RD
SITE
PLU
DESIGN PWWF TO PUMPING STATION: 22.46 L/s 66.29 L/s
NOW
PEA
APP
LE
M
PUMPING FLOW RATE(S): 30 L/s 88 L/s
RD
P
R ST
LE S
AM Y TR
D
T
STORAGE TIME IN SEWERAGE SYSTEM AT REN
X
E NL ADWF BETWEEN "DUTY START" AND BAT CK CUR
W
T "STOP" AND "DUTY START" 15840 L
E
EE
PE
WHEN RD
T R
FU
TOTAL STORAGE VOLUME TUR
T
3 3
AR
W
S 256.3m 312.8m
E
TLE
G CK
TU
W
FI - SYSTEM STORAGE VOLUME
NIL 403.1m3
TW
RE
W
- STORAGE TANK VOLUME
E
BM PSM RL W
ST
T W
LOCALITY PLAN
E
64.039 AHD
AG
W
T W
SCALE 1:2500 MAP GRID NO. J10
E
DETAIL PLAN NUMBER
75
0 FUTURE STAGE
E T
1. (OR DRAWING NUMBER)
E T
W
S S S S S S S S S S S S
SW SW SW SW SW SW SW SW SW SW SW SW SW
S
E
65.000 X 61.100 X 56.700 X
1 X 55.100 X 56.600 2 FSL 58.700
W
S
14 14 OB IL 57.700
4
ET
EXISTING 13
62
W
DWELLING 1 13
2
S
15 16
E
3 ET 14
W E
W
ET 00
T
S
4 .6
00 0
E
W 0
1.0 59
SW
ET
.4
8 59 SL
W
W
15.86
T
E F
S
T S L
FS X
SW
X 58.550
W SW S
1.00
X
0
E E T
17
20
SW S
W
W
T
40
1.
SW
E T
2
0
.5 S IL 59.630
ST
35
AD
E W 3
S
E T 00 E
5.9
RO
W S
W
T
13.
13
X 5
T
REW
W 6
E
00
S
5.9
S
1.7
W 1.000
069
20
X 5
ET
S
1.750
29.163 19
W
T
E
S S
50
S
4.00
E
X 58.900
1.7
E
S
W T
S
2 18 HB1
SW
E
FUTURE STAGE
S
E
50
1 5 41.531 S
W
0
4
W
E TS
75
1 ST
ET
S
1 40 W W E
.06 TE TE S TE S E
0
39.6 1
E
1.
S
S
X S S
1.00
T
25 W W W W HB3
W
0 ST W
E
SW
.80
S
1.0
56 HB2 5 S
65 ST W 5
70
2 E SW
W
S
E
00
SW 5 S
ST W
WT S
W
1.75
E
ET
E 10 13
PLU
E W
SW
S
S
T
S HB4
1 ROAD 3
SW
SW
E
W
SW
28.6S55
0
S 5 2
58
SW
M
T
SW 5
9
W
S
X
E
1A
SW
60
X
1.000
13
64.900
5
0
SW
21
64.60
S
W
S
ET
62
SW
8 5
64
1.000
S
W
E
X S
00 11
.0 RM
SW
63 X X 57.200
.80
0 X S S PARK
66
ET
W
61 300 1 54 58
68
55. X 13 RM
56
RO
30 0
55. SW
ET
W
AD
ET
SW
7 0
RM
W
75
1.
12
ET
W
7
SW
15 NOTES
ET
1. LEGEND - SEE DRAWING SEQ-GEN-1100-1
S
W
SW
E
SITE PLAN T
S
W
T
SCALE 1:500 E
6
S
15
S
EXISTING
°,
BE A
3m
D
PASCOE
30
ROAD
C
N
VA C
SO OC
SO
E
AI
R -SO
LV
M
S
C-
SI TO
O OC
G
TELECOMMUNICATIONS
SC , S
11 °, S
G O
U
,
N TI
°
6m 90
N 2.5
TI C
10 D
2
N
EX ON
BE
N
C
BE
BE
GAS MAIN
DN225 uPVC
SEWER RM
REINSTATE EXISTING
CONCRETE DRAIN AS
REQUIRED
Z
711
Z
711
PIPE DIA AND CLASS DN300 (MATERIAL OF CHOICE) - TRENCH TYPE 1 TRENCHLESS TECHNOLOGY DN300 (MATERIAL OF CHOICE) - TRENCH TYPE 1
DN300 DICL 10.82 11.21
PIPE GRADE (%) -0.40 -1.48 -0.58 0.27 1.07 5.55 16.15 5.94 2.03 -0.57
DATUM RL 1.000
3.118
3.117
2.602
1.68
1.71
1.15
0.94
1.25
1.32
1.32
1.40
1.20
1.34
2.66
2.20
1.47
1.04
0.94
1.00
0.97
0.94
0.97
1.01
0.99
DEPTH TO INVERT
3.839
3.833
3.816
3.408
3.362
3.333
3.312
3.022
3.012
2.990
3.153
3.702
3.739
4.225
4.817
5.694
6.307
6.633
7.110
8.125
8.196
8.165
7.932
7.912
INVERT LEVEL
5.516
5.543
4.970
4.344
4.613
4.649
4.633
4.418
4.211
4.325
5.755
6.820
6.856
6.886
7.013
7.168
7.349
7.568
250.000 8.113
300.000 9.091
303.479 9.131
308.989 9.135
350.000 8.943
353.558 8.902
EXISTING NATURAL
SURFACE LEVEL
100.000
101.728
105.656
199.150
204.641
210.109
215.539
221.005
226.495
33.287
41.319
46.304
50.000
163.96
196.60
0.000
1.500
5.790
CHAINAGE
LEGEND
GAS
VALVE
SCOUR
VALVE
NOTE:
AS PER SEQ SEWER CODE, LONGITUDINAL
SECTIONS SHALL BE PROVIDED AS DESIGN
DRAWINGS AND SUBMITTED AS "AS CONS"
MULTITRODE
ODOUR MANAGEMENT
SYSTEM IF REQUIRED BY MIN. DN
ODOUR IMPACT 100
ASSESSMENT REPORT CAMLOK
RISING MAIN
1
RFLX01 VLVE01
REFER TO
NOTE 7 1 2 NOTE 4
3
RFLX02 VLVE02
LS LS DRAIN
INLET 42 41
GRAVITY SEWER VALVES PRIMARY EMERGENCY
SEE NOTE 5 LEVEL PUMP VALVE PIT
TRANSMITTER STARTER
REFER TO PROBE
NOTE 1 REFER TO RETURN LINE
COLLECTION MANHOLE NOTE 6
PROPERTY BOUNDARY
BWL BOTTOM WATER LEVEL PAH PRESSURE ALARM HIGH
WATER METER AT
DN DIAMETER NOMINAL PAL PRESSURE ALARM LOW
FAH FLOW ALARM HIGH PE PRESSURE ELEMENT
FAL FLOW ALARM LOW PI PRESSURE INDICATOR
PUMP STATION CONTROL AND RTU TO QUEENSLAND URBAN FE FLOW ELEMENT PIC PRESSURE INDICATION & CONTROL
SPXXX SAMPLE ST UTILITIES CONTROL ROOM FIC FLOW INDICATION & CONTROL PT PRESSURE TRANSMITTER
FT FLOW TRANSMITTER RTU REMOTE TELEMETRY UNIT
LAH LEVEL ALARM HIGH SS SOFT STARTER
LAHH LEVEL ALARM HIGH HIGH TAH TEMPERATURE ALARM HIGH
LE LEVEL ELEMENT TS TEMPERATURE SWITCH
MCC PAH
01 LIC LEVEL INDICATION & CONTROL TWL TOP WATER LEVEL
SEE NOTE G3
01 PT
POINT 01
01
DN100 CAMLOK
LIC FAL
01 01
FIC
PE
SYMBOL LEGEND
DN40 X
01
01
DN32
LT LAH LAHH
01 02 03 LAH
SEE SEE 04 ZIC
PI
FT SLUICE VALVE
NOTE G2 NOTE G2 01 01
LE LS LS SS SS BALL VALVE
DN32
ZIC 01 02 03 01 02 LS
SEE NOTE G8
NON RETURN VALVE
DN15
03 04 D FE
ZS N
01 XX 01
X
SEE NOTE G7 DNXXX DNXXX SEWER RISING MAIN SOLENOID VALVE
TO DISCHARGE POINT
PI RPZ VALVE
WATER VACUUM BREAK VALVE
WELL
WASHER
HOSE COCK
DN15
SEE NOTE G7 DNXXX
WATER HAMMER ARRESTER
DN32
ZS
02
OVERFLOW LEVEL RLX.XXX PUMP
300
ZIC SEE
02 NOTE G3 REDUCER
100
CAMLOCK FITTING
LS BARREL UNION
05 VALVE PIT
SUMP PUMP P3
ELECTRONIC FUNCTION
SEE NOTE G4
SCOUR PI PORTABLE PRESSURE GAUGE
DNXXX
400
PUMP WELL
NOTES G7. FOR PUMPING STATIONS WITH GUIDE RAIL PUMPS AN AIR BLEED BALL VALVE
G1. THE DIAGRAM SHOWN ON THIS DRAWING IS INDICATIVE ONLY. THE DIAGRAM G3. THE POSITION SWITCHES SHOWN ON THIS DRAWING ARE TO BE INSTALLED AS AND PIPEWORK ARE REQUIRED UPSTREAM OF THE PUMP NON RETURN VALVE IN
REFLECTS AN INSTALLATION WITH TWO CHAIN SUSPENDED PUMPS. DIRECTED BY QUEENSLAND URBAN UTILITIES. THEY ARE GENERALLY NOT THE VALVE PIT.
THE PROJECT DRAWINGS MUST INCLUDE A DIAGRAM WHICH CONTAINS ALL INSTALLED ON PUMPS SMALLER THAN 30 kW. THE DISCHARGE FOR EACH OF THE AIR BLEEDS IS TO PASS INTO THE PUMP
INSTRUMENTATION AND PIPE DIAMETERS SPECIFIC TO THAT SITE. G4. THE SUMP PUMP IN THE VALVE PIT IS INDEPENDENT OF THE PUMP STATION WELL THROUGH THE WELL WALL. THE SMALL NON RETURN VALVE ON THE PUMP
THE FULL FUNCTIONALITY OF THE CONTROL SYSTEM IS NOT INDICATED ON THIS CONTROL AND IS SUPPLIED WITH AN INTERNAL LEVEL SWITCH. THIS LEVEL WELL DISCHARGE BEND AS SHOWN ON THIS DRAWING IS NOT REQUIRED FOR
DRAWING. TO ACHIEVE STANDARDISATION REFER TO QUEENSLAND URBAN SWITCH OPERATES OVER AN 80mm RANGE FROM TWL TO BWL. NOTE: FOR GUIDE RAIL PUMP INSTALLATIONS.
UTILITIES FOR THE DESIGN OF THE SWITCHBOARD, CONTROL SYSTEM AND RTU. SMALL STATIONS(<30L/S CAPACITY) REFER SEQ-SPS-1102-6. G8. THE POTABLE WATER WELL WASHER IS TO OPERATE ONCE A DAY FOR 10
THE FUNCTIONALITY MAY VARY AND IS PROJECT DEPENDENT. THIS G5. LEVELS SHOWN WITH AN * ARE TO BE SHOWN ON THE PROJECT DRAWING. MINUTES AND IS TO START WHEN THE FIRST PUMP STARTS AFTER MIDNIGHT.
FUNCTIONALITY IS TO BE APPROVED BY QUEENSLAND URBAN UTILITIES DURING G6. THIS DRAWING SHOWS PUMP MOTORS WITH THERMISTER MOTOR PROTECTION. FOR PUMPING STATIONS WITH VF DRIVES THAT OPERATE CONTINUOUSLY THE
THE PRELIMINARY DESIGN PHASE AND BEFORE FINAL DESIGNS ARE COMPLETED. THE PUMPS SELECTED FOR THE INDIVIDUAL PROJECT MAY INCLUDE OTHER WELL WASHER IS TO RUN FOR 10 MINUTES ONCE A DAY AND IS TO START WHEN
THE TWO PUMP INSTALLATION SHOWN HERE PROVIDES FOR ONE DUTY PUMP MOTOR PROTECTION FAULTS AND THESE ARE TO BE INCLUDED AS DIRECTED BY THE WELL LEVEL IS AT LOWEST LEVEL.
AND ONE EQUAL STANDBY PUMP. THESE PUMPS ARE TO ALTERNATE IN DUTY. QUEENSLAND URBAN UTILITIES.
G2. THIS DRAWING SHOWS MOTORS WITH SOFT STARTERS WHICH WILL NORMALLY
BE INSTALLED HOWEVER VARIABLE FREQUENCY DRIVES MAY BE INSTALLED IF
DIRECTED BY QUEENSLAND URBAN UTILITIES.
REV. No. DATE DESCRIPTION AUTH.
SEWAGE PUMP STATION STANDARD DRAWING CoGC LCC RCC QUU UW
SEQ WATER TYPICAL P & ID DIAGRAM
DRAWING No. VERSION
30.00
0.00
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150
FLOW - LITRES PER SECOND
FLOW DETAILS
FLOW RATE INTO VELOCITY IN NUMBER OF RISING MAIN PUMP CURVE
PUMPING STATION RISING MAIN PUMP STARTS DETENTION
L/S M/S PER HOUR TIME. MINUTES SYSTEM CURVE AT MWL (TOTAL MEAN HEAD) CURVE WITH
PWWF FRICTION FACTORS DERIVED AS PER CODE REQUIREMENTS
PDWF
ADWF SYSTEM CURVE AT OVERFLOW LEVEL WITH FRICTION
FACTORS DERIVED AS PER CODE REQUIREMENTS
IL
SWITCHBOARD IL SWITCHBOARD HIGH
DISCHARGE IL
RECEIVING POINT DISCHARGE RECEIVING
SEWER SEWER
VALVE CHAMBER VALVE CHAMBER d
d
NOTES
1."DUTY START LEVEL" ALSO KNOWN AS "CUT-IN" LEVEL AND
TWL.
PUMP
CASE 3 - UNDULATING RISING MAIN 2. "STOP LEVEL" ALSO KNOWN AS "CUT-OUT" LEVEL AND BWL.
* A HIGH INLET PIPE MAY BE REQUIRED ON SOME SITES
6000
PAID. THE APPLICATION SHALL BE IN THE NAME OF SEQ-SP. TO BE 125 THICK
- SITE ACCESS REQUIREMENTS SHALL ALLOW
9500 MIN.
REFER TO NOTE 3
FOR A 16.9m ARTICULATED VEHICLE ACCESS LANDSCAPING WITHIN
4000 SITE REFER NOTE 4
TO THE PUMP WELL. A TURNOUT AREA SHALL
R4 BE PROVIDED WHERE NECESSARY TO ENABLE
0
50
50 SAFE ACCESS TO AND FROM THE SITE. PROVIDE REDUCED
R4
0
PAVEMENT
PRESSURE ZONE
DEVICE. REFER
RES.
4000
MIN.
4000
3000
TO ROAD SEQ-SPS-1308-1
FALL
PROPERTY SERVICE
TYPICAL LAYOUT FOR PUMP
STATION SITES NOT ACCESSIBLE R.P. ALIGNMENT MIN
FROM ADJACENT ROADWAY WATER METER 4000
WATERMAIN
MGA CO-ORDINATES POWER SUPPLY
LANDSCAPING WITHIN
SITE REFER NOTE 4 CENTROID OF X (m) Y (m)
25 OR 40 O.D. MIN
R.11500 WET WELL TAKE UP EXISTING FOR ACCESS DRIVEWAY
PROPERTY DETAIL REFER NOTE 3
T.14000 RECEIVING MANHOLE KERB AND CHANNEL
SERVICE R7300
RISING MAIN VALVE
T.8000 TYPICAL LAYOUT FOR PUMP STATION SITES
SWITCHBOARD
ACCESSIBLE FROM ADJACENT ROADWAY
VARIES TO SUIT SITE
R.10000 (T.12500)
MIN R.13600 (T.1650)
SHOWN ON THE APPROVED DRAWINGS. RETIC = R, SWITCHBOARD PLINTH & THEN BATTER AT 1 IN 6
R.3750
BOARD
E TRUNK = T. (MAX.) TO NATURAL SURFACE.
F IL 0
O 0 2. THIS DRAWING SHALL BE READ IN CONJUNCTION 6. WHERE REQUIRED BY SEQ-SP PROVIDE A 1.8m
PR N 1 WITH SEQ-SP STANDARD DRAWINGS HIGH PERSON PROOF FENCE AND 4.0m WIDE
I RECEIVING MANHOLE FOR
1 3. DRIVEWAY ACCESS TO ALL PUMP AND LIFT STATIONS DOUBLE LEAF LOCKABLE GATE.
VALVE PUMP INCOMING SEWERS REFER NOTE 9. SHALL BE PROVIDED AS FOLLOWS: 7. DIMENSIONS ARE IN MILLIMETRES UNLESS
(T.2450)
SEWER
RISING MAIN (a) LONGITUDINAL GRADE SHALL BE MAXIMUM 10%. SHOWN OTHERWISE.
(b) LOCATED SO VEHICULAR TRAFFIC WILL NOT 8. ACCESS ROAD SHALL THE SAME FLOOD IMMUNTY
TRAVERSE THE COVERS. CRITERIA AS REQUIRED FOR CONNECTING ROADS.
(c) HEAVY VEHICLE ACCESS DRIVEWAYS SHALL BE 9. FOR GCCC SITES, FOR > 525 D SEWERS SHALL
REFER NOTE 3
(d) IN ACCORDANCE WITH ROAD SAFETY AUDIT PER DOWNSTREAM OUTLET. UNITYWATER HAVE
RELEVANT ROAD AUTHORITY. VALVE ON THE INLET TO WELL.
4. THE PUMP AND LIFT STATION SITE AREA SHALL BE A
INSTALL OVERFLOWS IN MINIMUM OF 250m² OR AS DIRECTED BY THE SEQ-SP.
ACCORDANCE WITH SEQ - THE SURROUNDS SHALL BE LANDSCAPED WITH
SEWERAGE CODE SHRUBS AND MULCH. INTERNAL LANDSCAPING -WEED
MAT AND MULCH.
/
/
/
100mm QDTMR TYPE 2.1 CONCRETE GARDEN
ELECTRICAL SUPPLY MAINS 1.8 m1.8 m
NOM 2m WIDE STRIP CBR 80 BASE EDGING
/
(UNDERGROUND) / LANDSCAPING TO S.P.
150mm QDTMR TYPE 2.3 CBR 1
/
2% REQUIREMENTS
ELECTRICAL CONDUIT DRAW PIT 3
/
FALL 45 SUB-BASE
3%
/
REFER IPWEAQ STD DWG G-0030
/
L RISING MAIN WEED BARK CHIP
FAL IMPORTED CBR 15 MATERIAL
/
/
100mm THICK CONCRETE SLAB E E E E E E VENT RETURN PIPELINE COMPACTED TO 90% BARRIER NOM 100 THICK
AR CH
POLE
/
WITH SL82 FABRIC
RM
MODIFIED RDD.(THICKNESS
INDICITIVE ONLY
BO IT
/
D
FLOW METER PIT SUBGRADE REMEDIATION SHALL BE COMPLETED IN
SW
E
/
REINFORCEMENT CAST ON A REFER SEQ-SPS-1300-4 TO SUIT SUBGRADE)
12 m
GENERATOR
AT MP
ACCORDANCE WITH SECTION 5 (SUBGRADE) OF QDTMR
N
/
RM
/
IO
OUTLINE
WATERPROOF MEMBRANE OVER
ST PU
RPZ DEVICE REFER PAVEMENT DESIGN MANUAL
50 NOM SAND BEDDING.
/
/
TYPICAL PAVEMENT AND EDGE PROFILE FOR AC PAVEMENT
RM
E
PROVIDE APPROPRIATE CJ'S TO /
W SEQ-SPS-1308-1
/
NOT TO SCALE
3.2 m
CONTROL CRACKING. E
3% GENERAL
1%
LL
W
/
/
FAL
RM
3m x 3m MIN AREA OF FA 1. DETAIL SHOWN IN THIS DRAWING IS TYPICAL ONLY. THE LOCATION OF ALL ITEMS WILL
E
W
S
/
R5
/
PAVEMENT WITH MAX 1% .0 BE AS SHOWN ON THE APPROVED DRAWINGS AND READ IN CONJUNCTION WITH SEQ
1.8 m1.8 m
FALL
RM
CROSS AND LONGITUDINAL FALL
2%
WATER SP SPECIFICATIONS FOR SEWAGE PUMPING STATIONS.
S
E
/
/
2. SECURITY FENCING INCLUDING 4M WIDE DOUBLE LEAF LOCKABLE GATE -REFER
W
S
45°
/
12 m
/
E
RM
PRODUCTS AND MATERIALS - LIST (CIVIL).
W ST
CONCRETE EDGE
SE NLE
ER
W
/
/
RESTRAINT ALL ROUND R5
S I
E
4. DRIVEWAY ACCESS TO ALL PUMP AND LIFT STATIONS SHALL BE IN ACCORDANCE WITH
RM
/
/
W
SERVICE
ROAD SAFETY AUDIT PER RELEVANT ROAD AUTHORITY.
S
E
/
5. ROADWAY DIMENSIONS ARE TO CATER FOR TURNING/MANOEVERING OF 8.8m SERVICE
RM
S
W
VEHICLE.
/
/
S
RM
/
W
/
WATER
E
S S S S S S S S S S S
C/W CONCRETE
S
S
OVERFLOW, REFER 1. ELECTRICAL SWITCHBOARD TO BE MINIMUM 1.5M FROM EDGE OF ANY OPENING.
PROPERTY BOUNDARY
/
MOWING STRIP
/
W
RM
E
/
EPA APPROVALS RE REQUIRED
PE
1. ODOUR CONTROL SHALL BE PROVIDED IN ACCORDANCE WITH THE ODOUR IMPACT
W
E
/
RM
/
S
ASSESSMENT REPORT.
PE80
/ / / / / / / / / LAND IN FAVOUR OF
OVERFLOW STORAGE (IF
/
E
LANDSCAPING
W
S
S.P.
RM
/
REQUIRED) IN ACCORDANCE
PN16
/
1. CONSTRUCT CONCRETE CAST IN SITU GARDEN EDGING AT THE BASE OF THE
E
W
S
PROPERTY BOUNDARY LANDSCAPED AREA. THE LINE AND LEVEL OF THE GARDEN EDGING SHALL BE
/
REQUIREMENTS REFER
RM
ESTABLISHED TO THE SATISFACTION OF THE SUPERINTENDENT.
E
DN32
/
S
W
SEQ-SPS-1402-1
/
2. SUPPLY AND PLACE WOODCHIP 100MM DEEP OVER AN APPROVED WEED INHIBITING
RM
/
ASPHALT PAVEMENT
E
MEDIUM. THE WHOLE AREA SHALL BE CLEARED OF WEEDS AND GRASS PRIOR TO
/
S
WATER SERVICE
W
/ / / / / / / / /
REFER TYPICAL PAVEMENT TO METER BY PLACING THE ABOVE MATERIALS.
E
3. SUPPLY, PLANT AND ESTABLISH TREES AND SHRUBS AS APPROVED. TOPSOIL STRIPPED
S
W W W W W W W W W W W W W W W W W W W W W W W W
SEWER RISING MAIN 4. AREA INSIDE FENCE TO BE FULLY LANDSCAPED WITH LOW MAINTENANCE PLANTS AND
S
RM RM RM RM
KERB AND CHANNEL NO GRASSED AREAS.
PAVEMENT
S
TYPICAL STREET TYPE A COMMERCIAL DRIVEWAY 1. PAVEMENT SHALL BE DRY AND THOROUGHLY BROOMED BEFORE SURFACING IS
S
/
/
/
/
/
/
/
/
/
EDUCT VENT SHAFT /
REDUCED
OR ODOUR CONTROL PRESSURE
/
/
ZONE DEVICE
/
/
/
FLOODLIGHT
/
/
W /
W
TO INCLUDE FLOWMETER WHERE REQUIRED
/
/
W
W
/
/
W
W
W /
W
T
W T T /
W
/
SECURITY FENCE ON BOUNDARY OF /
W
W
W
PROPERTY ACQUISITION
/
W
H
PP ER LE
W
RM
W TA W
S U AT B
/
RM
W
LY
POW
RM
EMERGENCY STORAGE (WHERE
/
INDUCT VENT
RM
REQUIRED BY SEQ-SP OR DESIGN)
RM
/
/
RM
/
/
/
VALVE CHAMBER
EL P
RM
M
/
/
PU
/
/
SWITCHBOARD
/
/
IN
/
CO /
MI
N
/
G
/
O LE NE
SE
EL
/
W
/
VALVE CHAMBER &
AB H LI
)
VE V
DN ER
TE
G T
/
/
13 LIN DN 150 SCOUR PIPING
SI
NE I E
50 E
LI 0 H INL
/
/
IT
RC LINE
P
SU
/
LL 30 00
/
D N3
/
/
(T
/
D
N
/
AI
/
FI
/
M
/
LE DN
NG
NG
/
/
RE TH A
SI
13
/
/
RI
QU S 50
IR R
/
/
ED EQU RC /
ST IRE
/
OR D P
AG TO
E P
VO ROV
INC
LU ID
ME E
OM
INLET MH TO ACCOMMODATE
ING
FLANGED HIGH LEVEL FILL LINE
SE
WE
NOTES:
RL
1. METHOD OF ODOUR MANAGEMENT AS PER ODOUR IMPACT DN300 LOW LEVEL
INE
ASSESSMENT REPORT. FILL/DRAIN
2. SCOPE OF STORAGE SHALL MEET REQUIREMENTS OF SEQ-SP.
3. PIPEWORK LAYOUT SHALL MEET SITE TOPOGRAPHY AND FLOWMETER
INSTALLATION - EACH PUMP STATION SITE SHALL BE CUSTOMISED TO SUIT. 1000 x 1000 BYPASS
PUMPING HATCH
SEQ-SPS.
E
E
E
W
W
W
\\\
\\\ T \\\
E W \\\
E W \\\
W
E
E W \\\ POTABLE WATER SERVICE FROM
E W \\\
WATER METER AT PROPERTY
/
E W \\\
E W \\\
PROPERTY BOUNDARIES TO BE E W
ALIGNMENT
E
E
W
W LP \\\
\\\
INDICATED ON PROJECT DRAWINGS.
/
E W \\\
2.0
E W \\\
THE SEWERAGE PUMPING STATION IS E W
E W
E W
TO BE LOCATED ON FREEHOLD MAINTENANCE FREE SURFACE
E
E W
E W
E
PROPERTY OWNED BY SEQ-SPS. THE E W TREATMENT
1.0
E W
E W
PROPERTY DESCRIPTIONS ARE TO BE E
E
W
W
2.0
E W
SHOWN ON THE PROJECT DRAWINGS. E W
E W
E COMBINATION EMERGENCY PUMP AND
W
LOT E
E
LOT
RP123 1 RP123 2 E
E PIG INSERTION POINT. NOTE: TO BE
456 45 6 E
/
VENT POLE NO. 2 FOR VENTILATION THE SAME DIAMETER AS THE RISING
W
E
OF EMERGENCY STORAGE CHAMBER. MAIN
1.0
VALVE PIT INTEGRAL WITH PUMP WELL.
W
LOT
RP123 3 FOR SMALL STATIONS (<30L/S
456
EMERGENCY STORAGE CHAMBER CAPACITY) REFER SEQ-SPS-1102-6.
E
VOLUME AND SHAPE TO SUIT PROJECT
W
PUMP WELL WITH VACTOR PIPE COUPLING
E
/
W
ACCESS MAINTENANCE HOLES ON ADJACENT TO ACCESS ROAD. NOTE: TOP
EMERGENCY STORAGE CHAMBER. THE SLAB LEVEL MUST BE 300mm ABOVE
/
E
NUMBER AND LOCATION TO SUIT ACCESS ROAD LEVEL
W
LOT
RP123 9
/
PROJECT 456
W
CREEK
/
S
MAGNETIC FLOWMETER AND PIT WHERE
CONCRETE BOX CULVERT OVERFLOW
W
E
S
S REQUIRED. NOTE: THE DIAMETER OF THE
S
S FLOWMETER TO BE THE SAME AS THE RISING
/
E
2.0 MAIN. NOTE: FLOWMETER PIT IS TO DRAIN TO
W
THE VALVE PIT. NOTE: FOR SMALL STATIONS
/
E
(<30L/S CAPACITY) REFER SEQ-SPS-1102-6.
1.0
LOT
W
DISCHARGE POINT MUST COMPLY RP123 4
45 6
WITH ALL LAWS AND REGULATIONS S
E
W
/
AND MUST BE ABOVE MAXIMUM HIGH BORE HOLE DETAILS AND LOCATIONS ARE
TIDE LEVEL AND ABOVE NORMAL TO BE SHOWN ON THE PROJECT DRAWINGS
S
/
S
S
S RISING MAIN ISOLATING VALVE TO BE
S
/
S
S
S S RISING MAIN SCOUR TO BE DOWNSTREAM OF
S
S S
S
S
S S FLOWMETER AND TO BE UTILISED DURING
S
OVERFLOW FLAP VALVE CHAMBER S
S
S
S
/ COMMISSIONING. MINIMUM DIAMETER TO
TYPE TO BE INDICATED ON PROJECT
/
/
/ BE DN100
/
/
DRAWINGS /
S
/ S
/ S
S
/
S
S
/
S GRIT COLLECTOR MAINTENANCE HOLE
S
/ / S
S
S
/
/
/ S WITH VACTOR COUPLING ADJACENT
PROJECT SPECIFIC LANDSCAPING 0
2.
/ /
/ TO ACCESS ROAD. NOTE: FOR SMALL
S
/
STATIONS (<30L/S CAPACITY) REFER
S
/
1. /
/
0 /
SEQ-SPS-1102-6.
S
LOT
RP123 8
/
S
456
STATION. TO BE DETAILED ON VENT POLE NO. 1 FOR VENTILATION
S
LOT
PROJECT DRAWINGS RP123 7 OF PUMP WELL AND GRIT COLLECTOR
S
45 6 LOT
RP123 6
/
LOT
S
RP123 5
PLAN
1.0
45 6
S
12500 MINIMUM
STORAGE SEE NOTE G2.
CHAMBER VENT VENT PIPES TO BE SET MINIMUM 100 ABOVE
POLE NO. 2 SEE 0BVERT OF OVERFLOW FLAP VALVE
NOTE G2.
A SURVEY MARK IS TO BE PLACED ON THE TOP
SURFACE OF THE PUMP STATION ADJACENT TO
WELL WASHER ARM LEVEL ELECTRODE BOX. THE LEVEL IN AHD TO 3 DECIMAL
PUMP PLACES IS TO BE ENGRAVED ON A BRASS PLAQUE
WELL AND FIXED TO THE TOP SLAB.THE LEVEL IS TO BE
ACCESS ROAD LEVEL RECORDED ON THE AS CONSTRUCTED DRAWINGS
1
GRIT 750 FOR CHAIN SUSPENDED PUMPS
EMERGENCY OVERFLOW COLLECTOR MINIMUM 100 SEE NOTE G3
DIVERSION STORAGE MH
CHAMBER FLAP VALVE
MH VENT GRADE 1 IN 50. TOP SLAB LEVEL
CHAMBER 9
300
FINISHED SURFACE LEVEL
Q100 FLOOD LEVEL
Q100 FLOOD LEVEL INVERT LEVEL RISING
MINIMUM
MIN.
100
VENT GRADE 1 IN 150 MAIN AT PIT WALL
VENT GRADE 1 IN 50. 10
40
GRADE 1 IN
100
INVERT OF VALVE PIT
OBVERT OF FLAP VALVE OBVERT OF FLAP VALVE 3
OVERFLOW LEVEL OVERFLOW LEVEL OVERFLOW LEVEL
12
100
MIN. 300
TO OUTLET. GRADE THE FLOORS SLOPING BOX
300
CULVERT OVERFLOW DISCHARGE PIPE TO A
TO THE CENTRAL COLLECTION CHANNEL AT
THE MINIMUM INVERT LEVEL QUEENSLAND URBAN UTILITIES GRADE 1 IN 40 PIPE
1 IN 40. FOR CHAMBERS CONSTRUCTED
OF THE INLET / OUTLET TO APPROVED DISCHARGE POINT AT 1 DIAMETER TO BE SAME
FROM PIPES THE INVERT OF PIPE IS TO
THE EMERGENCY STORAGE IN 100 MINIMUM GRADE AS THE INLET SEWER
GRADE AT 1 IN 50
CHAMBER IS TO BE LEVEL 0 OBVERT OF OVERFLOW TO BE
1 IN 5 HIGH LEVEL OVERFLOW. ONLY
WITH THE OBVERT OF THE GRADE LEVEL WITH OVERFLOW
100 MINIMUM
400
INCOMING SEWER IMMINENT ALARM IF REQUIRED BY QUEENSLAND
URBAN UTILITIES. SEE NOTE G6. HIGH LEVEL ALARM
PROVIDE VERTICAL BEND OR
INLET SEWER PIPE DEFLECTION ON INLET
OBVERT OF INLET PIPE INVERT LEVEL OF INLET AND OUTLET
SEWER EXTERNAL TO WALL
MIN.
