RCSPC Software

Instruction Manual

Nanjing Nari-Relays Electric Co., Ltd.


RCSPC Software

Copyright
Version: 1.02 NANJING NARI-RELAYS ELECTRIC CO., LTD.
P/N: EN_GJRJ0201.0086.0001 69 Suyuan Avenue, Jiangning, Nanjing 211102,China
Copyright © NR 2009. All rights reserved Tel: 86-25-87178185, Fax: 86-25-87178208
Website: www.nari-relays.com
We reserve all rights to this document and to the information Email: international@nari-relays.com
contained herein. Improper use in particular reproduction and
dissemination to third parties is strictly forbidden except where
expressly authorized.

The information in this manual is carefully checked periodically,


and necessary corrections will be included in future editions. If
nevertheless any errors are detected, suggestions for correction or
improvement are greatly appreciated.

We reserve the rights to make technical improvements without


notice.

NANJING NARI-RELAYS ELECTRIC CO., LTD. i


RCSPC Sfotware

Table of Content
Table of Content ......................................................................................................................... ii
Chapter 1 Introduction............................................................................................................... 1

1.1 Function ......................................................................................................................... 1

1.2 Run Software ................................................................................................................. 1

Chapter 2 Preparation................................................................................................................ 3

2.1 Make Communication Cable........................................................................................ 3

2.2 Parameter Configuration.............................................................................................. 5

2.2.1 4U RCS-900 Serial............................................................................................... 5

2.2.2 8U~12U RCS-900 serial ...................................................................................... 6

2.2.3 PCS-9690 Serial .................................................................................................. 8

Chapter 3 Usage Instruction ....................................................................................................11

3.1 Introduction of Menu Bar ............................................................................................11

3.2 Introduction of Tool Bar ............................................................................................. 12

3.3 View and Modify Settings........................................................................................... 15

3.4 View Real-time Sampled Value .................................................................................. 16

3.5 View Reports................................................................................................................ 16

3.6 Test Function............................................................................................................... 18

3.6.1 RCS-978 Serial .................................................................................................. 18

3.6.2 RCS-985 Serial .................................................................................................. 20

3.6.3 PCS-9690 Serial ................................................................................................ 22

3.7 Signal Reset................................................................................................................. 22

3.8 Clock Synchronization ............................................................................................... 22

Chapter 4 Manual Version History.......................................................................................... 23

ii NANJING NARI-RELAYS ELECTRIC CO., LTD.


Chapter 1 Introduction

Chapter 1 Introduction

NOTE:This manual gives detailed operation instruction of RCSPC (also called DBG2000)

software for user. The equipment type displayed on the interface is just an example to
show the operating steps to communicate with the equipment using RCSPC software.
The actual protection equipment for user is application-specific.

1.1 Function

RCSPC software is developed for users to test and maintain the protection equipment on site,
which is kind of local HMI (Human Machine Interface) as RCS-900 serial and PCS-9690 serial
protective equipments. User can view real-time sampled values, read and modify settings, view all
kinds of report, and do tests through the RCSPC software compatible with MW (Microsoft
Windows) 95, WM98, WM 2000, WM ME and WM XP operation systems on a computer.

Besides this kind of local communication, user still can realize the local human-machine
communication with the relay through the keypad and LCD on the frontpanel of the equipment, or
realize the remote human-machine communication on a PC with the SAS (Substation Automatic
System) software via a RS-485 port.

1.2 Run Software

Run the software RCSPC with the double click on the executable file (RCSPC.exe).

If the connection succeeds between the equipment with computer via RS-232 port, the computer
screen will display as following figure. If user fails to connect the equipment to a local computer,
please modify the communication parameters of equipment and RCSPC software respectively to
make them matched.

NANJING NARI-RELAYS ELECTRIC CO., LTD. 1


Chapter 1 Introduction

Figure 1.2-1 Display of connection with equipment using RCSPC

NOTE:There are four main functions for RCSPC software, and they are sampled value

display, settings reading and modification, report and test function. All these functions
can be executed with the four corresponding configuration files xxx_status.dat,
xxx_set.dat, xxx_rpt.dat and xxx_tst.dat equipped respectively (xxx represents the
software name of the equipment).

