IE - 3 HiAN Trouble-Shooting For Non-Closing-003
IE - 3 HiAN Trouble-Shooting For Non-Closing-003
2. Cause
2.1 HANDLE SHUTTER is open
2.2 UVT coil has malfunction electrically or mechanically.
2.3 Malfunction of mechanim
ACB does not work mechanically when the trip button of body is pushed.
If the UVT COIL is drop down, check the output voltage of UVT controller (C1,
C2).
1) about DC19V : change UVT coil as new one.
2) about “zero” : change UVT controller as new one.
Lock UVT Coil to energized position by rotating Lock Lever clockwise after lift up the
Actuator Pin in order to close ACB temporary.
OCR
5) Check whether Closing Latch could be moved well when Close Button is pushed.
If not, check whether harden grease make this unsmothness or not.
Closing rod
Closing button
Open button
Closing rod
Close lever/B
6) Check whether the relevant connected levers could be moved well when Open
Button is pushed
7) If the Closing Latch and relevant closing parts are not moved after 5~6 trials,
clean the harden grease and spray the lubricant, such as WD-40, in order to
clean the harden grease and make smoothness.
Zone to
spray
lubricant
If main spring is charged successfully, the half circuit shape parts, Latch unit cam,
will move arrow direction.
But when grease is to be hard, these did not move fully.
Latch
unit cam
Zone to
spray
lubricant