500
900
TO ALLOW VALVE SPINDLE TO 1 IN DESIGNED TO SUIT 5 STARTS PER HOUR FOR
1T
100
DIAMETER OF INLET / OUTLET TO BE BE VERTICAL O SINGLE PUMP. THE MINIMUM DISTANCE IS TO
1 IN
EQUAL TO DIAMETER OF PUMP STATION 3 BE 600
INVERT LEVEL OF GRIT COLLECTOR BWL BOTTOM WATER LEVEL
INCOMING SEWER NOTE: THIS SEWER TO 11 AT VACTOR PIPE INLET PUMP WELL INLET 6
BE KEPT AS SHORT AS POSSIBLE SEWER SEE NOTE G4
GRADE FLOOR AT 1 IN 20 INVERT OF INLET SEWER AT PUMP WELL
TO VACTOR PIPE INLET
4
1200
INLET BEND TO BE ANGLED
VERTICALLY DOWNWARDS AT
22.5° AND ANGLED INVERT OF PUMP WELL
HORIZONTALLY AT 22.5° AT VACTOR PIPE INLET
ANTICLOCKWISE TO PROMOTE 7
CIRCULATION BOTTOM OF PUMP WELL
8
GRADE FLOOR AT 1 IN 20
PUMP STATION LEVEL INTERACTION DIAGRAM TO VACTOR PIPE INLET
NOT TO SCALE
(SEE NOTE G7)
12500 MINIMUM
THE LEVEL INTERACTION STORAGE
EMERGENCY STORAGE CHAMBER XX.X
DIAGRAM CHAMBER VENT VENT PIPES TO BE SET MINIMUM 100 ABOVE
RETICULATION SYSTEM XX.X POLE NO. 2 0BVERT OF OVERFLOW FLAP VALVE
TOTAL XXX.X
A SURVEY MARK IS TO BE PLACED ON THE TOP
PEAK DRY WEATHER FLOW = XX.X L/S TOTAL SURFACE OF THE PUMP STATION ADJACENT TO
WELL WASHER ARM LEVEL ELECTRODE BOX. THE LEVEL IN AHD TO 3 DECIMAL
PUMP PLACES IS TO BE ENGRAVED ON A BRASS PLAQUE
EMERGENCY STORAGE TIME AT WELL
PEAK DRY WEATHER FLOW = X HRS. X MIN. AND FIXED TO THE TOP SLAB.THE LEVEL IS TO BE
SEE NOTE G5. RECORDED ON THE AS CONSTRUCTED DRAWINGS
MIN.
100
VENT GRADE 1 IN 150 MAIN AT PIT WALL
10
40
GRADE 1 IN INVERT OF VALVE PIT
OBVERT OF FLAP VALVE OBVERT OF FLAP VALVE 3
OVERFLOW LEVEL OVERFLOW LEVEL OVERFLOW LEVEL
2
100
MIN. 300
TO OUTLET. GRADE THE FLOORS SLOPING BOX
300
CULVERT OVERFLOW DISCHARGE PIPE TO A
TO THE CENTRAL COLLECTION CHANNEL AT
THE MINIMUM INVERT LEVEL QUEENSLAND URBAN UTILITIES
1 IN 40. FOR CHAMBERS CONSTRUCTED
OF THE INLET / OUTLET TO APPROVED DISCHARGE POINT AT 1
FROM PIPES THE INVERT OF PIPE IS TO
THE EMERGENCY STORAGE IN 100 MINIMUM GRADE
GRADE AT 1 IN 50
CHAMBER IS TO BE LEVEL STAINLESS STEEL KNIFE GATE VALVE.
0
1 IN 5 REFER SEQ-SPS-1400-1,
WITH THE OBVERT OF THE GRADE
400
INCOMING SEWER SEQ-SPS-1401-2 FOR VALVE AND
SPINDLE DETAILS. NOTE: SPINDLE HIGH LEVEL ALARM
150 MIN
OMITTED FOR CLARITY.
INLET SEWER
MIN.
500
100
WALL PIPE TO BE HORIZONTAL MANUFACTURER
TO ALLOW VALVE SPINDLE TO
BE VERTICAL
INVERT OF PUMP WELL AT VACTOR
HDPE DROP PIPE WITH 22.5° BEND PIPE INLET -SEE NOTE 6.
AT OUTLET FACING 7
ANTI-CLOCKWISE TO PROMOTE BOTTOM OF PUMP WELL
CIRCULATION. 8
GRADE FLOOR AT 1 IN 20
ALTERNATIVE PUMP STATION LEVEL INTERACTION DIAGRAM TO VACTOR PIPE INLET
NOT TO SCALE
(SEE NOTES G1 AND G6 - G13)
150
PUMP MANUFACTURER'S 2. DIMENSIONS ARE IN MILLIMETRES UNLESS SHOWN
REQUIREMENTS OTHERWISE.
LL
FA SS 3. PUMP BASEPLATES AND GUIDE RAILS SHALL BE FIXED TO THE
300 0 O
5 CR OR 250 600 MIN
STILLING TUBE - POSITION TO BE FLOOR AND TOP OF SLAB WITH GRADE 316 STAINLESS STEEL
MIN A FLO MIN OR 2D
DETERMINED BY PROJECT DESIGN DROP FLUSH ANCHOR MASONRY FASTENERS IN ACCORDANCE
WITH THE MANUFACTURERS RECOMMENDATION.
4. PROVIDE STAINLESS STEEL DROP PIPE SUPPORT BRACKETS AT
2500 MAX. CENTRES FIXED TO WALL WITH GRADE 316 SS
MASONRY FASTENERS. REFER NOTE 6.
SEE NOTE 12 5. ALL INTERNAL VERTICAL, SOFFIT & COVER OPENING WET WELL
SEE NOTE 8
SURFACES SHALL HAVE AN APPROVED POLYETHYLENE LINER
A
* 1250
2550
(MIN 2.5mm THICK) MECHANICALLY BONDED TO WALL VIA
1300-2 SEE NOTE 10 ANCHORS CAST INTO CONCRETE IN ACCORDANCE WITH THE
MANUFACTURERS RECOMMENDATIONS. POLYETHYLENE LINING
SHALL BE AS PER SEQ-SP PRODUCTS AND MATERIALS LIST.
BENCHING SHALL NOT BE COATED.
'MCBERNS' WET WELL WASHER
6. ALL ENTRIES THROUGH THE CONCRETE STRUCTURE AND ALL
OR APPROVED SIMILAR. SEE NOTE 9
FITMENT HOLES THROUGH THE POLYETHYLENE LINER SHALL BE
LADDER WITH EXTENDABLE SEALED WITH AN APPROVED SEALANT IN ACCORDANCE WITH
HANDGRIP STANCHIONS IN 50 DWGS SEQ-SPS-1407-1 AND SEQ-SPS-1407-2.
ACCORDANCE WITH AS 1657. AC FAL
L 7. FALL ARREST FLUSH MOUNT ANCHORAGE POINT. REFER SEQ-SP
SEE NOTE 10
150x75 FL ROS
SUPPORT BEAM OO S PRODUCTS AND MATERIALS LIST.
R
8. MINIMUM CIRCULATION CLEARANCES TO RUNG TYPE LADDER
Ø100 uPVC AIR VENT PIPEWORK
AS PER AS1657 CLAUSE 5.1.
9. GCCC/RCC/LCCC- NO WELL WASHER UNLESS SPECIFICALLY
RISING MAIN RETURN PIPEWORK 1425 DN80 - 1950 DN100 - 2050 225
REQUESTED
DN150 - 2200 DN200 - 2500
TYPICAL PLAN (WITH ROOF REMOVED) 10. GCCC/RCCC/LCCC- NO LADDER UNLESS SPECIFICALLY
RISING MAIN RETURN REQUESTED.
ENTRY PROHIBITED PIPEWORK
AUTHORISED PERSONNEL ONLY 11. GCCC/RCC/LCC -FLOWMETER NOT REQUIRED UNLESS
PLINTH MOUNTED SWITCHBOARD. Ø50 & Ø25 PVC ELECTRICAL
PRIOR TO ENTRY INTO THIS LOCATION TO BE CONFIRMED BY SEQ S.P. SPECIFICALLY REQUESTED.
STRUCTURE, PERSONNEL MUST CONDUITS FROM VENT POLE
COMPLY WITH SAFE WORK PRACTICE 12. GCCC/LCC/RCCC - NO INLET VALVE UNLESS SPECIFICALLY
- CONFINED SPACE ENTRY PROCEDURES. 2x Ø100 PVC REQUESTED.
VENT POLE
ELECTRICAL
POLYPROPYLENE SIGN TO BE PLACED ON
UNDERSIDE OF HINGED ACCESS COVERS TO CONDUIT FOR
600 MIN
PUMP STATION AND VALVE PITS. INCOMING POWER ALUMINIUM GRILLE FLOOR
OR 2D
SIGN SHALL BE IN ACCORDANCE WITH AS 1319 10
SUPPLY 2 x FALL ARREST WEBFORGE A323APM OR
SAFETY SIGN
MIN Ø100
MIN Ø150
MIN Ø150
45
REGISTERED WITH "DEWS" FLOWMETER & SECTION M16 EPOXY SET SS ANCHORS
(QLD GOV) VALVE CHAMBER AT 500 MAX C/C AND 75
650
REFER DWG SEQ-SPS-1300-4 FROM ENDS OF ANGLES.
HEAVY DUTY SAFE HATCH COVERS
CAST INTO TOP SLAB FINISHED SEE NOTE 10 SUPPORT AT CONRETE FACE
FLUSH WITH SLAB LEVEL. ALUMINIUM HANDGRIPS IN
20
0
HINGED SIDE
OPENING WITH RECESSED LOCKABLE LATCH
COMPLETE WITH WARNING SIGNS. ALUMINIUM GRILLE FLOOR
1550
600
HINGES TO BE FLUSH WITH TOP OF GRATING M16 SS EPOXY WEBFORGE A323APM OR SIMILAR
25
VALVE BOX FOR KNIFE SURFACE. SET ANCHOR
HINGED SIDE
55
ROUND AND FIXED IN PLACE IN ACCORDANCE
WITH THE MANUFACTURERS RECOMMENDATIONS.
M16 SS BOLTS
DIRECTION OF LOAD BEARINGS BARS
SHOWN THUS: 100x9.5 EA 55
25
MIN 2000
1 2
650
TO EDGE - -
141
OF OPENN 152x63x6
ING (TYP)
20
CHANNEL
0
J
AX
-
ITEM DESCRIPTION QTY
33 1
41 DI FBE FL-FL SPOOL PIECE 1
42 DI FBE SCOUR TEE FL TEE 1
43 DI FBE SP-SP SPOOL PIECE MIN 600mm LONG 1 2
44 GIBAULT JOINT 1 7
DI FBE RESILIENT SEATED SLUICE VALVE FL-FL C/W SPINDLE EXTN 1 7
45 1
& VALVE BOX
5
46 PE100 SDR11 FL-FL PIPE 1 3
4 6
47 DI FBE FL-FL SPOOL PIECE 1
32 48 DI FBE THRUST FLANGE
10 26 27 28 29 1
24 25 25 49 DI FBE FL-FL 90° BEND WITH 1500 LONG DI FBE DROPPER PIPE
23 1
9 34 21
50 NON-RETURN FLAP VALVE "HARDIE KING" OR EQUIVALENT APPROVED 2
30
DN100 uPVC FLOOR DRAIN WITH TRAP, GRATE & FLAP SEAL 14
7 11 51 2
CAST INTO PIT
10
11
10 17 13 8 17
8 12
11
31
49 12
48
20
47
A
JX
200
'D' 'C' 'D'
NOM
100 1100 600 1250 300 450 500 250 200
150 1100 600 1350 300 450 600 250 200
REFER SEQ-SPS-1300-3
200 1150 650 1500 300 500 700 250 200 FOR PIPEWORK DETAILS
'B'
'G'
250 1150 650 1650 300 500 800 300 200 FLOW
F
300 1200 700 2000 300 550 900 400 300 -
375 1250 750 2100 300 600 1060 400 300 'G' 'H' 'H' 900Sq. CONC. SLAB
AC
450 1300 800 2300 300 650 1220 400 300 MIN MIN flush to top of pit
'A'
50 S FL
RO
wall c/w edge
S
FA OO
500 1300 800 2450 300 650 1375 400 300
thickening
LL
500
600 1350 850 2600 350 700 1635 400 300
N12-150 EW EF
R
750 1450 950 3100 400 800 1975 400 300 (OPPOSITE WALL SIMILAR)
220
450mm WIDE
200
300 OD OF THRUST / WEEP "SALA" WALL MOUNT SLEEVE, MIN. ANCHOR SPEC.
ALUMINIUM LADDER
TYP FLANGE PLUS 120mm · 4/M16 316 S/STEEL "CHEMSET" ANCHORS N12-150 EW CP
COMPLETE WITH
· HOLE DIA.: 18mm (OPPOSITE WALL SIMILAR)
RETRACTABLE HANDGRIP
TRIM CUT BARS WITH CT-N16 EF · HOLE DEPTH: 125mm
PLAN STANCHIONS ALL IN
· MIN. CONCRETE THICKNESS: 200mm Ø100
ACCORDANCE WITH AS
PIPE BARREL · MIN. DISTANCE OF ANCHOR C/LINE TO DRAIN PIPE
1657
CONCRETE EDGE :150mm
OUTSIDE FACE REINFORCEMENT SHALL Note: NO LADDER FOR
THRUST / WEEP FLANGE · EPOXY RESIN SPEC. : HILTI HIT-RE-500 OR
BE CUT TO PIPE OD PLUS 100MM GCCC, LCC & LCC
FISCHER FIS VS 360 S
INSIDE FACE REINFORCEMENT SHALL · EACH ANCHOR TO BE LOAD TESTED AFTER
BE CUT TO WEEP FLANGE OD PLUS CURING TO 13.5 kN.
4/N16 TRIMMER BARS EACH FACE 25 CAST IN M12 SS FERRULE WITH
100MM
60 COVER TO BLOCKOUT M12 CSK SS SET SCREW
25
NOT TO SCALE WELDED TO UNDER SIDE OF COVER
80 x 6 REBATE
ALL ROUND
150 MAX
i
75 MIN
5 CLEARANCE
ALUMINIUM COVER ALL ROUND
150
REFER DETAIL
160mm min.
FSL STAINLESS STEEL VALVE
EXTENSION SPINDLE HEAVY DUTY ALUMINIUM 2 HEAVY DUTY HINGES PER COVER
(IF REQUIRED) COVERS CAST INTO TOP OPEN 180° TO ALLOW COVER TO BE
2 6 2 SLAB FINISHED FLUSH FULLY LAID BACK. HINGES TO BE FLUSH
MIN
3 4 5
'F'
HINGED SIDE
WELDED TO UNDERSIDE OF CONC. (NOT REQUIRED BY UNITYWATER)
MIN
SLAB
'E'
75
6/S-N16-150 T
75
75
70 COVER
10/CT-N16-150=2700 CP
L-N16-150 MAX
56/S-N16 CP
HH AND H-N16-150 BB
5/S-N16-150 MAX
(AS SHOWN)
N16-150 MAX EW CP EACH SIDE
NOT TO SCALE -
75
FIXED TO TOP OF 1/L-N16 T
CT-N16-150 MAX CP
75
75
S-N16
75 COVER
50 COVER
CT-N16
56/L-N16 CP CENTRALLY PLACED REFER
L-N16-150 MAX
EW 1/CT-N16 EF
B
L-N16
75
56/L-N16 CP REFER
SECTION A
CAST IN SITU BASE CONSTRUCTION
CT-N12-150 MAX EF CT-N12-150 MAX EF
REFER
STAGGER LAPS LOCATIONS
SECTION B
OD OF THRUST / WEEP
75
75
300
TYP FLANGE PLUS 120mm
TRIM CUT BARS 75 S-N16 LAPPED WITH 75
S-N16-300 EW L-N16-150 MAX
56/S-N16 ES CP WITH CT-N12 EF EACH SIDE
75
75 COVER
56/L-N12 ES
ON 1500 PCD 1 CENTRALLY PLACED REINFORCEMENT CUTTING SHALL ONLY OCCUR AFTER RELATION TO PROJECT SPECIFIC DESIGN
COMPLETION OF WALL CONSTRUCTION. DRAWINGS AND RELEVENT STANDARD DRAWINGS.
CAISSON BASE CONSTRUCTION
TYPICAL DETAIL OF ADDITIONAL 200 0 400 800 1200mm
35
Ø 6mm S/S
200
Ø3mm STAINLESS SUPPORT PLATE ROUND BAR
STEEL WIRE 340x60x6mm WELDED TO 6mm x 60mm
CONTROL CABLES TO
SUPPORT PLATE
40
CONTROL PANEL S/S PLATE S/S DYNA
S/S WIRE LOOP
BOLT C/W NUT
AND CRIMP CABLE MOUNTING & WASHER
3/8" BOLT, CLAMP STAINLESS STEEL
WASHERS & WIRE CLAMP TO
CABLE
NYLOC NUT SUIT Ø3mm S/S
TIE
WIRE
Ø3mm STAINLESS
STEEL WIRE
32mm HDPVC ORANGE CONDUIT LENGTH WHITE INSULATION
TO BE 3m MAX FOR WELL DEPTH 5m AND TAPE TO MARK DETAIL A
OVER. OTHER WELL DEPTHS, CONDUIT SENSOR DEPTH SCALE :- NTS -
LENGTH TO BE APPROVED BY SP. SENSOR CABLE
SWITCH
EMERGENCY BACKUP
START LEVEL GENERAL NOTES
EMERGENCY BACKUP 1. THE HEIGHT OF THE WELL WASHER IS SET AS PER SP STD DRG'S. THE LOCATION OF THE WELL WASHER IN PLAN
LEVEL SWITCH POSITION IS TO BE SUCH THAT THE WASHER IS ACCESSIBLE FOR MAINTENANCE FROM THE ACCESS LADDER. THE
WELL WASHER MAY BE ROTATED ON THE SWING ARM TO OBTAIN THIS ACCESS. THE ROTATING ARM MUST BE
CLEAR OF ALL CABLES, CHAINS, PIPES AND ELECTRODES. THE WELL WASHER IS TO BE LOCATED AS CLOSE AS
POSSIBLE TO THE CENTRE OF THE WELL AND IS TO ALLOW A MINIMUM 75 CLEARANCE OF THE PUMPS.
2. CLEARANCE MUST BE GIVEN TO ALLOW REMOVAL OF THE SWING ARM FROM THE WALL BRACKET.
3. THE WELL WASHER IS TO BE CONTROLLED BY THE SOLENOID VALVE ON THE POTABLE WATER SYSTEM
Ø6.0mm HOLES TO BE DRILLED DOWNSTREAM OF THE RPZ VALVE. THE WASHER IS TO OPERATE FOR THE FIRST MINUTE AFTER ANY PUMP STARTS.
OPPOSITE EACH OTHER AT 4. ALL STAINLESS STEEL IS TO BE GRADE 316.
100% DISPLAY & TELEMETRY
300mm INTERVALS 5. ALL STAINLESS STEEL BOLTS AND NUTS ARE TO BE INSTALLED WITH ANTI GALLING COMPOUND. THIS IS TO
INCLUDE THE BOLTS IN THE LINK SEAL.
300
NOTE 1
EXTERNAL GROUND WATER FULL DEPTH ALL EXTRUSIONS SHALL BE ALLOY 6061-T6. C3. THE DRYING SHRINKAGE AT 56 DAYS, FOR CONCRETE USED IN WATER RETAINING
PLATE 3MM AND THICKER SHALL BE ALLOY 5083-H321. STRUCTURES, SHALL NOT EXCEED 700 MICROSTRAIN AS DETERMINED IN
MAXIMUM PIPELINE TEST PRESSURE 900 kPA TREAD PLATE SHALL BE ALLOY 5251-0. ACCORDANCE WITH AS 1012.13.
FOUNDATIONS A5. ALL METALWORK CONNECTIONS NOT SHOWN BOLTED, SHALL BE WELDED AS C4. NOMINAL MAXIMUM AGGREGATE SIZE SHALL BE 20MM UNO.
FOLLOWS:-
F1. ALL TOPSOIL AND VEGETATION SHALL BE REMOVED BEFORE EXCAVATION. C5. ADMIXTURES SHALL NOT BE USED WITHOUT WRITTEN APPROVAL.
(a) ALL WELDING SHALL BE WELD QUALITY B IN ACCORDANCE WITH AS 1665.
F2. FOUNDATIONS HAVE BEEN DESIGNED FOR THE FOLLOWING SAFE ALLOWABLE GROUND (b) WELDS SHALL BE CONTINUOUS 6MM FILLET OR FULL PENETRATION BUTT WELDS ALL C6. ALL CONCRETE SHALL BE READY MIXED CONCRETE COMPLYING WITH AS 1379.
BEARING CAPACITIES:- ROUND USING FILLER ALLOY 5556.
(c) ALL JOINTS SHALL BE FULLY SEAL WELDED UNLESS SHOWN OTHERWISE. C7. THE TYPE OF CEMENT TO BE USED SHALL BE TYPE GP - GENERAL PURPOSE
ELEMENT ALLOWABLE BEARING CAPACITY (kPA) (d) GRIND WELDS FLUSH ONLY AT CONTACT POINTS WITH OTHER MEMBERS AND PORTLAND CEMENT UNLESS SPECIFIED OTHERWISE.
CONCRETE SURFACES.
VALVE PIT 100 C8. PROVIDE ALL EXPOSED EDGES AND CORNERS WITH A 20MM X 20MM CHAMFER OR
PUMP WELL 200 A6. ALL FASTENERS SHALL BE GRADE 316 STAINLESS STEEL. FILLET.
F3. THE SEQ-SP SHALL APPROVE FOUNDATION MATERIAL PRIOR TO PLACING A7. NYLON OR POLYETHYLENE WASHERS, TOP HAT SECTIONS AND SPACERS SHALL BE C9. CONCRETE SHALL BE COMPACTED BY MECHANICAL VIBRATION.
REINFORCEMENT OR CONCRETE. USED TO SEPARATE STAINLESS STEEL FASTENERS FROM ALUMINIUM. HOLE SIZES
SHALL BE DRILLED ONLY SUFFICIENTLY LARGE ENOUGH TO ACCOMMODATE THE C10. ALL CONCRETE SURFACES SHALL BE CURED BY APPROVED MEANS FOR A MINIMUM
F4. ANY OVER-EXCAVATIONS OR CAVITIES OF FOUNDATIONS SHALL BE FILLED WITH FASTENER AND ISOLATOR CHOSEN. OVERSIZED HOLES WILL NOT BE ACCEPTED. CONTINUOUS DURATION OF 7 DAYS COMMENCING IMMEDIATELY AFTER THE INITIAL
BLINDING CONCRETE. SET OF THE CONCRETE.
A8. ALL ALUMINIUM SURFACES PLACED IN CONTACT WITH CONCRETE SHALL BE PAINTED
WITH TWO HEAVY COATS OF ALKALI-RESISTANT BITUMINOUS PAINT OR OTHER C11. CONCRETE FACES AT CONSTRUCTION JOINTS SHALL BE THOROUGHLY SCABBLED,
GENERAL FREE OF LAITANCE, CLEANED AND WETTED THOROUGHLY PRIOR TO THE PLACEMENT
COATING PROVIDING EQUIVALENT PROTECTION BEFORE INSTALLATION.
OF ABUTTING CONCRETE.
G1. NO DIMENSION SHALL BE OBTAINED BY SCALING.
STAINLESS STEEL
C12. NO HOLES OR CHASES OTHER THAN THOSE SHOWN ON THE DRAWINGS SHALL BE
G2. ALL DIMENSIONS ARE IN MILLIMETRES UNO.
MADE IN CONCRETE MEMBERS WITHOUT THE PRIOR APPROVAL OF THE SEQ-SP.
SS1. ALL STAINLESS STEEL SHALL BE GRADE 316 IN ACCORDANCE WITH AS 1769 OR AS
G3. ALL LEVELS ARE IN METRES UNO. 2837 UNLESS SHOWN OTHERWISE.
C13. PROVIDE A FINE NON-SLIP SURFACE WITH A WOOD FLOAT TO THE TOPS OF ALL
WALLS AND FLOORS.
G4. ALL DIMENSIONS ARE TO BE VERIFIED ON SITE BY THE CONTRACTOR BEFORE SS2. ALL WELDS SHALL BE 6MM CONTINUOUS FILLET OR FULL PENETRATION BUTT WELDS
FABRICATION AND CONSTRUCTION. ALL ROUND IN ACCORDANCE WITH AS 1554.6 UNLESS SHOWN OTHERWISE.
C14. CONSTRUCTION JOINTS WHERE NOT SHOWN ON THE DRAWINGS SHALL BE LOCATED
TO THE APPROVAL OF THE SEQ-SP.
G5. REFER ALL DISCREPANCIES TO THE SEQ-SP BEFORE PROCEEDING WITH THE WORKS. SS3. STAINLESS STEEL SURFACES SHALL HAVE THE SCALE REMOVED BY PICKLING AND
SHALL BE PASSIVATED OR SURFACE TREATED TO PLACE THE ALLOY NEAR THE
C15. ALL INTERNAL CONCRETE SURFACES OF THE PUMP WELL, COLLECTOR MANHOLE AND
G6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE STRUCTURE AND CATHODIC END OF THE GALVANIC SERIES. ALL AREAS OF STAINLESS STEEL WHICH
EMERGENCY STORAGE SHALL BE PAINTED WITH "APPROVED SEALANT" IN STRICT
NEIGHBOURING STRUCTURES IN A SAFE AND STABLE CONDITION DURING ARE SUBSEQUENTLY MACHINED, GROUND OR WORKED IN ANY MANNER WHICH
ACCORDANCE WITH THE MANUFACTURERS WRITTEN INSTRUCTIONS.
CONSTRUCTION. NO PART SHALL BE OVERSTRESSED. TENDS TO DESTROY THE ORIGINAL PASSIVATED CONDITION SHALL AGAIN BE
PASSIVATED AS A FINAL CLEANING OPERATION. AFTER PASSIVATING, THE
G7. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING STRUCTURES AGAINST SURFACES SHALL BE FREE FROM PITTING OR SURFACE DEFECTS.
FLOATATION DURING CONSTRUCTION.
SS4. FABRICATED HANDRAILS, LADDERS, STAIRWAYS, PLATFORMS AND WALKWAYS
G8. ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH THE SHALL COMPLY WITH AS1657.
SPECIFICATIONS, THE REQUIREMENTS OF RELEVANT SAA CODES, BCA AND THE LOCAL
LAWS AND ORDINANCES OF THE RELEVANT GOVERNMENT AUTHORITY. SS5. LADDERS SHALL BE 450MM WIDE, FIXED IN PLACE WITH M20 FIXINGS.
REINFORCEMENT PIPEWORK
R1. REINFORCEMENT SYMBOL - 23/S-N16-200 EW P1. WHERE CONNECTING TO EXISTING PIPEWORK, THE LEVEL AND DIAMETER
OF THE EXISTING PIPEWORK, SHALL BE CONFIRMED BY THE CONTRACTOR,
23 NUMBER OF BARS IN GROUP (IF SHOWN) PRIOR TO CONNECTION.
S BAR SHAPE CODE, REFER AS1100.501 (IF SHOWN)
N16 BAR GRADE/TYPE AND DIAMETER P2. ALL FLANGES SHALL BE IN ACCORDANCE WITH AS 4087, CLASS 14 FOR
200 SPACING BETWEEN BARS IN MILLIMETRES CAST IRON AND, CLASS 16 FOR DUCTILE IRON AND STEEL, UNO.
EW LOCATION CODE (IF SHOWN)
P3. ALL FLANGE BOLT HOLE ORIENTATIONS SHALL BE OFF-CENTRE UNO.
REINFORCEMENT SYMBOL, STANDARD AND GRADE DESIGNATIONS ARE AS
FOLLOWS:- P4. ALL FLANGE BOLT SETS SHALL BE GRADE 316 STAINLESS STEEL.
REFER AS 4087 - TABLE C1 FOR CLASS.
N GRADE 500N DEFORMED BAR TO AS/NZS 4671.
SL SQUARE REINFORCING FABRIC TO AS/NZS 4671. P5. FLANGE GASKET MATERIAL AND THICKNESS SHALL BE IN ACCORDANCE
WITH
LOCATION CODES (IF SHOWN) :- AS 4087 - TABLE C1.
B BOTTOM FACE HORIZ HORIZONTAL P6. THRUST AND PUDDLE FLANGES SHALL BE CAST CENTRALLY WITHIN WALLS
BB BOTTOM BOTTOM (LAID FIRST) IL INNER LAYER UNLESS SHOWN OTHERWISE.
CP CENTRALLY PLACED INTF INTERNAL FACE
EF EACH FACE NF NEAR FACE P7. ALL SPIGOT AND SOCKET DICL PIPEWORK SHALL BE CLASS PN35.
ES EQUALLY SPACED OL OUTER LAYER
EW EACH WAY T TOP FACE P8. ALL GATE AND REFLUX VALVES SHALL BE INTERNALLY AND EXTERNALLY
EXTF EXTERNAL FACE TT TOP TOP (LAID LAST) COATED WITH A POLYMERIC COATING. ALL GATE VALVES SHALL BE
FF FAR FACE VERT VERTICAL RESILIENT SEATED. ALL REFLUX VALVES SHALL BE RESILIENT SEATED
SWING FLEX CHECK VALVE OR SIMILAR APPROVED TOP OPENING VALVE.
R2. REINFORCEMENT IS REPRESENTED ON THE DRAWINGS DIAGRAMMATICALLY,
AND IS NOT NECESSARILY SHOWN IN TRUE PROJECTION.
ELECTRICAL
R3. REINFORCEMENT SHALL BE CUT OR DISPLACED TO PROVIDE 50MM COVER TO
PIPES OR OPENINGS AS DIRECTED BY THE SEQ-SP. EL1. THE LOCATION OF ALL CONDUITS SHALL BE CONFIRMED BY THE SEQ-SP
PRIOR TO CONSTRUCTION OF THE SWITCHBOARD SLAB.
R4. REINFORCEMENT SHALL BE KEPT 40MM CLEAR OF WATERSTOPS.
EL2. ALL CABLES AND CONDUITS SHALL COMPLY WITH AS/NZS 3000 AND AUSTEL
R5. MINIMUM DEVELOPMENT/LAP LENGTHS FOR MINIMUM 25 MPA CONCRETE REQUIREMENTS.
UNO SHALL BE:-
EL3. UNDERGROUND CONDUITS SHALL BE HEAVY DUTY RIGID PVC WITH 600MM
VERTICAL BARS AND HORIZONTAL BARS WITH MINIMUM COVER.
BAR HORIZONTAL BARS WITH MORE THAN 300mm OF
DIAMETER LESS THAN 300mm OF EL4. POLYMERIC CABLE COVER STRIPS COMPLYING WITH AS 4702 SHALL BE
CONCRETE CAST BELOW
CONCRETE CAST BELOW USED AS ADDITIONAL MECHANICAL PROTECTION OF ALL UNDERGROUND
N10 250 325 WIRING ENCLOSURES.
N12 300 375
N16 400 600 EL5. ALL EXTERNAL ABOVEGROUND CONDUITS SHALL BE GALVANISED STEEL
UNO.
R6. MINIMUM LAP LENGTH FOR SLAB REINFORCING FABRICS SHALL BE ONE FULL EL6. ALL INTERNAL ABOVE GROUND ELECTRICAL CONDUITS SHALL BE MEDIUM
MESH PLUS 25MM. DUTY RIGID PVC UNO.
MINIMUM LAP LENGTH FOR FABRIC MESH AND BARS SHALL BE 300MM.
EL7. ALL CONDUITS SHALL HAVE LONG RADIUS BENDS.
R7. LAPS IN REINFORCEMENT SHALL BE MADE ONLY IN THE LOCATIONS SHOWN
ON THE DRAWINGS OR AS OTHERWISE APPROVED BY THE SEQ-SP.
65 COVER
CONTROL WELL WASHER SEE NOTE 8
PIPEWORK, FITTINGS AND LIQUID AND SHALL
ALSO REFER SEQ-SPS-1300-6 J HIGH LEVEL ALARM m
CUBICLE BE AS DETAILED ON THE DRAWINGS.