2 NANJING NARI-RELAYS ELECTRIC CO., LTD.


Chapter 2 Preparation

Chapter 2 Preparation

2.1 Make Communication Cable

(1) RCS-900 serial 4U height equipments

On the frontpanel of this serial equipments, there are a 9-pin RS-232 connector for communication
with PC and a 15-pin connector for analog quantity inputs by HELP-90A during commissioning,
which consist of RCS-900 serial line protections and auxiliary protections, RCS-917 reactor
protection, and RCS-974 transformer auxiliary protection.

(2) RCS-900 serial 8U~12U height equipments

On the frontpanel of this serial equipments, there is a 9-pin RS-232 connector for communication
with PC during commissioning, which consist of RCS-978 transformer protection, RCS-915 busbar
protection and RCS-985 generator protection and RCS-985 transformer protection.

(3) PCS-9690 serial equipments

On the front panel of this serial equipment, there is 9-pin RS-232 connector for communication
with PC during commissioning, which consist of PCS-9691A, PCS-9691B, PCS-9691C,
PCS-9691D, PCS-9692A and PCS-9692B relays).

User needs to make a communication cable to connect the equipment with a computer through
the RS-232 port on the front panel. One end of the cable is DB9 female serial connector, and the
other end of the cable is DB9 male serial connector. Each serial connector generally has two
screws measuring 0.3mm allow the serial connection to be securely connected to the equipment.
Please refer to Figure 2.1-1, Figure 2.1-2 and Figure 2.1-3 for correct connections of three kinds of
equipments mentioned above respectively.

NANJING NARI-RELAYS ELECTRIC CO., LTD. 3


Chapter 2 Preparation

MEC H7 HEA LTHY

RC
MEC H8 AL AR M

RCS-974

MEC H9 TR IP1

RELAY
S
TRANSFORMER AUXILIARY
TRANSFORMER AUXILIARY RELAY ME CH 10

ME CH 11
TR IP2

ME CH 1

ME CH 12 ME CH 2

ME CH 13 ME CH 3

ME CH 14 ME CH 4

NANJING NARI-RELAYS ELECTRIC CO., LTD ME CH 15 ME CH 5

ME CH 16 ME CH 6

TARGET RE SET

2
3
5

2
3
5

Figure 2.1-1 Connection diagram of 4U equipments


GRP
ESC

Figure 2.1-2 Connection diagram of 8U~12U equipments

4 NANJING NARI-RELAYS ELECTRIC CO., LTD.


Chapter 2 Preparation

Figure 2.1-3 Connection diagram of RCS-9690 serial equipments

2.2 Parameter Configuration

2.2.1 4U RCS-900 Serial

1) Equipment configuration

Set the setting [Debug_Baud]=9600 in the menu “EQUIP SETUP” ( or “EQUIP SETTINGS”)
through keypad and LCD on the frontpanel.

2) Software configuration

After finishing connecting a computer to the equipment, run the software with a double click on an
executable file (the corresponding configuration files needed).

There are 3 bars shown on the upper of display of RCSPC software, which are “Title bar” “Menu
bar” and “Tool bar” from top to bottom shown as Figure 2.2-1.

Figure 2.2-1 Title bar, menu bar and tool bar of RCSPC

NANJING NARI-RELAYS ELECTRIC CO., LTD. 5


Chapter 2 Preparation

Click the icon of tool bar “Parameter” , dialog box of parameter configuration for
communication is displayed. Only the parameter “COM port” shall be configured as same as the
port of computer which is actually connected with the equipment, all other parameters shall be
configured as same as displayed in Figure 2.2-2.

