GENERAL NOTES

1. ALL EQUIPMENT SHALL BE INSTALLED IN APPROXIMATE LOCATION AS SHOWN ON THE EQUIPMENT SCHEDULE
DRAWINGS.
2. ALL EQUIPMENT SHALL BE MOUNTED ON OR SUPPORTED WITH VIBRATION ISOLATOR OR SPLIT TYPE DX (INVERTER) AIR CONDITIONING UNIT SCHEDULE:
ASSEMBLIES AS SPECIFIED ON THE DRAWINGS. FAN COIL UNIT AIR COOLED CONDENSING UNIT
3. INSTALLATION OF ALL WORKS SHALL BE DONE IN A NEAT AND WORKMANLIKE MANNER,
IMPROPERLY SETWORK OR FINISH AS DETERMINED BY THE ARCHITECT SHALL BE REMOVED POWER
AND REPLACED AT NO EXTRA COST. SYSTEM SUPPLY
COOLING UNIT OPERATING UNIT OPERATING REMARKS
UNIT AREA UNIT POWER
4. ALL MATERIALS TO BE USED SHALL BE BRAND NEW & CLEAN. QTY DESCRIPTION LOCATION CAPACITY DIMENSIONS, WEIGHT QTY. DESCRIPTION LOCATION DIMENSIONS WEIGHT
DESIGNATION SERVED DESIGNATION INPUT
(TR) (HxWxD) (KGS) (HxWxD) (KGS)
5. DEVIATIONS AND REVISIONS FROM PLANS SHALL BE REFERED TO THE ARCHITECT FOR REVIEW (WATTS) V PH HZ
AND APPROVAL.
6. ALL NECCESSARY GOVERNMENT PERMIT SHALL BE SECURED AND PAID FOR BY THE
CONTRACTOR. FCU-1 WALL MOUNTED ACCU-1 OUTDOOR UNIT
1 MEZZ AS SHOWN 0.5 288 x 800 x 206 9.0 1 ROOFDECK 620 230 1 60 420 x 765 x 291 24
0.5 TR MODEL FTWK20AXVL 0.5 TR MODEL RWK20AXVL
7. ALL DIMENSION ARE IN MILLIMETER UNLESS OTHERWISE SPECIFIED.
8. ALL MECHANICAL WORKS SHALL BE . IN ACCORDANCE WITH THE LATEST MECHANICAL
ENGINEER'S CODE ASME, SMACNA AND ASHRAE STANDARD AND ALL ON SITE ACTIVITIES FCU-2 WALL MOUNTED ACCU-2 OUTDOOR UNIT UNIT IS BASED ON DAIKIN BRAND
SHALL BE SUPERVISED BY THE REGISTERED MECHANICAL RNGINEER. 1 GF KITCHEN 1.0 288 x 800 x 206 9.0 1 ROOFDECK 1,040 230 1 60 420 x 765 x 291 25
1.0 TR MODEL FTWK35AXVL 1.0 TR MODEL RWK35AXVL OR APPROVED EQUAL
9. MECHANICAL CONTRACTOR SHALL OBSERVED ALWAYS SAFETY AND ORDERLINESS.
10. MECHANICAL CONTRACTOR SHALL VERIFY SITE PRIOR TO ACTUAL INSTALLATION. ACCU-3
FCU-3 CEILING CASSETTE OUTDOOR UNIT
2 GF DINING 4.0 343 x 950 x 950 30 2 ROOFDECK 5,100 230 3 60 852 x 1030 x 400 87
11. ALL METAL SUPPORTS SHALL BE FULLY WELDED. 4.0 TR MODEL FCRN140AXVL 4.0 TR MODEL RR140AGXTL
12. ALL CONTROL WIRING SHALL BE BY THIS CONTRACTOR.
13. ALL POWER WIRING SHALL BE BY ELECTRICAL CONTRACTOR.
VENTILATING EQUIPMENT
14. ALL AIR-CONDITIONING UNITS SHALL BE PROVIDED WITH FILTER DRIERS.
AIRFLOW TOTAL STATIC
15. REFRIGERANT PIPING SHALL BE TYPE "L" HARD DRAWN SEAMLESS COPPER PIPE. MOTOR DRIVE ELECTRICAL DATA
QUANTITY PRESSURE
16. REFRIGERANT PIPE INSULATION SHALL BE 25mm MIN. THK. CLOSED CELL ELASTOMERIC UNIT
QTY AREA SERVED TYPE REMARKS
RUBBER INSULATION OR 20MM MIN. THK. FOR POLYOLIFIN INSULATION W/ REINFORCED DESIGNATION
CMH CFM Pa. INCH HP W VOLTS PHASE CYCLE
ALUMINUM SHEATHING AND ADHESIVE BACKING, CLASS O FIRE RATING.