300
20
PRESSURE MAIN TO BE STAINLESS STEEL - PUMP OPERATING LEVELS AND DEFAULT SETTINGS SHALL BE AS
316SS SCH40. PER THE SEQ-SP FUNCTIONAL DESCRIPTION.
Q100/STORM SURGE
150
125
LEVEL "M" 6. RCC - ACCESS COVER(S) TO BE MCBERNS
75
VARIES 900 MIN.
FOR PE LINING TOP SLAB AND FLUSH MOUNT 4-SIDED VOID PROTECTION
WALL PENETRATION DETAILS ACCESS COVER(S) OR APPROVED SIMILAR
DISCHARGE UNLESS SPECIFIED OTHERWISE.
500 85 REFER SEQ-SPS-1407-1&2
APPROVED 7. DIMENSIONS ARE IN MILLIMETRES UNLESS
MAINTENANCE CHAMBER SHOWN OTHERWISE.
HOLE COUPLING 8. GCCC/LCC/RCC - NO LADDER, NO WELL
1.5 × DIA. OVERFLOW ALARM LEVEL 'K' WASHER UNLESS SPECIFICALLY REQUESTED.
OF OUTLET 9. FALL PREVENTION INSERTS TO BE IN
ACCORDANCE WITH SELECTED OPTION FOR
OUTGOING SEWER
OUTLET I.L. COVERS SEE SEQ-SPS-1304 SERIES DRAWINGS. FLANGE TO
PRE-OVERFLOW ALARM LEVEL 'L' 10. MINIMUM CIRCULATION CLEARANCE FOR RUNG BE FLUSH
TYPE LADDERS AS PER AS1657 CLAUSE 5.1 ECCENTRIC TAPER
150
MIN 2.5mm THICK INTERNAL POLYETHYLENE LINER PUMP DUCTILE IRON ACCESS BEND PUMP
(LIGHT COLOUR) CORROSION PROTECTION SYSTEM TO OUTGOING
ALL INTERNAL CONCRETE SURFACES, TO TERMINATE WELL
ABOVE BENCHING INCOMING SEWER PRESSURE MAIN
100
DUTY START LEVEL 'C' REFER DETAIL 'A' FOR REFER NOTE 6
PRESENT & ULTIMATE uPVC DROP PIPE TO
200 MIN
150
CONFIGURATION WHERE
TAPERS APPLY. TERMINATE 200 ABOVE
PUMP STOP LEVEL 'F'
PUMP STOP LEVEL 'D'
150
300
450
400
150
350
280
230 70
100
* OUTGOING INCOMING
300
* 10°
1100
*
10°
280
350
CHEMICAL BOLT ANCHOR REFER SEWER SEWER
40 NOTE 2.
80 2260
BENCHING SHALL BE
DIAMETER+100
* REFER NOTES 3 & 4
STEEL TROWEL FINISHED
SLIP FORMED CAST INSITU 150 HOLES IN THE BOTTOM FLANGE OF
** DISCHARGE CHAMBER CLEAR OPENING SHALL
THE 90° VERTICAL BEND SHALL BE
BE 1000 x 800 FITTED WITH SELECTED BENCHING SUMP 150 CLEAR
DRILLED AT A 10° VARIATION TO
COVER OPTION AS PER SPS-1304 DWGS OF PUMPS AND SLIDE BASE
SECTIONAL ELEVATION THE NORMAL CENTRELINE POSITION TO C
L PLATE AND RECESSED TO FIT
ENABLE DISCHARGE PIPES TO BE
TURNED INWARD AS SHOWN. DUCKFOOT BEND
CONTROL
CUBICLE
** 1 IN 100 MIN.
TOP OF SLAB LEVEL 'A'
250
20
65 COVER
CUBICLE
CONTROL
125
175
75
2000
VARIES 900 MIN.
500
DISCHARGE
2430
CHAMBER
DIAMETER OF OUTGOING
SEWER D500N16-100T
D500SL62C D500N16-100T
OUTGOING SEWER
PUMP MIN 2.5mm THICK INTERNAL
POLYETHYLENE LINER (LIGHT COLOUR)
WELL
175
4260
ALL INTERNAL CONCRETE SURFACES,
TO TERMINATE ABOVE BENCHING
500
D500N16-100B
CONSTRUCTION
D500N12-300C, AT CJ
JOINT
200
D500N12-300C, 600 LONG AT CJ
WITH SUITABLE WATER STOP.
INCOMING SEWER
500
HINGED SIDE
HINGED SIDE
1260
DISCHARGE D500SL82
PUMP D500N12T TO ALL
CHAMBER
SIDES OF OPENING.
500
WELL
200
500
430
150
D500N12-300C, SET 500 INTO D500N12-300C
450
* D500N12T TO ALL
300
* 3410
PUMP WELL - DISCHARGE SIDES OF OPENING.
230
CHAMBER JUNCTION *
40 D500N16 600 LONG D500N16-100B
D500N12-150EW
110 1800 230 TOP COVER 90 ON TOP OF BOTTOM
* REFER NOTES 2 & 3
80 2260
STEEL, TO ALL CORNERS.
PLAN
** DISCHARGE CHAMBER CLEAR OPENING SHALL BE
1000 x 800 FITTED WITH LIGHT DUTY ACCESS
COVER AS PER SPS-1304 SERIES DWGS
SLIP FORMED CAST INSITU
1. THIS DRAWING SHOULD BE READ IN CONJUNCTION WITH SEQ-SPS-1300 7. LAPS IN REINFORCING SHALL BE 600 MINIMUM FOR BARS AND
SERIES DRAWINGS. 4. ALL CONCRETE SHALL:
ONE (1) MESH SPACING FOR FABRIC.
(a) BE GRADE S40
2. THE THICKNESS OF THE BASE SHOWN IS FOR LIFT STATIONS TO A MAX. DEPTH (b) COMPLY WITH THE REQUIREMENTS OF 8. CONCRETE COVER TO REINFORCEMENT SHALL BE A MINIMUM 65
OF 4.0m. SEQ-SP STANDARD SPECIFICATIONS UNLESS OTHERWISE DIRECTED.
3. FOR DEPTHS OF LIFT STATIONS GREATER THAN 4.0m THE BASE THICKNESS 5. ALL CORED HOLES IN LIFT WELL WALLS SHALL BE TAPERED TO BE Ø25 LARGER 9. DIMENSIONS ARE IN MILLIMETRES UNLESS SHOWN OTHERWISE.
SHALL BE INCREASED TO COVER FLOTATION OF THE STRUCTURE WHEN EMPTY IN DIAMETER ON THE OUTSIDE FACE THAN THE INSIDE FACE. PACK HOLES
OF PUMPS, PIPEWORK, FITTINGS AND LIQUID AND SHALL BE AS DETAILED ON WITH 3:1 CEMENT MORTAR UNLESS OTHERWISE DIRECTED.
THE DRAWINGS.
100
APRON SLAB MAY VARY TO SUIT
REQUIREMENTS
A
SPECIFIC SWITCHBOARD SIZE
PROVIDE Ø50 CONDUIT 125
BELOW SLAB LEVEL. (POSITION
TO BE DIRECTED ON SITE)
PROVIDE Ø32 CONDUIT FOR
Ø80 CONDUIT FOR TELEMETRY EARTH STAKE IN CONTROL
CUBICLE
400 MIN
AS DIRECTED.
150
Ø80 CONDUIT uPVC LONG RADIUS BEND
FOR RPZ DEVICE PUMP
SUITABLE PLUG TO ENDS
250 500 50 WELL
MINIMUM GRADE 1%
200
TO PUMP WELL
HINGED SIDE FOR ONE
Ø80 CONDUIT FOR POWER SUPPLY PART DOOR CABINET.
SECTION A-A TYPICAL CONDUIT DETAIL
CONTROL
CUBICLE
2000
Ø32 CONDUIT FOR EARTHING
1x80Ø uPVC
STAKE TO BE PROVIDED IN
2430
4260
NOTES
500
2x100Ø uPVC
GENERAL
200
4. FALL PREVENTION INSERTS TO BE IN ACCORDANCE WITH SELECTED OPTION FOR COVERS SEE
HINGED SIDE
HINGED SIDE
2260
1260
1400
ELECTRICAL CONDUITS
500
1. CONDUITS TO BE MINIMUM 100 NOMINAL DIAMETER FOR EACH PUMP AND MINIMUM 80 NOMINAL
DIAMETER FOR CONTROL CABLES OR TWICE THE OUTSIDE DIAMETER OF THE INSTALLED CABLE
WHICHEVER IS THE GREATER.
200
2. PUMP CONDUITS AND CONTROL CONDUIT SHALL BE SEPARATED BY A MINIMUM 300. PUMP
CONDUITS SHALL BE SEPARATED BY 30.
DAVIT BASE (LCC USES A 3. CONDUITS SHALL BE INSTALLED IN ACCORDANCE WITH AS/NZS3000.
500
430
G OW
RA N
THE MAINTENANCE HOLE.
D
THE INVERT OF THE UPSTREAM END MUST ALSO BE ABOVE
D
E
THE OVERFLOW IMMINENT ALARM (HIGH HIGH LEVEL
ALARM) LEVEL AND ALSO BE ABOVE THE CROWN OF THE
PUMP WELL. INCOMING SEWER.
GRAVITY SEWER. TO BE
SEE NOTE G2.
W E
DETAILED ON PROJECT
O D
OPTION 2 IS TO BE USED WHEN A SITE DOES NOT ALLOW
N
D RA
DN150 VENT PIPE TO VENT DRAWINGS. SEE NOTE G4
A BYPASS TO BE INSTALLED. THIS OPTION REQUIRES AN
G
POLE FROM PUMP WELL. 1000 MINIMUM 1000
COLLECTION MAINTENANCE EMERGENCY STORAGE CHAMBER TO BE INSTALLED.
THIS IS THE ONLY VENT MINIMUM
HOLE. SEE NOTE G4. THE LEVEL INTERACTIONS FOR THIS OPTION ARE TO BE AS
REQUIRED ON THIS OPTION.
SHOW ON DRAWING SEQ-SPS-1102-5.
EMERGENCY STORAGE OPTION 1 SECTIONAL PLAN VIEW LIFT POLYETHYLENE LINED Ø900
CHAMBER. REFER TO G2. THE PUMPING STATION PUMP WELL IS TO BE AS SHOWN
DRAWING NOS.
STATION WITH EMERGENCY BYPASS SEWER RISING MAIN DISCHARGE ON DRAWINGS NOS. SEQ-SPS-1301-1 TO 4 BUT WITH THE
SEQ-SPS-1402-1 NOT TO SCALE MAINTENANCE HOLE. SEE OMISSION OF THE VALVE PIT AND RISING MAIN.
SEQ-SPS-1102-5 NOTE: FOR CLARITY ALL PIPES ON THIS DRAWING ARE SHOWN ON THE NOTE G3.
SAME LEVEL BUT THEY ARE NOT ALL ON THE SAME LINE OF SECTION. G3. A SEPARATE POLYETHYLENE LINED Ø900 RISING MAIN
DISCHARGE MAINTENANCE HOLE IS REQUIRED FOR EACH
CONNECTION SEWER TO AND FROM
PUMP. THE DISCHARGE MAINTENANCE HOLE IS TO BE THE
PUMPING STATION EMERGENCY STORAGE CHAMBER. DETAILS
ALTERNATE OPTION DESIGN WHERE THE OUTLET PIPE
INCOMING SEWER TO BE GIVEN ON PROJECT DRAWINGS SEPARATE POLYETHYLENE RISING GRADES DOWN FROM THE DISCHARGE MAINTENANCE
SE MAIN FROM EACH PUMP. TO BE HOLE. THE DETAILS OF THIS OPTION ARE TO BE FOUND ON
E
NO DETAILED ON PROJECT DRAWINGS. STANDARD DRAWING NO. SEQ-SPS-1406-3.
DIVERSION MAINTENANCE TE
G2 POLYETHYLENE LINED Ø900
HOLE WITH CONNECTION TO
EMERGENCY STORAGE RISING MAIN DISCHARGE THE INVERT OF THE OUTLET SEWER FROM THE DISCHARGE
MAINTENANCE HOLE. SEE NOTE MAINTENANCE HOLE IS TO BE ABOVE THE OBVERT OF THE
CHAMBER. DETAILS TO BE
GIVEN ON PROJECT DRAWINGS. G3. SEWER ENTERING THE COLLECTION MAINTENANCE HOLE.
COLLECTION MAINTENANCE
GRIT COLLECTOR HOLE. SEE NOTE G4. G4. THE DETAILS OF THE COLLECTION MAINTENANCE HOLE
MAINTENANCE HOLE. GRAVITY SEWER. TO BE ARE TO BE INCLUDED ON THE PROJECT DRAWINGS. THIS
DETAILED ON PROJECT COLLECTION MAINTENANCE HOLE AND THE DOWNSTREAM
DRAWINGS. SEE NOTE G4. SEWER IS TO BE DESIGNED SUCH THAT THE MAINTENANCE
HOLE WILL NOT SURCHARGE AT MAXIMUM PUMP FLOW
CAUSING FLOW BACK INTO THE NON OPERATING
DISCHARGE MANHOLE OR INTO THE EMERGENCY BYPASS
SEWER IF IT IS INSTALLED.
PUMP WELL.
SEE NOTE G2. G5. A VENT PIPE TO A VENT POLE IS REQUIRED IN OPTION 2
INDUCT VENT PIPE FROM WHERE THE DOWNSTREAM SEWER IS AN END OF A
DN150 VENT PIPE TO VENT POLE FROM
POLE. SEE NOTE G5. GRAVITY SEWER LINE. THE MAIN FUNCTION OF THIS VENT
PUMP WELL. THIS VENT IS NOT TO BE
INTERCONNECTED WITH COLLECTION IS TO ACT AS AN INDUCT VENT. THE SIZE OF THIS VENT
POLYETHYLENE LINED Ø900 IS DESIGNED TO SUIT THE PROJECT.
MAINTENANCE HOLE VENT. RISING MAIN DISCHARGE THE VENT IS NOT TO BE CONNECTED TO THE PUMP WELL
OPTION 2 SECTIONAL PLAN VIEW LIFT STATION MAINTENANCE HOLE. SEE NOTE VENT.
WITH EMERGENCY STORAGE CHAMBER G3.
NOT TO SCALE
NOTE: FOR CLARITY ALL PIPES ON THIS DRAWING ARE SHOWN ON THE
SAME LEVEL BUT THEY ARE NOT ALL ON THE SAME LINE OF SECTION.
REV. No. DATE DESCRIPTION AUTH.
SEWAGE PUMP STATION STANDARD DRAWING CoGC LCC RCC QUU UW
SEQ WATER ALTERNATIVE LIFT STATION ARRANGEMENT
DRAWING No. VERSION
SEE NOTE
LOCATED ADJACENT TO THE ACCESS ROAD
M
G4.
AND ARE TO BE A MAXIMUM DISTANCE OF
IN
IM
COVER 1
PUMP 1
S1. THE STRUCTURE IS TO BE G5. FOR THE DETAILED REQUIREMENTS OF THE
SE
CODES AND PRACTICES AND IS TO AND THE VALVE PIT REFER TO DRAWINGS
NO
S2. THE TOP SLAB IN ANY LOCATION SEQ-SPS-1304-17 FOR THE REQUIREMENTS
G2
COVER 2
PUMP 1
W80 TO AS5100. HOWEVER THE SEQ-SPS-1304-10 THE PROJECT DRAWINGS
DESIGN SHALL COMPLY WITH ALL MUST CONTAIN DETAILS SUITABLE FOR THE
THE REQUIREMENTS SET OUT IN COVER MANUFACTURER TO DESIGN THE
AS5100. NOTE: THE ALUMINIUM INDIVIDUAL COVERS. INFORMATION MUST
COVERS ARE NOT DESIGNED TO INCLUDE CLEAR OPENING SIZES,
4500 MINIMUM BETWEEN COVERS. REMOVABLE BEAM POSITIONS, LOCATION OF
COVER 1
THIS LOAD. FOR THE COVER
PUMP 2
SEE NOTE G10. REQUIREMENTS REFER TO SAFETY MESH HOOKS AND INSCRIPTION
DRAWING SEQ-SPS-1304-10. DETAILS.
SEWER
S3. THE CONCRETE STRENGTH IS TO THE PERSON ACCESS MAINTENANCE HOLE
ELECTRICAL SWITCHBOARD TO SUIT PROJECT. THE BE S40 TO WATER SERVICES MUST NOT BE IMPEDED BY THE PUMP COVER
LOCATION OF CONDUITS SHOWN ON THIS DRAWING AUSTRALIA WSA 114 IN THE OPEN POSITION.
COVER 2
PUMP 2
CLASS D SEALED
ARE NOMINAL ONLY. SEE NOTES G2 AND G6. S4. THE TOP SLAB IS NOT TO BE G6. THE SWITCHBOARD SHOWN ON THIS
2000 MINIMUM SEE NOTE G2. STRUCTURALLY CONNECTED TO DRAWING IS THE PREFERRED DOUBLE-
DN20 UPVC ELECTRICAL CONDUIT THE WALLS OF THE PUMP WELL SIDED BOARD AND IS MOUNTED ON THE
CENTRALLY PLACED IN SLAB 2000 MINIMUM SEE NOTE G2. AND MUST BE PROVIDED WITH TOP SLAB. A NON-PREFERRED SINGLE-
"NESCO ERB1" ALUMINIUM EARTH ROD STAINLESS STEEL "REID SWIFT SIDED BOARD MAY BE APPROVED BY
CONNECTION BOX CAST FLUSH INTO TOP LIFT" LIFTING ANCHORS. QUEENSLAND URBAN UTILITIES TO SUIT
SLAB WITH DN100 HOLE THROUGH SLAB. S5. THE SWITCHBOARD SLAB MAY BE SELECTED SITE. ON SITES REQUIRING MORE
FORM HOLE WITH DN100 UPVC CONDUIT. DESIGNED SMALLER AND THAN 15000mm OF PUMP CABLE AND FOR
SEPARATED FROM THE WET WELL PUMPS OVER 30 kW THEN AN INTERMEDIATE
DN32 UPVC ELECTRICAL CONDUIT TOP SLAB. FIELD DISCONNECT BOX IS REQUIRED.
CENTRALLY PLACED IN SLAB 37
5 ET E
1050 MINIMUM FS ID 600 THE SWITCHBOARD IS TO BE NO MORE
WHERE A DOUBLE SIDED SWITCHBOARD IS INSTALLED A
CONTROL
OFINSL
MINIMUM THAN 15000mm FROM THE PUMP WELL AND
MHOM AL
VALVE
THE TOP OF THE PUMP WELL AND VALVE PIT
MINIMUM 1050 WIDE STRIP OF CONCRETE IS REQUIRED
TO THE OPENING FACES OF THE SWITCHBOARD. NOTE: A FR W MUST BE FULLY VISIBLE FROM THE
SWITCHBOARD.
DOUBLE SIDED BOARD IS SHOWN ON THIS DRAWING..
G7. THE PREFERRED OPTION OF THE ELECTRICAL
STANDARD TYPE D MAINTENANCE HOLE COVER AND CONDUITS CAST INTO TOP SLAB IS SHOWN
FRAME TO BE PROVIDED OVER ACCESS LADDER. ON THIS DRAWING. THE NON-PREFERRED
COVER TO BE FLUSH MOUNTED IN TOP SLAB OPTION WHERE THE ELECTRICAL CONDUITS
ARE LOCATED UNDER THE SLAB AND PASS
THROUGH THE WALL MAY BE APPROVED BY
POLYETHYLENE PIT FOR IP68 RATED SOLENOID VALVE SEWER QUEENSLAND URBAN UTILITIES, PROVIDED
FOR POTABLE WATER TO WELL WASHER. FOR
THE CABLES DO NOT CLASH WITH OTHER
DETAILS REFER TO DRAWING SEQ-SPS-1308-1 NOTE:
EQUIPMENT IN THE WELL.
TO BE INSTALLED IN NON TRAFFICABLE LOCATIONS. CLASS D SEALED
FR SET
2 x PIPE DIA. STAINLESS STEEL FULL BORE BALL VALVE AS4087 SUITABLE FOR PN16 PRESSURE RATING.
WA OM
MIN. MINIMUM MINIMUM G4. ALL SLUICE VALVES IN PUMPING STATION AND
LL
MINIMUM
F
300 300 300 NON THRUST TYPE FLANGE ADAPTOR FOR
OF
HIGH LEVEL OVERFLOW IF REQUIRED RISING MAIN ARE TO BE RESILIENT SEATED VALVES
0
PIPEWORK DISMANTLING.
30
BY SEQ-SP SEE NOTE G9. TO AS 2638.2
TYPICAL WALL PIPE FOR GRAVITY PIPE DOUBLE FLANGED SLUICE VALVE WITH G5. THE DIMENSION OF THE VALVE PIT WILL VARY TO
WITH THICKENED AND STRUCTURALLY HANDWHEEL. SEE NOTES G3 AND G4 SUIT THE PROJECT AND THE MINIMUM DIMENSIONS
PRESSURE SENSOR. FOR DETAILS REFER
CLEARANCE
REINFORCED WALLS. SEE NOTE G10 SHOWN ARE FOR DN100 AND DN150 PIPEWORK
MINIMUM
300
TO SEQ-SP. ONLY. ALL DIMENSIONS AND CLEARANCES MUST BE
375 WIDE GALVANISED STEEL LADDER SHOWN ON THE PROJECT DRAWINGS.
POTABLE WATER WELL WASHER. NOTE: WITH EXTENDABLE STILES. FOR DETAIL G6. THE 1016 DIMENSION BETWEEN CENTRE LINE OF
THE WASHER HEAD MUST BE ACCESSIBLE . REFER TO SEQ-SP. OUTLET PIPES IS FOR DN100 AND DN150 PIPES
FROM LADDER WHEN UTILISING SWING ARM. ONLY.
DN50 PVC ELECTRICAL CONDUIT FOR FOR LARGER DIAMETER PIPES THE MINIMUM
CLEARANCE
1600 MINIMUM
SUIT SWITCHBOARD TYPE AND LOCATION. THE OUTSIDE OF THE FLANGE IS TO BE 300 FOR
ALL LOCATION DIMENSIONS TO BE SHOWN PIPES LARGER THAN DN150 AND UP TO DN300
1016
ON PROJECT DRAWINGS. INCLUSIVE.
DN32 ELECTRICAL CONDUIT FOR G8. THE STAINLESS STEEL ANODE HOOK IS NOT SHOWN
IM 00
UM
FLOWMETER SIGNAL CABLE. ON THIS DRAWING BUT MUST BE INSTALLED ON THE
IN 1 UNDERSIDE OF THE ROOF SLAB FOR PUMPING
DN50 PVC ELECTRICAL CONDUIT FOR POWER STATIONS WITH MOTORS 30KW AND ABOVE. FOR
M
700
FLANGED STAINLESS STEEL WALL PIPE WITH G13. ALL FLANGES ARE TO BE INSTALLED WITH 316
THRUST FLANGE FOR SCOUR AND TEMPORARY STAINLESS STEEL BOLTS. BOLTS ARE TO BE
PUMP FLANGED CONNECTION. NOTE: FLANGE ASSEMBLED WITH ANTI GALLING COMPOUND
TO ALIGN WITH OPENING IN TOP SLAB. SEE "DURALAC" OR SEQ-SP APPROVED EQUIVALENT. ALL
NOTE G19. BURIED FLANGES ARE TO BE WRAPPED WITH
SEWER RISING MAIN. DIAMETER, MATERIAL, PETROLATUM TAPE "DENSO" TO MANUFACTURER'S
500
CLASS, LOCATION COORDINATES AND REQUIREMENTS.
FALL
DIMENSIONS ARE TO BE PROVIDED ON LL G14. WHERE NOT SPECIFIED THE MATERIAL OF THE
PROJECT DRAWINGS. FA PIPEWORK FROM THE HEADER PIPE TO THE START
SCOUR PIPE SEE NOTE G19. OF THE RISING MAIN MAY BE FLANGED CLASS DICL
(DUCTILE IRON CEMENT LINED) OR MSCL (MILD
RISING MAIN PIG. SEE NOTE G11. STEEL CEMENT LINED WITH MEDIUM DENSITY
COMBINATION EMERGENCY PUMP POLYETHYLENE EXTERNAL COATING).
DOUBLE FLANGED RISING MAIN ISOLATING 1200 300 G15. THE DELIVERY WALL PIPES SHOWN ON THIS
CONNECTION AND PIG INSERTION POINT
VALVE. SEE NOTE G4. MINIMUM DRAWING ARE FOR CHAIN SUSPENDED PUMPS WITH
WITH FLANGED ISOLATING VALVE. FOR
FLANGED EQUAL TEE WITH ANCHOR BLOCK. DETAILS REFER TO DRAWING SEQ-SPS-1608-1 THE PUMP WELL FLANGE ALIGNED WITH THE COVER
SEE NOTE G19. OPENING. FOR GUIDE RAIL PUMP INSTALLATIONS AN
DIAMETER OF PIPE X 5 MIMIMUM DIAMETER OF PIPE X 10 MIMIMUM AIR BLEED PIPE IS REQUIRED FROM THE DELIVERY
ELECTRICAL CABLE PIT. FOR DETAILS FOR DETAILS OF POTABLE WATER SYSTEM PIPE IN VALVE PIT BACK INTO WET WELL.
REFER TO DRAWING SEQ-SPS-1301-1 REFER TO DRAWING SEQ-SPS-1308-1 G16. THE VALVE PIT IS TO BE STRUCTURALLY INTEGRAL
WITH THE PUMP WELL WALL. SEE SEQ-SPS-1102-6
DN150 VENT PIPE. FOR DETAILS SEE FLOW METER PIT. FOR AN ALTERNATIVE ARRANGEMENT FOR SMALL
DRAWING SEQ-SPS-1405-1. SEE SEQ-SPS-1102-6 FOR AN ALTERNATIVE STATIONS
VENT POLE FOUNDATION FOR VENT POLE No 1 ARRANGEMENT FOR SMALL STATIONS G17. ALL ELECTRICAL CONDUITS ARE TO BE INSTALLED IN
SEE NOTE G20. FOR LOCATION REFER TO ACCORDANCE WITH AS/NZS3000. ALL CONDUITS
UPVC ELECTRICAL CONDUIT FOR
NOTE G8 ON DRAWING SEQ-SPS-1301-1 AND INCOMING POWER SUPPLY. SEE NOTE ARE TO BE INSTALLED WITH MARKER TAPE.
FOR DETAILS OF FOUNDATION REFER TO G9 ON DRAWING SEQ-SPS-1301-1 G18. ALL SERVICES INCLUDING TELEPHONE, WATER,
DRAWING SEQ-SPS-1405-1. SIGNAL AND POWER CONDUITS ARE TO BE DETAILED
MAGNETIC FLOW METER INSTALLED ON PROJECT CIVIL AND MECHANICAL GENERAL
WITH THRUST TYPE DISMANTLING DRAWINGS.
JOINT. THE DIAMETER IS TO BE THE
NOTE: FOR CLARITY ONLY, ALL PIPES PASSING THROUGH WALLS ARE SHOWN ON LINE OF SECTION SAME AS THE RISING MAIN.
750 FOR CHAIN SUSPENDED PUMPS ONLY STAINLESS WALL PIPE WITH FACE OF G1. THE DIMENSIONS AND LEVELS SHOWN ON THIS
FLANGE ALIGNING WITH INSIDE FACE DRAWING ARE INDICATIVE ONLY. THE LEVELS
600 x 200 LEVEL PROBE OPENING WITH OF OPENING IS FOR CHAIN SUSPENDED SHOWN AS *.*** ON THIS DRAWING AND ALL
ALUMINIUM COVER AND STAINLESS STEEL PUMP ONLY. DIMENSIONS MUST BE INCLUDED ON THE
FRAME AND HOOKS. REFER SEQ-SP FOR PROJECT DRAWINGS.
DETAILS ALUMINIUM VALVE PIT COVER WITH
HINGED PERSON ACCESS COVER AND G2. FOR THE RELATIONSHIP BETWEEN THE LEVELS
ANODE HOOK SEE NOTE G10. REMOVABLE BOLTED SIDE PANELS. FOR REFER TO THE LEVEL INTERACTION DIAGRAM
DETAILS REFER TO NOTE G5 ON ON DRAWING SEQ-SPS-1102-5
DRAWING SEQ-SPS-1301-1 &SEQ-SPS-1102-6.
FOR DETAILS OF JOINT BETWEEN WALL AND TOP G3. FOR DETAILS OF VALVE PIT PIPE FITTING
SLAB REFER TO DRAWING No SEQ-SPS-1407-1 REQUIREMENTS SEQ-SPS-1301-1.
GALVANISED STEEL LADDER WITH G4. THE MAXIMUM HEIGHT FROM THE FLOOR TO
12 THICK "FOSROC EXPANDAFOAM" SHEET EXTENDABLE STILES. REFER THE HAND WHEEL ON THE RESILIENT SEATED
TOPPED WITH FOSROC ROADSEAL" JOINT SEQ-SPS-1305-1. SLUICE VALVE IS TO BE 1400.
SEALANT OR APPROVED EQUIVALENT. ALUMINIUM COVER SUPPORT BEAM. FOR G5. THE MINIMUM CLEARANCE UNDER THE FLANGES
REQUIREMENTS REFER TO COVER IN THE VALVE PIT IS TO BE 300 FOR PIPE
CONCRETE ACCESS ROAD WITH 300 DRAWINGS SEQ-SPS-1304-1 DIAMETERS UP TO AND INCLUDING DN300.
VERTICAL KERB ADJACENT TO PUMP SEQ-SPS-1304-8 G6. FOR DETAILS OF PIPES AND FITTINGS SEE
WELL AND GRIT COLLECTOR DRAWING SEQ-SPS-1301-2
MAINTENANCE HOLE. G7. THE POLYETHYLENE INTERNAL LINING MAY BE
NOTE: SEE SEQ-SPS-1102-6 FOR PRESSURE SENSOR. FOR DETAILS OMITTED IF PRIOR APPROVAL IS GIVEN BY
AN ALTERNATIVE ARRANGEMENT REFER SEQ-SP SEQ-SP
FOR SMALL STATIONS. G8. THE PIPES THAT PASS THROUGH THE WELL
RL*.*** WALL ARE TO BE EITHER POLYETHYLENE OR
STAINLESS STEEL WITH A HEAT SHRUNK
MAXIMUM
POLYETHYLENE SLEEVE. THE PIPES ARE TO BE
350
300
FULLY SEALED FUSION WELDED TO THE LINING.
RL*.*** TOP OF FOR EXCEPTION SEE NOTE G7.
WALL G9. THE INTERNAL PUMP WELL DIAMETER IS TO
RL*.*** RL*.*** SUIT PROJECT REQUIREMENTS AND WILL VARY
20
CL ACCORDING TO THE PUMP SIZE, NUMBER OF
PUMPS AND LAYOUT. THE PUMP WELL INTERNAL
RL*.*** DIMENSION IS TO BE CHOSEN FROM ONE OF
MINIMUM
Q100 FLOOD LEVEL TO BE CL CL
RL*.*** THE FOLLOWING STANDARD SIZES:
1600
SHOWN ON PROJECT DRAWINGS. RL*.*** (1800) 2700 4000
(2100) 3000
CLEARANCE SEE
HANDWHEEL
2400 3600
HEIGHT
1800 & 2100 MAY BE CONSIDERED FOR SMALL
NOTE G5.
POTABLE WATER PIPE. FOR DETAILS
FLANGE
REFER TO DRAWING SEQ-SPS-1308-1 OVERFLOW LEVEL RL*.*** STATION ONLY, SUBJECT TO SEQ-SP APPROVAL.
G10. A STAINLESS STEEL ANODE HOOK IS TO BE
PROVIDED ON PUMPING STATION WITH PUMP
15
100
OBVERT OF PIPE S7. THE ACCESS ROAD MUST HAVE A 300 HIGH
THE WALLS ARE TO HAVE A MINIMUM VERTICAL KERB ADJACENT TO THE PUMP WELL
THICKNESS OF 230. SEE NOTE S9. AND GRIT COLLECTOR MAINTENANCE HOLE TO
BOTTOM WATER LEVEL *.*** PREVENT VEHICLE ACCESS TO TOP SLAB.