Figure 2.2-2 Parameter configuration for 4U RCS-900 serial equipments

Baud rate: 9600

Data bit: 8

Stop bit: 1

Parity bit: No parity

Download baud rate: 57600

Device type address: FDFFD0

CPU No: 1

Mainboard frequency: 20

Mainboard chip type: INTEL80296+ADSP2181

2.2.2 8U~12U RCS-900 serial

1) Equipment configuration

6 NANJING NARI-RELAYS ELECTRIC CO., LTD.


Chapter 2 Preparation

The baud rate of 8U~12U equipments for debugging is fixed at 9600bps in program.。

2) Software configuration

After finishing connecting a computer to the equipment, run the software with a double click on an
executable file (the corresponding configuration files needed).

There are 3 bars shown on the upper SLD (Single Line Diagram) display of RCSPC software,
which are “Title bar” “Menu bar” and “Tool bar” from top to bottom shown as Figure 2.2-1.

Click the icon of tool bar “Parameter” , dialog box of parameter configuration for
communication is displayed. Only the parameter “COM port” shall be configured as same as the
port of computer which is actually connected with the equipment, all other parameters shall be
configured as same as displayed in Figure 2.2-3.

Figure 2.2-3 Parameter configuration for 8U~12U RCS-900 serial equipments

Baud rate: 9600

Data bit: 8

Stop bit: 1

Parity bit: No parity

Download baud rate: 57600

Device type address: 7FFE0

NANJING NARI-RELAYS ELECTRIC CO., LTD. 7


Chapter 2 Preparation

CPU No: 2

Mainboard frequency: 20

Mainboard chip type: MC68332+ADSP2181

2.2.3 PCS-9690 Serial

1) Equipment configuration

The baud rate of 8U~12U equipments for debugging is fixed at 19200bps in program.。

2) Software configuration

After finishing connecting a computer to the equipment, run the software with a double click on an
executable file (the corresponding configuration files needed).

There are 3 bars shown on the upper SLD (single line diagram) display of RCSPC software, which
are “Title bar” “Menu bar” and “Tool bar” from top to bottom shown as Figure 2.2-1.

Click the icon of tool bar “Parameter” , dialog box of parameter configuration for
communication is displayed. Only the parameter “COM port” shall be configured as same as the
port of computer which is actually connected with the equipment, all other parameters shall be
configured as same as displayed in Figure 2.2-4.

Figure 2.2-4 Parameter configuration for PCS-9600 serial equipments

8 NANJING NARI-RELAYS ELECTRIC CO., LTD.


Chapter 2 Preparation

Baud rate: 19200

Data bit: 8

Stop bit: 1

Parity bit: No parity

Download baud rate: 57600

Device type address: 20000

CPU No: 1

Mainboard frequency: 20

Mainboard chip type: MC68332+ADSP2181

NANJING NARI-RELAYS ELECTRIC CO., LTD. 9


Chapter 2 Preparation

10 NANJING NARI-RELAYS ELECTRIC CO., LTD.


Chapter 3 Usage Instruction

Chapter 3 Usage Instruction

3.1 Introduction of Menu Bar

There are five menus in the menu bar: “File”, “Execute”, “View”, “Set” and “Help”. Click button
of each menu, and items will be displayed in drop-down list (see Figure 3.1-1). The gray items are
not accessible in the RCSPC software of this version.

Figure 3.1-1 Submenu of menu bar

1) File

There is only one item in this drop-down list.

- “Exit”: Exit the RCSPC software.

2) Execute

There are following items in this drop-down list.

- “Setting(E)” : Read and modify settings of the equipment, and please refer to section 3.3 for
details.

- “Load(L)”, “disassembly(U)”, “Step(S)”, “Go(G)” and ” Download(D)” :These functions are


not equipped in the RCSPC software of this version.

- “Trip_Test(T)” : Test the equipment output relays and communication, and please refer to
section 3.6 for details.

- “Identify device(I)”: Reconnect the equipment to a computer through the software.

3) View

There are five items in drop-down list.

- “Toolbar(T)”: Display or hide the tool bar. When the tool bar is displayed, a symbol “√” is
displayed before “Toolbar (T)”. If this item is clicked then, the tool bar will be hidden and the
symbol “√” will disappear.

- “Status(S)” : Display or hide status bar on the bottom of RCSPC softare SLD display.

NANJING NARI-RELAYS ELECTRIC CO., LTD. 11


Chapter 3 Usage Instruction

- “Register(R)” : This function is not equipped in the RCSPC software of this version.

