
B) Display BESS system data suitable for operation and fault finding, including
diagnostics and self-check functions.
C) Allow local control of the BESS, such as providing charge and discharge set points and
setting of ramp rates as per selected BESS operation mode.
E) It shall control all the inverters automatically to achieve the desired BESS operation
and EMS shall ensure operating inverters to achieve maximum efficiency in the
operating mode.
F) It shall support following standard protocols (included but not limited to) to
communicate with different sub system/Devices.
• Sunspec protocol for remote monitoring and controlling as per IEEE 1547.
11
SPECIFICATION
H) It shall provide nonvolatile storage memory to store BESS parameters for at least 3
months and the data can be downloaded locally by connecting Windows-based
computer.
I) It shall support input commands from control panel push buttons with the security of
authorized access.
J) It shall have spare ports for monitoring and controlling additional inverters and
battery storage for future expansion.
12
SPECIFICATION
The manufacturer shall submit all the type test reports by the laboratories which are
accredited by NABCB of the same product and component used in the BESS system as per
the following IEC standards
Battery
IEC-61427
Secondary cells and batteries for renewable energy storage for on-grid applications.
Non-chemistry specific (applicable to all secondarybattery types)
The rated capacity test and the charge retention test IEC 61427-1, 9.1
The cycling endurance test in photovoltaic application (extreme IEC 61427-1, 9.1
conditions).
IEC 62619
Safety requirements for secondary lithium cells and batteries, for use in industrial
applications
Safety of power converters for use in battery energy storage IEC 62109
13