S8. THE CONCRETE STRENGTH IS TO BE S40 TO
IL*.*** WATER SERVICES ASSOCIATION CONCRETE
PUMP WELL INLET SEWER IS TO BE A
200
MINIMUM ID225. WHERE THE SPECIAL CLASS WSA 114
INCOMING SEWER, TO THE GRIT BOTTOM OF LINING S9. THE MINIMUM EXPOSURE CLASS OF THE
COLLECTOR MAINTENANCE HOLE IS VACTOR AND AIR PIPES. REFER SEQ-SP INTERNAL CONCRETE SURFACE IS TO BE B2 TO
GREATER THAN ID225 THEN THE 22.5° FOR DETAILS. AS3735 . THE COVER TO THE REINFORCEMENT
PUMP WELL INLET PIPE IS TO BE THE NOTE: SEE SEQ-SPS-1102-6 FOR AN IS TO BE MEASURED FROM THE
1200
SAME DIAMETER AS THE INCOMING 300 ALTERNATIVE ARRANGEMENT FOR REINFORCEMENT STEEL TO THE EMBEDMENT
SEWER. REFER SEQ-SPS-1301-2 FOR SMALL STATIONS. LUGS OF THE POLYETHYLENE LINING AND NOT
DETAILS TO THE EXPOSED OUTER SURFACE.
GRIT COLLECTOR MAINTENANCE HOLE. S10. THE STRUCTURE IS TO BE TESTED IN
300
750 MAXIMUM
SEE NOTE G7
FOR DETAILS REFER TO DRAWING
LOCATION OF CABLE ENTRY. CARE MUST BE G3. THE PUMPS ARE TO BE SELECTED FROM SEQ-SP LIST FOR ZONES 1
SEQ-SPS-1304-10 TO SEQ-SPS-1304-17 TO 6. FOR PUMPS OUTSIDE THE STANDARD RANGE APPROVAL
TAKEN IN LOCATING PUMPS TO ENSURE
MAXIMUM CLEARANCE WHEN REMOVING PUMPS. MUST BE GIVEN PRIOR TO FINAL DESIGN BY SEQ-SP.
VALVE G4. WHERE THE TOP SLAB SIZE AND LAYOUT ALLOW, THE MINIMUM
PIT CLEAR OPENING WIDTH IN THE TOP SLAB IS TO BE THE TOTAL OF
THE WIDTH OF THE PUMP INCLUDING THE 90° DISCHARGE BEND
DN25 BRONZE SWING CHECK VALVE TO AS1628 PLUS A 75 CLEARANCE ALL ROUND.
OR QUEENSLAND URBAN UTILITIES APPROVED FOR DETAILS OF THE DN100 AND DN150 HOSE THE OPENING HOWEVER CANNOT BE LESS THAN THE LENGTH OF
EQUIVALENT. VALVE TO BE INSTALLED AT 30° CONNECTION BEND ASSEMBLIES REFER SEQ-SP THE HOSE CONNECTION BEND PLUS THE SWING-CHECK VALVE
SLANT TO THE VERTICAL. .
PLUS 150 CLEARANCE. THE MINIMUM OPENING FOR DN100
STAINLESS STEEL PUMP DISCHARGE WALL PIPE PIPEWORK IS 815 AND FOR DN150 PIPEWORK IS 940.
TO BE DETAILED ON PROJECT DRAWINGS. THE HOSE CONNECTION BEND MUST BE ABLE TO BE REMOVED
VERTICALLY WITHOUT ROTATING HORIZONTALLY.
150 MINIMUM CLEARANCE SEE NOTE G4. 3 THICK INSERTION RUBBER GASKET IF THE BEND DIMENSION IS LESS THAN THE PUMP DIMENSION
THEN THE DESIGNER MUST ENSURE THAT THE PUMP CAN BE
SS316 HOSE CONNECTION BEND QUICK COUPLING
REMOVED BY ROTATING THE PUMP ASSEMBLY AFTER THE HOSE
DN25 STAINLESS STEEL NIPPLE TO BE INSTALLED WITH RUBBER O RING. THE QUICK COUPLING IS CONNECTION BEND HAS CLEARED THE TOP SLAB.
WITH THREAD TAPE OR ANTI-GALLING COMPOUND. AVAILABLE FROM QUEENSLAND URBAN UTILITIES. IN A ROTATED POSITION A MINIMUM CLEARANCE OF 75 AROUND
DIAMETER TO BE DETAILED ON PROJECT THE PUMP AND BEND IS TO BE MAINTAINED.
ELECTRICAL CABLES SEE NOTE G10. DRAWINGS. THE PROJECT DESIGNER MUST POSITION ALL FITTINGS SUCH AS
SAFETY MESH HOOKS AND CABLE ACCESS TO GIVE THE MAXIMUM
3 THICK INSERTION RUBBER GASKET
ROOM TO REMOVE THE PUMPS. BY POSITIONING THE ABOVE
SHACKLE LOCATIONS ARE TO BE DETERMINED BY ITEMS WITH CARE, THE CLEAR OPENING MAY BE THE SAME AS THE
QUEENSLAND URBAN UTILITIES. SEE ALSO NOTE G6. CONCRETE OPENING SIZE.
PUMP
6000 MAXIMUM
G5. FOR PUMP ASSEMBLIES LESS THAN 350kg TOTAL WEIGHT, USE
(SEE NOTE G2)
WELL SS316 HOSE CONNECTION BEND. THIS BEND IS 10mm LONG LINK SS316 CHAIN WITH A MAXIMUM WORKING LOAD
AVAILABLE FROM QUEENSLAND URBAN UTILITIES. OF 0.75 TONNES.
DIAMETER AND MODEL TO BE DETAILED ON FOR PUMP ASSEMBLIES 350kg. OR GREATER TOTAL WEIGHT, USE
.
.
PLICORD WATER DISCHARGE 150" WITH SEQ-SPS-1102-5 &SEQ-SPS-1102-6 TESTED SS316 SHACKLES WITH A WORKING LOAD LIMIT OF A
DIAMETER AND LENGTH TO SUIT PROJECT. MINIMUM OF TWICE THE TOTAL WEIGHT OF THE PUMP ASSEMBLY.
BOTTOM WATER LEVEL THE MINIMUM SHACKLE SIZE IS TO BE 10mm.
G7. FOR CHAIN SUSPENDED PUMPS THE MAXIMUM DEPTH FROM TOP
SLAB LEVEL TO THE CENTRELINE OF THE DISCHARGE PIPE IS TO
16 WIDE 316 STAINLESS STEEL "BAND-IT" STRAP BE 750.
TYPICAL SUBMERSIBLE PUMP SUPPLIED WITH 90° WHERE POSSIBLE THIS DISTANCE SHOULD BE REDUCED TO
AND BUCKLES TO SECURE HOSE. TYPICAL BOTH
PROVIDE EASIER ACCESS TO THE BOW SHACKLE ON TOP OF THE
ENDS. HOSE TAIL DELIVERY BEND. DETAILS ARE TO BE
1200
HOSE CONNECTION BEND.
SHOWN ON PROJECT DRAWINGS. SEE NOTES G3 NOTE: CARE IS TO BE TAKEN TO ENSURE CLEARANCE FOR THE
AND G8. OPERATION OF THE HANDWHEEL ON THE METAL WEDGE SLUICE
THE PUMP CLEARANCE IS TO BE SET AS LOW AS VALVE ON THE DISCHARGE PIPE IN THE VALVE PIT.
POSSIBLE AND IS TO BE AT THE PUMP G8. THE 90° PUMP DISCHARGE BEND IS NORMALLY SUPPLIED WITH
THE PUMP. THE DESIGNER IS TO CONFIRM THE FLUID VELOCITY IN
MANUFACTURER'S MINIMUM REQUIREMENTS. THE
THE DELIVERY HOSE. IF HIGH HEAD LOSSES ARE INDICATED A
.
DIMENSION IS TO BE SHOWN ON THE PROJECT FABRICATED SS316 ENLARGING BEND IS REQUIRED AND IS TO BE
DRAWINGS. DETAILED ON THE PROJECT DRAWINGS.
G9. ALL BOLTS AND NUTS ARE TO BE GRADE 316 STAINLESS STEEL
90° PUMP DISCHARGE BEND. SEE NOTE G8. AND ARE TO BE INSTALLED WITH ANTI-GALLING COMPOUND.
MASS CONCRETE BENCHING. TO BE DETAILED ON G10.ALL PUMPS ARE TO BE SUPPLIED WITH CABLES 15.000m LONG.
PROJECT DRAWINGS THE CABLE MUST BE OF SUFFICENT LENGTH TO ALLOW THE PUMP
FLOOR TO GRADE TO VACTOR PIPE INLET TO BE REMOVED TO A POSITION 2.500m FROM THE TOP SLAB
OPENING WITHOUT ELECTRICALLY DISCONNECTING IT. THE
75 MINIMUM CLEARANCE TO TOTAL PUMP 75 MINIMUM CLEARANCE TO CABLES ARE TO BE CABLE-TIED TO THE CHAIN AND THESE TIES
FITTINGS IN COVER OPENING . LENGTH
. . FITTINGS IN COVER OPENING CAN BE REMOVED AS THE PUMP IS EXTRACTED. EXCESS CABLE IS
TO BE SUSPENDED FROM THE CABLE HOOK ON THE WALL PIPE
.
BRACKET.
CLEAR OPENING IN TOP SLAB IF THE PUMPS REQUIRE MORE THAN 15.000m OF CABLE TO REACH
COVER SEE COVER OPENING ABOVE THE SWITCHBOARD THEN AN INTERMEDIATE ELECTRICAL
SEE NOTE G4 DISCONNECT BOX IS REQUIRED.
SECTION ELEVATION
NOT TO SCALE
REV. No. DATE DESCRIPTION AUTH.
SEWAGE PUMP STATION STANDARD DRAWING CoGC LCC RCC QUU UW
SEQ WATER CHAIN SUSPENDED
DRAWING No. VERSION
TYPICAL
MULTI- COVER
ARRANGEMENT
85
TEMPORARY BARRICADE
GUARDRAIL WITH TOE
BOARD BELOW
2
TYPICAL 1304-9 85
SINGLE COVER 4
1304-8
ARRANGEMENT TYPICAL
DOUBLE COVER
ARRANGEMENT
20 YP
SAMPLING FLAP
0
GRILLE
T
85
IN OTHER VIEWS) LOCK BOX CLEAR
REFER TO DWG 1304-5
DAVIT BASE FOR "SALA" POST POSITIONED TO
PORTABLE DAVIT DAVIT BASE FOR PROVIDE CLEAR ACCESS
"SALA" PORTABLE TO PIT STEPLADDER
DAVIT
REV. No. DATE DESCRIPTION AUTH.
SEWAGE PUMP STATION STANDARD DRAWING CoGC LCC RCC QUU UW
SEQ WATER ALUMINIUM ACCESS COVERS - OPTION 1
DRAWING No. VERSION
10
SECTION A
SCALE NTS -
HINGE OPEN DETAIL
NTS
A
2
1304-9
DRAIN HOLE
14 (BOTTOM PLATE)
50
3
65x3 SQUARE Ø5 DRAIN
BOX-RADIUSED HOLE TYP
B 40x40x4 EA 250
ALUMINIUM HINGE -
130 6 THK ALUMINIUM LID
PIVOT BLOCK 120 34 64
WELDED TO FRAME EXTENDED LID PLATE
84 OVER HINGE
10 10
32
5 TYP
54X6 ALUMINIUM 25x25x8 ALUMINIUM PAD 10
PLATE FULLY 10 WELDED TO EACH
SEAL WELD CORNER REFER TO
10
1304-8
70
5 TYP
FULLY
60
SEAL WELD
A
- M12x75 LONG BOLT
5 TYP
72 TYP C/W NYLON NUT &
S/S WASHERS
70x6 ALUMINIUM PLATE S/S WASHER B
FULLY SEAL WELDED TO -
BACK OF 60x60x6 EA FRAME NYLON SHOULDERED
BUSHES HINGE LID PLATE TRANSPARENT FOR CLARITY
ALUMINIUM ANGLE NTS
STIFFENER COVER
60x60x6 EA FRAME
MANUFACTURE TO
WITH TOP LEG TRIMMED
DOWN OVER LENGTH OF PROVIDE AND CONFIRM
HINGE BOX FINAL SIZE 64
70 60 39
20x10 NEOPRENE FOAM 45 DRILL TO ALLOW
STRIP SEAL ADHESIVE 14
6
184 INSERTION OF M12 NYLON
BACKED REFER TO 1304-8 5
SHOULDERED BUSH R2
DRILL TO ALLOW
INSERTION OF M12
50
54
44
SECTION 1
29
NYLON SHOULDERED
NTS BUSH
4
DETAIL B
DETAIL A SCALE NTS -
SCALE NTS -
60 TYP
9 TYP
9
COVER #1 9 COVER #2 COVER #3
9
9
40x40x4 EA ALUMINIUM 60x60x6 EA ALUMINIUM COVER #1 LHS COVER #1 RHS COVER #2 LHS
FRAME ON COVER 1 TRIMMED TO SUIT ON COVER 2
20
FLAP DOOR, LOCK DETAIL
BLIND RIVETS
125
227
16
40
DRAIN HOLE Ø5
COATS OF BITUMINOUS PAINT B
20
ON SURFACES IN CONTACT - 50 x 30 x 32 HIGH AL
GROUT
STOPPER BLOCK WITH
SET SCREW TO FIX TO
110
FLOOR OF LATCH BOX 58
30 118
LATCH
SECTION B
225
45 NTS
60
GREASE
NIPPLE NOTE
A 1. ALL MEASUREMENTS IN MILLIMETRES.
85 - 2. CONFIRM SIZE OF LOCK WITH SEQ-SP AND POSITION
LOCKING BOLT & PLATES TO ALLOW EASY INSERTION &
PLATE WITHDRAWAL OF LOCK & KEY WITH LATCH BOX.
50x20x10 THK LATCH HANDLE 3. THESE DRAWINGS COMMUNICATE INTENT & FUNCTION OF
FOR QUARTER 85 x 100 LONG x LATCH MECHANISM & ARE NOT FABRICATION OR
TURN LATCH 10 THK. SS G316 CONSTRUCTION DRAWINGS.
55 365 4. FRAME & SAFETY GRILL TO ALLOW FOR LOCKING & LATCH.
15
16
50x10 ALUM.
PLATE 6 6
TYP
22
85 TYP 10
26
50
SECTION 2
36
SCALE NTS
10
10
CLEAR
35 TYP
TYP
GRILLE DOUBLE HINGE
DETAIL-UP POSITION 50x10 ALUMINIUM FLAT BAR DETAIL 3
OUTER BEARER BARS SCALE NTS
10
35
10
50
DETAIL 1
SCALE NTS
80
TYP
10
SLIDE-FIT SAFETY HINGED SAFETY
10 GRILLE GRILLE
10
10
10
10
RADIUS R5 ON LOWER
CORNER OF GRILLE 60x60x6 EA
FLAT BAR ALUMINIUM 60x3 FLAT BAR 60 5
ANGLE FRAME
HINGE PIN SECTION A
REFER TO DWG SCALE NTS
1304-6
HINGED SAFETY
GRILLE
SLIDE-FIT SAFETY 20 TYP
GRILLE
A
-
10
DETAIL 2
SCALE NTS
CENTRE GRILLE DETAILS
NEOPRENE FOAM A 70
STRIP SEAL
- SLOT 14 WIDE
BONDED TO
FRAME x 25 CTRS
35
60
23
6
C
25
70
BACK OF ACCESSES COVER -
BLOCK 25x25x8
FOUR REQ'D ON
SINGLE COVER
25 KEYWAY DETAIL SECTION C
NTS SCALE NTS -
B
-
AFFIX 1 OR 2 PLATES
TREAD PLATE DEPENDING ON
APPLY YELLOW POSSITION OF
PAINT CENTRE OF GRAVITY
40
10
NEOPRENE FOAM
STRIP SEAL BONDED
TO FRAME 20x10 THK
46
LID
6 15
DETAIL 1
8
GRILLE CENTRE
NOT TO SCALE OF GRAVITY TYP 38
FOR SECTION VIEWS DETAIL 4
REFER TO DWG 1304-4 25 SAMPLING FLAP NTS
SECTION A
SCALE NTS -
WELD DETAIL SECTION B
NOT TO SCALE SCALE NTS -
67
6
EX 50x3
3
EXTRUDED
32
GUIDE BLOCK COLLAR TUBE
FLAT 32 x 10 x 32 LONG 20
45
° Ø60 x 3 THK TUBE
30 LONG
4 SLOTS
14 WIDE x
A
25 TYP
35 CTRS-TYP
-
965
LOCKING PIN WELD
Ø60 x 3 THK LOCKING PIN
TUBE EX Ø12 BAR
70 LONG TO STANTION
56
50
100
M8 S/S BOLT
200
120
50
35
190
BRACE
20 TWO REQ'D
70 21 21
35
20
SUPPORT POST POST ASSEMBLY
60
SECTION A DETAILS ELEVATION
SCALE 1:10 -
90
150
42
42 40 TYP
TYP Ø60 x 3 THK 18 24
10 SLOPING FACES M12 ANCHOR
TUBE
4 TYP STUDS 316 S/S
100
20
42
TYP
32
46
40
70
88
5 2
8 Ø5
20
TYP
150
90
Ø5
30°
12 20
38
10
13
6 88 DETAIL 2
TYP 14 SCALE 1:5
TYP
SEE NOTE 16
COVER 2
PUMP 2
* A LIQUID APPLIED ACRYLIC-POLYURETHANE COMPOSITE INSCRIPTIONS. THE MINIMUM TEXT HEIGHT IS TO BE 50 THE FOR DETAIL OF ADJOINING SEAL
COATING INCLUDING A 16/30 CRUMBED RUBBER (SUCH AS ORIENTATION OF THE TEXT SHOULD BE SUCH THAT THE TEXT CAN OF PART OPENING COVERS REFER
DIMENSION FOR
NEOFERMA NEOTOP). BE READ FROM THE SWITCHBOARD.
PUMP REMOVAL
TO DWG. NO. SEQ-SPS-1304-12
SEE NOTE 16
3.2. WHERE THE ALUMINIUM FRAME MAY BE IN CONTACT WITH 15. COVER WIDTH: THE MAXIMUM WIDTH OF THE COVER INCLUDING
CONCRETE THE ALUMINIUM IS TO BE PAINTED WITH A HINGES IS TO BE 1200mm. THIS IS TO ALLOW MANUAL REMOVAL FOR DETAILS OF HINGE REFER
MINIMUM OF TWO COATS OF BITUMENOUS PAINT OR SEQ-SPS OF THE COVER WHEN OPEN IN THE VERTICAL POSITION. TO DWG. NO. SEQ-SPS-1304-12
SEE NOTE 16
APPROVED ALTERNATIVE. 16. DIMENSIONS: THE INTERNAL DIMENSIONS OF THE OPENINGS
COVER 1
4. SAFETY MESH: STAINLESS STEEL SAFETY MESH PANELS ARE TO BE ARE TO BE INDICATED ON THE PROJECT DRAWINGS. THE SIZE OF
PUMP 2
PROVIDED UNDER THE COVERS OVER THE PUMPS. THE SAFETY EACH SEPARATE COVER IS TO BE INDICATED ON THE PROJECT REMOVABLE FRAME SUPPORT
MESH IS TO BE DESIGNED TO PREVENT A PERSON FROM FALLING DRAWINGS AS INDIVIDUAL COVERS ACROSS THE WHOLE OPENING REQUIRED BETWEEN PUMPS TO
THROUGH AN OPEN HATCH. THE SAFETY MESH IS TO BE IN MAY VARY IN SIZE. ALLOW COVERS TO BE REMOVED
INDIVIDUAL PANELS OVER EACH SEPARATE PUMP THE MESH MUST 17. CLEARANCE: THE SIZE OF THE COVER OPENING IS TO BE DESIGNED INDEPENDENTLY OF OTHER PUMP
BE EASILY REMOVABLE FROM THE SURFACE. THE MESH IS TO BE INSTALLATION. FOR GUIDE RAIL PUMPS THE CLEARANCE TO THE COVERS
CLEAR OPENING
SEE NOTE 16
FITTED AS CLOSELY AS POSSIBLE TO THE UNDERSIDE OF THE THE AFORE-MENTIONED 75mm CLEARANCE APPLIES TO ALL
COVER TO PROVIDE MAXIMUM CLEARANCE FOR CABLES AND PUMP FITTINGS IN THE OPENING INCLUDING THE SAFETY MESH HOOKS
SEE NOTE 16
FITTINGS WITHOUT PROVIDING EXTRA OPENINGS IN THE MESH AND CABLE SUSPENSION HOOKS.
PUMP 1
PANEL. THE MESH IS TO HAVE DIAMETER 6 BARS AT 75 CENTRES.
5. REMOVABLE SUPPORT BEAMS: WHERE MULTI-PART COVERS NON-TRAFFICABLE LOCATIONS ARE TO BE DESIGNED TO AS3996
REQUIRE ADDITIONAL SUPPORT BEAMS THESE BEAMS SHOULD NOT TABLE 3.1 CLASS A FOR NON-TRAFFICABLE LOCATIONS AND FOR
BE PLACED OVER EQUIPMENT REQUIRING REMOVAL SUCH AS PEDESTRIAN LOADS ONLY. THE TOP SLAB OF THE PUMP STATION IS
SEE NOTE 16
VALVES. THESE BEAMS SHOULD BE PROVIDED WITH LIFTING LUGS TO BE 300mm VERTICALLY ABOVE SURROUNDING GROUND LEVEL
OR HOLES. THE BEAMS SHOULD BE BOLTED IN PLACE. AND ACCESS ROAD TO PREVENT ANY POSSIBLE VEHICLE ACCESS.
FRAME HOLD DOWN LUGS.
6. STRENGTHENING WEBS: ADDITIONAL STRENGTHENING WEBS MAY 19. FLUSH MOUNTING: ALL COVERS, FRAMES, HINGES AND HANDLES
NOTE: NUMBER AND LOCATION
VACTOR COUPLING
BE REQUIRED ON THE UNDERSIDE OF COVERS. THE SIZE, TO BE FLUSH MOUNTED LEVEL WITH CONCRETE TOP SLAB.
DIMENSION FOR
LOCATION AND DIRECTION SHOULD BE DESIGNED TO SUIT EACH 20. STAINLESS STEEL THREADED ASSEMBLY: ALL THREADED
PUMP ACCESS
SEE NOTE 16
INDIVIDUAL COVER. ALSO SEE NOTE 18. STAINLESS STEEL NUTS AND BOLTS ARE TO BE ASSEMBLED WITH HANDLE AND LATCH MECHANISM
COVER 1
PUMP 1
7. WEIGHT: EACH SEPARATE COVER SHOULD HAVE A MAXIMUM ANTI-GALLING COMPOUND "DURALAC" OR SEQ-SPS APPROVED REFER TO DWG NO.
WEIGHT OF 32 Kg. THE MAXIMUM LIFT AT THE HANDLE IS TO BE NO EQUIVALENT. SEQ-SPS-1304-13 FOR DETAILS.
GREATER THAN 16 Kg. 21. WELDING: ALL ALUMINIUM WELDING SHALL COMPLY WITH THE NOTE: SEPARATE MECHANISM
8. FRAME MOUNTING: THE ALUMINIUM FRAME SHOULD BE GROUTED REQUIREMENTS SET OUT IN AS/NZS 1665.2004 AND AS/NZS ISO REQUIRED FOR EACH COVER
MIN.
IN PLACE USING NON-SHRINK EPOXY GROUT. CAST INSITU FRAMES 18273.2006. TO MINIMISE CREVICE CORROSION THE COVERS AND
MAY BE APPROVED BY QUEENSLAND URBAN UTILITIES. SEE NOTE 3 FRAME ARE TO BE FULLY SEAL WELDED.
FOR PAINTING. FOR DETAILS OF EDGE SEAL
9. HINGES: HINGES MUST BE FLUSH MOUNTED WITH NO TRIPPING AND FRAME REFER TO DWG.
HAZARD. REMOVABLE HINGE GUDGEONS ARE NOT PERMITTED. NO. SEQ-SPS-1304-12 300
HINGES SHOULD ALLOW COVER TO ROTATE 180°. THE COVER IS MIN.
TO BE EASILY REMOVED WHEN IN VERTICAL POSITION AND
WHERE A PUMPING STATION DOES
CARRIED TO A REMOTE LOCATION. HINGES MUST PROVIDE
NOT HAVE A SEPARATE MH COVER
POSITIVE LOCKING WHEN COVER IS IN CLOSED POSITION.
FOR ACCESS TO THE VACTOR PIPE
10. SEAL: A NEOPRENE RUBBER ODOUR SEAL IS TO BE PROVIDED
THE VACTOR PIPE MAY BE INSTALLED
UNDER THE COVERS. THE SEAL IS TO BE MOUNTED ON THE COVER
UNDER THE ALUMINIUM PUMP WELL PLAN OF TYPICAL PUMP WELL COVER INSTALLATION
AND NOT ON THE FRAME. THE SEAL IS TO BE FIXED TO ALLOW NOT TO SCALE
COVER. THE COVER OVER THE
REPLACEMENT. THE SEAL IS NOT TO TAKE THE LIVE AND DEAD
VACTOR PIPE COUPLING IS TO OPEN
LOADS OF THE COVER. THE ALUMINIUM COVER IS TO BE SEAL
FIRST IN THE SERIES.
WELDED TO COMPLETE THE ODOUR SEAL. TO BE USED IN
11. LIFTING HANDLES: A RECESSED LIFTING HANDLE IS TO BE NON-TRAFFICABLE
PROVIDED ON THE UPPERSIDE OF EACH COVER. THIS HANDLE MAY LOCATIONS ONLY
BE COMBINED WITH THE LATCHING MECHANISM. IN ADDITION A
MINIMUM OF TWO LIFTING HANDLES ARE TO BE PROVIDED ON THE
UNDERSIDE OF THE COVER. HANDLES ARE TO ALLOW LIFTING BY
PERSONS OR ALTERNATIVELY BY TRUCK MOUNTED HOIST.
TO SUIT PROJECT
REMOVABLE SECTION OF FRAME BOLTED TO Ø6 BARS AT 75 CRS WITH ALL
EDGE FRAME WITH STAINLESS STEEL BARS RESISTANCE WELDED
DIMENSIONS TO BE DETAILED
1. STAINLESS STEEL IS TO BE INSULATED CPUMP Ø8 STAINLESS STEEL EDGE
L
FROM ALUMINIUM.
ON PROJECT DRAWINGS
CIRCUMFERENCE BARS FULLY WELDED
2. IF MORE THAN 2 NO. OFF PUMPS ARE
INSTALLED THEN A REMOVABLE FRAME IS PROVIDE SEPARATE SAFETY MESH
REQUIRED BETWEEN EACH PUMP. PANELS OVER EACH INDIVIDUAL PUMP
3. THE REMOVABLE FRAME IS TO BE
STAINLESS STEEL MESH WITH
LOCATED TO PROVIDE MAXIMUM
TO SUIT PROJECT
Ø6 BARS AT 75 CRS WITH ALL
CLEARANCE TO PUMP CASING WHICH MAY
CPUMP BARS RESISTANCE WELDED
NOT BE EQUAL DISTANCE FROM PUMP L
CENTERLINE. Ø8 STAINLESS STEEL EDGE
CIRCUMFERENCE BARS FULLY WELDED
2 NO. OFF HINGES REQUIRED FOR EACH COVER
IN 5
1 NO. OFF STRIKER BOX REQUIRED FOR EACH COVER TE 44 TO SUIT PROJECT
RN
AL
HOLES IN FRAME FOR HOLD-DOWN BOLTS. IN PUMPING STATIONS WHERE THE VACTOR
DIAMETER AND NUMBER REQUIRED TO BE PIPE IS LOCATED UNDER THE PUMP COVER
DETERMINED BY COVER MANUFACTURER PROVIDE A CIRCULAR OPENING IN THE
MESH FOR THE VACTOR PIPE COUPLING
ALL WELDED JOINTS TO BE CONTINUOUS WELDED
TO SUIT PROJECT
ALUMINIUM FRAME
TWIN HINGE Ø16 GUDGEON PINS FOR EACH 2 NO. OFF Ø10 ALUMINIUM
HINGE ROD LIFTING EYES
100100
6 THICK ALUMINIUM FLOOR PLATE WITH PATTERN ON UPPER
SIDE. FOR DETAILS OF PAINTING ON UPPER SIDE REFER TO
NOTE 3 ON DRAWING NO. SEQ-SPS-1304-10
TO BE USED IN
UNDERSIDE VIEW OF COVER NON-TRAFFICABLE
LOCATIONS ONLY
NOTE: THE COVER SHOWN IS FOR THE FIRST OPENING
COVER. THE SECOND AND ANY FUTHER OPENING
COVERS REQUIRE A MODIFIED SIDE TO ACCOMMODATE
THE ADJACENT ODOUR SEAL.
RECESS
60 6 54 G1. FOR ALL NOTES DETAILING COVER
*
8 REQUIREMENTS REFER TO DRAWING
100
NO. SEQ-SPS-1304-10
20 G2. THE HINGE DETAIL SHOWN ON THIS
ALUMINIUM PIVIOT BLOCK 38 156
WELDED TO FRAME. FOR DRAWING IS TO BE USED FOR BOTH
DIMENSIONS SEE DETAIL COVER MANUFACTURER TO PROVIDE THE PUMP WELL COVERS AND THE
102
BELOW ALUMINIUM ANGLE STRENGTHENING VALVE PIT COVERS
5 RIBS TO SUIT EACH COVER
2 NO. OFF Ø16 NON-SHRINK EPOXY GROUT
ALUMINIUM ROUND HINGE M12 STAINLESS STEEL CHEMICAL ANCHOR
PINS WITH INSULATING WASHERS AND SLEEVE SECOND BAR ON HINGE SIDE OF COVER
SECTION THROUGH ASSEMBLED HINGE IN CONTACT WITH ALUMINIUM FRAME TO BE SET AT 75 CENTERS FROM EDGE
BAR TO ALLOW MESH TO PIVOT
SCALE 1 : 2 FULL SIZE A1 SHEET P SHAPED NEOPRENE SEAL
COVER 2
PUMP 2
AROUND HOOK
COVER 1
PUMP 2
RECESS BAR ON SAFETY MESH PANEL
B
HOOK FORMED FROM Ø12 ROUND -
6 THICK ALUMINIUM
BAR WITH YELLOW HEAT SHRINK
HINGE SIDE PLATES
SLEEVE. LOCATIONS OF HOOKS ARE
12 9 TO BE SHOWN ON PROJECT FRAME
COVER 2
TYPICAL SECTION OF INSTALLED FRAME
PUMP 1
PLAN.