- “Report(L)” : View reports, and please refer to section 3.5 for details.

- “Status(Z)” : View real-time sampled values, and please refer to section 3.4 for details

- “Message(M)” : show data flow between RCSPC software and the protection equipment will
be displayed. This function is not designed for the users but for R&D members and
commissioning engineers of the equipment manufacture.

4) Set

There are five items in drop-down lit

- “Switch_CPU_MON(P)” : Switch to MON module from CPU module or switch to CPU


module from MON module. This function is only used during download program to the
equipment, which is not designed for users but for R&D members and commissioning
engineers of the equipment manufacture.

- “Parameter(C)” : The function is same as the icon of tool bar “Parameter” , see Figure
B.3.

- “Back_Color(B)” : Select preferred color for background color displayed of the frame of the
software SLD.

- “Font_Color(F)” : Select preferred color of font displayed on the frame of the software SLD.

- “Font(O)”: Select preferred font, style and size of character displayed on the frame of the
software SLD.

5) Help

There are three items in drop-down list.

- “Help(H)” : display the commands used for the program, which are not designed for user but
for R&D members and commissioning engineers of the equipment manufacture, and no
further information about them is presented here.

- “Version(N)” : Display the version of the software.

- “About RCSPC” : Display the copyright declaration of the software.

3.2 Introduction of Tool Bar

Figure 3.2-1 Description of tool bar

12 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 3 Usage Instruction

There are 23 icons in the tool bar, in which 16 icons are enabled. They are depicted in sequence
from left to right as follows:

6) Parameter

Function of this icon is the same as that of item “Parameter(C)” of menu “Set “of the menu bar.
Click this icon, dialog box of communication parameters will be displayed, see Figure 2.2-2.

7) Data parameter

Click this icon, other parameters will be displayed. These parameters are set for extracting fault
waveform from the equipment through the software, which is not designed for user but for R&D
members and commissioning engineers of the equipment manufacture.

8) Device type

Click this icon, a small dialog box “Input device type” is displayed. The type of the protection
equipment shall be entered, which shall be consistent with the configuration file name. This
function can be used for the user to make off-line setting configuration.

9) Device Setting

Function of this icon is the same as item “Setting(E)” of menu “Execute” of menu bar. Please refer
to section 3.3 for details.

10) Show device status

Function of this icon is the same as item “Status(Z) “of menu “View” of menu bar. Please refer to
section 3.4 for details.

11) Show device report

Function of this icon is the same as item “Report(L)” of menu “View” of menu bar. Please refer to
section 3.5 for details.

12) Trip test

Function of this icon is the same as item “Trip_Test(T)” of menu “Execute”. Please refer to section
3.6 for details.

13) Switch to command

When several dialog boxes are displayed, and the operator wants to enter Command mode
without closing dialog boxes, this icon can be used to switch to command mode and hide all dialog

NANJING NARI-RELAYS ELECTRIC CO., LTD. 13


Chapter 3 Usage Instruction

boxes. However, it is not needed for the user on site generally.

14) Download program

This icon is gray and this function is not equipped in the RCSPC software of this version.

15) CPU<–>MON

Function of this icon is the same as item “Switch_CPU_MON(P)” of menu “Set” of menu bar.
Click this icon, data displayed will be changed between those acquired by module CPU and
module MON one after another.

16) Set font

Function of this icon is the same as item “Font(O)” of menu “Set” of menu bar.

17) Set font color

Function of this icon is the same as item “Font_Color(F)” of menu “Set” of menu bar.

18) Set background color

Function of this icon is the same as item “Back_Color(B)” of menu “Set” of menu bar.

Six icons on right hand of are all gray. These functions are not
equipped in the RCSPC software of this version.

19) Signal Rest

Please refer to section 3.7 for details.

20) Synchronize time

Please refer to section 3.8 for details.

21) Device info

Function of this icon is to display the software version information of equipment.

22) Help

Function of this icon is the same as item “Help(H)” of menu “Help” of menu bar.