17. DRAIN LINE SHALL BE CLOSED CELL ELASTOMERIC RUBBER INSULATION M 15MM. MIN. THK.
CLASS O W/ ADHESIVE BACKING, CLASS 0 FIRE RATING. TEF CEILING CASSETTE CABINET TYPE EXHAUST CENTRIFUGAL FAN, CEILING MOUNTED,
2 TOILET 187 110 125 0.50 0.25 39 230 1 60
18. ALL PLANS WITH COMMENTS MUST ALWAYS BE PRESENT ON SITE PRIOR TO CONSTRUCTION 1 FAN DUCTED, NIAGARA BRAND MODEL NIA150
MONITORING AND AS BASIS OF CONSTRUCTION.
19. ALL ALTERNATIVE MATERIALS/EQUIPMENT TO BE USED BY CONTRACTOR/SUPPLIER OTHER EF SIMILAR TO KDK BRAND MODEL K21CG1 OR
1 KITCHEN MINI SIRROCO FAN 1019 600 100 - - 340 230 1 60
THAN THOSE SPECIFIED BY THE ENGINEER SHALL BE COMMUNICATED FOR CHANGE 2 APPROVED EQUAL
SPECIFICATION APPROVAL.
ELECTRICAL
20. THE CONTRACTOR SHALL ENSURE THAT EVERYTHING HAS BEEN VERIFIED AND COORDINATED FAF SIMILAR TO KDK BRAND MODEL K21CG1 OR CONDUIT (BY EE)
WITH ALL OTHER DICIPLINES AS TO CONSTRUCTIBILITY, FUNCTIONALITY AND MAINTAINABILITY 1 KITCHEN MINI SIRROCO FAN 1019 600 100 - - 340 230 1 60
1 APPROVED EQUAL
OF THE EQUIPMENT AND UTILITIES. IF FOR ANY REASON, CONFLICT ARISE DUE TO WEATHER
CONTRACTORS FAILURE TO FOLLOW STANDARD SPECIFICATIONS AND GOOD ENGINEERING REMOTE TIGHT
PRACTICES OR ITS LACK OF DUE DELIGENCE, ALL WORKS AS NECESSITATED SHALL BE NOTE: BREAKER ELECTRICAL
PERFORMED BY THE CONTRACTOR WITHOUT ADDITIONAL COST VARIATION ORDER TO THE REFRIGERANT SUCTION LINES ENCLOSURE
LEGENDS LOCATED OUTSIDE THE BUILDING
OWNER.
