Professional Documents
Culture Documents
Important Notes
Thank you for using the product of CET Electric Technology Inc. In
2) Please read the User Manual carefully, and carry out setting, testing
3) Never insert or pull out each plug-in unit of PMC-851D, or touch the
and equipment.
I
The copyright of this Manual is reserved by CET Electric Technology Inc. No copy, distribution or use of this
Manual and its content is allowed without written permission.
We have checked relevant contents of this manual. As it is impossible to avoid all errors, we cannot
guarantee the complete consistency of the manual with actual device. The data in the manual will be reviewed
periodically and necessary amendments will be made in the documents of new version. You are welcomed to
bring forward suggestions on amendments. The change of later versions won’t be notified.
II
Table of Contents
1. Introduction ............................................................................................................................................................... 1
II
4.6.5. Power Quality ................................................................................................................................................ 82
4.6.6. Maintenance .................................................................................................................................................. 82
4.6.7. Factory ........................................................................................................................................................... 83
4.6.8. Settings List .................................................................................................................................................... 83
III
PMC-851D User Manual
1. Introduction
1.1. Overview
PMC-851D is a bus-tie Breaker protection and automatic transfer switch relay developed meticulously by
CET and applicable to middle and high voltage level power system. PMC-851D adopts high-end configuration
in hardware design, and special protection algorithm and high-reliability real-time multi-task operating
system in software configuration, and supports Ethernet-based IEC-61850 international standard protocol.
1.2. Features
Adopting high-performance 32-bit dual-core processor with dominant frequency of 300MHz, 64-bit
high-speed floating-point DSP, 16-bit high-performance synchronous sampling A/D, big-capacity
high-speed non-volatile memory chip with infinite number of reading and writing times, big liquid
crystal display, graphical interface;
Two Ethernet communication interfaces (optional 10/100 base-T, 100 base-FX): Supporting ring
network, and failover switching function;
Supporting IEC61850 protocol, MODBUS-TCP/RTU protocol and IEC 60870-5-103 protocol;
PMC-851D is equipped with complete protection functions, has reliable performance, and operates
quickly;
Online switching of eight groups of protection settings, and support copy one group of protection
setting to each other;
Flexible configuration of protection outputs;
Flexible design of operation circuit which is applicable to various kinds of electrical facilities;
2nd~63th harmonic analysis of three-phase currents and three-phase voltages;
Perfect remote control and central signal output functions: It’s available to control the switch
through communication port, device panel and binary input, etc.;
Big capacity, and 512 entries of event logs supporting classified query (resolution 1ms);
Long-time WFR records (available to maintain for more than 10 years in case of power failure), and
unique fault logs graph;
Instantaneous high-speed waveform capturing function;
Supporting IRIG-B timing, GPS hard pulse timing, and SNTP network timing;
PMC-851D software and hardware have perfect self-check function;
It supports online software upgrading;
Fully-closed case is adopted to separate strong and weak current completely. Corresponding
anti-interference measure is adopted for software to realize top grade of various criteria of
electromagnetic compatibility;
Meeting the most adverse application environment: Meeting the requirement of wide operating
1
PMC-851D User Manual
temperature (-25℃~+70℃);
PMC-851D may be installed in a scattered way locally, or be installed by screen combination
collectively.
1.3. Functions
Table 1-1 Functions
2
PMC-851D User Manual
3
PMC-851D User Manual
4
PMC-851D User Manual
2. Technical specifications
2.1. Environment Parameters
1) Operating temperature: -25℃ ~+70℃
2) Storage temperature: -40℃~+85℃
3) Atmospheric pressure: 70 kPa~110 kPa
4) Relative humidity: 5%~95% (Non-condensing)
5) Above sea level: <3000m
2.3. Accuracy
1) Accurate working scope
Measurement current: 0.01In~1.2In
Protective current: 0.04In~20In
Frequency: 45.00~65.00Hz
Voltage: 0.4~120V
2) Accuracy of protection settings
Current setting: ≤±2.5% or ±0.01In
Voltage setting: ≤±2.5% or 1V
Frequency setting: ≤±0.02Hz
Direction angle: ≤±3°
3) Time setting accuracy
Natural action time: ≤40ms (impose 1.5X action setting excitation for over-protection, and 0.7X
action setting excitation for under-protection)
Definite time-lag action time: ≤±40ms or 1% (impose 1.5X action setting excitation for
over-protection, and 0.7X action setting excitation for under-protection)
5
PMC-851D User Manual
Inverse time limit action time: ≤±5% (1 – I/(Iset*80)) or ±40ms, I is the exciting current imposed,
while Iset is the set current value.
4) Measurement accuracy
Table 2-1 Measurement Accuracy
Parameters Accuracy Maximum resolution
Primary voltage 0.2% 0.001kV
Primary current 0.2% 0.001A
Secondary voltage 0.5% 0.01V
Secondary current 0.5% 0.001A
Active power 0.5% 0.001kW
Reactive power 0.5% 0.001kvar
Power factor 1.0% 0.001
Frequency 0.02Hz 0.001Hz
Harmonic analyzing Level B (2nd~31th) 0.01%
Bi-directional Real Energy Level 0.5S 1kWh
Bi-directional Reactive Energy Level 2 1kvarh
6
PMC-851D User Manual
2.9. Torque
Power supply terminal:0.8N.m
Voltage & Current Inputs terminal:1.5N.m
Other terminal: 0.5N.m
7
PMC-851D User Manual
3. Function description
3.1. Protection function
The protection function of PMC-851D includes bus-tie breaker protection and automatic transfer (ATS)
switch relay. ATS includes ATS_B1, ATS_B2, ATS_L1, ATS_L2, all of them can select ART (automatic retransfer)
function.
“System->Main Diagram” can be collocated to “Mode 1”, “Mode 2”, or “Mode 3”, as shown in following
figure:
QF
Bus Ⅰ Bus Ⅱ
Mode 1
Line 1# Line 2#
QF1 QF2
QF3
Bus Ⅰ Bus Ⅱ
Mode 2
Line 1# Line 2#
QF1 QF2
QF3
Bus Ⅰ Bus Ⅱ
Mode 3
If “System->Main Diagram” is collocated to “Mode 1”, PMC-851D only adopts bus-tie breaker protection,
without ATS.
If “System->Main Diagram” is collocated to “Mode 2”, PMC-851D adopts bus-tie breaker protection, ATS
and ART.
If “System->Main Diagram” is collocated to “Mode 3”, PMC-851D adopts bus-tie breaker protection and
ART.
The transfer diagram of ATS and ART is shown in following figure:
8
PMC-851D User Manual
Line 1# Line 2#
Status 1
QF1 Cloesd QF2 Cloesd
QF3 Open
Bus Ⅰ Bus Ⅱ
AT
1
_B
S _B
S
AT
2
B1
AR
T_
T_
AR
B2
Line 1# Line 2# Line 1# Line 2#
ATS_L2 or ART_L1
In status 1, under the condition of ATS_B1 logic, if Line 2# loses its power, it will trip QF2 first, and then
close QF3, and then the running status changes from status 1 to status 2. In status 2, after the voltage recovery
of Line 2#, if “ATS_B1-> ART_B1” is not collocated to “Off”, it will step in the logic of automatic recovery transfer.
If “ATS_B1-> ART_B1” is collocated to “Mode 1” and ART_B1 gets ready, PMC-851D will close QF2 when the
conditions of synchronization check are met, and then trip QF3; if “ATS_B1->ART_B1” is collocated to “Mode 2”,
PMC-851D will trip QF3 first, and then close QF2, and then the running status recovers from status 2 to status
1.
In status 1, under the condition of ATS_B2 logic, if Line 1# loses its power, it will trip QF1 first, and then
close QF3, and then the running status changes from status 1 to status 3. In status 3, after the voltage recovery
of Line 1#, if “ATS_B2-> ART_B2” is not collocated to “Off”, it will step in the logic of automatic recovery transfer.
If “ATS_B2-> ART_B2” is collocated to “Mode 1” and ART_B2 gets ready, PMC-851D will close QF1 when the
conditions of synchronization check are met, and then trip QF3; if “ATS_B2->ART_B2” is collocated to “Mode 2”,
PMC-851D will trip QF3 first, and then close QF1, and then the running status recovers from status 3 to status
1.