14 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 3 Usage Instruction

3.3 View and Modify Settings

After connecting with equipment successfully, click the icon of tool bar “Device setting” , the
following figure will be displayed.

Figure 3.3-1 the diagram of showing device settings

User can view and modify the setting values. Besides, many other functions such as save setting
values, printing and etc. are also provided for user by clicking the buttons on the bottom of the
dialog.

1) “Print”: print the current settings

2) “Default”: reset all setting groups to default settings.

3) “Reading”: reading the active group setting from a relay.

4) “Upload”: reading settings of the active group to display on the dialog.

5) “Download”:download current settings displayed on the dialog to the equipment.

6) “Save”: save the current settings displayed on the dialog to a setting file.

7) “Close”: close the dialog.

NANJING NARI-RELAYS ELECTRIC CO., LTD. 15


Chapter 3 Usage Instruction

3.4 View Real-time Sampled Value

After connecting with equipment successfully, click the icon of tool bar “Show device status” ,
the following figure will be displayed.

Figure 3.4-1 the diagram of showing device status

User can observe real time sampled data and binary inputs status, and save them as a file.

3.5 View Reports

After connecting with equipment successfully, click the icon of tool bar “Show device report” ,

the following figure will be displayed. Three kinds of reports including tripping report, alarm report
and binary input changing report can be viewed by clicking icons on the bottom left corner to
switch report display. Tripping report is always showed first, and only the latest three pieces of
tripping reports are shown in order to save reading time. User can click the icon “REFRESH”
on the right bottom corner to read all tripping reports.

16 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 3 Usage Instruction

Figure 3.5-1 the diagram of showing device report

There are three buttons on the bottom left corner used to display different reports.

1) “TRIP”: Read and display all tripping reports of the equipment.

2) “FAIL”: Read and display all alarm reports of the equipment.

3) “SW CHG”: Read and display all binary input changing reports of the equipment.

The functions of five buttons on the bottom right corner are listed below

4) “RECORD”: Select one tripping report, and click this icon to read the waveform from the relay
and save as a waveform file. Waveform analyzing software will run automatically if the
waveform analyzing software and RCSPC software should be in the same directory on
computer.

NOTE: 8U~12U RCS-900 serial equipments and PCS-9690 serial equipments can save 8

pieces of the latest fault waveforms, but 4U RCS-900 serial equipments can save 24
pieces. Please refer to the instruction manual of equipment for detailed information.

5) “REFRESH”: Read the newest report data from the relay and refresh the report display on the
software.

6) “SAVE”: Save current reports displayed on the dialog as a file.

7) “PRINT”: Print current reports displayed on the dialog as a file.

NANJING NARI-RELAYS ELECTRIC CO., LTD. 17


Chapter 3 Usage Instruction

8) “CLOSE”: close the dialog.

3.6 Test Function

RCS-978 serial transformer protections, RC-985 serial generator protection, RCS-985T(TM/TW)


serial transformer protections, and PCS-9690 serial management relays are equipped with this
function, and other RCS-900 serial protection equipments are not equipped.

WARNIING:When a equipment is in test mode, the trip circuit should remain

isolated to prevent accidental operation of the associated circuit breaker!

3.6.1 RCS-978 Serial

Before the test, the logic setting [En_Trp_TestMode] in the item “System-parameter” should be
set as “1” (i.e. “Enable”) to enable test function and the setting can be modified only through
RCSPC software shown in the following figure.

Figure 3.6-1 Display of settings configuration of RCS-978

This test function is composed of binary output test and SAS (substation automatic system)

communication test. Click the “Test mode” icon on the tool bar to enter test mode with a
dialog shown as the Figure 3.6-2.

1) Binary output test

Binary output test is used to check whether tripping output relays can operate correctly without
18 NANJING NARI-RELAYS ELECTRIC CO., LTD
Chapter 3 Usage Instruction

injecting analog currents and voltages.

Set the fist bit of the tripping matrix setting [TrpLog_Diff] as “1”, and then user can make the
differential protection operates by click the icon on the dialog. User can test all tripping output
relays by setting all bits of the setting as “1”,

2) SAS communication test

SAS communication test is used to check whether the SAS host computer can correctly receive
the message from the equipment without injecting analog currents and voltages.