A A
SCALE 1 : 2 FULL SIZE A1 SHEET
INSIDE HINGE
6 - -
SIDE PLATES
BLOCK
PIVOT
85 53 50 50
SECTION A
-
6
B
COVER 1
PUMP 1
9 -
12 FIRST OPENING COVER FIRST OPENING COVER
SECOND OPENING COVER
PUMP NO. 2 PUMP NO. 1 PUMP NO. 1
DO NOT WELD HINGE PINS
ON INSIDE OF SIDE PLATES ALUMINIUM COVER SHOWN SHADED
12
ALUMINIUM FRAME
43
10 19 14 20 6 6
3 66 66 116
R3 TYPICAL 132
9 6 ADJOINING EDGE SEAL SUPPORT MADE FROM SPECIAL
ALUMINIUM EXTRUSION (AS DETAILED IN EXTERNAL
12 REMOVABLE BEAM MADE FROM CUT DOWN SPECIAL FRAME) SEAL WELDED TO SECOND OPENING COVER
ALUMINIUM EXTRUSION SEAL WELDED BACK TO
3 BACK. BOLT TO EXTERNAL FRAME WITH 2 NO. OFF COVER MANUFACTURER TO PROVIDE
22 COUNTER SUNK STAINLESS STEEL BOLTS EACH ALUMINIUM ANGLE STRENGTHENING
54 R9.5
45 END. FOR PLAN VIEW SEE PLAN OF FRAME ON RIBS TO SUIT EACH INDIVIDUAL COVER
2 R22 10 DRAWING NO. SEQ-SPS-1304-11
15 250
3 14 15 16 17 21
WALL OF BOX THREADED TO SUIT
BOLT AND ASSEMBLED USING 18
4
"DURALAC" ISOLATING COUMPOUND
7 20 SEE NOTE G3
15
50
INSTALL SHAFT WITH GREASE, "BP 19 SEE NOTE G3
ENERGREASE HYDROTAC" OR SEQ-SP
15 APPROVED WATER RESISTANT GREASE 80 20 SEE NOTE G3
22
8 3
HOLES FOR PIANO 5 15 1
HINGE BLIND RIVETS
9
GAP
80 2 130 NOMINAL
2
A A
- - 6
37 40 15
8 SHOWN IN
4
6 OPEN POSITION
15 50 9 14 15 16 16
WALL OF BOX THREADED TO SUIT
5 BOLT AND ASSEMBLED USING
5 "DURALAC" ISOLATING COUMPOUND
10 11 12 13 23
1 ASSEMBLED USING "DURALAC"
ISOLATING COUMPOUND
SECTION A
14 15 16 17 -
50 25 50 175 6
WALL OF BOX THREADED TO SUIT
306 BOLT AND ASSEMBLED USING (FRAME AND STRIKER BOX SHOWN IS FOR PUMP WELL ONLY)
"DURALAC" ISOLATING COUMPOUND SCALE 1 : 2 FULL SIZE A1 SHEET
40
25 6 12
12 190
45 175 20 150 20
R6 15 2 NO. OFF M10 12 47 25 3
35 40
7 THREADED HOLES
20 X 13 SLOTTED HOLE 15 22
10 R20 R20
Ø7 HOLE
END VIEW SIDE VIEW
50 12 50
66 40
95
75 20 Ø20 ROD
6 3 22 6 Ø13 HOLE
25 30
Ø21 12 THICK PLATE R75
SECTIONAL VIEW
Ø30
21 40
SECTIONAL VIEW 6
R6
25
50 X 50 X 6 ANGLE
TOP VIEW
50
ITEM 5 LOCKING TONGUE
SCALE 1 : 2 FULL SIZE A1 SHEET
222
94 50 X 6 FLAT
25 X 25 X 6 ANGLE
Ø1.5 HOLE
325 225 R10 10 6
Ø20 ROD
94
Ø13
12
3
24 TOP VIEW
37 ITEM 6 LIFTING HANDLE
12
Ø20 ROD SCALE 1 : 2 FULL SIZE A1 SHEET
90 Ø6.5 HOLE
15 13 X 20 LONG
50
SLOTTED HOLE
SIDE VIEW
Ø40
25
Ø21
50 250 6 200 3
306 20 160 20
110 44
66
30 70
25 X 6 FLAT ALUMINIUM 40 80
STRIKER PLATE
120
54 CL TONGUE
12 38
RECESSED STRIKER BOX FOR PUMP WELL COVERS WITH ODOUR SEAL
SCALE 1 : 2 FULL SIZE A1 SHEET
TO BE USED IN
NON-TRAFFICABLE
LOCATIONS ONLY
750
CL
75
53
50
AND COVER
1
-
35
HINGE COVER EDGE FRAME WITH
TYPICAL
SIZE DETERMINED BY COVER
MANUFACTURER
ALUMINIUM PIVOT
5
BLOCK WELDED TO SEE DETAIL OF SIDE SEAL FOR
REMOVABLE BEAM Ø16 TWIN CL
GUDGEON PINS SIZES OF EDGE SEAL
20 30
TO BE USED IN
NON-TRAFFICABLE
LOCATIONS ONLY
RECESS
STRIP GLUED TO UNDERSIDE OF FLOOR PLATE
18
6 38
6
ALUMINIUM EXTRUSION WITH TWO
COATS OF BITUMEN PAINT ON
5
UNDERSIDE SURFACES WHICH ARE
MIN. 2 NO. OFF ALUMINIUM LOCK STAPLES COVER MANUFACTURER TO PROVIDE
IN CONTACT WITH CONCRETE
TO BE PROVIDED ON UNDERSIDE OF ALUMINIUM ANGLE STRENGTHENING RIBS TO
NON-HINGED BOLTED PANELS Ø10 STAINLESS STEEL COUNTERSUNK SUIT EACH COVER
MECHANICAL ANCHOR. NOTE: SILICON 120
SEALANT TO BE PLACED UNDER HEAD IN RECESS
PADLOCK AS INDICATED IN NOTES. CONTACT WITH ALUMINIUM
12
ALUMINIUM ANGLE EDGE FRAME WITH 2 3
ALUMINIUM ANGLE WITH SIZE SIZE TO BE DETERMINED BY COVER - -
TO BE DETERMINED BY COVER MANUFACTURER TO SUIT EACH COVER
MANUFACTURER TO SUIT EACH
COVER
750 CLEAR WIDTH OF OPENING SECTION AND DETAIL LOCATION PLAN
NOT TO SCALE SEE SEQ-SPS-1304-16
ALUMINIUM ANGLE WELDED TO EDGE 2 NO. OFF MIN. PER
25 WIDE X 6 THICK FLAT RUBBER HARDNESS
FRAME. SIZE TO BE DETERMINED BY ATTACHMENT STAINLESS
40 GLUED TO UNDERSIDE OF HINGED COVER
COVER MANUFACTURER. NOTE: TO BE STEEL BOLTS WITH
40 X 40 X 6 ALUMINIUM ANGLE ATTACHED TO EDGE FRAME AND NOT INSULATING WASHERS
WALL TO BE USED IN
NON-TRAFFICABLE
SIDE SEAL BETWEEN BOLTED REMOVABLE SUPPORT BEAM ATTACHMENT LOCATIONS ONLY
AND HINGED COVERS DETAIL 2
SECTION D -
-
V l = 1.2m (typ.)
INSULATED WITH APPROVED SEALANTS, GASKETS, WASHERS AND SLEEVES.
Wl
7. ALL ACCESS COVERS SHALL HAVE THEIR TOP SURFACES COVERED WITH A GREEN COLOURED 'EPIREZ SAFE STEP 550' EXPOXY
ANTI-SLIP COATING OR APPROVED EQUIVALENT.
8. WHERE ALUMINIUM IS IN CONTACT WITH CONCRETE, THE ALUMINIUM SHALL BE PAINTED WITH A MINIMUM TWO COATS OF
BITUMINOUS PAINT OR APPROVED EQUIVALENT.
9. REPLACEABLE SEALS SHALL BE PROVIDED ON THE UNDERSIDE OF THE WET WELL COVERS TO PROVIDE A FULL ODOUR TIGHT SEAL.
COVER Wc
10. ALL ALUMINIUM WELDING TO COMPLY WITH AS/NZS1665 AND ISO18273. HINGE
Dlp
Lc
Hl = 0.2m (typ.)
SINGLE COVER
ARRANGEMENTS
DUAL COVER
ARRANGEMENTS
THREE COVER
ARRANGEMENTS
FIXED REMOVABLE
INTERNAL INTERNAL
SUPPORT SUPPORT BEAM
BEAM REFER NOTE 3
FOUR COVER
ARRANGEMENTS
REMOVABLE
INTERNAL
SUPPORT BEAM
TYPE 4LA TYPE 4LB REFER NOTE 3 TYPE 4LC TYPE 4LD TYPE 4LE
NOTES
1. REFER DRG NO. SEQ-SPS-1304-18 FOR GENERAL AND MATERIAL NOTES.
2. REFER DRG NO. SEQ-SPS-1304-22 FOR WET-WELL ACCESS COVERS GENERAL ARRANGEMENT PLANS.
3. REFER DRG NO. SEQ-SPS-1304-28 FOR REMOVABLE INTERNAL SUPPORT BEAM DETAILS.
4. ARROWS INDICATE OPENING DIRECTION OF COVERS.
SINGLE COVER
ARRANGEMENTS
DUAL COVER
ARRANGEMENTS
THREE COVER
ARRANGEMENTS
REMOVABLE REMOVABLE
INTERNAL INTERNAL
ALTERNATIVE SUPPORT
BEAM
SUPPORT
BEAM
MULTI-COVER REFER NOTE 3 REFER NOTE 3
ARRANGEMENTS
NOTES
1. REFER DRG NO. SEQ-SPS-1304-18 FOR GENERAL AND MATERIAL NOTES.
2. REFER DRG NO. SEQ-SPS-1304-24 AND SEQ-SPS-1304-25 FOR VALVE CHAMBER ACCESS COVERS GENERAL ARRANGEMENT PLANS -
TYPE A AND TYPE B RESPECTIVELY.
3. REFER DRG NO. SEQ-SPS-1304-28 FOR REMOVABLE INTERNAL SUPPORT BEAM DETAILS.
4. ARROWS INDICATE OPENING DIRECTION OF COVERS.
DUAL COVER
HANDRAIL
ARRANGEMENTS
TYPE 2H1 TYPE 2H2
THREE COVER
HANDRAIL
ARRANGEMENTS
TYPE 3H1 TYPE 3H2 TYPE 3H3 TYPE 3H4 TYPE 3H5 TYPE 3H6 (SPECIAL)
FOUR COVER
HANDRAIL
ARRANGEMENTS
TYPE 4H1 TYPE 4H2 TYPE 4H3 TYPE 4H4 TYPE 4H5 TYPE 4H6
ALTERNATIVE
MULTI-COVER
HANDRAIL
ARRANGEMENTS
TYPE 4AH1 TYPE 4AH2 TYPE 4AH3 TYPE 4AH4 TYPE 4AH5 TYPE 4AH6
NOTES
1. REFER DRG NO. SEQ-SPS-1304-18 FOR GENERAL AND MATERIAL NOTES.
2. REFER DRG NO. SEQ-SPS-1304-27 FOR HANDRAILS AND TOEBOARDS DETAILS.
3. FOR VALVE CHAMBER COVER ARRANGEMENT TYPE 5VCA USE THREE COVER HANDRAIL ARRANGEMENT.
4. FOR VALVE CHAMBER COVER ARRANGEMENT TYPE 5VCB USE FOUR COVER HANDRAIL ARRANGEMENT.
5. HANDRAILS FOR VALVE CHAMBERS ARE OPTIONAL, REFER NOTE 3 ON DRG NO. SEQ-SPS-1304-24 OR SEQ-SPS-1304-25.
NOM.
NOM.
B
200
150
(TYP.) 4. HANDRAIL TOEBOARDS ON THE PUMP GUIDE RAIL SIDE SHALL HAVE A 'HINGED AT BOTTOM'
REFER NOTE 12
11 REFER
PUMP GUIDE
RAIL SIDE CONNECTION, REFER TYPE 2 TOEBOARD CONNECTION DETAIL ON DRG NO. SEQ-SPS-1304-27.
NOTE 8
5. SELF CLOSING GATE/S WITH ACCESS COVERS OPENING TOWARDS AND BENEATH THEM, SHALL
130
EXTERNAL
SURFACE TO HAVE TOEBOARDS WITH A 'HINGED AT TOP' CONNECTION, REFER TYPE 3 TOEBOARD CONNECTION
FRAME
BE COATED
EDGE DETAIL ON DRG NO. SEQ-SPS-1304-27.
WITH
PUMP GUIDE
ANTI-SLIP WARNING PLATE 6. SELF CLOSING GATE/S SHALL SWING OUTWARDS AND THE NUMBER OF GATE/S REQUIRED SHALL
RAIL SIDE
ACCESS D
COVER EPIREZ SAFE (TYP.) WELDED TO BE AS FOLLOWS:
COVER
11
REFER STEP 550 6.1. A SINGLE GATE FOR SPANS BETWEEN STANCHIONS OF UP TO A MAXIMUM OF 1500mm.
NOTE 2 WARNING (GREEN) OR
PLATE WELDED
D 6.2. DOUBLE GATES FOR SPANS BETWEEN STANCHIONS GREATER THAN 1500mm AND UP TO A
11 APPROVED
TO COVER EQUIVALENT MAXIMUM OF 2400mm.
ALUMINIUM G 2
BULLET
1
11 6 7. WHERE GATES SPAN THE ENTIRE LENGTH OF A HANDRAIL'S SIDE AND WHERE DEEMED
HINGE
LOCK UNLOCK
ACCESS NECESSARY, ADDITIONAL STANCHIONS AND RAILS SHALL BE PROVIDED EITHER SIDE OF THE
(TYP.) MIN. G 6
11 COVER GATE/S TO INCREASE HANDRAIL STABILITY.
LEN.
REFER
LOCK UNLOCK
120mm 8. FOR COVERS WITH A TOTAL LIFTING WEIGHT LESS THAN 16kg, A SINGLE KEYWAY BOX SHALL BE
C HANDRAIL NOTE 2
WELD TO PROVIDED CENTRALLY (REFER THREE AND FOUR COVER PLANS), UNLESS REQUESTED OTHERWISE
ACCESS
11 REFER
NOTES EXTERNAL BY THE PRINCIPAL. FOR COVERS WITH A TOTAL LIFTING WEIGHT GREATER THAN 16kg, DUAL
COVER AND
3&4 FRAME KEYWAY BOXES AND AN ETCHED WARNING PLATE SHALL BE PROVIDED (REFER SINGLE AND DUAL
EXTERNAL
FRAME EDGE
COVER PLANS).
REFER
9. WHERE POSSIBLE, THE PADLOCK TONGUE SHOULD NOT BE LOCATED ON THE PUMP GUIDE RAIL
NOM.
NOM.
NOTE 10
150
200
SIDE.
NOM.
10. BULLET HINGES SHALL BE ORIENTATED IN OPPOSITE DIRECTIONS TO RESTRICT THE REMOVAL OF
200
THE COVER.
SURFACE TO BE COATED WITH 11. WET WELL COVERS SHALL BE COMPLETELY SEALED WITH 'TESA' PERMAFOAM TAPE OR APPROVED
200 200
110 ANTI-SLIP EPIREZ SAFE STEP NOM.
NOM. EQUIVALENT, REFER TYPICAL SEALING TAPE CORNER DETAIL AND NOTE 3 ON DRG NO.
NOM. 550 (GREEN) OR APPROVED 1800 MAX.
EQUIVALENT STANCHION SPACING (TYP.) SEQ-SPS-1304-28.
SINGLE COVER PLAN (ALONG FACE OF PUMP GUIDE RAIL)
N.T.S (GATE/S NOT SHOWN) 12. HANDRAIL SHALL HAVE A 130mm OFFSET ON THE PUMP GUIDE RAIL SIDE ONLY.
DUAL COVER PLAN
N.T.S (GATE/S NOT SHOWN) ALUMINIUM BULLET
1800 MAX. ALUMINIUM BULLET HINGE (TYP.) HINGE (TYP.) MIN. LEN. 1800 MAX.
STANCHION SPACING (TYP.) EXTERNAL
120mm WELD TO ACCESS
C STANCHION SPACING (TYP.)
200 C MIN. LEN. 120mm WELD TO 200 FRAME 11 200
NOM. ACCESS COVER 11 ACCESS COVER AND EXTERNAL REFER NOM. COVER AND EXTERNAL ACCESS COVER NOM.
EXTERNAL FRAME EDGE EDGE
150
REFER NOTE 2 FRAME REFER NOTE 10 NOTE 7 FRAME REFER NOTE 10 REFER NOTE 2
NOM.
NOM.
200
200
INTERNAL SUPPORT BEAM
REFER NOTE 12
REFER NOTE 12
G
11
130
130
NOM.
NOM.
110
110
PUMP GUIDE LOCK UNLOCK
PUMP GUIDE
RAIL SIDE RAIL SIDE
150
300 NOM.
REFER NOTE 3
MIN. 4mm THICK
ALUMINIUM CHEQUER
PLATE THICKNESS TO BE SEAL WITH 'TESA' S/S M10 EYE BOLT WITH HANDRAILS
DESIGNED INDIVIDUALLY PERMAFOAM TAPE 60112 NUT AND WASHER
TO SUIT OPENING 12.7 THICK x 36 WIDE OR ATTACHED TO THE
APPROVED EQUIVALENT CENTRAL STRENGTHENING
BONDED TO FRAME ON ALL RIB
SIDES UNLESS SHOWN COVER IN OPEN POSITION
COVER MANUFACTURER TO OTHERWISE
PROVIDE AN ALUMINIUM
MANUFACTURER'S
2
.
PERIMETER FRAME (i.e. HANDRAILS
NO X
E G G
TE
R MA
ANGLES OR CHANNELS) TO PLATE WELDED TO
11 - -
FE °
SUIT EACH INDIVIDUAL COVER COVER REFER SECTION 3 WARNING PLATE
RE 84
FOR MIRRORED
COVER IN CLOSED
DETAIL CHEQUER PLATE
CHEQUER PLATE EDGE POSITION
COVER MANUFACTURER TO
PROVIDE ALUMINIUM
STRENGTHENING RIBS (i.e.
PLATES, ANGLES OR CHANNELS) KEYWAY BOX
TO SUIT EACH INDIVIDUAL COVER
STRENGTHENING RIBS
BULLET HINGE SHALL HAVE A
MINIMUM 120mm LENGTH WITH
THE SIZE TO BE DETERMINED BY SECTION 1 SECTION 2
THE COVER MANUFACTURER TO N.T.S 5 N.T.S 5
SUIT EACH INDIVIDUAL COVER
'TESA' PERMAFOAM TAPE 60106 6.4 THICK 'TESA' PERMAFOAM TAPE 60106 6.4
TYPICAL BACK OF ACCESS COVER - PLAN x 18 WIDE OR APPROVED EQUIVALENT MINIMUM 50x6 THICK x 18 WIDE OR APPROVED MINIMUM 50x6
N.T.S SEAL BONDED TO COVER STRIP ALUMINIUM EQUIVALENT SEAL BONDED TO ALUMINIUM
COVER STRIP COVER STRIP COVER STRIP
10 min.
FULLY SEAL FULLY SEAL
25 CHEQUER PLATE PERIMETER FRAME 25 CHEQUER PLATE
WELDED REFER 10 WELDED REFER
NOTE 4 NOTE 4
40
UNDERNEATH CHEQUER PLATE
46
25
31
EXTERNAL FRAME EMBEDMENT DEPTH REFER NOTE 4 3. COVERS OPENING TOWARDS A HANDRAIL SHALL BE SECURED TO THE HANDRAIL BY A
RIBS
IN ACCORDANCE STAINLESS STEEL LANYARD WITH SWIVEL EYE CARABINER; THE LANYARD SHALL BE
WITH THE M12 S/S COUNTERSUNK
MANUFACTURER'S 10 20 10 ATTACHED TO THE COVER'S CENTRAL STRENGTHENING RIB.
ANCHOR STUD FULLY SEAL
SPECIFICATIONS AT 500 MAX. CENTRES WELDED 4. WET WELL COVERS SHALL BE COMPLETELY SEALED BY FULLY SEAL WELDS AS SPECIFIED
59 MIN.
REFER NOTE 4
OR ALTERNATIVELY INTERMITTENT WELDS WITH SIKAFLEX TANK N OR APPROVED
200 NOM. OFFSET EQUIVALENT SEALANT.
130 OFFSET ON PUMP
GUIDE RAIL SIDE 5. SIKAFLEX TANK N SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S
G PERIMETER FRAME SPECIFICATIONS, WITH ALUMINIUM SURFACES TREATED WITH A VERY FINE ABRASIVE
DETAIL STRENGTHENING RIB
- PAD AND SIKA AKTIVATOR-205.
(COVER IN CLOSED 6. WET WELL COVERS SHALL BE DESIGNED TO BE COMPLETELY SEALED TO PROVIDE A FULL
POSITION) SECTION 5
ODOUR TIGHT SEAL.
5
REV. No. DATE DESCRIPTION AUTH.
SEWAGE PUMP STATION STANDARD DRAWING CoGC LCC RCC QUU UW
SEQ WATER ALUMINIUM ACCESS COVERS-OPTION 3
DRAWING No. VERSION
NOM.
B
150
KEYWAY BOX (TYP.)
11 REFER NOTE 4 NOTES
1. REFER DRG NO. SEQ-SPS-1304-18 FOR GENERAL AND MATERIAL NOTES.
2. REFER DRG NO. SEQ-SPS-1304-26 FOR VALVE CHAMBER ACCESS COVER
AND GRATE DETAILS.
3. VALVE CHAMBERS SHALL HAVE ONE OF THE FOLLOWING FALL PREVENTION
WARNING PLATE
ACCESS COVER SURFACE TO BE COATED D OPTIONS, AS SPECIFIED BY THE PRINCIPAL:
(TYP.) WELDED TO
REFER NOTE 2
WARNING WITH ANTI-SLIP EPIREZ COVER
11
D 3.1. TYPE A - LID AND GRATE (i.e. NO HANDRAIL) WITH TYPE 2 BOLLARDS
PLATE WELDED SAFE STEP 550 (GREEN)
11 OR APPROVED EQUIVALENT (REFER GCCC STD DRG 13-05-616) ON CONCRETE SURFACES AND
TO COVER
TYPE 3 BOLLARDS (REFER GCCC STD DRG 13-05-617) ON GRASS OR
G RECESSED LOCK ASPHALT SURFACES AROUND THE PERIMETER OF THE VALVE
11 CHAMBER; THE PRINCIPAL SHALL DETERMINE THE NUMBER AND
LOCK UNLOCK
LOCATION OF BOLLARDS.
LOCK UNLOCK
ALUMINIUM BULLET 6 RECESSED G 3.2. TYPE B - LID AND HANDRAIL (i.e. NO GRATE) WITH VALVE SPINDLE
HINGE (TYP.) MIN. LEN.
9 ACCESS COVER LOCK 11
REFER NOTE 2 OPENING/S PROVIDED ON THE COVER.
120mm WELD TO C
4. FOR COVERS WITH A TOTAL LIFTING WEIGHT LESS THAN 16kg, A SINGLE
ACCESS COVER AND 11
EXTERNAL FRAME KEYWAY BOX SHALL BE PROVIDED CENTRALLY (REFER THREE AND
REFER NOTE 5 ALTERNATIVE MULTI-COVER PLANS), UNLESS REQUESTED OTHERWISE BY
NOM.
150
THE PRINCIPAL. FOR COVERS WITH A TOTAL LIFTING WEIGHT GREATER
THAN 16kg, DUAL KEYWAY BOXES AND AN ETCHED WARNING PLATE SHALL
110 SURFACE TO BE COATED WITH BE PROVIDED (REFER SINGLE AND DUAL COVER PLANS).
NOM. ANTI-SLIP EPIREZ SAFE STEP 5. BULLET HINGES SHALL BE ORIENTATED IN OPPOSITE DIRECTIONS TO
550 (GREEN) OR APPROVED RESTRICT THE REMOVAL OF THE COVER.
EQUIVALENT
SINGLE COVER PLAN - TYPE A DUAL COVER PLAN - TYPE A
N.T.S N.T.S
G RECESSED
11 LOCK (TYP.)
NOM.
LOCK UNLOCK
110
75
LOCK UNLOCK
NOM.
KEYWAY BOX
B
G RECESSED (TYP.)
REFER NOTE 4
11
11 LOCK (TYP.)
NOM.
110
75
NOM. SURFACE TO BE COATED WITH
KEYWAY BOX SURFACE TO BE COATED WITH ANTI-SLIP EPIREZ SAFE STEP
B ANTI-SLIP EPIREZ SAFE STEP 550 (GREEN) OR APPROVED
(TYP.)
11 REFER NOTE 4 550 (GREEN) OR APPROVED EQUIVALENT
ALTERNATIVE MULTI-COVER PLAN - TYPE A
THREE COVER PLAN - TYPE A EQUIVALENT N.T.S
N.T.S
NOM.
200
NOTE 4 NOM. SPECIFIED BY THE PRINCIPAL:
NOM.
200
KEYWAY 3.1. TYPE A - LID AND GRATE (i.e. NO HANDRAIL) WITH TYPE 2 BOLLARDS (REFER GCCC STD
B BOX (TYP.) DRG 13-05-616) ON GRASS OR ASPHALT SURFACES AND TYPE 3 BOLLARDS (REFER GCCC
11 REFER
EXTERNAL NOTE 8 STD DRG 13-05-617) ON CONCRETE SURFACES AROUND THE PERIMETER OF THE VALVE
FRAME EDGE SURFACE TO BE CHAMBER; THE PRINCIPAL SHALL DETERMINE THE NUMBER AND LOCATION OF BOLLARDS.
COATED WITH 3.2. TYPE B - LID AND HANDRAIL (i.e. NO GRATE) WITH VALVE SPINDLE OPENING/S PROVIDED
ANTI-SLIP ON THE COVER.
EPIREZ SAFE WARNING PLATE
D 4. HANDRAIL LAYOUT AND GATE LOCATION/S ARE INDICATIVE ONLY, REFER DRG NO.
ACCESS COVER STEP 550 (TYP.) WELDED TO
COVER
11 SEQ-SPS-1304-21 FOR ARRANGEMENT OPTIONS AND DRG NO. SEQ-SPS-1304-27 FOR DETAILS.
REFER NOTE 2 WARNING (GREEN) OR
PLATE WELDED
E
APPROVED 5. SELF CLOSING GATE/S WITH ACCESS COVERS OPENING TOWARDS AND BENEATH THEM, SHALL
TO COVER
11
EQUIVALENT
HAVE TOEBOARDS WITH A 'HINGED AT TOP' CONNECTION, REFER TYPE 3 TOEBOARD
G RECESSED CONNECTION DETAIL ON DRG NO. SEQ-SPS-1304-27.
ALUMINIUM 11 LOCK
BULLET 6. SELF CLOSING GATE/S SHALL SWING OUTWARDS AND THE NUMBER OF GATE/S REQUIRED
LOCK UNLOCK
HINGE ACCESS SHALL BE AS FOLLOWS:
LOCK UNLOCK
COVER
(TYP.) MIN. 10 RECESSED G 6.1. A SINGLE GATE FOR SPANS BETWEEN STANCHIONS OF UP TO A MAXIMUM OF 1500mm.
REFER
LEN. 9 LOCK 11 6.2. DOUBLE GATES FOR SPANS BETWEEN STANCHIONS GREATER THAN 1500mm AND UP TO A
NOTE 2
120mm
WELD TO
C MAXIMUM OF 2400mm.
ACCESS
11 EXTERNAL
7. WHERE GATES SPAN THE ENTIRE LENGTH OF A HANDRAIL'S SIDE AND WHERE NECESSARY,
COVER AND FRAME
EDGE ADDITIONAL STANCHIONS AND RAILS SHALL BE PROVIDED EITHER SIDE OF THE GATE/S TO
EXTERNAL
NOM.
INCREASE HANDRAIL STABILITY.
150
FRAME
REFER
NOM.
8. FOR COVERS WITH A TOTAL LIFTING WEIGHT LESS THAN 16kg, A SINGLE KEYWAY BOX SHALL
200
NOTE 9
NOM.
200
150
REFER NOTE 2 EXTERNAL FRAME REFER NOTE 9 REFER NOTE 2 NOTE 4
REFER NOTE 9
NOM.
NOM.
200
200
G RECESSED
11 LOCK (TYP.)
NOM.
LOCK UNLOCK
110
LOCK UNLOCK
KEYWAY BOX
B
G RECESSED (TYP.)
REFER NOTE 8
11
11 LOCK (TYP.)
NOM.
110
NOM.
200
200
150
VALVE SPINDLE OPENING KEYWAY BOX SURFACE TO BE COATED WITH 1800 MAX.
75 H (TYP.) LOCATIONS TO SUIT B ANTI-SLIP EPIREZ SAFE STEP 550
EXTERNAL SURFACE TO BE COATED WITH
(TYP.) STANCHION SPACING (TYP.)
HANDRAIL NOM. 9 INDIVIDUAL VALVE CHAMBERS 11 REFER NOTE 8 (GREEN) OR APPROVED EQUIVALENT
FRAME EDGE ANTI-SLIP EPIREZ SAFE STEP 550
VALVE SPINDLE OPENING (TYP.) (GREEN) OR APPROVED EQUIVALENT
REFER NOTE 4 200 H
THREE COVER PLAN - TYPE B NOM.
LOCATIONS TO SUIT INDIVIDUAL
9
ALTERNATIVE MULTI-COVER PLAN - TYPE B
N.T.S VALVE CHAMBERS N.T.S (GATE/S NOT SHOWN)
REV. No. DATE DESCRIPTION AUTH.
SEWAGE PUMP STATION STANDARD DRAWING CoGC LCC RCC QUU UW
SEQ WATER ALUMINIUM ACCESS COVERS-OPTION 3
DRAWING No. VERSION
40 MAX.
CHAMBERS
PITCH
ANGLES OR CHANNELS) TO DESIGNED INDIVIDUALLY NUMBER, SIZE AND CARABINER REQUIRED BY COVER
CUT-OUTS GREATER
SUIT EACH INDIVIDUAL TO SUIT OPENING POSITION OF CUT-OUTS LENGTH TO SUIT EACH INDIVIDUAL MANUFACTURER
Ø25 LIFT HOLE THAN 100mmx100mm
COVER COVER
REMOVE SHARP
300 NOM.
- REFER NOTE 4 100
CLEAR OPENING EDGES
50 NOM.
CHEQUER PLATE EDGE S/S M10 EYE BOLT WITH
NUT AND WASHER
30
ATTACHED TO THE
CLEAR OPENING
CLEAR OPENING
CENTRAL STRENGTHENING
RIB
30
100
100
CLEAR OPENING
COVER IN OPEN POSITION AS
SPECF
IEDBY
MANUFACTURER'S E PRN
ICP
IAL
PLATE 11
2
.
HANDRAILS
NO X
L
TE
R MA
FE °
ALUMINIUM
RE 84
SPRING HINGE VALVE
RECESSED COVER IN CLOSED POSITION LOADED TO VALVE SPINDLE SPINDLE
LOCK CLOSE OPENING LOCATIONS TO OPENING
OR APPROVED 18 SUIT INDIVIDUAL VALVE LOCATIONS
EQUIVALENT CHAMBERS TO SUIT
DETAIL H DETAIL J INDIVIDUAL
VALVE
8 CHAMBERS
KEYWAY BOX ALUMINIUM CHEQUER
SECTION 10 COVER CHEQUER PLATE THICKNESS
PLATE 10 TO MATCH COVER
N.T.S 8
BULLET HINGE SHALL HAVE
50 NOM.
COVER MANUFACTURER TO TYPE B
PROVIDE ALUMINIUM A MINIMUM 120mm LENGTH 50 NOM. ALUMINIUM
WITH THE SIZE TO BE ALUMINIUM SPRING HINGE
STRENGTHENING RIBS (i.e. K BULLET HINGE
DETERMINED BY THE COVER HINGE PIN ALUMINIUM LOADED TO CLOSE
PLATES, ANGLES OR
MANUFACTURER TO SUIT (TYP.) EXTERNAL MINIMUM PLATE SECTION 18 OR APPROVED
CHANNELS) TO SUIT EACH FRAME
EACH INDIVIDUAL COVER 75x75x6 EQUIVALENT
INDIVIDUAL COVER COVER
ALUMINIUM EA
TYPICAL OPEN ACCESS COVER - PLAN EXTERNAL 25 MIN.
N.T.S (TYPE B HANDRAILS NOT SHOWN) TOEBOARD FRAME 15 PERIMETER CHEQUER
S/S 316 LANYARD CHAIN
CLEARANCE
HANDRAILS FRAME PLATE
(MEDIUM LINKS - 4 x 28 x 14 OD)
10 MIN.
25 MIN. ALUMINIUM
WITH SWIVEL EYE CARABINER
LENGTH TO SUIT EACH HINGE
25 REFER DETAIL L FOR PIN OR
INDIVIDUAL COVER REFER NOTE 5
COVER CONNECTION EQUIVALENT
S/S M10 EYE BOLT DETAILS
GRATE IN OPEN POSITION
WITH NUT AND
TO SUIT
WASHER ATTACHED TO
3
NO AX.
TE
THE CENTRAL
FE ° M
IN ACCORDANCE IN ACCORDANCE
R
40
GUSSET AS REQUIRED
M12 S/S ANCHOR STUD TO BE DETERMINED BY THE
200 NOM. OFFSET
AT 500 MAX. CENTRES COVER MANUFACTURER
GRATE IN CLOSED POSITION
SECTION 6 DETAIL L
DETAIL M
N.T.S 7
(COVER IN CLOSED POSITION)
TYPE A
ALUMINIUM ALUMINIUM (COVER & GRATE IN CLOSED POSITION)
10 DOWEL PIN
10 min. DOWEL PIN NOTES
CHEQUER PLATE 10
CHEQUER PLATE
PERIMETER FRAME 20 MIN. 20 MIN. 10 1. REFER DRG NO. SEQ-SPS-1304-18 FOR GENERAL AND MATERIAL NOTES.
Ø22
2. HANDRAILS AND COVERS SHALL BE DESIGNED TO ALLOW COVERS TO OPEN AT
LEAST 6° PAST THE VERTICAL.
10
FULLY
50
10 20 10
3. GRATES SHALL BE DESIGNED TO ALLOW THE GRATE TO OPEN AT LEAST 6° PAST
10
WELDED
35
THE VERTICAL.
4. COVERS OPENING TOWARDS HANDRAILS SHALL BE SECURED TO THE HANDRAIL BY
Ø22
35
A STAINLESS STEEL LANYARD WITH SWIVEL EYE CARABINER; THE LANYARD SHALL
50 ALUMINIUM
COVER MANUFACTURER TO BE ATTACHED TO THE COVER'S CENTRAL STRENGTHENING RIB.
ALUMINIUM PLATE
PROVIDE ALUMINIUM INTERNAL 11 PLATE 5. GRATES SHALL OPEN IN THE SAME DIRECTION AS THE COVER AND SHALL BE
PERIMETER FRAME STRENGTHENING SUPPORT BEAM TO SUIT EACH SECTION 11
STRENGTHENING RIB SECURED TO THE COVER BY A STAINLESS STEEL LANYARD WITH SWIVEL EYE
SECTION 8 RIBS INDIVIDUAL COVER REFER DRG NO.