In status 3, under the condition of ATS_L1 logic, if Line 2# loses its power, it will trip QF2 first, and then
close QF1, and then the running status changes from status 3 to status 2. In status 2, after the voltage recovery
of Line 2#, if “ATS_L1-> ART_L1” is not collocated to “Off”, it will step in the logic of automatic recovery transfer.
If “ATS_L1-> ART_L1” is collocated to “Mode 1” and ART_L1 gets ready, PMC-851D will close QF2 when the
conditions of synchronization check are met, and then trip QF1; if “ATS_L1->ART_L1” is collocated to “Mode 2”,
PMC-851D will trip QF1 first, and then close QF2, and then the running status recovers from status 2 to status
3.
9
PMC-851D User Manual
In status 2, under the condition of ATS_L2 logic, if Line 1# loses its power, it will trip QF1 first, and then
close QF2, and then the running status changes from status 2 to status 3. In status 3, after the voltage recovery
of Line 1#, if “ATS_L2-> ART_L2” is not collocated to “Off”, it will step in the logic of automatic recovery transfer.
If “ATS_L2-> ART_L2” is collocated to “Mode 1” and ART_L2 gets ready, PMC-851D will close QF1 when the
conditions of synchronization check are met, and then trip QF2; if “ATS_L2->ART_L2” is collocated to “Mode 2”,
PMC-851D will trip QF2 first, and then close QF1, and then the running status recovers from status 3 to status
2.
3.1.1. Auxiliary Element
1) Compound voltage element (27E/59Neg.E)
Because PMC-851D has two busbars, compound voltage element is judged by voltages of two busbars. If
neither of two busbars is LOP(Loss-of-Potential), 27E/59Neg.E operates only when voltages of two busbars
meet the operating conditions; if one of two busbars is LOP, 27E/59Neg.E operates when the busbar voltage
which is not LOP meet the operating conditions; if both of two busbars are LOP, 27E/59Neg.E operates only
when “LOP_B1->27E/59Neg.E” and “LOP_B2->27E/59Neg.E” are both collocated to “Release”.
27 Element On
&
Ullmin < Ud ≥1
& “27E/59Neg.E Operate”
59Neg. Element On
&
U2 > U2d
LOP
&
LOP release 27E/59Neg. E.
&
27 Element Off
&
59Neg. Element Off
10
PMC-851D User Manual
“50P-E1 Operate”
50P-E1 On
&
Imax > Id Output
SOTF-1 On
DI strap meets conditions “SOTF-1 Operate”
t 0
SOTF Release &
delay
Imax > Id Output
27E/59Neg.E Off
≥1
27E/59Neg.E Operate
11
PMC-851D User Manual
SOTF_ATS On
DI strap meets conditions “SOTF_ATS Operate”
t 0
SOTF_ATS Release &
delay
Imax >Id Output
27E/59Neg.E Off
≥1
27E/59Neg.E Operate
SOTF_DI On
DI strap meets conditions “SOTF_DI Operate”
t 0
SOTF_DI Release &
delay
Imax > Id Output
27E/59Neg.E Off
≥1
27E/59Neg.E Operate
12
PMC-851D User Manual
50P-1 On
DI strap meets conditions “50P-1 Operate”
t 0
Imax > Id &
delay
Output
DI Block Off
≥1
IN6 Deassert
27E/59Neg.E Off
≥1
27E/59Neg.E Operate
50P-2 On
DI strap meets conditions “50P-2 Operate”
t 0
Imax > Id &
delay
Output
27E/59Neg.E Off
≥1
27E/59Neg.E Operate
13
PMC-851D User Manual
C1 0.14 13.5
tp=TD* tr=TD* 2
1 1 M
0.02
Normal Inverse M
C2 13.5 47.3
tp=TD* tr=TD* 2
Very Inverse M 1 1 M
C3
80.0 80.0
Extremely tp=TD* tr=TD* 2
M 1 1 M
2
Inverse
C4 120.0 120.0
tp=TD* tr=TD*
Long Inverse M 1 1 M
C5 0.05 4.85
tp=TD* tr=TD* 2
M 1 1 M
0.04
Short Inverse
14
PMC-851D User Manual
US standard curves:
Curve Name Operate Formula Return Formula
U1 0.0104 1.08
tp=TD* 0.0226 tr=TD* 2
Moderately Inverse M 0.02 1 1 M
U2 5.95 5.95
tp=TD* 0.180 tr=TD* 2
Inverse M 2 1 1 M
U3 3.88 3.88
tp=TD* 0.0963 tr=TD* 2
Very Inverse M 2 1 1 M
U4
5.67 5.67
Extremely tp=TD* 0.0352 tr=TD* 2
M 2 1 1 M
Inverse
U5 0.00342 0.323
tp=TD* 0.00262 tr=TD* 2
Short Inverse M 0.02 1 1 M
In the formulas above, M=Imax/Ip, Ip is the fixed value of pickup, Imax is the maximum value of
three-phase currents, TD is the multiple of time dial, tp is the operation time, tr is the reset time.
The “Time Dial” of C1~C5 curve should be collocated to 0.05~1.00, while “Time Dial” of U1~U5 curve
should be collocated to 0.50~15.00
The reset model of inverse time over-current protection can be selected as “At Once” or “Equation”. When
“At Once” is selected, the inverse protection will drop out and the accumulated time will be reset after the
maximum value of three-phase currents keeps less than 0.95 times of fixed current continuously for 30ms.
However, when “Equation” is selected, the accumulated time will be reduced according to the formula of tr.
After inverse time over-current protection operates, “Trip” or “Alarm” indicator lamp is optional.
3.1.9. Neutral Current SOTF Protection (SOTF_I0-1, SOTF_I0-2)
PMC-851D has 2 sections neutral current SOTF protections (SOTF_I0-1, SOTF_I0-2). As the same with
phase current SOTF, neutral current SOTF protection is also released only during a period of time after the
circuit breaker switches from open to close.
The status of tie breaker gets from operate board or digital input IN3 which can be collocated through
“System->Breaker State Config.->Tie BRK”.
SOTF_I0-1 On
DI strap meets conditions “SOTF_I0-1 Operate”
& t 0
SOTF_I0 Release
delay
I0 > Id Output
15
PMC-851D User Manual
SOTF_I0-1 is on;
DI strap meets conditions: DI strap selects “Off”, or selects input DI and corresponds to DI position;
SOTF_I0 is released;
I0 > Id. I0 is the value of zero-sequence current; Id is the fixed value of SOTF_I0-1.
After neutral current SOTF protection operates, “Trip” indicator lamp lights up. Drop-off to pick-up ratio is
0.95.
3.1.10. Neutral Current Acceleration SOTF Protection (SOTF_I0_ATS)
As the same with SOTF_ATS, neutral current acceleration SOTF protection is released only during a period
of time after ATS_B1 or ATS_B2 operates and controls tie breaker switching from open to close. The period of
time can be collocated under the “Config. Setup->Relay-> Aux. Element->SOTF Time” menu.
SOTF_I0_ATS On
DI strap meets conditions “SOTF_I0_ATS Operate”
t 0
SOTF_I0_ATS Release &
delay
I0 >Id Output
16
PMC-851D User Manual
standard, which are all the same with Inverse time over-current protection (see 3.1.8 for details).
51I0 On
&
DI strap meets conditions
“51I0 Operate”
Inverse
I0
Curve
Output
27PP_B1-1 Start
17
PMC-851D User Manual
27PP_B1-1 On
DI strap meets conditions
LOP “27PP_B1-1 Operate”
t 0
&
delay
Ever Volt Off Output
≥1
Ever Volt is set
Ullmax < Ud
&
dU/dt Block On
& ≥1
dU/dt > Pickup
18
PMC-851D User Manual
27PP On
DI strap meets conditions “27PP Operate”
t 0
Imax > 0.02Inom
& Delay
Output
LOP_B1 Operate
&
LOP_B2 Operate
Ullmax_all < Ud
dU/dt Block
& ≥1 &
dU/dt > Pickup
19
PMC-851D User Manual
The flag of “df/dt Block” is set and latched when “df/dt Block” is on and df/dt is more than the pickup
value. The flag of “df/dt Block” is reset when frequency is more than fd.