BTUH BRITISH THERMAL UNIT PER HOUR SHALL BE PROVIDED WITH GAGE ALUMINUM METAL
21. IN THE ABSENCE OF ANY OTHER REQUIREMENT NOT FOUND IN PSME CODE. THE MATERIALS, ACCU AIR COOLED CONDENSING UNIT #26 ALUMINUM CLADDING JACKET FOR
CONSTRUCTION AND INSTALLATION OF DUCTWORKS SHALL COMPLY WITH THE REQUIREMENT Pa PASCAL EXPOSED PIPING ELECTRICAL
OF SMACNA OR ASHRAE. FCU FAN COIL UNIT
HP HORSEPOWER PIPE ALUMINUM BAND SUPPLY TO ACCU
22. ALL DUCTWORKS SHALL CONFORM WITH THE PHILIIPPINE MECHANICAL CODE, AMERICAN CFM CUBIC FEET PER MINUTE
STANDARDS FOR TESTING MATERIALS, AMERICAN SOCIETY OF HEATING, REFRIGERATION AND HZ HERTZ CONCRETE SLAB PIPE INSULATION
CMH CUBIC METER PER HOUR WITH VAPOR BARRIER
AIR CONDITIONING ENGINEERS, AIR CONDITIONING AND REFRIGERATION INSTITURE, NATIONAL W WATTS ELECTRICAL CONDUIT
FIRE PROTECTION ASSOCIATION, SHEET METAL AND AIR CONDITIONING CONTRACTORS EF EXHAUST FAN TO POWER SUPPLY
NATIONAL ASSOCIATION, BUILDING OFFICIALS AND CODE ADMINISTRATORS, INTERNATIONAL, QTY. QUANTITY
RH RANGEHOOD ER
MANUFACTURERS STANDARDIZATION SOCIETY OF THE VALVE AND FITTINGS INDUSTRY, INC., OF ORBIT FAN / OSCILLATING FAN NG
AND OTHER LOCAL AND INTERNATIONAL CODES PERTINENT TO THIS SECTION. TSP TOTAL STATIC PRESSURE HA DS REFRIGERANT PIPING
CONTROL WIRES/
RO TO CONDENSING UNIT
CONDUIT TO FCU
23. ALL AIR CONDITIONING, FRESH AIR AND EXHAUST VENTILATION DUCTS SHALL BE OF ASTM 653
HOT DIPPED, ZINC COATED STEEL SHEET CONFORMING TO SMACNA STANDARDS AND LOCK 25mm @ CONDENSATE
FORMED AND SEALED WITH DUCT SEALANT CONFORMING TO ASTM E 84. IL ING CONNECT TO DRAIN
DRAIN PIPE MIN. SIZE
CE LINE (INSULATED)
24. KITCHEN EXHAUST DUCT SHALL BE MADE OF ASTM 653 BLACK STEEL SHEET WITH A MINIMUM
THICKNESS OF 1.2mm (GA. 18) FULL WELDED ON DUCT CONNECTIONS. KED SHALL BE FIELD FABRICATED
DRAIN P-TRAP
INSULATED WITH 50mm THICK ASTM C 800-94 FIBER GLASS BOARD TYPE WITH A DENSITY OF AT 19mm THK RUBBER
LEAST 48 kg per cubic meter WITH ALUMINUM VAPOR BARRIER HAVING A MAXIMUM WATER INSULATION WRAPPED IT T E)
UN SET REFRIGERANT
VAPOR PERMEANCE OF 0.20 perm INACCORDANCE WITH ASTM E 96 Procedure A PROPERLY W/ PE TAPE
C OILCAS PIPES (SL/LL) 2"x2"x1/4" ANGLE BAR
FASTENED ACCORDING TO ASTM C 916. PROVIDE SERVICE HANDHOLE FOR CLEANING. N G
FA ILIN STEEL PLATFORM
25. PROVIDE CONTINUOUS CORNER BENDS ON ALL DUCTS MADE OF 0.6mm ASTM 653 HOT DIPPED, (CE BY OTHERS
ZINC COATED STEEL SHEET, PROPERLY FASTENED WITH PLASTIC STRAPS EVERY 300mm. RUBBER PAD
TAPPED TO THE WALL MOUNTED COMBINATION ACCU - AIR COOLED
26. ALL HVAC WORKS SHALL BE SUPERVISED BY A REGISTERED MECHANICAL ENGINEER OF GOOD NEAREST THERMOSTAT & FAN SWITCH (TYPICAL) CONDENSING UNIT
STANDING. DRAIN PROVISION VIBRATION ISOLATOR
27. THERMOSTATIC, TEMPERATURE - OPERATED CONTROL SENSING ELEMENTS SHALL BE
INSTALLED IN A LOCATION NEAR THE UNIT RETURN OR AS PER MANUFACTURER'S
A FCU WALL MOUNTED DETAIL A FCU CEILNG CASSETTE DETAIL C ACCU INSTALLATION DETAIL
INSTALLATION MANUAL.
M-1 ME-04 M-1

GENERAL NOTES
PET COFFEE SHOP: KTYM CONSULTING
LEGENDS
AR. NAME PAW-PAL CAFE INC.
EQUIPMENT SCHEDULE
MISCELLANEOUS DETAILS
ME-1
R109-R110 & R111-R112, GF, VENICE GRAND CANAL MALL