MMS 3311/xxx-xxx
Speed- and Key-Transmitter
Application:
The Speed- and Key-Transmitter Application fields of the MMS 3311 The inputs of the transmitter may be
MMS 3311 is part of the revised transmitters are all kinds of rotating operated with all standard types of
MMS 3000 transmitter system for machines, e.g. turbo machines, fans, epro eddy current sensors:
monitoring and protecting any kind of compressors, gear boxes, pumps and
turbo machines. similar, rotating machines. PR 6422/.., PR 6423/..,
The transmitters of the new generation MMS 3000 transmitter are applicable PR 6424/.., PR 6425/..
are characterized by their highly for big systems with programmable
flexible hardware options and their logic controls and host computers as The transmitter mustn't be used in
versatile combination possibilities and used in power stations, refineries and hazardous areas.
can thus optimally be adapted on the chemical plants, as well as for small
demands of the respective plant. plants with only few measuring points
They permit economic measurement and decentralized data processing.
and supervision of speed and
generation of key pulses.
Page 1 of 4
Machine Monitoring Systems
Technical Data:
Sensor inputs: Buffered sensor signal: Power supply:
Two independent inputs for eddy Two signal outputs for analysis and Option for redundant power supply,
current sensors of type diagnosis purposes, one for each decoupled via diodes.
PR 6422/.., PR 6423/.. channel, proportional to the dynamic Nominal:
PR 6424/.. and PR 6425/.. sensor signal. Accessible via +24 V DC
Standard: terminals. Unfiltered voltage output: Permissible voltage range:
2...10 V; error ±2,5 % +18...31,2 V DC
• Int. CON;
“Lemo” connector Power consumption:
Limit value and channel Depending on the built-in options.
Optional: max. 6 W
supervision:
• Ext. CON; The transmitter provides altogether 5 Housing:
“Harting” connector function outputs. Limit values can be Diecast aluminum, non-corroding
Linearity error (excluding sensor): programmed for the speed
0,25% at 25°C measurement. Beyond this, the Protection class:
function outputs can be used to IP 65 according to DIN 40050, IEC 144,
Linearity error (including sensor): CE certified
PR 6422: ≤ ±1,5% at 25°C indicate of operating states e.g. the
PR 6423: ≤ ±1,0% at 25°C Channel Clear state. The function EMC tested:
PR 6424: ≤ ±1,5% at 25°C outputs can be freely assigned by According to EN 55011 and EN 61326
PR 6425: ≤ -6% at 25°C means of the configuration software.
Environmental conditions:
The following options are possible:
Output stability as function of (according to IEC 359, DIN 43745)
temperature: Maximum permissible temperature of
• Without function outputs the mounting surface 65°C.
< 0,08%/10 K
Operating temperature range:
Long-term drift: • 5 x opto-coupler output -20...+65°C
Max. 1% of the measuring range UMAX: 48 V DC
IMAX: 100 mA Mounted on 10 mm spacing bolts:
Measuring range: PMAX: 5 W Maximum permissible temperature of
Freely selectable via the configuration the mounting surface 90°C.
software, max. 65535 rpm • 5 x relay contact (make contact) Operating temperature range:
limited by the input frequency UMAX: 48 V DC -20...+45°C
IMAX: 1 A By all means, heat concentrations
Frequency range: PMAX: 50 W must be avoid by constructive
0...20 kHz, measure.
automatic setting of trigger level • 5 x photomos relay
UMAX: 48 V DC Permissible relative humidity:
Parameter outputs: IMAX: 500 mA 0...95% non- condensing
Standard: PMAX: 25 W
Vibration and shock:
• Two current outputs, proportional to shock: 20 g over 2 ms
the chosen characteristic value and Data interfaces:
Standard: vibration: 5 g at 60 Hz
related to the system ground. Both
outputs can be assigned to channel Mounting direction:
1. • RS 232 interface for configuration of Preferably with the cable glands down‐
Optional: the transmitter and for displaying the wards.
measuring data.
• Two galvanically separated current Dimensions:
outputs, proportional to the chosen Optional: See drawing
characteristic. Both outputs can be
assigned to channel 1. Weight:
• RS 485 bus with epro protocol V2.0 Depending on the chosen hardware
• Without current output options:
Current output ranges: • PROFIBUS DP Net weight: max 1,3 kg
0/4...20 mA or 20...4/0 mA Gross weight: max. 1,5 kg
Maximum burden:
500 Ohm
Open circuit and short-circuit proof.