Single-bus under-frequency protection will be blocked if the phase-to-phase voltages of corresponding
busbar are all less than 15V.
81U_B1-1 On
DI strap meets conditions
“81U_B1-1 Operate”
f < fd t 0
&
delay
Output
df/dt Block On &
& ≥1
df/dt > Pickup
20
PMC-851D User Manual
81U On
DI strap meets conditions
Imax > 0.02Inom
“81U Operate”
f < fd t 0
&
delay
Output
df/dt Block On &
& ≥1
df/dt > Pickup
Direction forward
& ≥1
P > Pd
&
P < (-Pd)
After power protection operates, “Trip” or “Alarm” indicator lamp is optional. Drop-off to pick-up ratio is
0.95.
21
PMC-851D User Manual
25 On
DI Strap meets conditions
25 Element Operate 10s 0
& “Busbar Voltage Abnormal”
Ullmin > 90V Delay
Breaker Closed
≥1
Imax > 0.02Inom
25 On
DI Strap meets conditions
UAB1 > 0.7Unom
UAB2 > 0.7Unom 25 Element Operate
&
Frequency Qualified
Angle Diff. Qualified
Voltage Diff. Qualified
22
PMC-851D User Manual
25 On
DI Strap meets conditions & 25 Close Release
25 Element Operate
≥1
Ull1max < 30V
Ull2max < 30V
0 30s
25 Close Operate
23
PMC-851D User Manual
25 close is released.
The closing command from communication is received in the check time.
If the check time reached and the 25 remote close is still not operated, then the log of “25 Remote Close
Fail” is generated.
3.1.21. Loss of Potential (LOP_B1, LOP_B2)
When the following conditions are met at the same time, after 10s of time delay, loss of potential
operates:
Two busbars have loss of potential protection respectively (LOP_B1, LOP_B2). If the “27E/59Neg.E” is
collocated to “Release”, the compound voltage element will be released if corresponding busbar is LOP; if the
“27E/59Neg.E” is collocated to “Block”, the compound voltage element will be blocked if corresponding busbar
is LOP.
LOP_B1 On
Ullmin > 0.9Unom
“CT Abnormal”
10s 0
CT Monitor On
& delay
Max (I2、I0) > 0.04In + 0.1Imax Output
24
PMC-851D User Manual
“74TC Abnormal”
t 0
74TC On
& delay
BRK Closed = BRK Open Output
27PS On
DI Strap meets conditions
US1 < Ud & “27PS Operate”
US2 < Ud
Ullmax_all < Ud
25
PMC-851D User Manual
26
PMC-851D User Manual
“BLK ATS_L1”: when a certain bit is collocated to 1, it indicates that the corresponding DI is used to block
ATS_L1. For example, if “BLK ATS_L1” is collocated to 110000, it indicates that IN9 and IN10 are used to block
ATS_L1.
“BLK ATS_L2”: when a certain bit is collocated to 1, it indicates that the corresponding DI is used to block
ATS_L2. For example, if “BLK ATS_L2” is collocated to 110000, it indicates that IN9 and IN10 are used to block
ATS_L2.
“DI Block ATS Delay” of IN9~IN14 can be collocated separately.
3.1.31. Automatic Transfer Switch of Busbar Ⅰ (ATS_B1)
Line 1# Line 2# Line 1# Line 2#
ATS_B1
Status 1 Status 2
ART_B1
QF1 Cloesd QF2 Closed QF1 Closed QF2 Open
ATS_B1 On
QF1 Closed
t1 0 0 t2
QF2 Closed & “ATS_B1 is Ready”
Delay Delay
QF3 Open
Ullmax_all>Ulive
28
PMC-851D User Manual
QF3 is open;
Ullmax_all > Ulive. Ullmax_all is the maximum value of all phase-to-phase voltages of two busbars;
Ulive is the fixed value of “Live Volt.”.
When the above conditions are met, after delay setting of “Ready Delay” (t1), ATS_B1 is ready, and gets a
SOE recorded of “ATS_B1 is Ready”; when anyone of above conditions is not met, after delay setting of
“Un-Ready Delay” (t2), ATS_B1 is Un-ready.
ATS_B1 is Ready
“ATS_B1 Trip BRK2 Operate”
IA2 < 0.02Inom t3 0
&
Ullmax2 < Udead Delay
Output
Trip Check LiveLine Off
≥1
Ullmax1 > Ulive
29
PMC-851D User Manual
“Trip Check Liveline” is off, or Ullmax1>Ulive, Ullmax1 is the maximum value of three phase-to-phase
voltages of busbar Ⅰ; Ulive is the fixed value of “Live Volt.”.
ATS_B1 is Ready
QF2 Open “ATS_B Close Tie BRK Operate”
t4 0
QF3 Open &
Delay
Ullmax1 > Ulive Output
0 4s Falling Edge
ATS_B1 Close Tie BRK Operate
Delay & “ATS_B Succeed”
QF3 Closed
0 t5 Falling Edge
ATS_B1 Trip BRK2 Operate
Delay Falling Edge ≥1 & “ATS_B Fail”
0 4s
ATS_B1 Close Tie BRK Operate
Delay
QF3 Open
30
PMC-851D User Manual
ART is enable(IN5 = 1)
QF1 Open
t8 0
QF2 Closed ≥1
Delay
QF3 Open
Mode 1
0 1
ART Trip Tie BRK Operate &
Delay Falling
Edge
≥1
0 t7+2
ART Close BRK2 Operate
Delay Falling
Edge
Mode 2
0 1
ART Close BRK2 Operate &
Delay Falling
Edge
≥1
0 t6+2
ART Trip Tie BRK Operate
Delay Falling
Edge
25_L2 Operate
32
PMC-851D User Manual
Status 1 Status 3
ART_B2
QF1 Cloesd QF2 Closed QF1 Open QF2 Closed
ATS_B2 On
QF1 Closed
t1 0 0 t2
QF2 Closed & “ATS_B2 is Ready”
Delay Delay
QF3 Open
Ullmax_all>Ulive
ATS_B2 is Ready
“ATS_B2 Trip BRK1 Operate”
IA1 < 0.02Inom t3 0
&
Ullmax1 < Udead Delay
Output
Trip Check LiveLine Off
≥1
Ullmax2 > Ulive
34
PMC-851D User Manual
ATS_B2 is Ready
QF1 Open “ATS_B Close Tie BRK Operate”
t4 0
QF3 Open &
Delay
Ullmax2 > Ulive Output
0 4s Falling Edge
ATS_B2 Close Tie BRK Operate
Delay & “ATS_B Succeed”
QF3 Closed
0 t5 Falling Edge
ATS_B2 Trip BRK1 Operate
Delay Falling Edge ≥1 & “ATS_B Fail”
0 4s
ATS_B2 Close Tie BRK Operate
Delay
QF3 Open
35
PMC-851D User Manual
ART is enable(IN5 = 1)
QF1 Closed
t8 0
QF2 Open ≥1
Delay
QF3 Open
Mode 1
0 1
ART Trip Tie BRK Operate &
Delay Falling
Edge
≥1
0 t7+2
ART Close BRK1 Operate
Delay Falling
Edge
Mode 2
0 1
ART Close BRK1 Operate &
Delay Falling
Edge
≥1
0 t6+2
ART Trip Tie BRK Operate
Delay Falling
Edge
25_L1 Operate
37
PMC-851D User Manual
Status 3 Status 2
ART_L1
QF1 Open QF2 Closed QF1 Closed QF2 Open
ATS_L1 On
QF1 Open
QF2 Closed t1 0 0 t2
& “ATS_L1 is Ready”
QF3 Closed Delay Delay
Us1>Ulive
Us2>Ulive
38
PMC-851D User Manual
SOE recorded of “ATS_L1 is Ready”; when anyone of above conditions is not met, after delay setting of
“Un-Ready Delay” (t2), ATS_L1 is Un-ready.