SECTION 9 CARABINER; THE LANYARD SHALL BE ATTACHED TO THE COVER'S CENTRAL
7&8 SEQ-SPS-1304-28 FOR DETAIL K
7&8 CONNECTION DETAILS STRENGTHENING RIB.
(OPTIONAL GRATE NOT SHOWN) (OPTIONAL GRATE NOT SHOWN) A1 UNREDUCED
REV. No. DATE DESCRIPTION AUTH.
SEWAGE PUMP STATION STANDARD DRAWING CoGC LCC RCC QUU UW
SEQ WATER ALUMINIUM ACCESS COVERS-OPTION 3
DRAWING No. VERSION
410
410
KNEE RAIL BY PRINCIPAL) REFER NOTE 6
REFER NOTE 6
1017
820
50 GAP (75 IF REQUESTED KNEE RAIL
Ø38 ALUMINIUM POST BY PRINCIPAL)
6 THICK ALUMINIUM REFER
560
410
410
REMOVABLE STANCHION
AND END EDGES
AND END EDGES
EXISTING
10
150
150
150
SURFACE
20
SCALE A
REMOVABLE CENTRE
55
SCALE B STANCHION CLEAR DEBRIS FROM 'RAILSAFE'
140
HOLE AND SET POST POST INSERT
INSERT IN EPOXY OR APPROVED
13 RESIN, ENSURING NO EQUIVALENT
118
10 THICK ALUMINIUM 50
150 MIN.
RUBBER STRIP AIR POCKETS IN
PADLOCK TONGUE TO SUIT CAVITY
50
5 NOM.
SCALE A -
RUBBER STRIP STOPPER WITH CUTOUT 80
TYP.
50
TO SUIT TO SUIT PADLOCK 33 Ø70
TONGUE 40
DETAIL P DETAIL R
65
GATE POST
31
SCALE A
SCALE A -
10 THICK ALUMINIUM 150
10 140 10 THICK STOPPER WITH Ø12 31
THICK ALUMINIUM Ø18 HOLE 24 24
HOLE
ALUMINIUM PADLOCK TONGUE (TYP.)
150
N R2
DETAIL PLATE WITH Ø12 HOLE 5
GATE POST
12 THICK
SCALE A - TY
P. ALUMINIUM
10 THICK ALUMINIUM
80
80
STOPPER WITH REMOVABLE CENTRE
10 THICK ALUMINIUM
40
CUTOUT TO SUIT Ø18 HOLE
40
PADLOCK TONGUE STANCHION
PADLOCK TONGUE (TYP.)
WITH Ø12 HOLE RUBBER STRIP 15x15 15x15
EQUAL ANGLE RUBBER STRIP TO SUIT
12 THICK ALUMINIUM CHAMFER BASE PLATE CHAMFER
(6 THICK) SECTION 12 TO SUIT Q SCALE A
SCALE A
DETAIL RIGHT ANGLE BASE PLATE
SCALE A
SCALE A
Ø50 NOTES
FULLY STANCHION Ø50 FULLY WELDED ALUMINIUM Ø46 GATE Ø50 1. REFER DRG NO. SEQ-SPS-1304-18 FOR GENERAL AND MATERIAL NOTES.
WELDED STANCHION BULLET HINGE POST STANCHION FULLY WELDED
SPRING BOLT LATCH 2. REFER DRG NO. SEQ-SPS-1304-21 FOR HANDRAIL ARRANGEMENTS.
M16 S/S (FULLY WELDED SPRING BOLT LATCH
LOCKABLE IN OPEN
THREADED EQUAL ANGLE (6 TO GATE POST LOCKABLE IN OPEN 3. HANDRAILS SHALL BE WEBFORGE OR APPROVED EQUIVALENT.
POSITION (WITH Ø46 GATE
ROD AND THICK) AND TOEBOARD) POSITION (WITH TAMPER 4. TOEBOARDS SHALL BE PROVIDED ON ALL SIDES AND CONNECTED AS
TAMPER PROOF BOLTS) M16 S/S POST
NUT WITH PROOF BOLTS)
M16 S/S THREADED FOLLOWS TO EACH STANCHION:
NOM.
NYLON
50
25 HIGH
A 190
B
75
12 DIA. ALUMINIUM ROUND
BAR WELDED TO LID 155
C
ALUMINIUM SHEET 3mm THICK
R2
OR REGISTERED TRADEMARK
WITH RED LETTERING ON WHITE
MANUFACTURER'S NAME
MIN. Ø5 DRAIN HOLE AND
BACKGROUND. LETTERING TO BE
L ALUMINIUM CHEQUER PLATE LID PLUG
ENGRAVED TO A MINIMUM OF D
R 1mm DEPTH INTO PLATE
DETAIL THICKNESS TO MATCH COVER
5,7,8 20
15 HIGH
SCALE B
-
D
BEVELLED END 25 x 60 LONG x 3 THICK
190 NOM.
OD 15 x ID 12 NYLON
220
INSULATING SLEEVE
DETAIL C
N.T.S 5,7,8 ALUMINIUM SHEET 3mm
REFER NOTE 2 LOCK UNLOCK THICK LETTERING SHALL BE
75
GREASE NIPPLE
5mm HIGH AND ENGRAVED
80 NOM.
ALUMINIUM BULLET HINGE DIMENSIONS TO A MINIMUM OF 1mm
DEPTH INTO PLATE
A (mm) B (mm) C (mm) D (mm) R (mm) L (mm)
DATE OF MANUFACTURE
55
40
R2
120 59 20 16 2 60 OD 25 x ID 16
5
150 74 25 20 2 75 ALUMINIUM SHEET 3mm THICK ALUMINUM TUBE
(MM/YYYY)
WELDED TO COVER 30
8 HIGH
LETTERING TO BE ENGRAVED TO A
MINIMUM OF 1mm DEPTH INTO PLATE 100
OD 25 x ID 16 ALUMINUM
DETAIL E TUBE OR SIMILAR FULLY
6&9 WELDED TO ADJACENT
30 MIN.
SCALE A
COVER, EXTERNAL FRAME Ø25 LIFT HOLE
OR INTERNAL BEAM REMOVE SHARP
ALUMINIUM COVER 15 Ø5 DRAIN HOLE EDGES
Ø5 DRAIN HOLE
LOCATED ON THE
DETAIL G
TYP.
15 HINGE SIDE
3
50
SCALE A 7&8
FULLY WELDED
SIDE PLATE SQUARE
LOCALLY CUTOUT S/S M6 BOLT
CUTOUT TO SUIT ALUMINIUM CHEQUER PLATE LID
14 SECTION 14
40
65 KEYWAY HOLE
TYP.
45
REMOVE SHARP 12 DIA. ALUMINIUM ROUND
EDGES 6 THICK ALUMINIUM BAR WELDED TO LID
DETAIL B PADLOCK TONGUE
10 MIN.
SCALE A 5,7,8 S/S LATCH HANDLE 25 Ø12 S/S ROD 6 THICK
WELD NUT TO
x 60 LONG x 3 THICK ALUMINIUM PLATE
BOLT AND PLATE
40 5 NOM.
OD 25 x ID 16 ALUMINUM 220
TUBE OR SIMILAR FULLY 40 x 25 x 3
WELDED TO ADJACENT THICK PLATE
COVER, EXTERNAL FRAME MIN. Ø5 DRAIN
35
TO BEAM HINGE
1100 NOM.
S/S BOLT WITH
ALUMINIUM
NYLON WASHER 6 THICK ALUMINIUM PLATE 10 MIN. PLATE TO SUIT
TO SUIT
CLEARANCE.
MINIMUM 6 THICK INTERNAL
ALUMINIUM PLATE SUPPORT BEAM HINGED INTERNAL
SUPPORT BEAM
FULLY WELDED INSTALL IN ACCORDANCE
(TYP.) WITH THE MANUFACTURER'S TYPICAL HINGED INTERNAL SUPPORT BEAM
RECOMMENDATIONS KEYWAY HOLE AND LANYARD ATTACHMENT
ALUMINIUM PLATES AND SPECIFICATIONS BEAM IN CLOSED
TO SUIT INTERNAL POSITION N.T.S
SUPPORT BEAM PROVIDE APPROVED S/S ANCHOR STUD
PACKING / SHIMS UNDER WITH NYLON WASHER S/S BOLT WITH POSITIVE
HINGED INTERNAL SUPPORT BEAM LOCKING DEVICE
FASTENERS AS REQUIRED
CONNECTION DETAIL
N.T.S SECTION 19
(COVER NOT SHOWN) N.T.S -
REFER NOTE 3, 4 & 5
S/S ANCHOR
STUD WITH
MINIMUM 6 THICK
NYLON WASHER
ALUMINIUM PLATE
S/S BOLT WITH
S/S POSITIVE
NYLON WASHER INSTALL IN ACCORDANCE
LOCK PINS OR
TO SUIT WITH THE MANUFACTURER'S
FULLY WELDED EQUIVALENT
INTERNAL RECOMMENDATIONS
MINIMUM 6 SUPPORT BEAM AND SPECIFICATIONS
THICK
ALUMINIUM S/S 316 LANYARD CHAIN
PLATE TO SUIT (MEDIUM LINKS - 4 x 28 x
14 OD) TO PIN
S/S POSITIVE ALUMINIUM PLATE TO PROVIDE APPROVED ALUMINIUM
LOCK PIN OR SUIT AND S/S M8 EYE PACKING / SHIMS CHANNEL
EQUIVALENT ALUMINIUM CHANNEL BOLT WITH NUT AND UNDER FASTENERS AS
TO SUIT INTERNAL WASHER REQUIRED 100 MIN.
SUPPORT BEAM NOTES
S/S 316 LANYARD CHAIN ALUMINIUM PLATE TO
1. REFER DRG NO. SEQ-SPS-1304-18 FOR GENERAL AND MATERIAL NOTES.
REMOVABLE INTERNAL SUPPORT BEAM (MEDIUM LINKS - 4 x 28 x SUIT AND S/S M8 EYE
2. WHERE POSSIBLE REMOVABLE INTERNAL SUPPORT BEAMS SHALL BE LOCATED TO
14 OD) TO PIN BOLT WITH NUT AND
CONNECTION DETAIL WASHER AVOID OBSTRUCTION OF NORMAL MAINTENANCE PROCEDURES.
N.T.S 3. HINGED INTERNAL SUPPORT BEAMS SHALL HAVE A MAXIMUM LIFTING WEIGHT OF
(COVERS NOT SHOWN) SECTION 17 16kg.
N.T.S - 4. HINGED INTERNAL SUPPORT BEAMS SHALL HAVE A SUITABLY LOCATED KEYWAY HOLE
(40 x 15) OPENING, REFER TYPICAL DETAIL THIS SHEET
5. HINGED INTERNAL SUPPORT BEAM SHALL HAVE A S/S LANYARD AND ALUMINIUM
PLATE LOCATED TO SUIT SECUREMENT TO THE HANDRAIL WHEN THE BEAM IS IN AN
OPEN POSITION, REFER TYPICAL DETAIL THIS SHEET.
900 MIN
6 17
1300 MAX
DIM 6
'A' CLEAR
450 GRILL PLATFORM
LADDER FIXING 6 12
110
BRACKET REFER TO DETAIL.
FIXING REFER TO DETAIL. 12mm THICK
100
BOLT. CEMENT
5
PLATFORM. PLATFORM. MORTAR PAD. FIXING
DRAWINGS
MIN
BOLT
75
DIM MIN. 75x8 STILE
260
FIXING
450 'A' 120 6
BOLT.
LADDER
100
RUNG
LADDER FIXING REFER 500 x 215 OPEN
FIXING BRACKET G TO DETAIL. GRILLE STAIR TREAD 6
BRACKET REFER TO TOP OF STAIR TREAD SHALL
TOP OF RUNG
REFER TO F DETAIL. BE LEVEL WITH PLATFORM.
SHALL BE
DETAIL. LEVEL WITH FRONT ELEVATION SIDE ELEVATION (G - G) SECTIONAL ELEVATION (K - K)
PLATFORM.
TYPE 'B' LADDER TOP
FRONT ELEVATION SIDE ELEVATION (F - F)
250
TYPE 'A' LADDER TOP 348
318 FIXING
SIDE ACCESS 30 280 K
4 BOLT
STAINLESS STEEL
HANDGRIP BRACKET
STAINLESS STEEL BRACKET EX 48 OD X 4MM WALL 75 x 75 x 75 x 8
TOP OF 75 x 75 x 75 x 8 ALUMINIUM TUBE
4 STILE 110 x 12 PL
900
WALL RADIUS Ø24
450 MAX
35
(b) ALL WELDS SHALL BE 6mm FILLET ALL AROUND USING FILLER ALLOY 5356.
TYPICAL BOLTING DETAIL 4. ALL FASTENERS SHALL BE GRADE 316 STAINLESS STEEL.
SHOWING SEPARATION INSERT UNLESS OTHERWISE NOTED, FASTENERS SHALL BE AS DESCRIBED BELOW
85
MIN. 75 x 8 STILE (a) FIXING TO CONCRETE - BOLTS SHALL BE M16 DROP-IN ANCHORS.
DRAWING
REFER JOB
ALUMINIUM Ø24 (RAMSET DYNASET OR SIMILAR)
DIM 'A'
RUNG 35 (b) FIXING TO METALWORK - BOLTS SHALL BE M16 HEX HEAD BOLTS.
250 MIN. 3 NO Ø18 HOLES FOR M16 5. ANTI GALLING LUBRICANT 'LOCTITE 222 OR 567' OR SIMILAR SHALL BE USED ON ALL
300 MAX. EPOXY SET STAINLESS 160 THREAD AND BETWEEN ALL STAINLESS STEEL MATING SURFACES.
DRAWING
REFER JOB
MIN. 75x8 STILE REFER TO NOTE 8 STEEL ANCHORS 6. PROVIDE APPROVED NYLON OR POLYTHENE SEPARATION INSERTS BETWEEN ALL
BASE PLATE STAINLESS STEEL ANCHORS AND ALUMINIUM SECTIONS.
LADDER FIXING BRACKET REFER RUNG
450 NOT TO SCALE 7. 3mm H.D.P.E. GASKETS SHALL BE PLACED BETWEEN ALL ALUMINIUM MOUNTS AND
REFER TO DETAIL DETAIL 320x120x12 PL OTHER SURFACES TO PREVENT DIRECT CONTACT.
STAINLESS STEEL BRACKET FIXING BOLT 8. LADDER RUNG SPACING SHALL BE A MINIMUM 0F 200 FOR THE LADDERS LESS THAN
RUNG SPACING MINUS 12mm
75 x 75 x 75 x 8 1500 LONG.
UNLESS NOTED OTHERWISE
450 MAX
PROVIDE KEY
WAY KNURLED FINISH DIAMOND -
SHAPE (CRISS-CROSS)
NOTE: POSITION
PATTERN TO STANCHION
120
HANDLE 6mm
ALL MATERIAL FOR STANCHION TO BE
A CFW TO
20
FABRICATED FROM MARINE GRADE - 25 STANCHION
ALUMINIUM ALLOY 6061 OR APPROVED -
EQUIVALENT 10
20
10 PLATE
60
LOCKING PIN
1000
6mm CFW TO
5
STANCHION
STANCHION IN
EXTENDED POSITION
110
100x100x10
50
EA. BRACKET
STOP PLATE 6mm CFW TO
T.O. PRECAST LID
LADDER
/ NATURAL SURFACE
STOP PLATE DETAIL 6mm CFW TO
REFER SEQ-SPS-1305-1 (2 No REQ'D) LADDER
60
110
FOR DETAILS 100x100x10 EA.
BRACKET
END CAP /
HANDLE
140
KNURLED FINISH
R2
DIAMOND - SHAPE
5
TOP
BRACKET (CRISS-CROSS)
PATTERN TO
STANCHION
100
1280
60
100
END CAP /
LOCKING HANDLE TO BE 45
55 100
PIN PINNED IN-SITU
2900
25
25
150
55 45
46mm DIA. STANCHION EXTENSION
BOTTOM R25
BRACKET
100x100x10 E.A LADDER
LADDER
18
48
R25
130
96
90
48
1390
3
13
DETAIL A
-
6mm CFW TO
STOP PLATES LOCKING PIN LADDER
450
3. ALL FASTENERS SHALL BE GRADE 316 STAINLESS STEEL.
UNLESS OTHERWISE NOTED, FASTENERS SHALL BE DESCRIBED BELOW
(a) FIXING TO CONCRETE - BOLTS SHALL BE M16 DROP-IN ANCHORS
450
R 140 MIN. WALL. (RAMSET DYNASET OR SIMILAR)
38 OD MIN. INTERMEDIATE
END MOUNTING 46 OD MIN. HANDRAIL (b) FIXING TO METALWORK - BOLTS SHALL BE M16 HEX HEAD BOLTS.
TREAD NOSE
RAIL (2mm WALL).
450 ABOVE
TYPE 'E' (3.5mm WALL). 4. NYLON OR POLYTHENE SEPARATION INSERTS SHALL BE USED BETWEEN
STAINLESS STEEL FASTENERS AND ALUMINIUM SECTIONS.
R 140 MIN. HOLE DIAMETER TO SUIT THESE INSERTS. REFER TO BOLTING DETAIL.
900
50 OD MIN. STANCHION 5. ANTI-GALLING LUBRICANT "LOCTITE 222 OR 5567" OR SIMILAR APPROVED
STRINGER.
50 OD MIN. STANCHION (4mm WALL). SHALL BE USED ON ALL THREADS AND BETWEEN ALL STAINLESS STEEL
REFER TO JOINT DETAIL 'J'.
(4mm WALL). MATING SERVICES.
6. UNLESS OTHERWISE NOTED, ALL METALWORK CONNECTIONS SHALL BE
75
WALKWAY BASE MOUNTING WELDED AS FOLLOWS:
TYPE 'C' FOR (a) ALL WELDING TO BE WELD QUALITY B IN ACCORDANCE WITH AS1665.
CHANNEL STRINGER. (b) ALL WELDS TO BE 4mm FILLET ALL ROUND USING FILLER ALLOY 5356.
BASE MOUNTING TYPE 'B'
BASE MOUNTING FOR PLATE STRINGER. 7. WHERE JOINTS IN HANDRAIL AND INTERMEDIATE RAILS ARE NECESSARY
TYPE 'A'. THEY SHALL BE WELDED ON SITE IN A MANNER APPROVED BY THE
BASE MOUNTING
SEQ-SP. SLIP JOINTS WILL NOT BE ACCEPTED UNLESS SPECIFICALLY
TYPE 'B'.
NOTED TO THE CONTRARY ON THE JOB DRAWINGS.
8. 3mm H.D.P.E GASKETS SHALL BE PLACED BETWEEN ALL ALUMINIUM MOUNTS
HANDRAIL FOR WALKWAYS HANDRAIL FOR STAIRWAYS AND OTHER SURFACES TO PREVENT DIRECT CONTACT.
80 9. KICK PLATES, WHERE REQUIRED BY AS1657, SHALL COMPLY.
CUT HANDRAIL TO SHAPE OF 10. ALTERNATIVE JOINTING SYSTEMS SUBJECT TO SEQ-SP SPECIFIC APPROVAL.
STANCHION.
CUT HANDRAIL TO SHAPE OF 10 PL
STANCHION. STAINLESS STEEL
150
100
50
NYLON SEPARATION
M16 FIXING BOLT. INSERT (TYP.).
10mm PLATE M16 FIXING BOLT.
40
TYPICAL BOLTING DETAIL
80
18
80
50
80
TYPE `E'
150 100
WALL MOUNTING
EDGE OF 10mm PLATE
WALKWAY. 150
PLAN PLAN PLAN
75
0
14
10mm PLATE
R
0
80
15
75
40
0
20
100
50
70
80
25
40
100 150
OPEN END.
H.D.P.E GASKET M16 FIXING BOLT. 100
125
ANCHORS FOR PUMP
STATION SURFACES.
3. ALL FASTENERS SHALL BE GRADE 316 STAINLESS
ROUND OFF
STEEL. WHERE HANDRAILS AND LADDERS ARE
EDGES
LADDER FIXING FIXED TO CONCRETE THE FASTENER SHALL BE
BRACKETS AT 1800 EITHER:
60
MAX. CTRS (a) M16 x 150 MIN. LONG HEX BOLT PROJECTING 50
R3
5
250 MIN
5
(b) M16 DROP IN ANCHOR (RAMSET DYNASET OR
DEPTH OF PIT
SIMILAR).
40 Ø10 BAR
FABRICATE FROM EX 4. UNLESS NOTED OTHERWISE, STEELWORK SHALL BE
SPLIT END OF
AS REQUIRED
RUNGS AT
5 PLATE AND 5. NYLON OR POLYTHENE SEPARATION INSERTS SHALL
HEIGHT
150
VALVE SUPPORT 450 PIT FLOOR LEVEL
M16 G316 SS BOLT
WELDED TO STRAP
MIN
238
ALUMINIUM NYLON
LADDER IN SPACER WITH WASHER &
NUT ASSEMBLY Ø16 STAINLESS STEEL BOLT
PUMP WELL TO BLOCK
HAVE PIT LADDER 3mm THICK NEOPRENE
LENGTH TO SUIT. DRILL Ø18
HOLE THROUGH STRAP
RETRACTABLE 220 LADDER SHEET WRAP AROUND
HANDGRIPS TOP OF PUMP STATION
M
75x10 G316
IN
2 SLOTTED
10
SS STRAP
0
HOLES IN DISTANCE TO
BEAM ONLY; SUIT HALF OD
75
30
Ø18x40 2xM16 S.S. BOLTS OF PIPE PLUS
HOLES TO SUIT
LONG 15 HALF OD OF
PIPE FLANGE
3xM16 S.S. SPACER PLUS 5
CHEMSET OR
MASONRY
140
30°
155
ANCHOR
50
15
LADDER 325 150 BOTH 75 x 10 G316
200x80 ALUMINIUM PARALLEL SIDES STAINLESS
PLAN END
100
LADDER
M16 STAINLESS STEEL DROP IN
FIXING ALUMINIUM ALUMINIUM CLEAT
X X ANCHOR (RAMSET DYNASET OR
BRACKET AT PLATE 12 THICK 80x180x12 THICK
SIMILAR)
1800mm MAX
CTRS.
50 100
75
THE PROJECT DESIGNER MUST OBTAIN DN20 IP68 RATED 24V. SOLENOID VALVE. ENERGISE TO
A SEQ SP APPROVED DESIGN FOR THE OPEN VALVE AND VALVE TO CLOSE ON FAILURE. FOR THE
SERVICE AND METER ARRANGEMENT. OPERATION OF THIS VALVE REFER TO DRAWING
THE MINIMUM DIAMETER OF SERVICE SEQ-SPS-1101-2 NOTE 8.
SHALL BE 25. SEE NOTE G2. DN20 STAINLESS STEEL BARREL UNIONS SHALL BE
WARNING
PROVIDED ON BOTH SIDES OF SOLENOID VALVE.
DO NOT
DRINK
PUMP WELL TOP SLAB
PROPERTY SERVICE
MINIMUM
CONNECTION. SEE
300
NOTE G2 FOR SIZE. NOTE: WELL WASHER
NOT REQUIRED FOR GCCC
NOMINAL FINISHED SURFACE LEVEL
POTABLE WATER
RETICULATION
MAIN IN STREET "Mc BERNS" AUTO WELL
WASHER INSTALLATION.
SAFETY SIGN ON INTERNAL
SURFACE OF DOOR. REFER DN20 SCHEDULE 40S GRADE 316 STAINLESS STEEL
TO NOTE G6 FOR DETAILS. PIPE UNDER CONCRETE SLAB. SEE NOTE G1.
PROVIDE Ø75 HOLE IN BASE DN20 HOSE COCK WITH DN25 BSP
OF CABINET DIRECTLY UNDER THREADED CONNECTION FOR HOSE
HOSE COCK OUTLET DN25 HOSE CONNECTION VACUUM
TYPICAL SECTIONAL VIEW OF POTABLE WATER SUPPLY BREAKER ATTACHED TO HOSE COCK
NOT TO SCALE
.
SLAB AT MAXIMUM OF 1 IN 10 VERTICAL KERB OR AN APPROVED ALTERNATIVE.
GEARBOX ON STAINLESS G4. THE MAINTENANCE HOLE COVERS ARE TO BE
STRUCTURAL REQUIREMENTS
TOP OF WALL RL*.***
STEEL TORQUE TUBE PROVIDED WITH A MINIMUM 2000mm CLEARANCE
300
DN150 VENT PIPE TO
EXTENSION PLINTH. TO ALL ABOVE GROUND STRUCTURES WITH THE
20
VENT POLE NO. 1 SEWER
GRADED AT 1 IN 50 MECHANICALLY ANCHORED SEE NOTE G7. EXCEPTION OF THE VALVE OPENING MECHANISM.
MINIMUM DOWN TO POLYETHYLENE LINING IS TO BE THE VACTOR PIPE IS TO BE LOCATED WITHIN
Q100 FLOOD LEVEL RL*.*** 1500mm OF THE ACCESS ROAD KERB. THIS
600
CAST INTO UNDERSIDE OF TOP
CLASS D SEALED
GRIT COLLECTOR
2260 MIN.
MAINTENANCE HOLE. SLAB WITH LINING ON SIDES OF ACCESS ROAD IS TO HAVE A 300 HIGH VERTICAL
SEE NOTE G13. ALL OPENINGS. FOR DETAILS REFER KERB.
1800
TO DRAWING SEQ-SPS-1407-1 THIS CLEARANCE IS TO BE MAINTAINED TO
ALLOW EASY ACCESS FOR VACTOR TRUCKS.
INVERT OF VENT TO BE OBVERT OF OVERFLOW PIPE G5. FINISHED SURFACE TREATMENT AND LEVEL
525
100 MINIMUM ABOVE IL.*.*** 4 NO. OFF STAINLESS
TO BE SET 300 BELOW STEEL 'REID SWIFT PROFILE IS TO BE DETAILED ON PROJECT
OBVERT OF FLAP VALVE IN OVERFLOW SYSTEM OVERFLOW LEVEL DRAWINGS. NOTE: SURFACE IS TO GRADE DOWN
OVERFLOW CHAMBER. LEVEL LIFT" LIFTING ANCHORS SEWER
375
SE
STAINLESS STEEL TORQUE TUBE REQUIRED BY SEQ-SP) DIAMETER TO CLASS D SEALED
E
CONTAINING RISING SPINDLE WITH BE SAME AS SEWER INLET PIPE AND PROVIDE 25 CHAMFER MINIMUM OF 1500 HORIZONTALLY FROM THE
NO
GUIDE BUSHES FOR INSTALLATIONS WITH MINIMUM GRADE OF 1 IN 40. EDGE OF THE TOP SLAB.
75
SEE ALSO NOTE G10 BETWEEN `600 OPENING
TE.
WITH GEARBOXES FOR VALVES AND UNDERSIDE OF SLAB G6. THE TOP SLAB LEVEL IS TO BE ABOVE THE Q100
DN450 AND OVER IL.*.*** FOR GRIT COLLECTORS 2 FLOOD LEVEL.
G2
TYPICAL WALL PIPE TO BE A EG
.
G7. FOR INLET PIPES UNDER DN600 A FULL 316
STAINLESS STEEL TORQUE TUBE POLYETHYLENE PIPE WITH THRUST WITHOUT POLYETHYLENE
N OT STAINLESS STEEL LUGGED KNIFE GATE VALVE
FLANGE AND "HYDROTITE" SEALS LINING. SEE NOTE G11. E
ATTACHMENT BRACKETS SPACED TO AND TO BE FUSION WELDED TO SE WITH METAL SEAT AND RTFE SCRAPER,
MANUFACTURER'S REQUIREMENTS INTERNAL WALL LINING. DN600 CLASS D "KEYSTONE FIGURE 952" OR SEQ-SP APPROVED
MINIMUM CLEARANCE TO BACK MAINTENANCE HOLE ALTERNATIVE, IS TO BE INSTALLED.
VACTOR PIPE AND AIR PIPE. FOR DETAILS COVER AND FRAME THIS VALVE IS TO BE MODIFIED WITH SPINDLE
AND INSTALLATION REFER SEQ-SP FACE OF FLANGE TO BE 150. NUT REMOVED AND THROUGH SPINDLE SHAFT
FOR PERSON ACCESS.
TYPICAL WALL THICKENING FOR SEE NOTES G4 AND G8 INSTALLED.
FOR INLET PIPES UNDER DN600 ALL WALL PIPES TO PROVIDE FOR INLETS DN600 AND ABOVE A FULL 316
INSTALL A FULL STAINLESS 150 MINIMUM CONCRETE COVER PLAN OF TOP SLAB STAINLESS STEEL WEDGE CLOSING DESIGN
STEEL LUGGED KNIFE GATE TO BACK FACE OF FLANGES NOT TO SCALE PENSTOCK WITH INSITU REPLACEMENT SEAL IS
VALVE WHICH IS MODIFIED WITH TO BE INSTALLED. VALVES AND PENSTOCKS
SPINDLE NUT REMOVED AND DN450 AND ABOVE ARE TO BE FITTED WITH
SPINDLE EXTENDED TO SURFACE. POLYETHYLENE MECHANICALLY DN160 POLYETHYLENE GEARBOXES. VALVES SMALLER THAN DN450 ARE
SEE NOTE G7. ANCHORED LINING CAST INTO VACTOR PIPE. FOR TO BE FITTED WITH A RISING SPINDLE
WALL WITH 100 HORIZONTAL DN32 POLYETHYLENE AIR PIPE. DETAILS REFER SEQ-SP MECHANISM.
POLYETHYLENE HEAT SHRUNK RETURN AT TOP OF WALL. LINING FOR DETAILS REFER SEQ-SP G8. THE MAINTENANCE HOLE COVERS ARE TO BE
SLEEVE ATTACHED DURING TO TERMINATE 200 BELOW FLUSH MOUNTED WITH THE TOP SLAB. THE FRAME
FABRICATION OF WALL PIPE. BOTTOM WATER LEVEL. FOR MASS CONCRETE BENCHING EXTERNAL COATING AND THE 35 HIGH RISER RING MAY BE INSTALLED
DETAILS SEE DRAWING TO CONCRETE. SEE IN RECESS IN TOP SLAB WITH NON SHRINK
SEQ-SPS-1407-1
DOUBLE FLANGED THICKEN AND REINFORCE G2 NOTE S10. EPOXY GROUT OR ALTERNATIVELY CAST IN PLACE.
STAINLESS STEEL 300 WALLS TO STRUCTURALLY TE G9. IF PIPES OF MATERIAL OTHER THAN
SE
WALL PIPE. THE PIPE TOP OF BRACKET RL*.*** SUPPORT INLET AND NO. POLYETHYLENE ARE USED, EXTERNAL TO THE
E
IS TO BE FULLY OUTLET PIPES. PROVIDE E STRUCTURE, THEN SHORT SOCKETED PIPES ARE
N.
150 MINIMUM COVER TO SE
O
DETAILED ON REMOVABLE SS316 TO BE USED DIRECTLY ADJACENT TO THE WALLS.
TE
PROJECT DRAWINGS SCREENS WITH SS316 BACK OF FLANGES. G10. IF DIRECTED BY SEQ-SP A HIGH LEVEL OVERFLOW
3 NO. OFF SS316 BAR
900
G
TO SUIT INCOMING SUPPORT BRACKET AND PIPE MAY BE REQUIRED ON ALL NEW PUMPING
2
SEWER DIAMETER INLET SS316 LOCATING PINS. SCREENS. FOR DETAILS
100
200
MUST BE VERTICAL. IL*.*** G13. A VENT POLE (VENT POLE NO. 1) IS REQUIRED
SECTION A FOR THE GRIT COLLECTOR MAINTENANCE HOLE
IL*.*** OUTLET PIPE REFER AND THE PUMP WELL. THIS POLE IS TO BE
OUTLET PIPE TO THE PUMP STAINLESS STEEL TO SECTION A SEPARATE FROM VENT POLE NO. 2 WHICH VENTS
INCOMING SEWER FROM
50
WELL IS TO HAVE A MINIMUM WALL PIPE FOR THE EMERGENCY STORAGE CHAMBER. THE VENT
SE
DIVERSION MH. FULL DETAILS INTERNAL DIAMETER OF VALVE. REFER TO
TO BE GIVEN ON PROJECT 2 2 NO. OFF STAINLESS PIPE TO THE POLE IS TO BE INTERCONNECTED
E
ID225. WHEN THE INCOMING SECTION A G STEEL BAR SCREEN WITH THE VENT PIPE FROM THE PUMP WELL.
NO
DRAWINGS. IF VC OR DICL PIPE RL*.***
IS USED THEN SHORT LENGTHS SEWER IS GREATER THAN TE LOCATING PINS. REFER NOTE: THE WELLS ARE NOT TO BE DIRECTLY
.T
ID225 THE OUTLET PIPE IS TO KNIFE GATE O TO DRAWING INTERCONNECTED.