Page 2 of 4
Machine Monitoring Systems
Dimensions:
127,5 127,50
4 x ∅6
30
106
12,5
91
38
2 x M20
82
SW22
61.5
Verschraubungen ∅10
125,5
2 x M20
17.5
cable inlets
2 x Aufnehmer
Lemokupplung
2 x transducer 60
Lemo socket
∅6
119,00
Wenn die Option externer Konverter gewählt wird, wird das Gehäuse mit seitlichen
Hartingsteckern geliefert. Die dann geltenden Abmessungen können dem Datenblatt des
MMS 3120 entnommen werden.
If the option of an external converter is chosen, the housing is supplied with
Harting connectors on the sides. The dimensions applying in that case can
be found in the data sheet of the MMS 3120
Page 3 of 4
Machine Monitoring Systems
Additional functions:
The transmitter MMS 3311/xxx-xxx When using two speed sensors, it is Dual current mode:
contains the following additional possible to detect the rotational This function splits the output current in
functions, which can be used direction of the machine. The detected two ranges.
depending on the configuration of the direction is indicated via a function Example:
transmitter: output. Measuring range 0...3000 rpm.
Zero speed and rotational direction Redundant modus (speed): One part of this range, e.g. 0...300
detection : This mode requires two speed rpm, is scaled to 0/4...20mA.
If the transmitter does not receive sensors. Both sensors provide their Having exceeded the limit of
pulses within a certain time period, the signal to the transmitter inputs. In case 300rpm, the total measuring range
transmitter recognises this as of an error, the program switches of the transmitter will be scaled to
machine-standstill and indicates it via automatically to the second, redundant 0/4...20mA.
a function output. sensor.
In- / outputs:
MMS 3311/xxx-xxx
Standard
RS 232 Configuration
interface
+24 V/1
Power supply Optional PIN assignment MMS 3000/xxx-xxx
+24 V/2 2 x +24 V Binary outputs OUT 1
redundant Supply:
GND without, or OUT 2
5 x opto-coupler, or 1 UN+ U = 18...24...31,2 V
5 x relay contact, or OUT 3 2 UB+
3 U- LED Assignment:
5 x photomos OUT 4
Channel 1 4 OUT3 1
OUT 5 5 OUT1+
Standard Optional 4 2
PR 6422 - internal converter Current outputs 6 OUT1-
0/4...20 mA 7 OUT2+ 5
- Optional without, or 0/4...20 mA 8 OUT2-
PR 6426 - external converter 2 x standard, or 9 OUT3+ Close JP1 for
2 x galv. separated 10 OUT3- Bus termination:
Optional 11 OUT4+
Channel 2 12 OUT4- 1 Term B.
bus comminication Data 2 Mid. Term.
PR 6422 Standard none, or 13 OUT5+
- internal converter 14 OUT5- 3 Term A
- RS 485, or 15 IOUT1+
Optionen PROFIBUS DP PIN assignment
PR 6426 16 IOUT1 -
- external converter 17 IOUT2 + Bus connector:
Standard Channel 1 18 IOUT1 - 1 L2N (A)
bufferd Channel 2 19 Sens1+ 2 L2P (B)
Reset Latch Binary input sensor signal 20 GND 3 CNTR_P
Open-collector- Key pulse 21 Sens2+ 4 SHIELD
output
Ordering options:
For the Speed- and Key-Transmitter Communication: Function outputs:
MMS 3311/xxx-xxx, the following • RS 232 [Standard]
order options are possible: • 5x opto-coupler [Standard]
Printed in Germany. Due to our continuous research and product improvements, epro reserves the
• RS 485 • 5x relays (make contact)
Sensor inputs C1 und C2: • PROFIBUS DP
Two identical input channels; no mixed • 5x photomos
Parameter output:
applications! Display:
• without
• Internal converter [Standard] • 2x with system ref. [Standard] • without [Standard]
• External converter • 2x galvanically separated • with 8-digit display
Standard types:
MMS 3311/010-000 Internal signal converter, RS 232, without bus-communication, current output 9100-03081
with common ground, no function outputs, without display.
MMS 3311/011-000 Internal signal converter, RS 232, without bus-communication, current output 9100-03080
with common ground, with function outputs (opto-coupler), without display.
right to change these specifications without notice.
Accessories: Configuration kit with configuration software MMS 3910 for MMS 3000 9510-00027
MMS Para Kit transmitter
Warning note:
6010 - 00025 07/08 V1.00
Installation and commissioning of the transmitter may only be made by trained staff.
The manufacturer is not liable for damages which were caused by improper use or
by operation error of not authorized persons.