ATS_L1 is Ready
“ATS_L1 Trip BRK2 Operate”
IA2 < 0.02Inom t3 0
&
Us2 < Udead Delay
Output
Ullmax_all < Udead
39
PMC-851D User Manual
ATS_L1 is Ready
QF1 Open
QF2 Open
“ATS_L1 Close BRK1 Operate”
IA2 < 0.02Inom t3 0 t4 0
& &
Ullmax_all < Udead Delay Delay
Output
0 4s Falling Edge
ATS_L1 Close BRK1 Operate
Delay & “ATS_L1 Succeed”
QF1 Closed
0 t5 Falling Edge
ATS_L1 Trip BRK2 Operate
Delay Falling Edge ≥1 & “ATS_L1 Fail”
0 4s
ATS_L1 Close BRK1 Operate
Delay
QF1 Open
40
PMC-851D User Manual
ART is enable(IN5 = 1)
QF1 Open
t8 0
QF2 Closed ≥1
Delay
QF3 Open
Mode 1
0 1
ART_L1 Trip BRK1 Operate &
Delay Falling
Edge
≥1
0 t7+2
ART Close BRK2 Operate
Delay Falling
Edge
Mode 2
0 1
ART Close BRK2 Operate &
Delay Falling
Edge
≥1
0 t6+2
ART_L1 Trip BRK1 Operate
Delay Falling
Edge
25_L2 Operate
42
PMC-851D User Manual
Status 2 Status 3
ART_L2
QF1 Closed QF2 Open QF1 Open QF2 Closed
ATS_L2 On
QF1 Closed
QF2 Open t1 0 0 t2
& “ATS_L2 is Ready”
QF3 Closed Delay Delay
Us1>Ulive
Us2>Ulive
43
PMC-851D User Manual
SOE recorded of “ATS_L2 is Ready”; when anyone of above conditions is not met, after delay setting of
“Un-Ready Delay” (t2), ATS_L2 is Un-ready.
QF2 Close
≥1 “ATS_L2 is Un-Ready”
ATS_L2 Close BRK2 Opreate
ATS_L2 Succeed or failed
DI Block ATS_L2
ATS_L2 is Ready
“ATS_L2 Trip BRK1 Operate”
IA1 < 0.02Inom t3 0
&
Us1 < Udead Delay
Output
Ullmax_all < Udead
44
PMC-851D User Manual
ATS_L2 is Ready
QF1 Open
QF2 Open
“ATS_L2 Close BRK2 Operate”
IA1 < 0.02Inom t3 0 t4 0
& &
Ullmax_all < Udead Delay Delay
Output
0 4s Falling Edge
ATS_L2 Close BRK2 Operate
Delay & “ATS_L2 Succeed”
QF2 Closed
0 t5 Falling Edge
ATS_L2 Trip BRK1 Operate
Delay Falling Edge ≥1 & “ATS_L2 Fail”
0 4s
ATS_L2 Close BRK2 Operate
Delay
QF2 Open
45
PMC-851D User Manual
ART is enable(IN5 = 1)
QF1 Closed
t8 0
QF2 Open ≥1
Delay
QF3 Open
Mode 1
0 1
ART_L2 Trip BRK2 Operate &
Delay Falling
Edge
≥1
0 t7+2
ART Close BRK1 Operate
Delay Falling
Edge
Mode 2
0 1
ART Close BRK1 Operate &
Delay Falling
Edge
≥1
0 t6+2
ART_L2 Trip BRK2 Operate
Delay Falling
Edge
25_L1 Operate
47
PMC-851D User Manual
25_L1 On
DI Strap meets conditions
25_L1 Operate 10s 0
& “VS1 Abnormal”
Ullmin1 > 90V Delay
QF1 Closed
≥1
IA1 > 0.02Inom
25_L1 On
DI Strap meets conditions
UAB1 > 0.7Unom
Us1 > 0.7Unom 25_L1 Operate
&
Frequency Qualified
Angle Diff. Qualified
Voltage Diff. Qualified
48
PMC-851D User Manual
25_L2 On
DI Strap meets conditions
25_L2 Operate 10s 0
& “VS2 Abnormal”
Ullmin2 > 90V Delay
QF2 Closed
≥1
IA2 > 0.02Inom
25_L2 On
DI Strap meets conditions
UAB2 > 0.7Unom
Us2 > 0.7Unom 25_L2 Operate
&
Frequency Qualified
Angle Diff. Qualified
Voltage Diff. Qualified
49
PMC-851D User Manual
&
50
PMC-851D User Manual
3.2. Measurements
3.2.1. Measurement Data
Table 3-1 Measurement Data
Uab1, Ubc1, Uca1, Us1, Uab2, Ubc2, Uca2, Us2
Primary value Ia, Ib, Ic
P, Q, S, PF
51
PMC-851D User Manual
52
PMC-851D User Manual
defined outputs as following respectively: close (operate automatically after ATS_B close tie BRK operate), trip
(can be set), remote trip output, remote close output (operate automatically after 25 remote close operate),
abnormal alarm, KKJ output, link output (don’t be controlled by CPU).
Remote trip output, remote close output and OUT1~OUT6 digital outputs enjoy the remote control
function. Remote control is conducted by starting relay, remote trip relay, remote close relay, and OUT1~OUT6
relay together. After PMC-851D received the command of remote control from supervisory control system, it
will send out a response message, when supervisory control system received the response message and send
out the remote control command again, the remote trip relay (or remote close relay, OUT1~OUT6 relay) of the
device will operate. if the remote control status of PMC-851D is “Local”, the supervisory control system is
unable to remote control the device. Remote control function is featured as a very high reliability since
multiple maloperation preventive measures are considered in the hardware and software of PMC-851D. if the
“SBO” (select before operating) is collocated to “Off”, it is unnecessary to send preset message before remote
control.
There are 3 kinds of operation board (board D): DC 220V operation board, DC 110V operation board and
AC 220V operation board. Users should select the right operation board according to the actual operation
power supply type.
53
PMC-851D User Manual
54
PMC-851D User Manual
55
PMC-851D User Manual
category, fault characteristic value(such as short circuit current or voltage) and then wave form; the wave form
is displayed in pair(phase voltage and phase current are in a page, while break status changes are in another
page); the wave form curve is searched by moving to the left and right; 4 cycles are moved once; the cycle
scale is marked below; the second method aims to read the graph of fault recording in the monitoring
computer—The wave form is even distinct.
The full length of WFR logging is 100 cycles; the recorded wave form includes 5 cycles before the
malfunction and 95 cycles after that; there are 32 points in the first 10 cycles and 16 points in the last 90
cycles. The wave form of latest 8 WFR logging is reserved in PMC-851D; these data are reserved in the
nonvolatile storage; the communication supports the summoning of WFR logging data.
PMC-851D is able to start WFR logging in remote control method.
3.6.3. Instantaneous Capturing Function of Waveform
A huge amount of current and voltage harmonic waves exist in the industrial, commercial and civil power
consumption which have increasingly become the common concern of power system and user. It is necessary
to diagnose the root cause by wave form analytic tools and confirm necessary protective measures to upgrade
the power supply quality.
PMC-851D is able to provide 10 cycles (128 points in each cycle) of wave form sampling service for
three-phase currents and voltages input through manual remote control function and protection action; the
sampled wave form data is stored in the nonvolatile storage and read by the computer through communication
port as shown in the figure. The real-time monitoring software PECSTAR developed by the company is able to
obtain the wave form data, make FFT to each wave form and display 63 harmonic waves in the form of bar
chart which is beneficial for the user to swiftly diagnose the source and severity of harmonic wave.
PMC-851D is able to start wave form record in remote control method.
56
PMC-851D User Manual
U2
u 100%
U1
I2
i 100%
I1
57
PMC-851D User Manual
Hardware Software
58
PMC-851D User Manual
RTC RTC
PMC-851D PMC-851D
GPS
59
PMC-851D User Manual
synchronization method is able to analyze precise year/month/day/hour/minute/second from the input signal;
it is able to realize millisecond timing accuracy without other synchronization methods. Communication
synchronization is not recommended to avoid mutual interruption between numerous clocks. The following
parameters are set up for IRIG-B synchronization of PMC-851D.
Time zone of the system: It means the gap between regional time and GMT in PMC-851D of minute;
the default value is +480; correct setup of existing time zone will obtain a correct result. For instance,
China mainland adopts Beijing time which is 8h later than GMT; this value is +480 (default value).
Calibration of IRIG-B: The connected IRIG-B signal may not be in standard GMT; the parameter is
adopted to transfer input IRIG-B clock into standard GMT in PMC-851D of minute; the default value is
0. For instance, the output signal of IRIG-B clock source is Beijing time which is later than GMT for 8h;
the parameter is set to be -480 in order to transfer Beijing time into GMT. Please refer to Figure 3.9d
for the typical application.