E
ARE TO BE USED ADJACENT TO
.
BE THE SAME DIAMETER AS VALVE. REFER N SEQ-SPS-1401-1 FOR DETAILS OF THE VENT AND POLE REFER TO
G2
GRIT COLLECTOR WALL AND
VERTICAL DEFLECTIONS ARE 200 THIS INCOMING SEWER TO TO SECTION A
S EE DRAWING NO. SEQ-SPS-1405-1
ALLOWED AT PIPE JOINTS. IF THE GRIT COLLECTOR. TO BE
DETAILED ON PROJECT PROVIDE 50 FALL 375 WIDE STAINLESS
POLYETHYLENE PIPE IS USED DRAWINGS. IN BASE SLAB STEEL OR APPROVED STRUCTURAL
THEN PIPE MAY BE BENT FLOOR TO INLET 300 200 ALTERNATIVE LADDER
VERTICALLY AT A MINIMUM BENCHING S1. THE STRUCTURE IS TO BE DESIGNED TO ALL
MASS CONCRETE BENCHING. OF VACTOR PIPE BOLTED TO WALL. FOR RELEVANT CODES AND PRACTICES AND IS TO
RADIUS AS PER POP 202. REFER TO DRAWING 100 DETAILS REFER SEQ-SP
NOTE. INSTALLATION METHOD 1200 INCLUDE AS3735 AND AS3600.
SEQ-SPS-1401-1 FOR FORM BENCHING AT BASE OF S2. THE TOP SLAB IN ANY LOCATION SHALL BE
MUST ALLOW WALL PIPE TO BE 230 MIN. 230 MIN. DETAILS OF SCREEN PINS BENCHING
LAID HORIZONTALLY. BASE OF LADDER TO DESIGNED FOR A TRAFFICABLE LOAD OF AT
1800 AND BONDING TO GIVE CLEARANCE TO Ø1200 LEAST W80 TO AS5100. HOWEVER THE DESIGN
POLYETHYLENE LINING BOTTOM RUNG SHALL COMPLY WITH ALL REQUIREMENTS SET
PROVIDE 50 FALL IN 2260 MIN. Ø1800 OUT IN AS5100.
BASE SLAB FLOOR TO S3. THE TOP SLAB IS TO BE OF SUFFICIENT MASS TO
INLET OF VACTOR PIPE OUTSIDE DIAMETER VARIES TO SUIT WITHSTAND THE UPTHRUST FROM THE VALVE
STRUCTURAL REQUIREMENTS FORM BENCHING OVER
VACTOR PIPE TO PROVIDE SPINDLE. THE TOP SLAB IS TO HAVE A MAXIMUM
BASE OF VACTOR TO BE A 150 MINIMUM COVER TO THICKNESS OF 350.
TRIMMED TO ALLOW INVERT PIPE S4. THE MINIMUM EXPOSURE CLASS OF THE
OF PIPE TO BE LEVEL WITH SECTION ELEVATION A SECTION PLAN B INTERNAL CONCRETE SURFACE IS TO BE B2 TO
INVERT OF FLOOR AS3735 AND THE COVER IS TO BE MEASURED
NOT TO SCALE - NOT TO SCALE FROM THE REINFORCEMENT STEEL TO THE
- EMBEDMENT LUGS OF THE POLYETHYLENE LINING.
900
A 1 4
100
-
INVERT OF OUTLET
A C
- -
900
40
800
C
-
MAXIMUM
MAINTENANCE HOLE REQUIREMENTS REFER
50 100
75 TO DRAWING NO. SEQ-SPS-1400-1. FOR
175
PROJECTION
SPECIFIC DETAILS OF THE ANGLE BETWEEN
4 THE INLET AND OUTLET PIPES REFER TO
NOTE G2 ON DRAWING NO. SEQ-SPS-1400-1.
100
6 NO. OFF Ø12 GRADE 316 G2. THE SCREEN SUPPORT BRACKET IS TO BE
3
STAINLESS STEEL L SHAPED INSTALLED WITH INSULATING WASHERS
REINFORCEMENT BARS AND SLEEVES BETWEEN THE BRACKET AND 4 MECHANICALLY BONDED
300
CHEMICALLY ANCHORED THE STAINLESS STEEL ANCHORS. THE NUTS POLYETHYLENE LINING
WITH 110 EMBEDMENT ARE TO BE ASSEMBLED WITH ANTI GALLING CAST INTO WALL
INTO MH WALL. PITCH = COMPOUND.
100
75 50 STAINLESS STEEL
175. COVER = 50. MASS CONCRETE
REINFORCEMENT
BENCHING 200 SEE SECTIONAL
4
PLAN C
200
DETAILS SHOWN ON
ITEM DESCRIPTION MATERIAL NO. REQUIRED
300 Ø1200 300 DRAWING NO.
BENCHING
1 SCREEN SUPPORT BRACKET TYPE 316 STAINLESS STEEL 1 REFER SEQ-SP
Ø1800
TYPE 316 STAINLESS STEEL
2 M16 CHEMICAL ANCHOR SEE NOTE G2. 4 SEE NOTE G2.
SECTIONAL PLAN C
NOTE: SCREENS NOT - 3 BAR SCREEN TYPE 316 STAINLESS STEEL 3 REFER SEQ-SP
SHOWN ON THIS VIEW
4 SCREEN LOCATING PIN TYPE 316 STAINLESS STEEL 2 REFER SEQ-SP
VALVE INSTALLATION WITH POLYETHYLENE INLET PIPE VALVE INSTALLATION WITH DICL INLET PIPE
NOT TO SCALE SEE NOTE G5.NOT TO SCALE
SEWER
SEWER
CLASS D SEALED
500
(MACHINE TO SUIT SEAL ATTACHED TO THE SWITCHBOARD, VENT POLE TO BE
BETWEEN uPVC PIPE AND POLE) USED IF EXTRA HEIGHT REQUIRED.
WITH APPROVED SEALANT 3. VENT POLES SHALL BE DESIGNED TO ACHIEVE ODOUR
AND AIR MOVEMENT AS PER ODOUR ASSESSMENT
IMPACT REPORT.
4. HEIGHT AS PER ODOUR ASSESSMENT IMPACT REPORT,
TELEMETRY AND LIGHTING PREFERRED COLOURS ARE HERITAGE OR MIST GREEN.
WHERE SPECIFIED. 5. THE FOUNDATION DESIGN SHOWN ON THIS DRAWING
IS GIVEN AS AN EXAMPLE. THE VENT POLE SUPPORT
SHALL BE DESIGNED AND CERTIFIED BY A RPEQ
DN225 FRP/GRP/STEEL VENT POLE HEIGHT STRUCTURAL ENGINEER TO CURRENT AUSTRALIA
TO SUIT (SEE NOTE 4) (REFER ACCEPTED STANDARDS AND CODES.
MATERIALS LISTING) 6. DIMENSIONS ARE IN MILLIMETRES UNLESS SHOWN
OTHERWISE.
SEE NOTE 4
uPVC TAPER WHERE
REQUIRED TO FIT POLE ID
INSPECTION
OPENING AND
COVER
DN200 uPVC
VENT PIPE
SEE
NOTE 5
MAINTENANCE HOLE
SHORT PIPE 500 MAX.
TOP OF BENCHING
APPROVED FBE DI
MIN.
MH COUPLING
THRUST GRAVITY
FLANGE FLOW MAIN
50
RISING MAIN
5
THE ARRANGEMENT DETAILED ON THIS DRAWING SHALL BE USED
11
WHERE THE PUMP FLOW RATES CAN NOT ACHIEVE NON-TURBULENT
200
RISING MAIN FROM
DISSIPATION IN THE DISCHARGE MAINTENANCE HOLE.
PUMPING STATION
00
Ø9
A A NOTES
- -
1. ALL WORK AND MATERIALS SHALL BE IN ACCORDANCE WITH
FLOW FLOW
FLOW CURRENT SEQ-SP SPECIFICATIONS AND STANDARDS.
MIN
150
2. UNLESS SPECIFIED OTHERWISE ALL MATERIALS AND WORK
200
SHALL COMPLY WITH THE RELEVANT AUSTRALIAN
5
11
PE LINING STANDARDS.
3. ALL CONCRETE SHALL BE SPECIAL CLASS TO WSA PS-358.
DISCHARGE M.H. RETICULATION M.H. 4. REINFORCING BARS SHALL BE TACK WELDED AT ALL
INTERSECTIONS.
SECTIONAL PLAN 5. TOP SLAB THICKNESS SHALL BE INCREASED FROM 115mm TO
150mm WHERE CLASS "D" COVERS ARE SPECIFIED FOR
MAINTENANCE HOLE TOP SLAB SEE TRAFFICABLE LOCATIONS.
ARRANGEMENT SEE NOTE 6 1000 MIN
NOTE 19 6. MAINTENANCE HOLE FRAME, COVER AND COPING SHALL SUIT
MAX
SEE NOTE 5 10000 MAX SEQ-SEW-1301-1, AND SEQ-SEW-1308 SERIES FOR DETAILS.
(SEE NOTE 18) SURFACE LEVEL
SURFACE LEVEL 7. ALL CONCRETE SHALL BE VIBRATED.
8. VC SEWERS SHALL BE CLASS 4 TO A.S. 1741 OR CONFORM
REFER SEQ-SPS-1407-1 TO EN295-1. DICL SEWERS SHALL BE CLASS PN35 TO A.S.
115
1150 MIN
FOR PE LINING DETAILS EXISTING OR PROPOSED 2280 AND POLYETHYLENE SLEEVED. PE PIPELINES SHALL BE
3000 MAX
150
I.L. 3 9. DISCHARGE MAINTENANCE HOLE LINER SHALL BE
(NTS)
PE PIPE SEE NOTE 10 POLYETHYLENE CLASS PE100 TO AS/NZS 4130 AND AS/NZS
MIN
100
4131.
PE LINING DETAILS 10. ALL POLYETHYLENE PIPES AND FITTINGS SHALL BE JOINED
SEE FLOW USING BUTT WELDING AND/OR ELECTRO FUSION WELDING
SEQ-SPS-1407-1 I.L. 2 PROCESSES.
FLOW 250
11. ALL DIMENSIONS ARE IN MILLIMETRES.
45° GRAVITY SEWER
I.L. 1 2D 12. THIS STANDARD DRAWING APPLIES FOR ALL RETICULATION
D
SEWERS UP TO DN250 NUSEWER.
50mm FALL ACROSS
13. DISCHARGE MAINTENANCE HOLES SHALL NOT BE LOCATED IN
FLOW MAINTENANCE HOLE
SEAL WELD PE PRIVATE PROPERTY.
RISING MAIN FROM SEE NOTE 17
LINING AT 14. MAINTENANCE HOLES IN FOOTPATH LOCATION SHALL BE
PUMPING STATION
MIN
150 CORNER
15. ALL PIPEWORK SHALL FINISH FLUSH WITH INSIDE FACE OF
SEE NOTE 10 NOTE MAINTENANCE HOLE WALL.
ANCHOR BLOCK SIZE INVERT LEVELS 1, 2 & 3 TO 16. UPVC PIPES SHALL NOT BE USED BETWEEN THE DISCHARGE
VARIES WITH PIPE BE PROVIDED FOR EACH MAINTENANCE HOLE AND THE FIRST RETICULATION
1D x 2D ENLARGER SIZE AND PUMP LINE INDIVIDUAL PROJECT MAINTENANCE HOLE.
CHARACTERISTICS
17. FOR DISCHARGE TO OTHER THAN RETICULATION SEWERS OR
90° ELBOW WITH MINIMUM DEEP SEWERS, REFER TO POLYETHYLENE LINE SEWER
150mm CONCRETE SURROUND
MAINTENANCE HOLE STANDARD DRAWING SEQ-SEW-1307-2.
18. MAINTENANCE HOLES SHALL BE CONSTRUCTED AS CLOSE AS
PRACTICABLE.
DISCHARGE M.H. RETICULATION M.H. 19. FOR TOP SLAB ARRANGEMENT SEE SEQ-SEW-1301-3.
SECTIONAL ELEVATION A
-
REV. No. DATE DESCRIPTION AUTH.
SEWAGE PUMP STATION STANDARD DRAWING CoGC LCC RCC QUU UW
SEQ WATER PREFERRED RISING MAIN DISCHARGE
DRAWING No. VERSION
5
FROM PUMPING SEWER 1. ALL WORK AND MATERIALS SHALL BE IN ACCORDANCE WITH CURRENT
11
STATION SEQ-SP SPECIFICATIONS AND STANDARDS.
MIN
200
2. UNLESS SPECIFIED OTHERWISE ALL MATERIALS AND WORK SHALL
00
COMPLY WITH THE RELEVANT AUSTRALIAN STANDARDS.
Ø9
A A 3. ALL CONCRETE SHALL BE SPECIAL CLASS TO WSA PS-358.
- - 4. REINFORCING BARS SHALL BE TACK WELDED AT ALL INTERSECTIONS.
5. TOP SLAB THICKNESS SHALL BE INCREASED FROM 115mm TO 150mm
FLOW FLOW FLOW WHERE CLASS "D" COVERS ARE SPECIFIED FOR TRAFFICABLE
MIN
200
LOCATIONS.
5
11
PE LINING 6. MAINTENANCE HOLE FRAME COVER AND COPING SHALL SUIT
APPLICATION REFER STANDARD DRAWING NOS SEQ-SEW-1301-1 AND
SEQ-SEW-1308 SERIES FOR DETAILS.
DISCHARGE M.H. RETICULATION M.H. 7. ALL CONCRETE SHALL BE VIBRATED.
8. VC SEWERS SHALL BE CLASS 4 TO A.S 1741 OR CONFORM TO
EN295-1.DICL SEWERS SHALL BE CLASS PN35 TO A.S. 2280 AND
SECTIONAL PLAN POLYETHYLENE SLEEVED PE PIPELINES SHALL BE CLASS PE100 TO
AS/NZS 4130 AND AS/NZS 4131.UPVC SEWERS SHALL BE SN8 EXCEPT
FOR DN100 WHICH SHALL BE SN10.
TOP SLAB SEE 9. DISCHARGE MAINTENANCE HOLE LINER SHALL BE POLYETHYLENE
NOTE 18. CLASS PE100 TO AS/NZS 4130 AND AS/NZS 4131.
10. ALL POLYETHYLENE PIPES AND FITTINGS SHALL BE JOINED USING
MAINTENANCE HOLE 40000 MAX BUTT WELDING AND/OR ELECTRO FUSION WELDING PROCESSES.
ARRANGEMENT SEE NOTE 6 11. ALL DIMENSIONS ARE IN MILLIMETRES.
12. THIS STANDARD DRAWING APPLIES FOR ALL RETICULATION SEWERS
MAX
350
1150 MIN
1150 MIN
115 Ø900 115 15. ALL PIPEWORK SHALL FINISH FLUSH WITH INSIDE FACE OF
MAX
RETICULATION
MAINTENANCE HOLE MAINTENANCE HOLE WALL.
16. UPVC PIPES SHALL NOT BE USED BETWEEN THE DISCHARGE
MIN
100
MIN
150
PE LINING DETAILS MAINTENANCE HOLE AND THE FIRST RETICULATION MAINTENANCE
SEE SEQ-SPS-1407-1 I.L. 2 I.L. 3 SEE NOTE 10 HOLE.
17. FOR DISCHARGE TO OTHER THAN RETICULATION SEWERS OR DEEP
SEWERS, REFER TO POLYETHYLENE LINE SEWER MAINTENANCE HOLE
I.L. 1 45° FLOW FLOW
2D STANDARD DRAWING SEQ-SEW-1307-2.
D
PE PIPE 250 18. FOR TOP SLAB ARRANGEMENT SEE SEQ-SEW-1301-3.
FLOW GRAVITY
SEE NOTE 17 SEWER PUMP FLOW RATES SHALL BE DESIGNED TO PROVIDE A
SEAL WELD PE NON-TURBULENT DISSIPATION IN THE DISCHARGE
MIN
150
RISING MAIN FROM 150 LINING AT MAINTENANCE HOLE. THE GRAVITY SEWER BETWEEN
PUMPING STATION CORNER NOTE THE DISCHARGE MAINTENANCE HOLE AND THE
SEE NOTE 10 ANCHOR BLOCK SIZE VARIES WITH PIPE INVERT LEVELS 1, 2 & 3 TO RETICULATION MAINTENANCE HOLE SHALL BE TREATED
SIZE AND PUMP LINE CHARACTERISTICS BE PROVIDED FOR EACH AS THE LAST LENGTH OF SEWER TO AN END. THE
1D x 2D ENLARGER INDIVIDUAL PROJECT DESIGN VELOCITIES FROM THE DISCHARGE
90° ELBOW WITH MINIMUM
MAINTENANCE HOLE SHALL CONFORM WITH THE DESIGN
150mm CONCRETE SURROUND
VELOCITIES FOR GENERAL SEWER DESIGN AS SET OUT
IN THE "SEWERAGE CODE OF AUSTRALIA WSA-02".
SECTIONAL ELEVATION A
-
200
RISING MAIN FROM 5. TOP SLAB THICKNESS SHALL BE INCREASED FROM 115mm TO 150mm
WHERE MH IS GREATER
PUMPING STATION WHERE CLASS "D" COVERS ARE SPECIFIED FOR TRAFFICABLE LOCATIONS.
THAN 4250 DEEP
6. MAINTENANCE HOLE FRAME, COVER AND COPING SHALL SUIT
0
20
A A APPLICATION. REFER STANDARD DRAWING NOS. SEQ-SEW-1301-1 AND
Ø1
- - SEQ-SEW-1308 SERIES FOR DETAILS.
FLOW FLOW 7. ALL CONCRETE SHALL BE VIBRATED.
FLOW 8. VC SEWERS SHALL BE CLASS 4 TO A.S. 1741 OR CONFORM TO EN295-1.
200
SEE NOTE 10
DICL SEWERS SHALL BE CLASS PN35 TO A.S. 2280 AND POLYETHYLENE
PE SEE NOTE SLEEVED. PE PIPELINES SHALL BE CLASS PE100 TO AS/NZS 4130 AND
LINING 10 AS/NZS 4131. UPVC SEWERS SHALL BE SN8 (SN10 FOR DN100) TO A.S.
1260.
9. DISCHARGE MAINTENANCE HOLE LINER SHALL BE POLYETHYLENE CLASS
DISCHARGE M.H. RETICULATION M.H. PE100 TO AS/NZS 4130 AND AS/NZS 4131.
10. ALL POLYETHYLENE PIPES AND FITTINGS SHALL BE JOINED USING BUTT
WELDING AND/OR ELECTRO FUSION WELDING PROCESSES.
SECTIONAL PLAN 11. ALL DIMENSIONS ARE IN MILLIMETRES.
12. THIS STANDARD DRAWING APPLIES FOR ALL RETICULATION SEWERS UP
TO DN315 NU SEWERS.
TOP SLAB SEE SEQ-SEW-1301-5
13. DISCHARGE MAINTENANCE HOLES SHALL NOT BE LOCATED IN PRIVATE
OR SEQ-SEW-1301-11
PROPERTY.
MAINTENANCE HOLE
14. MAINTENANCE HOLES IN FOOTPATH LOCATION SHALL BE CONSTRUCTED
ARRANGEMENT SEE NOTE 6 1000 MIN
ON CENTRE LINE OF SEWERAGE ALLOCATION.
MAX
FOR PE LINING DETAILS PE BRACKET 17. FOR DISCHARGE INTO EXISTING TRUNK SEWERS OR DEEP SEWERS,
EXISTING OR PROPOSED
RISING MAIN FROM (SEE NOTE 20) REFER TO STANDARD DRAWING SEQ-SEW-1307-2.
I.L. 1
PUMPING STATION 18. MAINTENANCE HOLES SHALL BE CONSTRUCTED AS CLOSE AS
PE LINING PRACTICABLE.
FLOW MECHANICALLY RETICULATION MAINTENANCE
19. OGEE PROFILE BEND WITH INSPECTION OPENING FABRICATED FROM
BOXED NOTES
3000 MIN SEE
150
PE BEND I.L. 3 ADDITIONAL BRACKETS SHALL BE AT MAXIMUM 1500mm SPACINGS.
(SEE NOTE 19) PE DROP PIPE
(NTS)
MIN
100
PE PIPE
300
GRAVITY SEWER TO BE LESS THAN 3.0m. IN THIS CASE, GRAVITY SEWER SYSTEM
WHERE PRACTICABLE, THE BOTTOM INLET REQUIRES THE DISCHARGE
50mm FALL ACROSS CONFIGURATION SIMILAR TO DRG MAINTENANCE HOLE TO BE
(NTS)
MAINTENANCE HOLE
200
***
FIBREBOARD "FOSROC DRAWINGS FOR DETAILS
CELLFLEX" OR APPROVED 20 TOP OF BENCHING LEVEL AS OUTLET PIPE TO PUMP WELL
30 100
EQUIVALENT INDICATED ON PROJECT WALL BRACKET
DRAWINGS INVERT OF OUTLET PIPE
150
200
20 MASS CONCRETE WALL BRACKET ATTACHMENT
TOP OF WALL LEVEL AS BENCHING NOT TO SCALE
INDICATED ON PROJECT
DRAWINGS
MECHANICALLY BONDED
POLYETHYLENE LINING
100 MINIMUM WIDTH CAST INTO WALL
MECHANICALLY ANCHORED
WRAP PORTION OF POLYETHYLENE LINING WITH POLYETHYLENE LINING
FIBREBOARD IN CONTACT ANCHOR KNOBS FACING STAINLESS STEEL
REINFORCEMENT PE1. POLYETHYLENE LINING TO BE A MECHANICALLY
WITH SEALANT WITH 40 OUTWARDS TO BE WELDED TO ANCHORED LINING CAST INTO WALL AND TOP
POLYETHYLENE SHEETING POLYETHYLENE WALL LINING 200 SLAB. "STEULER LINING 400" OR SEQ-SP
AND TAPE IN PLACE. MASS CONCRETE APPROVED EQUIVALENT. LINING IS TO HAVE
100
SEE NOTE PE11 BENCHING MINIMUM SHEET THICKNESS OF 2.5mm. THE
LINING IS TO BE WHITE OR A SEQ-SP APPROVED
LIGHT COLOUR.
BENCHING AND WALL JUNCTION BAR SCREEN BENCHING PE2. THE LINING IS TO BE INSTALLED BY AN
"EMER-SEAL CR" OR NOT TO SCALE NOT TO SCALE SEE NOTE PE10 INSTALLER ACCREDITED BY THE LINING
MANUFACTURER.
APPROVED EQUIVALENT PE3. THE LINING IS TO BE CONTINUOUS OVER ALL
SEALANT. THE TOP SLAB INTERNAL SURFACES.
MUST BE INSTALLED NOTES: PE4. THE LINING IS TO BE EXTRUSION WELDED TO ALL
BEFORE THE SEALANT HAS PIPES PASSING THROUGH WALL.
CURED. SEE NOTE PE11 G1. MECHANICALLY ANCHORED POLYETHYLENE PE5. ALL THE JOINS IN THE LINING ARE TO BE
LINING IS REQUIRED ON ALL PUMPING EXTRUSION WELDED. WHERE A FILLER ROD IS
STATIONS AND MAY ONLY BE OMITTED IF REQUIRED IT IS TO BE TO THE LINING
DETAIL OF TOP SEAL PRIOR WRITTEN APPROVAL IS GIVEN BY MANUFACTURER'S SPECIFICATION.
SEQ-SP. PE6. ALL HOLES DRILLED THROUGH LINER FOR
G2. THE DIMENSIONS OF THE STRUCTURES ANCHOR BOLTS, ETC, SHOULD BE SEALED WITH A
TWO LAYERS OF 10 SEWER CLASS D WILL VARY AND THE DIMENSIONS SHOW 12 THICK SPONGE NEOPRENE GASKET
20 MH COVER AND
THICK BITUMINOUS 30 *** ARE TO BE INDICATED ON THE COMPRESSED BETWEEN LINING AND EQUIPMENT
IMPREGNATED 50 FRAME PROJECT DRAWINGS. WALL PLATE.
FIBREBOARD "FOSROC NTS NON SHRINK PE7. THE POLYETHYLENE LINING IS TO BE INSTALLED
EPOXY GROUT TO THE MANUFACTURER'S REQUIREMENTS TO
CELLFLEX" OR PREVENT DISTORTION WHEN THE CONCRETE IS
APPROVED EQUIVALENT POURED.
PE8. IF WHITE COLOURED NATURAL POLYETHYLENE IS
20 USED IT IS NOT TO BE EXPOSED TO DIRECT
SUNLIGHT AT ANY TIME. THE POLYETHYLENE
MANUFACTURER'S REQUIREMENTS FOR STORAGE
***
AND HANDLING AND SHELF LIFE MUST BE
WRAP PORTION OF FOLLOWED.
FIBREBOARD IN 20 PE9. AFTER INSTALLATION THE LINING IS TO BE
CONTACT WITH SEALANT TESTED IN ACCORDANCE WITH WSA 02 OR
WITH POLYETHYLENE SEQ-SP REQUIREMENTS. THE TESTING INCLUDES
SHEETING AND TAPE IN SPARK TESTING AND PULL-OUT TESTS WHICH ARE
PLACE. SEE NOTE PE11 40 POLYETHYLENE LINING SEAL WELD POLYETHYLENE TO BE CARRIED OUT BY AN NATA ACCREDITED
SEAL WELD INDEPENDENT TESTER. THE TEST RESULTS MUST
POLYETHYLENE ON UNDERSIDE OF TOP LINING AT CORNERS BE SUBMITTED TO SEQ-SP AS PART OF THE
175 LINING AT SLAB AND INSIDE COMMISSIONING. THE AFOREMENTIONED
"EMER-SEAL CR" OR CORNERS OPENINGS PE100 SDR41 PN4 POLYETHYNENE TESTING IS IN ADDITION TO THE TESTING
APPROVED EQUIVALENT PIPE. DN250 FOR TORQUE TUBE REQUIRED UNDER AS3735.
SEALANT. THE TOP SLAB 100 INSTALLATIONS AND DN110 FOR PE10. THE POLYETHYLENE LINING IS TO FINISH 200
MUST BE INSTALLED SEAL WELD
EXPOSED VALVE SPINDLE MINIMUM BELOW BOTTOM WATER LEVEL. THE
BEFORE THE SEALANT HAS POLYETHYLENE LINING LINING IS TO FINISH WHERE POSSIBLE ABOVE
AT CORNERS INSTALLATIONS. THIS PIPE MAY BE
CURED. SEE NOTE PE11 POLYETHYLENE LINING BLACK IN COLOUR. ALTERNATIVELY TO THE BENCHING LEVEL. THE EXCEPTION IS THE
CAST INTO CONCRETE BENCHING FOR THE GRIT COLLECTOR
***
USING PIPE THE `250 HOLE MAY BE MAINTENANCE HOLE BAR SCREEN BENCHING.
44 WITH 100 RETURN ON FORMED USING THE LINING MATERIAL. PE11. THE "EMER-SEAL CR" SEALANT MUST NOT COME
CLOSED CELL POLYETHYNENE TOP SURFACE OF WALL HOLE DIAMETER IS TO BE DETAILED IN CONTACT WITH THE BITUMINOUS
FOAM BACKING Ø25 ROD ON THE PROJECT DRAWINGS IMPREGNATED FIBREBOARD.
"FOSROC EXPANDAFOAM" OR
APPROVED EQUIVALENT
WALL AND TOP SLAB JUNCTION VALVE SPINDLE OPENING
NOT TO SCALE NOT TO SCALE
REV. No. DATE DESCRIPTION AUTH.
SEWAGE PUMP STATION STANDARD DRAWING CoGC LCC RCC QUU UW
SEQ WATER POLYETHYLENE LINING
DRAWING No. VERSION
EMERGENCY STORAGE
RISING SPINDLE
900mm TO 1100mm
PLATE DIMENSIONS
FOR INLET MH AND
LETTERING HEIGHT
MECHANISM
STAINLESS STEEL
HIGH
SUPPORT PLINTH.
TO SUIT
100 FOR WET-WELL 60
FOR INLET MH AND
EMERGENCY STORAGE
GRADE 316
1.5 THICK
SS PLATE
ELEVATION
NOTE: INSTALL LABEL PLATE TYPICAL RISING SPINDLE MECHANISM ABOVE GROUND
WITHIN 100 OF BENCH MARK (SECURITY FENCED AREAS ONLY)
SURVEY LABEL PLATE DETAILS
MAX.
PROVIDE ONE BOLT
380
PLAN EACH CORNER (4 OFF)
GRADE 316
SS PLATE
3 THICK
EXISTING CONCRETE
SURFACE
Ø6 GRADE 316 SS ROUND HEAD BOLT RISING SPINDLE MECHANISM UNDER SLAB
80 LONG. EPOXY GROUT INTO HOLE
OPPOSITE
BACKGROUND
100
VALVE
14 15
67.5
SECURE NOTICE PLATE
72.5
KERB MARKING AS
WITH GALVANISED POP
DETAILED BELOW
RIVETS LETTERING TO SUIT
KERB & CHANNEL
1000 MIN
40
V
OPPOSITE
312.5
ORANGE MARKER POST DIMENSION TO BE CONFIRMED
*
1350 MIN
VALVE
OF A STRUCTURAL BY SEQ-SP PRIOR TO PAINT
240
SHAPE APPROVED BY APPLICATION PAVEMENT MARKING
SEQ-SP. AS DETAILED
40
ROAD PAVEMENT ℄
OR FACE OF MEDIAN KERB GLASS BEADS
KERBED STREETS/ROADS
350 MIN
I MINIMISED.
250 NOM
DISTANCE TO VALVE KERB MARKING THE EXACT LOCATION SHALL BE DETERMINED BY THE SEQ-SP FOLLOWING SITE
3
INSPECTIONS.
250 SIZE OF VALVE
3. MARKER POSTS SHALL ONLY BE USED IN STREETS AND ROADS WHERE THERE IS NO
V IV - ISOLATION VALVE
GV - GAS VALVE
KERB & CHANNEL OR AS DIRECTED BY THE SEQ-SP.
4. THE NOTICE PLATE SHALL BE REFLECTORIZED ALUMINIUM WITH BLACK LETTERING ON
A ORANGE BACKGROUND.
SV - SCOUR VALVE 5. MARKER POSTS SHALL BE POSITIONED AT THE FRONT OF THE PROPERTY BOUNDARY
VV - VACUUM SECTION VALVE OPPOSITE THE FITTING.
TYPICAL NOTICE PLATE
RM - RISING MAIN 6. DIMENSIONS ARE IN MILLIMETRES UNLESS SHOWN OTHERWISE.
ARRANGEMENT
FIXED TO POST MARKER DISCS & NOTICE PLATE CODES
30
6 NO. OFF M16 STAINLESS STEEL CHEMICAL ANCHORS WITH SPINDLE CAP OR EXTENDED SPINDLE: 316 STAINLESS
LEVELLING NUTS (CHEMSET INJECTION 800 SERIES OR STEEL
VALVE STEM COVER: 316 STAINLESS STEEL
APPROVED EQUIVALENT)
EXTERNAL COATING: THERMAL BONDED EPOXY
PROJECT DRAWINGS
125
GROUT MUST PROVIDE AN ODOUR SEAL MOUNTING FLANGE: ISO 5210-F14 (4 X M16 ON
PCD140)
THE GEARBOX FOR INLET SIZES GREATER THAN DN600
ON PROJECT DRAWINGS
VARIES. TO BE SHOWN
OD455 STAINLESS STEEL BASE PLATE FLANGE WITH 6 IS TO BE SIMILAR TO THE ABOVE BUT WITH GEAR
NO. OFF Ø19 HOLES ON PCD406. TO BE DESIGNED AND RATIO TO SUIT WEDGE GATE PENSTOCK
SUPPLIED BY PENSTOCK MANUFACTURER MANUFACTURER'S REQUIREMENTS.
G3. THE THREADED SPINDLE IS TO PROTRUDE A MINIMUM
OF FOUR THREADS ABOVE THE SPINDLE STOP. THE
DN250 PE100 SDR41 POLYETHYLENE PIPE OR FORMED SPINDLE STOP IS TO BE SIMILAR DESIGN TO SPINDLE
ID237 MIN POLYETHYLENE LINING WELDED TO SLAB UNDERSIDE LINING. STOP SHOWN ON SEQ-SP DRAWINGS.
SEE NOTE G7
THIS POLYETHYLENE MAY BE BLACK IN COLOUR STOP TO BE INSTALLED ON SITE AFTER INSTALLATION
OF VALVE AND GEARBOX AFTER ONSITE DRILLING THE
POLYETHYLENE LINING SPINDLE THREAD IS TO BE CLEANED TO ALLOW
REMOVAL OF SPINDLE NUT.