3.6.1.1 Binary output test

Click the item to enter to tripping output test. Click the icon to make
differential protection operate, and the corresponding tripping output relays pick up which are
decided by the logic setting [TrpLog_Diff] with the icon changing to state from
state . User can check whether the corresponding contacts operate through a tool such
as multimeter.

Click the icon to make operated relays drop off, and then the icon state is also back to
original state .

Figure 3.6-2 Display of binary output test of RCS-978

3.6.1.2 Communication Test

The logic settings [En_Trp_TestMode] and [En_Comm_TestMode] in submen


“System-parameter” must be both set as “1” (i.e. “Enable”) to enable this function only through
RCSPC software.

NANJING NARI-RELAYS ELECTRIC CO., LTD. 19


Chapter 3 Usage Instruction

Click the item to go to the communication test display as the following figure shows.

Click the icon of each test item and each event will be recorded in the equipment,
which is also sent to SAS host computer. User can check whether the message sent to SAS is
same to the corresponding record in equipment.

Figure 3.6-3 Display of communication test of RCS-978

3.6.2 RCS-985 Serial

Before the test, the logic setting [En_TestMode] in submenu “System Setting(*)” ->”Protection
Cofig” should be set as “1” (i.e. “Enable”), which can be modified only through RCSPC software
shown in the following figure, to enable the test function. Besides, the corresponding enabling
logic setting of a protection in the same submenu should be set as “1” to do the test.

20 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 3 Usage Instruction

Figure 3.6-4 Display of settings configuration of RCS-985

Click the “Test mode” icon on the tool bar to enter test mode with a dialog shown as the
Figure 3.6-2. The test items are classified according to different protected objects.

Figure 3.6-5 Display of test mode of RCS-985

NANJING NARI-RELAYS ELECTRIC CO., LTD. 21


Chapter 3 Usage Instruction

This test function is used to check whether tripping output relays and signal relays (including
annunciation signal, remote signal and FDR signal) can operate correctly without injecting analog
currents and voltages. User can test all tripping output relays by setting all bits of some tripping
matrix logic setting, such as [TrpLog_Diff], to make all tripping output relays operate for testing.
Besides, contacts of CT/VT circuit alarm and other abnormalities can also operate in this test
mode.

Select the test item to click its icon and the corresponding output relays will pick up to
send all kinds of signals with the icon changing to state from state . User
can check whether the corresponding contacts operate through a tool, such as multimeter.

Click the icon to make operated relays drop off, and then the icon state is also back to
original state .

3.6.3 PCS-9690 Serial

Before the test, the logic setting [En_TestMode] in submenu “SYS SETTINGS”->”PROT CONFIG”
should be set as “1”, which can be modified only through RCSPC software, to enable the test
function. Besides, the corresponding enabling logic setting of a protection in submenu “SYS
SETTINGS”->”PROT CONFIG” should be set as “1” to do the test.

For detailed operation instruction, please refer to section 3.6.2.

3.7 Signal Reset

After connecting with equipment successfully, click the icon of tool bar “Signal reset” , all
magnetic latched output relays and signal relays will be reset.

3.8 Clock Synchronization

After connecting with equipment successfully, click the icon of tool bar “Time” , a clock
synchronizing command is issued to the relay to synchronize the clock time of the relay with the
time of the computer DBG9000 installed.

NOTE:8U~12U RCS-900 serial equipments have no clock synchronization function.

22 NANJING NARI-RELAYS ELECTRIC CO., LTD


Chapter 4 Manual Version History

Chapter 4 Manual Version History


The version histories of the software and the manual for RCSPC software are listed below.

Software Manual
Source Documentation
Version Version

RCSPC V3.20 V1.02 RCSPC_Software_Standard_V1.02.doc

Modifying description of each manual version is shown below.

Manual Page
Section Description of change Note
Version No.

V1.02 Original Issue to standard version

NANJING NARI-RELAYS ELECTRIC CO., LTD. 23