IRIG-B
IRIG-B source
60
PMC-851D User Manual
stop.
Address of SNTP server: IP address is set up for SNTP time server; the address has to guarantee same
network segment with PMC-851D or visit through the gateway.
Since the broadcast synchronization function fails to identify the source of synchronization message as
legal time server, the gap between existing time and broadcast synchronization time is required to be less than
5 minutes in PMC-851D; otherwise, the synchronization message will be abandoned. Please refer to Figure
3.9e for the typical application.
SNTP server
PMC swtich
SNTP broadcast
61
PMC-851D User Manual
Ethernet
Switch
P1 P1 P1 P1 P1 P1
Ethernet
Switch
P1 P2 P1 P2 P1 P2
P1 P2 P1 P2 P1 P2
Ethernet
P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2
62
PMC-851D User Manual
a self-healing ring network with PMC-2205/2208 looped network exchanger in CLP Technology.
Ethernet
PMC-2205
P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2
Ethernet
Switch Switch
P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2
63
PMC-851D User Manual
4. Operating Instructions
4.1. Front Panel
: Shift left of cursor or page up, “◄” appears at the upper corner of the page of which page-up is
: Shift right of cursor or page down, “►” appears at the upper corner of the page of which page-up
Menu
: Default that the interface enters the main menu;
Enter
: Confirm the current selection or parameter revision;
Esc
: Exit from current operation or parameter revision;
Reset
: Reset the protection light, alarm light, and configuration Output.
Trip
: Red light ON indicates protective action on tripping, and can be turned off by pressing “Reset”
key if all protective action on tripping return;
Alarm : Yellow light ON indicates self-check fault of device or protection action on signals, and can be
turned off by pressing “Reset” key if all protective action on signals return;
Open
: Green light ON indicates breaker is open;
79R : Yellow light flashing indicates the condition of ATS ready is satisfied and starts time delay; yellow
light ON indicates ATS is ready; yellow light OFF indicates not ready.
The Wiring Diagram on the left side of default page can be collocated through “Config. Setup->System->Main
Diagram” to “Mode 1”, “Mode 2”, or ”Mode 3”.
If PMC-851D is not operated in 10min, the system will return to the page automatically, and meanwhile,
the backlight will be turned off.
kV kV
A
A
A
kW
PF I II
kV kV
2012 -01 - 10 09:36:49 2012 -01 - 10 09:36:49
Fig. 4-2 Default Display (Mode 1) Fig. 4-3 Default Display (Mode 2)
Relay Metering
UAB1 0.00V 0.0°
UBC1 0.00V 0.0°
UCA1 0.00V 0.0°
US1 0.00V 0.0°
I II UAB2 0.00V 0.0°
UBC2 0.00V 0.0°
kV kV
UCA2 0.00V 0.0°
US2 0.00V 0.0°
2012 -01 - 10 09:36:49
66
PMC-851D User Manual
4.5. Logs
SOE report display screen is as shown in Fig. 4-10. The screen is bounced out in case of that protection
operates or fault is discovered with PMC-851D from self-check. In case the protection operates, the “Trip” light
or “Alarm” light will be turned on according to the protection configuration; if fault or error is discovered from
self-check, “Alarm” light will be turned on. The page popped up will display the fault nature, characteristic
value and action time.
Each page may display one SOE report. After “Esc” key is pressed, this page will disappear, and the default
page will be displayed. If multiple SOE reports are displayed, “◄”, “►” may be used for page up and page
down.
▶
001 50P-1 Operate
13-04-22 09:36:52:662
IA=1.53A IB =0.00A
IC=0.00A
4.6. Menu
In case of default display page, press “Menu” key to access the main menu page, as shown in Fig. 4-11.
Here, press “▲”, “▼” key for selection, and the menu selected is highlighted. Here, press “Enter” key to access
the next-level menu.
67
PMC-851D User Manual
Main Menu
1 Measurements
2 View Setup
3 Config. Setup
4 Logs
5 Power Quality
6 Maintenance
7 Factory
Various functions of PMC-851D device may be accessed through menu, and the menu structure of
PMC-851D is as shown below:
Maintenance Communication
Communicaton
Group Operate
Time Sync.
68
PMC-851D User Manual
Uab2 Harmonic
Ubc2 Harmonic
Uca2 Harmonic
4.6.1. Measurements
Select “Measurements” with cursor, and press “Enter” key to access the next-level menu.
“Measurements” menu is as shown in Fig. 4-13; the sub menu is shown as following:
Metering: Display all the primary measuring values such as current, voltage, power, energy, etc. See Fig.
4-14.
Relay Metering: Display all the secondary measuring values such as current, voltage, positive-sequence
current, negative-sequence current, zero-sequence current, etc. See Fig. 4-15.
Digital Inputs: Display the real-time status of binary quantity, as shown in Fig. 4-16.
Digital Outputs: Display the real-time status of outputs, as shown in Fig. 4-17.
Energy: Display the real-time energy accumulation, as shown in Fig. 4-18.
Measurements Metering ▶
1 Metering Uab1 0.000kV 0.0°
2 Relay Metering Ubc1 0.000kV 0.0°
3 Digital Inputs Uca1 0.000kV 0.0°
4 Digital Outputs Us1 0.000kV 0.0°
5 Energy Uab2 0.000kV 0.0°
Ubc2 0.000kV 0.0°
Uca2 0.000kV 0.0°
Us2 0.000kV 0.0°
69
PMC-851D User Manual
Fig. 4-15 Menu of Relay Metering Fig. 4-16 Menu of Digital Inputs
Fig. 4-17 Menu of Digital Outputs Fig. 4-18 Menu of Energy Data
70
PMC-851D User Manual
Digital Outputs: It’s available to view the output broadening time of configuration outputs, as shown
in Fig. 4-26.
Analog Output: It’s available to view AO configuration parameters, as shown in Fig. 4-27.
Communication:
1. Access the page of communication parameters and then select the communication parameters to
be viewed, as shown in Fig. 4-28.
2. Select the communication parameter to be viewed, and then view the concrete parameter, as
shown in Fig. 4-29.
Time Sync.: It’s available to view the time synchronism parameters, as shown in Fig. 4-30.
Fig. 4-23 Menu of Auxiliary Element Fig. 4-24 Menu of Digital Inputs
71
PMC-851D User Manual
Fig. 4-25 Menu of IN1 Settings Fig. 4-26 Menu of Digital Outputs
Key Ia 1 RS-485
Zero 0 2 Ethernet
Full 99999999 3 SNTP
to cancel parameter revision, and the parameter will return to original value saved;
6, When “Esc” key is pressed to exit from every parameter setup page, PMC-851D will bounce out
“confirm the save setup” page, as shown in Fig. 4-36; press “◄”, “►” to select “Yes” or “No”, and press
“Enter” key to save or not according to the option selected. If “Esc” is pressed on the screen, the data
won’t be saved, and the operation will exit from the previous screen directly.
Default password before delivery: “0000”.
System System ▶
Fig. 4-33 Input password error page Fig. 4-34 System Parameters setup page
System ▶ System
Pri. Vnom 010.00kV Save Changes
Sec. Vnom 100.00A
Yes No
VS1 Pri. Vnom 10.00kV
VS1 Sec. Vnom 100.00V
VS2 Pri. Vnom 10.00kV
VS2 Sec. Vnom 100.00V
M. CT Ratio 500
P. CT Ratio 500
Fig. 4-35 System parameters setup page Fig. 4-36 Settings save page
73
PMC-851D User Manual
▶
▶
System System ▶
Pri. Vnom 10.00kV IA1 Ratio 100
Sec. Vnom 100.00A IA2 Ratio 100
VS1 Pri. Vnom 10.00kV System Freq. 50Hz
VS1 Sec. Vnom 100.00V DI Source DC
VS2 Pri. Vnom 10.00kV SBO On
VS2 Sec. Vnom 100.00V Main Diagram Mode 1
Language English
M. CT Ratio 500
P. CT Ratio 500
▶ ▶
System ▶ System
Note 1: “DI Source” is defaulted to be “DC”, indicating supporting DC voltage excitation; if it is collocated
to “AC”, it indicates supporting AC voltage excitation. If AC voltage excitation is used, it shall please be
collocated to “AC”.