G4. ALL BOLTS AND NUTS ARE TO BE ASSEMBLED WITH
REMOVABLE STAINLESS STEEL GEARBOX MOUNTING PLINTH WITH
ANTI-GALLING COMPOUND "DURALAC" OR SEQ-SP
TORQUE TUBE EXTENTION WITH FLANGES AS INDICATED. TO BE
APPROVED EQUIVALENT.
DESIGNED AND SUPPLIED BY PENSTOCK MANUFACTURER
G5. ALL STAINLESS STEEL IS TO BE GRADE 316 OR 316L.
ALL OTHER MATERIALS USED ARE TO BE SUITABLE FOR
SPINDLE SPLICE SUPPLIED WITH PENSTOCK. LOCATION AND DESIGN CONTACT WITH SEWAGE AND SEWER GAS.
AS REQUIRED BY PENSTOCK MANUFACTURER. SEE NOTE G7 G6. WHERE THE GEARBOX IS INSTALLED ABOVE THE LEVEL
STAINLESS STEEL TORQUE OF THE TOP SLAB AS SHOWN ON THIS DRAWING AND
TUBE WITH ATTACHMENT BOLTED FLANGE. NOTE: FLANGE TO FIT THE PUMPING STATION IS WITHOUT A SECURITY FENCE
BRACKETS TO WALL. TO BE THROUGH OPENING IN TOP SLAB. SEE THEN A VALVE SPINDLE KEY LOCKABLE COVER IS
DESIGNED AND SUPPLIED BY NOTE G7 REQUIRED.
PENSTOCK MANUFACTURER G7. THE TOP SPLICE IN THE SPINDLE AND TORQUE TUBE
SPINDLE GUIDE BUSH SUPPLIED WITH ABOVE GROUND GEARBOX ARE TO BE LOCATED A NOMINAL 300 BELOW THE
PENSTOCK. LOCATION AND DESIGN AS MOUNTING FOR INLET UNDERSIDE OF THE TOP SLAB. THE DESIGN IS TO
STAINLESS STEEL PENSTOCK
REQUIRED BY PENSTOCK SEWERS DN450 AND ABOVE ALLOW THE SEPARATE REMOVAL OF THE GEARBOX
RISING SPINDLE SUPPLIED
WITH PENSTOCK GEARBOX INSTALLATION MANUFACTURER PLINTH AND THE SEPARATE REMOVAL OF THE
NOT TO SCALE THREADED SECTION OF THE SPINDLE.
EMBEDMENT
GRANULAR FILL 6. WHERE THE MAIN CROSSES EXISTING SERVICES, THE MINIMUM
PIPE
SEE NOTE 3 VERTICAL AND HORIZONTAL CLEARANCE SHALL BE IN
DN ACCORDANCE WITH SEQ-SP CONSTRUCTION SPECIFICATIONS
PIPE 7. METAL TRACER TAPES FOR LOCATION AND IDENTIFICATION OF
BURIED PVC/PE/GRP PRESSURE MAINS AND IDENTIFICATION
100 MIN. TAPES FOR IDENTIFICATION OF BURIED DICL PIPELINES SHALL BE
CREAM COLOURED POLYETHYLENE TAPE WITH THE INSCRIPTION:
"CAUTION - SEWER MAIN BURIED BELOW".
50 ADDITIONAL EXCAVATION METAL TRACER TAPE SHALL BE LAID ALONG THE MAIN ON TOP OF
REQUIRED FOR ROCK. THE PIPE EMBEDMENT MATERIAL, AND SHALL BE ATTACHED TO
METAL SURFACE FITTINGS TO PROVIDE CONNECTION POINTS FOR
TYPICAL PIPE INSTALLATION
LOCATING DEVICES.
REFER SEQ-SP DRAWINGS - SEQ-WAT 8. FOR PIPE COVER AT OTHER LOCATIONS, REFER TO RELEVANT ROAD
1200 SERIES FOR DETAILS OWNER'S REQUIREMENTS.
9. FOR OTHER BURIED CROSSINGS - UNDER OBSTRUCTIONS AND
RAILWAYS, REFER TO SEQ-SP CONSTRUCTION SPECIFICATIONS.
10. FOR BORED AND JACKED ENCASING PIPE DETAILS, REFER TO
SEQ-SP CONSTRUCTION SPECIFICATIONS.
11. FOR ANCHOR BLOCK SIZING REFER TO SEQ-WAT-1205 AND TO THE
CODE FOR DESIGN PRESSURE.
TABLE 1-MINIMUM TRENCH WIDTHS TABLE 2-PIPE COVER REQUIREMENTS 12. THIS IS A TYPICAL DRAWING, REFER TO SEQ-WAT 1200 SERIES
NOMINAL MINIMUM DRAWINGS FOR PIPE INSTALLATION DETAILS.
LOCATION
PIPE TRENCH <=200mm NB >200mm NB
BORE WIDTH (SEE NOTE 8)
NON-TRAFFICABLE AREAS, DRIVEWAYS,
NB (SEE NOTE 5)
VERGES/FOOTWAYS 600 1,000
<100 300 CARRIAGEWAYS OF SEALED LOCAL
ROADS
600 1,000
100 400
CARRIAGEWAYS OF UNSEALED ROADS 750 1,000
150 400 CARRIAGEWAYS OF MAJOR ROADS,
EMBANKMENTS 750 1,000
200 530
INDUSTRIAL / COMMERCIAL AREAS 750 1,000
250 600
CARRIAGEWAYS OF MOTORWAYS /
FREEWAYS 1,200 1,200
300 700
MAXIMUM
"SEWER" (OFFSET CAM LOCK TO ALLOW ACCESS TO MH).
DN 100 MECHANICAL 4. PRECAST CHAMBERS MAY BE USED IN NON-TRAFFICABLE
750
UPVC SHROUD PIPE
COUPLING SEE NOTE 7 AREAS. JOINTS SHALL BE 20 TO 50 THICK FOR CEMENT
EXTENSION SPINDLE MORTAR. ALTERNATIVELY, A 6 THICK BED OF BUTYL
WSA PS-262 MASTIC MAY BE USED.
FL/FL PIPE OR TAPER TO SUIT
SCOUR VALVE SEE NOTE 8 5. CONCRETE FOR SLAB SHALL BE N20.
JOINT SEE NOTE 4 6. REINFORCING FABRIC FOR CONCRETE SLAB SHALL BE TO
S0 & SO & FL MULTI GIB ABFLEX
CONCRETE SLAB AS 1304. EQUIVALENT REINFORCEMENT IN DEFORMED
SCOUR TEE COUPLING
DN SEE NOTES 5 & 6 7. MALE CAMLOCK-TYPE COUPLING TO SUIT: (i) TRAILER
MOUNTED PUMP UNITS AS USED BY SEQ-SP AND (ii)
FL/FL PIPE TO SUIT
TANKERS WITH 16,000/21,000 LITRES CAPACITY.
FL/FL 90° BEND 8. RESILIENT SEATED GATE VALVE TO WSA PS-260.
STABILISED SAND THRUST BLOCK
OR EQUIVALENT FL-SP CONNECTOR
FLEXIBLE JOINT
ELEVATION PIPE
RISING MAIN SCOUR
SEE NOTE 2
EXTENSION SPINDLE
WSA PS-262 UPVC SHROUD PIPE
SCOUR VALVE SEE NOTE 8
S0 & SO & FL SCOUR TEE
DN
TO MAINTENANCE HOLE
ON NEARBY SEWER
PIPE TO SUIT
ELEVATION
RISING MAIN SCOUR
SEE NOTE 2
MAXIMUM
MAXIMUM
350
350
THE MINIMUM DIAMETER OF THE SEWER IS TO BE DN150 AND IS TO BE
230 MAXIMUM
80 MINIMUM
NO LARGER THAN THE RECEIVING SEWER. THE LOCATION OF THE DRAIN
230 MAXIMUM
700
700
80 MINIMUM
SHOWN ON THIS DRAWING IS INDICATIVE ONLY.
G4. INVERT SCOUR TEE FITTINGS MUST BE USED WHEN FITTING IS
600
MANUFACTURED. IN POLYETHYLENE RISING MAINS WHERE AN INVERT
TYPICAL
TYPICAL
DN100 HOLE CAST INTO TOP SLAB. NOTE: DN100 HOLE CAST INTO TOP SLAB. SCOUR TEE MAY NOT BE MANUFACTURED A FABRICATED INVERT SCOUR
300
300
HOLE IS NOT TO BE CORED AFTER NOTE: HOLE IS NOT TO BE CORED TEE IS THE PREFERRED OPTION. THE NON PREFERRED (SEE DETAIL 1) IS
CONCRETE IS POURED AFTER CONCRETE IS POURED AN EQUAL TEE WITH A SHORT ECCENTRIC REDUCER TO AN OD125 STUB
FLANGE. THE VALVE IS TO BE INSTALLED AS CLOSE AS POSSIBLE TO THE
VALVE SPINDLE EXTENSION SEE NOTE G13 FOR MAINTENANCE HOLES LESS THAN 3000 VALVE SPINDLE EXTENSION FOR MAINTENANCE HOLES LESS THAN RISING MAIN.
DN100 SLUICE VALVE. SEE NOTES G4 AND G5 DEEP STEP IRONS ARE TO BE INSTALLED. FOR SEE NOTE G13 3000 DEEP STEP IRONS ARE TO BE G5. THE DIAMETER OF THE SCOUR VALVE FOR RISING MAINS DN300 AND
DEPTHS GREATER THAN 3000 A LADDER IS TO INSTALLED. FOR DEPTHS GREATER THAN SMALLER IS TO BE DN100. ON OD180 PE PIPES AN EQUAL TEE AND A
POLYETHYLENE INVERT SCOUR BRANCH BE INSTALLED INVERT SCOUR TEE 3000 A LADDER IS TO BE INSTALLED DN150 VALVE MAY BE USED. THE VALVE IS TO BE A DOUBLE FLANGED
MACHINED AND FABRICATED FROM SOLID RESILIENT SEATED SLUICE VALVE TO AS 2638.2 WITH FUSION COATED
BLOCK OF POLYETHYLENE AND TESTED TO PN16 POLYMETRIC INTERNAL AND EXTERNAL SURFACES. ALL SURFACES ARE
TO BE SUITABLE FOR SEWERAGE ENVIRONMENTS.
1 GRADE FLOOR AT 1 IN 40 TO OUTLET PIPE IF GRADE FLOOR AT 1 IN 40 TO
G6. THE MINIMUM CLASS FOR THE RISING MAIN PIPES AND FITTINGS IS TO
CLEARANCE
CLEARANCE
- INSTALLED OR IF NOT INSTALLED TO LOW OUTLET PIPE IF INSTALLED OR IF
BE PN16.
FLANGE
FLANGE
UNDER
UNDER
POINT ADJACENT TO ACCESS POINT NOT INSTALLED TO LOW POINT
300
G7. ALL DICL FTTINGS USED INSIDE THE SCOUR MAINTENANCE HOLE ARE TO
300
ADJACENT TO ACCESS POINT
BE FUSION BONDED POLYMETRIC COATED.
G8. ALL BOLTS ARE TO BE GRADE 316 STAINLESS STEEL INSTALLED WITH
ANTI GALLING COMPOUND.
G9. ON POLYETHYLENE RISING MAINS THE BACKING PLATES TO THE FLANGES
OD125 BUTT WELDED STUB FLANGE WITH GRADE 316 GRAVITY SEWER CONNECTION TO SEWERAGE MASS CONCRETE SUPPORT AND GRAVITY SEWER CONNECTION TO ARE TO BE GRADE 316 STAINLESS STEEL.
STAINLESS STEEL BACKING RING. SEE NOTE G15 RETICULATION MAINTENANCE HOLE. SEE NOTE G3 THRUST BLOCK. NOTE: ALLOW SEWERAGE RETICULATION G10. THE DIAMETER OF THE SCOUR MAINTENANCE HOLE FOR DN100, DN150
CLEARANCE FOR BOLT REMOVAL MAINTENANCE HOLE. SEE NOTE G3 AND DN200 RISING MAINS IS TO BE Ø1500 AND FOR DN250 AND DN300
MASS CONCRETE SUPPORT UNDER VALVE AND SCOUR VALVE TEE MUST BE INSTALLED SLUICE VALVE. SEE NOTES G4 AND G5 RISING MAINS IT IS TO BE Ø1800.
BRANCH. NOTE: ALLOW CLEARANCE FOR BOLT REMOVAL HORIZONTALLY TO ALLOW VALVE VALVE TEE MUST BE INSTALLED G11. SCOURS ARE TO BE LOCATED AT THE LOW POINTS IN THE RISING MAIN.
SPINDLE TO BE VERTICAL HORIZONTALLY TO ALLOW VALVE FOR LOCATIONS SUCH AS CREEK CROSSINGS THE SCOUR NEED NOT BE
SECTIONAL ELEVATION SPINDLE TO BE VERTICAL. LOCATED AT THE VERY LOW POINT BUT AT AN ADJACENT ACCESSIBLE
SECTIONAL ELEVATION LOCATION. ALL SCOUR MAINTENANCE HOLES ARE TO BE ACCESSIBLE BY
ARTICULATED TANKER TRUCKS. THIS MAY NECESSITATE THE
NOMINAL LOCATION OF GRAVITY SEWER CONNECTION TO CONSTRUCTION OF AN ALL WEATHER TRACK. IF THE SCOUR
SEWERAGE RETICULATION MAINTENANCE HOLE. SEE NOTE G3 MAINTENANCE HOLE IS IN A ROAD LOCATION THEN CARE MUST BE
TAKEN WHEN POSITIONING THE ACCESS COVER. THE COVER IS NOT TO
BE IN THE WHEEL TRACKS OF THE ROAD LANE.
POLYETHYLENE SEWER RISING SEWER RISING MAIN G12. THE COVERS IN NON TRAFFICABLE LOCATIONS ARE TO BE Ø600 CLASS B
MAIN OD 355 OR SMALLER DN300 OR SMALLER COVERS AND FRAMES AND IN TRAFFICABLE LOCATIONS ARE TO BE Ø600
CLASS D. SEE SEQ-SEW-1308 SET.
PROVIDE SHORT PIPES 1.5 TO
SEE NOTE G15 G13. WHEN THE VALVE SPINDLE EXTENSION EXCEEDS 2000 IN LENGTH 316
2 X DIAMETER LONG ADJACENT
STAINLESS STEEL GUIDES ARE TO BE PROVIDED AT THE TOP AND AT
TO STRUCTURE
WRAP POLYETHYLENE PIPE WHERE PIPE INTERMEDIATE POINTS AS REQUIRED BY THE VALVE MANUFACTURER.
750 MINIMUM CLEARANCE TO STEP IRONS G14. FULLY WELDED MILD STEEL CEMENT LINED PIPE RISING MAINS ARE TO
PASSES THROUGH WALL. SEE NOTE G16 25 X 7 "HYDROTITE
SEE NOTE G15 NOMINAL LOCATION OF GRAVITY BE INSTALLED SIMILARLY TO THE POLYETHYLENE PIPE INSTALLATION.
SEAL CJ-0725-3K"
INVERT SCOUR BRANCHES ARE TO BE USED WITH THIS PIPE. THE PIPE
SEWER CONNECTION TO
POLYETHYLENE INVERT SCOUR BRANCH MACHINED DN100 SLUICE VALVE. INCLUDING THE FLANGE IS TO BE FUSION BONDED POLYETHYLENE
SEWERAGE RETICULATION
AND FABRICATED FROM SOLID BLOCK OF SEE NOTES G4 AND G5 COATED EXTERNALLY. WHERE THE PIPE PASSES THROUGH THE
MAINTENANCE HOLE. SEE NOTE G3
POLYETHYLENE AND TESTED TO PN16 CONCRETE WALL THE WRAPPING IS TO BE REPLACED WITH "HYDROTITE
POLYETHYLENE RISING MAIN OD355
750 MINIMUM 750 MINIMUM SEAL".
OR SMALLER WITH SHORT BUTT
G15. THE FLANGED BRANCH ON POLYETHYLENE AND MILD STEEL RISING
WELDED EQUAL TEE. SEE NOTE G15
MAINS IS TO BE KEPT AS CLOSE AS POSSIBLE TO THE MAIN PIPE. THIS IS
TO REDUCE SLUDGE BUILD UP.
CLEARANCE
LL
LL
FA
FA
MAXIMUM
MAXIMUM
350
350
80 MINIMUM 230 MAXIMUM G3. WHERE POSSIBLE THE SCOUR MAINTENANCE HOLE IS TO DRAIN TO
THE NEAREST SEWERAGE RETICULATION MAINTENANCE HOLE. WHEN
DN100 HOLE CAST INTO TOP SLAB.
700
700
10mm CEMENT MORTAR JOINT INSTALLED THE GRAVITY SEWER CONNECTION MUST DRAIN FROM
NOTE: HOLE IS NOT TO BE CORED
THE INVERT OF THE SCOUR MAINTENANCE HOLE. THE PIPE IS TO BE
AFTER CONCRETE IS POURED Ø600 VALVE SPINDLE EXTENSION Ø600
A STANDARD RETICULATION SEWER WITH A MINIMUM GRADE OF 1
TYPICAL
TYPICAL
SEE NOTE G13
VALVE SPINDLE EXTENSION IN 150. THE MINIMUM DIAMETER OF THE SEWER IS TO BE DN150
300
300
SEE NOTE G13 600 MAXIMUM AND IS TO BE NO LARGER THAN THE RECEIVING SEWER. THE
125 MINIMUM LOCATION OF THE DRAIN SHOWN ON THIS DRAWING IS INDICATIVE
600 MAXIMUM
SLUICE VALVE. SEE ONLY.
125 MINIMUM RISING MAIN WITH FLANGED
FOR MAINTENANCE HOLES LESS THAN NOTES G4 AND G5 G4. INVERT SCOUR TEE FITTINGS MUST BE USED WHEN FITTING IS
INVERT SCOUR BRANCH
3000 DEEP STEP IRONS ARE TO BE MANUFACTURED. IN POLYETHYLENE RISING MAINS WHERE AN
INSTALLED. FOR DEPTHS GREATER THAN FOR MAINTENANCE HOLES LESS THAN INVERT SCOUR TEE MAY NOT BE MANUFACTURED A FUSION SOCKET
POLYETHYLENE 600 MAXIMUM
3000 A LADDER IS TO BE INSTALLED 3000 DEEP STEP IRONS ARE TO BE BRANCH OR MOULDED BUTT WELDED BRANCH IS TO BE USED. THE
RISING MAIN 125 MINIMUM INSTALLED. FOR DEPTHS GREATER BRANCH IS TO BE PRETESTED TO MEET THE PIPE PRESSURE RATING.
CLEARANCE UNDER FLANGE THAN 3000 A LADDER IS TO BE G5. FOR SCOUR VALVE DIAMETER REFER TO TABLE A. THE VALVE IS TO
FLANGE AND FLANGE TAIL
INSTALLED BE A DOUBLE FLANGED RESILIENT SEATED SLUICE VALVE TO AS
PIPE. LENGTH TO BE
GRADE FLOOR AT 1 IN 40 TO 2638.2 WITH FUSION COATED POLYMETRIC INTERNAL AND
FULL STRENGTH GRADE FLOOR AT 1 IN 40 TO OUTLET PIPE DETAILED ON PROJECT
OUTLET PIPE IF INSTALLED OR IF EXTERNAL SURFACES. ALL SURFACES ARE TO BE SUITABLE FOR
POLYETHYLENE SOCKET IF INSTALLED OR IF NOT INSTALLED TO DRAWINGS. SEE NOTE G7
CLEARANCE
NOT INSTALLED TO LOW POINT SEWERAGE ENVIRONMENTS.
300
300
FUSION WELDED BRANCH LOW POINT ADJACENT TO ACCESS POINT
FLANGE
UNDER
ADJACENT TO ACCESS POINT G6. THE MINIMUM CLASS FOR THE RISING MAIN PIPES AND FITTINGS IS
WRAP FLANGE WITH TO BE PN16.
45° BUTT WELDED ELBOW PETROLATUM TAPE "DENSO" G7. ALL DICL FTTINGS USED INSIDE THE SCOUR MAINTENANCE HOLE
TO MANUFACTURER'S ARE TO BE FUSION BONDED POLYMETRIC COATED.
WRAP PIPE WHERE PIPE PASSES REQUIREMENTS
GRAVITY SEWER CONNECTION TO GRAVITY SEWER CONNECTION TO G8. ALL BOLTS ARE TO BE GRADE 316 STAINLESS STEEL INSTALLED
THROUGH WALL. SEE NOTE G14
SEWERAGE RETICULATION SEWERAGE RETICULATION WITH ANTI GALLING COMPOUND.
200 MAINTENANCE HOLE. SEE NOTE G3 RISING MAIN WITH 200 MAINTENANCE HOLE. SEE NOTE G3 G9. ON POLYETHYLENE RISING MAINS THE BACKING PLATES TO THE
SLUICE VALVE. SEE
FLANGED INVERT FLANGES ARE TO BE GRADE 316 STAINLESS STEEL. THE DIAMETER
NOTES G4 AND G5 25 X 7 "HYDROTITE VALVE TEE MUST BE INSTALLED
VALVE TEE MUST BE INSTALLED SCOUR TEE OF THE SCOUR MAINTENANCE
HORIZONTALLY TO ALLOW VALVE SEAL CJ-0725-3K" HORIZONTALLY TO ALLOW VALVE
MASS CONCRETE SUPPORT UNDER G10. HOLE IS TO BE Ø1500 FOR RISING MAINS OVER DN300 WHICH ARE
VALVE. NOTE: ALLOW CLEARANCE SPINDLE TO BE VERTICAL. SPINDLE TO BE VERTICAL INSTALLED EXTERNAL TO THE MAINTENANCE HOLE.
CLEARANCE
FOR BOLT REMOVAL G11. SCOURS ARE TO BE LOCATED AT THE LOW POINTS IN THE RISING
FLANGE
UNDER
SECTIONAL ELEVATION SECTIONAL ELEVATION MAIN. FOR LOCATIONS SUCH AS CREEK CROSSINGS THE SCOUR
300
NEED NOT BE LOCATED AT THE VERY LOW POINT BUT AT AN
ADJACENT ACCESSIBLE LOCATION. ALL SCOUR MAINTENANCE HOLES
ARE TO BE ACCESSIBLE BY ARTICULATED TANKER TRUCKS. THIS
25 X 7 "HYDROTITE SEAL 200 MAY NECESSITATE THE CONSTRUCTION OF AN ALL WEATHER TRACK.
CJ-0725-3K" IF THE SCOUR MAINTENANCE HOLE IS IN A ROAD LOCATION THEN
CARE MUST BE TAKEN WHEN POSITIONING THE ACCESS COVER.
THE COVER IS NOT TO BE IN THE WHEEL TRACKS OF THE ROAD
ALTERNATE SECTIONAL ELEVATION LANE.
G12. THE COVERS IN NON TRAFFICABLE LOCATIONS ARE TO BE Ø600
SHOWING A DICL INVERT SCOUR TEE CLASS B COVERS AND FRAMES AND IN TRAFFICABLE LOCATIONS
ARE TO BE Ø600 CLASS D. SEE SEQ-SEW-1308 SET.
G13. WHEN THE VALVE SPINDLE EXTENSION EXCEEDS 2000 IN LENGTH
316 STAINLESS STEEL GUIDES ARE TO BE PROVIDED AT THE TOP
AND AT INTERMEDIATE POINTS AS REQUIRED BY THE VALVE
POLYETHYLENE
MANUFACTURER.
RISING MAIN
G14. WHERE THE POLYETHYLENE SCOUR BRANCH PASSES THROUGH THE
CONCRETE WALL THE PIPE IS TO BE WRAPPED WITH 10 THICK X 75
NOMINAL LOCATION OF WIDE CLOSED CELL POLYETHYLENE FOAM STRIP "JOINTFLEX" OR
NOMINAL LOCATION OF GRAVITY RISING MAIN. NOTE: THIS
GRAVITY SEWER CONNECTION QUEENSLAND URBAN UTILITIES APPROVED ALTERNATIVE. NO GAP IS
SEWER CONNECTION TO SECTION PLAN DRAWING
TO SEWERAGE RETICULATION PERMITTED BETWEEN WRAPPINGS AND JOINTS ARE TO BE TAPED IN
SEWERAGE RETICULATION SHOWS A MSCL PIPE
MAINTENANCE HOLE. SEE PLACE.
MAINTENANCE HOLE. SEE NOTE G3
NOTE G3 G15. WHERE THE RISING MAIN RUNS PARALLEL TO ANOTHER RISING MAIN
THE SCOURS ARE TO BE PLACED ADJACENT TO EACH OTHER IN
SEPARATE MAINTENANCE HOLES. THIS IS TO ALLOW SCOURING BY
CROSS PUMPING.
STRUCTURAL
LL LL S1. EACH SCOUR MAINTENANCE HOLE IS TO BE DESIGNED TO SUIT THE
FA FA PROJECT LOCATION AND GROUND CONDITIONS AND IS TO HAVE A
INVERT SCOUR TEE 100 YEAR DESIGN LIFE.
ACCESS OPENING IS TO BE S2. ALL SCOUR MAINTENANCE HOLES ARE TO BE DESIGNED TO CARRY
POLYETHYLENE ACCESS OPENING IS TO BE
DIRECTLY OPPOSITE VALVE TRAFFICABLE LOADS.
BRANCH DIRECTLY OPPOSITE VALVE
RISING MAIN SCOUR VALVE S3. THE CONCRETE IS TO HAVE A MINIMUM EXPOSURE CLASS OF B2 TO
DIAMETER DIAMETER AS3600.
SLUICE VALVE. SEE SLUICE VALVE. SEE
NOTES G4 AND G5 DN300 DN100 NOTES G4 AND G5
>DN300 DN150
TO DN600
>DN600 DN200
WRAP PIPE WHERE PIPE PASSES TO DN900
THROUGH WALL. SEE NOTE G14
SECTIONAL PLAN >DN900 DN250 SECTIONAL PLAN
TO DN1200
SCOUR ARRANGEMENT FOR SCOUR ARRANGEMENT FOR RISING
>DN1200 DN300
POLYETHYLENE RISING MAINS LARGER MAINS LARGER THAN DN300 WITH
THAN OD355 SEE NOTES G1 INVERT SCOUR BRANCHES
TABLE A
SCOUR VALVE
SIZES
MIN
300
RISING MAIN CONCRETE SUPPORT
300X300X150 SUMP
DN100 FLANGE-SPIGOT
TAILPIPE WITH PUDDLE
FLANGE
SECTIONAL ELEVATION
DN300 - DN600 RISING MAIN
DN150-DN100 ECCENTRIC
REDUCER FOR DN375 TO
DN600 RISING MAINS
INVERTED SCOUR TEE WITH FLANGED
BRANCH FLANGED SLUICE VALVE
DN100 BRANCH - DN300 RISING MAIN NOTE:
DN150 BRANCH - DN375 TO DN600 RISING DN100 FLANGED PIPE TO SUIT
MAINS 1. DETAILS SHOWN ARE FOR A BURIED DN100 SEWERAGE
RISING MAIN.
DN100 x 90° 2. FOR LARGER THAN DN100 SEWERAGE RISING MAINS A
BEND LARGER MANHOLE MAY BE REQUIRED.
DN100
3. FOR LARGER THAN DN100 RISING MAINS PROVIDE A DN100
FLANGE-SPIGOT ELONGATED
FLANGED BRANCH HYDRANT TEE.
CONNECTOR GIBAULT JOINT
FLEXIBLE JOINT 4. CARE SHALL BE TAKEN TO ENSURE THAT ALL CONCRETE IS
1545
KEPT CLEAR OF THE FLEXIBLE AND FLANGED JOINTS.
5. FOR PAVEMENT AND KERB & CHANNEL MARKING DETAILS
300 THRUST FLANGE
REFER SEQ-SP STDS.
MIN C/W WATER STOP
6. DIMENSIONS ARE IN MILLIMETRES UNLESS SHOWN
FLANGED
270
OTHERWISE.
METAL ACCESS SLUICE VALVE 7. PROVIDE PIPE STUB FOR ODOUR MANAGEMENT WHERE
COVERS REFER NOTE 9 REQUIRED BY ODOUR IMPACT ASSESSMENT REPORT.
900X600
8. MANHOLES SHALL BE LINED WITH PE LINER; FLOOR,
250 CONNECT TO ODOUR WALLS, ROOF AND OPENING.
MANAGEMENT VENT 9. PROVIDE SLUICE VALVE IN CHAMBER FOR DOUBLE
RISING MAIN BRACKET FOR ISOLATION AS DIRECTED BY SEQ-SP.
EXTENSION SPINDLE 10. METAL ACCESS COVER TO BE 900X600 (GAS TIGHT)
CLASS 'B' FOOTPATHS
STANDARD SEWERAGE CLASS 'D' ROADWAYS
MANHOLE (Ø1200) OFFSET GRV TO ALLOW ACCESS TO MANHOLE.
700 COVER 200
PLAN
REV. No. DATE DESCRIPTION AUTH.
SEWAGE PUMP STATION STANDARD DRAWING CoGC LCC RCC QUU UW
SEQ WATER AUTOMATIC GAS RELEASE VALVES
DRAWING No. VERSION
16 14 14 8 12
MIN
20
18
22
B B
98sq
64
22
A A 12
152
12
24
R6 R3
PLAN
PLAN
98sq
152sq
12
101sq
15 52
98sq
15° 15° 15°
86sq
15° 8 NOTES
79sq MIN
16
3
3
1. ALL WORK AND MATERIALS SHALL BE
22
IN ACCORDANCE WITH CURRENT
16
MIN 3R MIN 3R SEQ-SP SPECIFICATIONS AND
33 6R 29 STANDARDS.
120sq R
R 33 2. UNLESS SPECIFIED OTHERWISE ALL
60
48
15° MATERIALS AND WORK SHALL
44
5°
70
33 R
R Ø200 33 AUSTRALIAN STANDARDS.
3. RECYCLED PLASTIC COLLAR TO BE
16
MIN 3R USED IN CONJUNCTION WITH THIS
70
46sq
6R CASTING.
69sq 4. FOR TYPICAL VALVE CHAMBER
DETAILS REFER DRAWINGS
19
83sq
SEQ-PSS-1005-1 AND
54 Ø216 54
95sq SEQ-WAT-1306-1.
Ø324
DOUBLE FLANGED DICL 45° BEND. VALVE BOX INSTALLATION. SEE SECTION
DIAMETER TO BE THE SAME AS FOR DETAILS.
RISING MAIN DIAMETER PLAN VIEW
DN100 BSP THREADED
FEMALE SOCKET
MAINTENANCE HOLE COVER AND FRAME TO BE
INSTALLED AS SHOWN ON STANDARD DRAWING 4
SEQ-SEW-1301-1 COVER CLASS TO BE DETAILED ON 6
PROJECT DRAWINGS
FOR CONCRETE SLAB USE 115 THICK G TYPE COUPLING FLANGE CONSISTING OF BLANK
MAINTENANCE HOLE TOP SLAB AS SHOWN FLANGE WITH DN100 BSP THREADED FEMALE
ON STANDARD DRAWING SEQ-SEW-1301-3 SOCKET WELDED AT CENTRE. SEE DETAIL.
TOP SLAB TO BE PLACED ON 10 Ø1130 VALVE TO BE INSTALLED WITH VALVE BLANK FLANGE TO SUIT
THICK PAD OF FRESH CEMENT BOX AS SHOWN ON STANDARD DIAMETER OF RISING MAIN AND
Ø600
MORTAR DRAWING SEQ-SPS-1607-1 TO AS4087 FIGURE B7. DRILL
20
DRAWING
MATERIAL: MILD STEEL HOT DIPPED
GALVANISED AFTER FABRICATION
DN100 BRONZE "KAMLOK" NOT TO SCALE
MALE ADAPTOR WITH MALE
BSP THREADED END RISING MAIN. DEPTH, DIAMETER,
300
200
MAIN DIAMETER. LENGTH TO SUIT SAME AS RISING MAIN.
DEPTH OF RISING MAIN AND LENGTH OF
PIG. SEE NOTE G4 DOUBLE FLANGED RESILIENT SEATED
12-N12S-300
SLUICE VALVE. DIAMETER TO BE THE
ALL FILL TO BE SELECTED AND SAME AS RISING MAIN DIAMETER.
PLACED RADIALLY
COMPACTED TO BCC DESIGN
SPECIFICATION S140 EARTHWORKS 100% CONCRETE THRUST
STANDARD COMPACTION BLOCK. SEE NOTE G3 DETAIL OF SUPPORT COLLAR
CONCRETE STRENGTH IS TO BE GRADE N40
DOUBLE FLANGED DICL 45° BEND. DIAMETER SECTIONAL ELEVATION A NOT TO SCALE
TO BE THE SAME AS RISING MAIN DIAMETER -
GENERAL ARRANGEMENT
NOT TO SCALE