Professional Documents
Culture Documents
Name of Work: Testing of existing earthing and providing lightening protection system, maintenance free chemical-earthing and aviation light for 4G Towers
Name of the
Bidder/ Bidding
Firm / Company
:
PRICE SCHEDULE
(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable
enter the Bidder Name and Values only )
1 2 3 4 5 6 13
1 TESTING OF EXISTING OLD EARTHING FOR TELECOM
TOWERS: Testing of existing earthing with digital earth-
meggar kit and submitting the report to the engineer-in-
charge. Value of earth-resitance as tested individually for
each earthing as well as the combined value after
interconnecting earthing through GI earth strip must be
less than 1 ohm. Watering the existing earthing (i/c
addition of salt, if required) also to be done by the firm for
achieving desired earth results wherever existing earthing
found dry. (Note: One job implies one earth-pit,
irrespective of the number of earth-pits at one site.
However, the item shall be measured and paid only in case
existing earthing results are satisfactory and existing old
earthing need not to be replaced with new earthing)
Item
8.01 a) 3x1.5 Sq mm 8.01 600 Mtr 10.00
9 Supplying and fixing following way, single pole and neutral,
sheet steel, MCB distribution board, 240 V, on surface/
recess, complete with tinned copper bus bar, neutral bus
bar, earth bar, din bar, interconnections, powder painted
including earthing etc. as required. (But without
MCB/RCCB/Isolator)
Item
9.01 a) 6 way double door 9.01 12 job 10.00
10 S/F of 6A to 32A rating 240/415V ,10 KA,"C" curve MCB
suitable for inductive load of following poles in the
existing MCB DB complete with connections testing and
commissioning etc.as reqd