Note2: “BRK1” (or BRK2) is defaulted to be “NO” (normally open contact). If “BRK1” (or BRK2) is
collocated to “NO”, QF1 (or QF2) is closed when IN1 (or IN2) asserted, QF1 (or QF2) is open when IN1(or IN2)
deasserted. If “BRK1” (or BRK2) is collocated to “NC” (normally closed contact), QF1 (or QF2) is closed when
IN1 (or IN2) asserted, QF1 (or QF2) is open when IN1(or IN2) deasserted.
Note3: “Tie BRK” is defaulted to be “Normal”. If “Tie BRK” is collocated to “Ext. NC” (normally closed
contact), QF3 is closed when IN3 asserted, QF3 is open when IN3 deasserted. If “Tie BRK” is collocated to “Ext.
NO” (normally open contact), QF3 is open when IN3 asserted, QF3 is closed when IN3 deasserted. If “Tie BRK”
is collocated to “Normal”, the status of QF3 gets from operate board, detected by BRK closed status and BRK
open status.
Note 4: the default value of Events Setting is all “Off”.
If “On” is selected for “Start Events” and “Dropout Events”, then relevant protection start-up events,
trip events, and return events will be recorded.
If “On” is selected for “Start Events”, but “Off” is selected for “Dropout Events”, then relevant
protection start-up events and trip events will be recorded.
If “Off” is selected for “Start Events”, but “On” is selected for “Dropout Events”, then relevant
protection trip events and return events will be recorded.
If “Off” is selected for “Start Events” and “Dropout Events”, then relevant protection trip events will
only be recorded.
74
PMC-851D User Manual
Relay Select ▶
01 Aux. Element
02 SOTF-1 □
03 SOTF-2 □
04 SOTF_ATS □
05 SOTF_DI □
06 50P-1 □
07 50P-2 □
08 67P-3 □
Fig. 4-38 Setting group selection page
Fig. 4-39 Setting group selection page Fig. 4-40 Relay setup page
75
PMC-851D User Manual
50P-1 Output
Fig. 4-41 50P-1 setup page Fig. 4-42 Output configuration page
As shown in Fig. 4-40, we shall press “►”, “◄” key to move to the location of the right “50P-1” Relay,
select “On” or “Off”, and press “Enter” key to access setting; press “▲”, “▼” key to select “On” or “Off”, and
press “Enter” key to confirm “50P-1” Relay setting.
Select corresponding protection function. For example, select “50P-1” menu, press “Enter” key to access
the setup page, and then set up the “50P-1”, as shown in Fig. 4-41.
Select value of “Output” and press “Enter” to access the setup page of output, as shown in Fig. 4-42.
press “Enter” to select output, press “Enter” again to cancel the output, press “Esc” to return to the previous
menu.
4) Digital Inputs settings setup
Digital Inputs is as shown in Fig. 4-43, and the operation is the same as that of relay settings setup;
5) Digital Outputs
The page for setup of Digital Output width is as shown in Fig. 4-44, and the operation is the same as that
of relay settings setup;
If the output is set up to be “1.00s”, it indicates that after action of output, the contact is maintained until
protection dropout and then is reset 1s later automatically.
If the output is set up to be “Latch”, it indicates that, after action of output, the contact is maintained, and
not reset until “Reset” key is pressed or “reset” is executed through remote control.
76
PMC-851D User Manual
Analog Output
key Ia
Zero 0
Full 9999999
7) Communication
Communication menu page is as shown in Fig. 4-46, and the operation is the same as that of system
parameters setup;
PMC-851D has dual Ethernet ports, and supports four port modes: Failover, switch, PMC-Ring, and
standalone. Users may make choice according to the actual form of network topology.
If the port IP address is wrongly set up, the prompt “Config. Error!” will appear, and the parameter wont’
be saved.
If the port mode is set up to be PMC-Ring network mode, it’s available to form self-cure ring network
together with CET’s PMC serial industrial ring network, and the ID of ring network must be set up accordant
with that of ring network switch for the sake of communication. If the port mode is set up to be
primary-standby switching and switchboard, the ID of ring network won’t work. The specific port mode and
application situations can refer to content of the section 3.10.
PMC-851D supports SNTP network timing. The timing server address and time query interval are set up in
the “SNTP” interface, and wherein, the update rate is the interval between PMC-851D’s timing and the server’s
synchronous clock, and if it is set up to be 0, timing won’t act.
77
PMC-851D User Manual
Communication RS-485
Fig. 4-46 Communication setup menu Fig. 4-47 RS-485 setup page
Ethernet Ethernet
Fig. 4-48 Ethernet setup page Fig. 4-49 Ethernet setup page
SNTP
Server
IP 0. 0. 0. 0
Update Rate 1min
8) Group operate
Group operation includes two functions: active group switching, and group copying.
Group Operate
1 Active Group
2 Group Copy
The setting group currently in operation may be switched online on the page of Active Group and settings
78
PMC-851D User Manual
Active Group
Present Group 1
Select Group 2
On the page of group copying, all the parameters of one setting group may be totally copied to another
setting group.
On this page, select the source group number and the target group number successively, move the cursor
to behind the copy button, then press “Enter” button, and all parameters of the source group will be copied to
the target group. After group copy, there will be a prompt of successful copy, and the page won’t be closed.
Here, another target setting group may be selected for continuous copy operation.
Group Copy
Source Group 1
Target Group 2
Exit Copy
79
PMC-851D User Manual
Time Sync.
1) SOE Logs
As shown in Fig. 4-57~4-60, each page may display 1~2 events at one stroke. Press “◄”, “►” key to
page down or page up for viewing records. There are 512 entries of SOE Logs at the most.
Fig. 4-57 DI/DO logs page Fig. 4-58 Relay logs page
80
PMC-851D User Manual
Fig. 4-59 Diag. logs page Fig. 4-60 Maint. logs page
2) WFR
WFR page is as shown in Fig. 4-61~4-64. Press “▲”, “▼” key to display WFR index and log, then display
waveform. The length of each complete wave record is 100 cycles. Press “►”, “◄” to view waveforms, and 4
cycles are moved each time.
WFR1 WFR1
IA/A 1-4 BRK Closed 1-4
77.4
-77.4
IB/A BRK Open
77.4
-77.4
3) Diagnosis
Diagnosis page is as shown in Fig. 4-65, and it shows Diagnosis information.
81
PMC-851D User Manual
Diagnosis
Relay CPU OK
EEPROM OK
NVRAM OK
A/D OK
Settings OK
Analog Ch. OK
4.6.6. Maintenance
The following work may be completed after accessing this page: Clear SOE Logs, WFR, WFC; set up original
value of energy; revise user password; revise system time; display device information, as shown in Fig. 4-67.
82
PMC-851D User Manual
4.6.7. Factory
The page is used for factory calibration.
PMC-851D has been subject to strict debugging and calibration before being delivered, and shall not be
changed at random by non-professional maintenance personnel! Factory password is required for accessing
this menu.
4.6.8. Settings List
Table 4-1 Settings List
83
PMC-851D User Manual
BRK2 NO/ NC NO
Tie BRK Ext. N0/ Ext. NC/Normal Normal
Start Events Off/On Off
Dropout Events Off/On Off
0.25~100.00(5A rated)
Pickup A 20.00
0.05~20.00(1A rated)
Aux. Element Output 0000000~1111111(Binary) 0
50P-E2 Off/On Off
0.25~100.00(5A rated)
Pickup A 20.00
0.05~20.00(1A rated)
Output 0000000~1111111(Binary) 0
50P-E3 Off/On Off
0.25~100.00(5A rated)
Pickup A 20.00
0.05~20.00(1A rated)
Output 0000000~1111111(Binary) 0
SOTF-1 Off/On Off
DI Strap Off/IN1~IN14 Off
27E/59Neg.E Off/On Off
SOTF-1,2 0.25~100.00(5A rated)
Pickup A 20.00
0.05~20.00(1A rated)
Delay s 0.00~3.00 0.00
Output 0000000~1111111(Binary) 0
SOTF_ATS Off/On Off
DI Strap Off/IN1~IN14 Off
SOTF_ATS 27E/59Neg.E Off/On Off
0.25~100.00(5A rated)
Pickup A 20.00
0.05~20.00(1A rated)
84
PMC-851D User Manual
Output 0000000~1111111(Binary) 0
0.25~100.00(5A rated)
Pickup A 20.00
50P-5 0.05~20.00(1A rated)
Delay s 0.00~600.00 1.00
Output 0000000~1111111(Binary) 0
85
PMC-851D User Manual
Curve C1/C2/C3/C4/C5/U1/U2/U3/U4/U5 C3
0.25~15.00(5A rated)
Pickup A 3.00
0.05~3.00(1A rated)
Time Dial 0.05~15.00 1.00
Output 0000000~1111111(Binary) 0
Signal Alarm/ Trip Alarm
Reset Type At Once/Equation At Once
SOTF_I0-1 Off/On Off
DI Strap Off/IN1~IN14 Off
0.25~100.00(5A rated)
SOTF_I0-1,2 Pickup A 20.00
0.05~20.00(1A rated)
Delay s 0.00~3.00 0.00
Output 0000000~1111111(Binary) 0
SOTF_I0_ATS Off/On Off
DI Strap Off/IN1~IN14 Off
0.25~100.00(5A rated)
SOTF_I0_ATS Pickup A 20.00
0.05~20.00(1A rated)
Delay s 0.00~3.00 0.00
Output 0000000~1111111(Binary) 0
50I0-1 Off/On Off
DI Strap Off/IN1~IN14 Off
0.25~100.00(5A rated)
Pickup A 20.00
50I0-1,2 0.05~20.00(1A rated)
Delay s 0.00~99.99 1.00
Output 0000000~1111111(Binary) 0
Signal Alarm/ Trip Alarm
51I0 Off/On Off
DI Strap Off/IN1~IN14 Off
Curve C1/C2/C3/C4/C5/U1/U2/U3/U4/U5 C3
0.25~15.00(5A rated)
51I0 Pickup A 3.00
0.05~3.00(1A rated)
Time Dial 0.05~15.00 1.00
Output 0000000~1111111(Binary) 0
Signal Alarm/ Trip Alarm
86
PMC-851D User Manual
87
PMC-851D User Manual
10.00~500.00(5A rated)
32P-1,2 Pickup W 100.00
2.00~100.00(1A rated)
Delay s 0.10~99.99 1.00
Output 0000000~1111111(Binary) 0
Signal Alarm/ Trip Alarm
25 Off/On Off
DI Strap Off/IN1~IN14 Off
Max. Angle ° 10~90 30
Max. Frequency Hz 0.10~1.00 1.00
Max. Voltage V 1.00~24.00 5.00
25
Manual Close Off/On Off
Output 0000000~1111111(Binary) 0
Remote Close Off/On Off
Check Time s 1.00~99.99 1.00
Output 0000000~1111111(Binary) 0
LOP_B1 Off/On Off
LOP_B1,2
27E/59Neg.E Release/Block Release
88
PMC-851D User Manual
Output 0000000~1111111(Binary) 0
CT Monitor Off/On Off
CT Monitor
Output 0000000~1111111(Binary) 0
74TC Off/On Off
74TC Delay s 0.50~99.99 1.00
Output 0000000~1111111(Binary) 0
Live Volt. V 1.00~144.00 70.00
Dead Volt. V 1.00~120.00 30.00
Ready Delay V 1.00~99.99 15.00
Un-Ready Delay s 1.00~60.00 10.00
Trip Check
Off/On On
LiveLine
Close Check
Off/On On
LiveLine
Aux. Para.
DI Mode 000000~111111(Binary) 000000
BLK ATS_B1 000000~111111(Binary) 000000
BLK ATS_B2 000000~111111(Binary) 000000
BLK ATS_L1 000000~111111(Binary) 000000
BLK ATS_L2 000000~111111(Binary) 000000
DI Block ATS
Delay s 0.00~99.99 0.00
IN9~IN14
27PS Off/On Off
DI Strap Off/IN1~IN14 Off
Pickup V 1.00~120.00 30
27PS
Delay s 0.00~99.99 1.00
Output 0000000~1111111(Binary) 0
Signal Alarm/ Trip Alarm
50PS Off/On Off
DI Strap Off/IN1~IN14 Off
0.25~100.00(5A rated)
50PS Pickup A 20.00
0.05~20.00(1A rated)
Delay s 0.00~99.99 1.00
Output 0000000~1111111(Binary) 0
89
PMC-851D User Manual
0.25~100.00(5A rated)
Pickup A 20.00
50P_L1,2 0.05~20.00(1A rated)
Delay s 0.00~600.00 1.00
Output 0000000~1111111(Binary) 0
Signal Alarm/ Trip Alarm
50LR Off/On Off
DI Strap Off/IN1~IN14 Off
0.50~100.00(5A rated)
Pickup A 20.00
50LR 0.10~20.00(1A rated)
Delay s 0.10~99.99 1.00
Output 0000000~1111111(Binary) 0
Signal Alarm/ Trip Alarm
ATS_B1 Off/On Off
Trip Delay s 0.00~60.00 1.00
Trip Output 0000000~1111111(Binary) 0
Close Delay s 0.00~60.00 0.50
Close Output 0000000~1111111(Binary) 0
ATS_B1,2
ART_B1 Off/Mode 1/Mode 2 Off
Close Delay s 0.00~30.00 1.00
Close Output 0000000~1111111(Binary) 0
Trip Delay s 0.00~30.00 1.00
Trip Output 0000000~1111111(Binary) 0
ATS_L1 Off/On Off
Trip Delay s 0.00~60.00 1.00
Trip Output 0000000~1111111(Binary) 0
Close Delay s 0.00~60.00 0.50
ATS_L1,2
Close Output 0000000~1111111(Binary) 0
ART_L1 Off/Mode 1/Mode 2 Off
Close Delay s 0.00~30.00 1.00
Close Output s 0000000~1111111(Binary) 0
90
PMC-851D User Manual
0.25~100.00(5A rated)
50LS_L1-1,2,3 Pickup A 20.00
0.05~20.00(1A rated)
50LS_L2-1,2,3
Delay s 0.00~99.99 1.00
Output 0000000~1111111(Binary) 0
Signal Alarm/ Trip Alarm
91
PMC-851D User Manual
NOTES:
1. The event type of digital inputs is optional: Pressure, Temp. 1, Temp. 2, Temp. 3, DCS1, DCS2, DCS3,
Spring, and DCS4.
2. 5A rated and 1A rated in current setting of phase protection current indicate the rated value of phase
current.
3. When digital output width is set up to be ”0.00s”, the setting is displayed as “Latch”.
92
PMC-851D User Manual
PMC-851D is fixed with two metal clamps at the upside and downside. The installation method and size
are as shown in the Fig. 5-1.
93
PMC-851D User Manual
Fig. 5-2 Wiring terminal drawing of DC operation board and dual 10/100 Base-T
94
PMC-851D User Manual
The terminal drawing of the DC operation board and dual 100 Base-FX device is as shown in Fig. 5-3:
Fig. 5-3 Wiring terminal drawing of DC operation board and dual 100 Base-FX
95
PMC-851D User Manual
The terminal drawing of the AC operation board and dual 10/100 Base-T device is as shown in Fig. 5-4:
Fig. 5-4 Wiring terminal drawing of AC operation board and dual 10/100 Base-T
96
PMC-851D User Manual
The terminal drawing of the AC operation board and dual 100 Base-FX device is as shown in Fig. 5-5:
Fig. 5-5 Wiring terminal drawing of AC operation board and dual 100 Base-FX
97
PMC-851D User Manual
99
PMC-851D User Manual
101
PMC-851D User Manual
positive pole and (A-2)~(A-15) of PMC-851D, and the DI status displayed is changed from “ON” to “OFF”.
4) DO debugging
DO debugging may be conducted in “DO Test” of “Factory”. Select the output to be debugged, and press
“Enter” key to test whether the output operate correctly.
5) Relay action test
Conduct debugging according to concrete project setting.
6) Communication function debugging
It is conducted under “Config. Setup-> Communication” menu to confirm the continuous number of each
protection device inside the substation, and that there is no repeated address number. Connect PMC-851D
with communication management machine, and connect it to the monitoring background. Conduct related
operations at the background, like reading the metering value and protection setting, revising and
downloading settings, remote resetting, protection time check, DI/DO call, reading protection action event
information and WFR information, etc., and check whether the protection device can normally respond to and
correctly execute commands; meanwhile, observe whether the communication between the protection device
and upper-position computer is normal by monitoring the communication management machine and
background messages.
7) Work before PMC-851D is put into operation
Confirm that all straps are off;
Confirm that the wiring of PMC-851D and external circuit is correct strictly before PMC-851D is put
into operation;
Check the cables behind the screen, confirm that they are accordant with installation drawings, and
all interim wires and anti-error measures have been restored;
Check whether each plug-in unit of PMC-851D is connected reliably, and whether each cable and
terminal are connected firmly and reliably, and screw down the bolts firmly;
Switch on DC power supply, calibrate that AC circuit is sound, and the crest and phase position of
voltage and current are normal;
Confirm that the communication number of PMC-851D is continuous, and make sure that there is no
repeated address number and the communication of PMC-851D is normal;
Confirm that the simulation diagram of bus line displayed on the defaulted page is matched with
actual working mode;
Check the clock of PMC-851D;
Set up the settings of PMC-851D strictly according to the advice note on setup of dispatching
settings, configure unnecessary protection to be Off, and confirm that the setting group is correct;
Clear all records available to clear;
After other items of PMC-851D are proved correct after inspection, input corresponding trip output
strap, protection strap and other functional straps according to the requirements of dispatching, and
102
PMC-851D User Manual
103
PMC-851D User Manual
104
PMC-851D User Manual
6. Wiring Diagram
6.1. Schematic Wiring Diagram
L2
*
*
QF2 TA4 PMC-851D
* *
TV2
Z13b
UL *
*
Z14b VS2
*
Z8a
*
*
* UN Z8b IA2
* Z10b
*
*
* Z11b VAB2
*
Z12b VBC2
*
UN
TV02
Z1a
*
Z1b Ia
A B C
M2 Z2a
*
Z2b Ib
Z3a
*
Z3b Ic
Z4a
*
Z4b IA
Z5a
*
Z5b IB
Z6a
*
Z6b IC
*
*
*
*
*
*
*
*
*
*
*
*
UL
*
*
*
* UN
* Z10a
*
*
* Z11a VAB1
*
Z12a VBC1
*
*
Z7a
*
TV01 Z7b IA1
Z13a *
Z14a VS1
* *
TV1
L1
*
*
QF1 TA1
A B C
M1
105
PMC-851D User Manual
L2
*
*
QF2 TA4 PMC-851D
* *
TV2
Z13b
UL *
*
Z14b VS2
*
Z8a
*
*
* UN Z8b IA2
* Z10b
*
*
* Z11b VAB2
*
Z12b VBC2
*
*
UN
TV02
Z1a
*
Z1b Ia
A B C
M2 Z2a
*
Z2b Ib
Z3a
*
Z3b Ic
Z4a
*
Z4b IA
Z5a
*
Z5b IB
Z6a
*
Z6b IC
*
*
*
*
*
*
*
*
*
*
*
*
UL
*
*
*
* UN
* Z10a
*
*
* Z11a VAB1
*
Z12a VBC1
*
*
Z7a
*
TV01 Z7b IA1
Z13a *
Z14a VS1
* *
TV1
L1
*
*
QF1 TA1
A B C
M1
106
PMC-851D User Manual
PMC-851D
Z1a *
+WC B1
Ia
Z1b RemPS B2
Z2a *
M-Close IN B3
Ib
Z2b Close IN B4
Z3a *
Close OUT B5
Ic
Z3b Supervi B6
Z4a * C-Coil B7
IA
Z4b M-Trip IN B8
Z5a * Trip IN B9
IB
Z5b Trip OUT B10
Z6a * T-Coil B11
IC
Z6b Link IN B12
Z7a * Link OUT B13
IA1
Z7b -WC B14
Z8a *
B15
IA2 KKJ
Z8b B16
*
Z10a B17
VAB1 OUT1
Z11a B18
* VBC1
Z12a B19
* OUT2
Z10b B20
VAB2
Z11b B21
* VBC2 OUT3
Z12b
B22
* B23
Z11b OUT4
VS1
Z12b B24
Z13b * B25
VS2 OUT5
Z14b B26
A1 COM B27
OUT6
B28
A2 IN1
A18
Alarm
A3 IN2 A19
D+
IN3 C1
A4 D- C2
RS-485
SH C3
A5 IN4
GPS+
C5
A6 IN5 GPS-
Time Sync. C6
SH C7
A7 IN6
AO+
A8 IN7 C9
AO Output AO-
C10
A9 IN8
A10 IN9
Ethernet P1
A11 IN10
A12 IN11
Ethernet P2
A13 IN12
107
PMC-851D User Manual
PMC-851D
Z1a * OpePS B1
Ia RemPS B2
Z1b
Z2a * M-Close IN B3
Ib Close IN B4
Z2b
Z3a * Jump B4a
Ic Close OUT B5
Z3b
* M-Trip IN B6
Z4a
IA Trip IN B7
Z4b
* Trip OUT B8
Z5a
IB Link OUT B9
Z5b
* Link IN B10
Z6a
IC C-Coil B11
Z6b
* Supervi B11a
Z7a
IA1 T-Coil B12
Z7b
Z8a * L/+ B13
IA2 N/- B14
Z8b
*
Z10a B15
VAB1 KKJ
Z11a B16
* VBC1
Z12a B17
* OUT1
Z10b B18
VAB2
Z11b B19
Z12b * VBC2 OUT2
B20
* B21
Z11b OUT3
VS1 B22
Z12b
Z13b * B23
OUT4
VS2 B24
Z14b
A1 B25
COM OUT5
B26
A2 IN1
B27
OUT6
A3 IN2 B28
A18
Alarm
A4 IN3 A19
A5 IN4 D+
C1
RS-485 D- C2
A6 IN5 SH C3
A7 IN6 GPS+
C5
Time Sync. GPS- C6
A8 IN7 SH C7
A9 IN8 AO+
C9
AO Output AO-
A10 IN9 C10
A11 IN10
Ethernet P1
A12 IN11
108
PMC-851D User Manual
TBV
R3 JP1
Operation Power Supply+ HBJ TBJ Operation Power Supply-
B01 TBV B14
Relay Close
XB3 Output CHZ
B05 HBJ LC
Relay Close Input TBV QF
B04 B07
SC KKJ BRK Open
M-Close Input R2
3 4 S Monitor
B03 B06
Remote YKH
5 6
B02
YKT
KKJ
M-Trip Input R1
1 2 R
B08
Relay Trip Input
TBJ LT
B09 QF
TBJ
B11
BHT
XB2 Relay Trip
Output
B10
WBH
XB3 Ext. Link Trip
Output
B13 WBH
Ext. Link Trip R4
Input
P B12
Signal Collect
and the user should connect the open status contact of breaker to B6 through –WC directly.
Note 5: When external trip protection is not needed to operate on trip, please open the external trip output
protection strap, then the protection external trip will only send signals without tripping.
6.2.2. AC Operation Circuit
L N
220VAC
QA
TBV
TBV
R1
Operation Power Supply+ HBJ TBJ
B13 B14
Relay Close QF K0
XB3 Output CHZ
HBJ
B05 K0
TBV Close Coil QF QF LC
Relay Close Input
B04 B11
SHJ
BRK Open
Jump Monitor
B04a SHJ B11a
SC B01 R2
M-Close Input
3 4
B03
Remote YKH
5 6
B02 STJ
YKT
M-Trip Input R3
1 2
B06
STJ TBJ
LT
Relay Trip Input QF
B07 B12
TBJ
Trip Coil
BHT
Relay Trip KKJ
XB1 Output
B08 R4
S
KKJ
R5
R
WBH
XB2 Ext. Link Trip RL1
Output
B09
Ext. Link Trip R6
Input
P B10
WBH
RL1 R7
R8
Signal Collect
Note 4: When external trip protection is not needed to operate on trip, please open the external trip output
protection strap, then the protection external trip will only send signals without tripping.
111
PMC-851D User Manual
112 UMPMC851DV15A-1803