You are on page 1of 2

Width of beam X direction 500 500 Fy 500

Width of beam Y direction 500 500 Fck 25


Left Right

DATE
PROJECT: CHILIME-TRISHULI 220 kV TRANSMISSION LINE PROJECT
15/11/20
TITLE: 33 KV INDOOR SWITCHGEAR BUILDING SLAB

Design of Two Way Slab Marked S7 4) Two adjacent edges discontinuous


A B
Span along shorter side = 4.120 m 11
lx = 4120 - 500 /2 - 500 /2 + 125
= 3.745 m ly

Span along longer side = 7.400 m


ly = 7400 - 500 /2 - 500 /2 + 115 lx 12
= 7.015 m

ly / lx 7.015 / 3.745
=

= 1.87 < 2 Hence, Two Way Slab


Cl. D-1.1 of IS 456:2000
Depth of Slab
Assume Depth of Slab = 150 mm
Clear Cover = 20 mm
Dia of Reinforcement = 10 main & 10 mm secondery
Effective depths of slab
dx = 150 - 20 - 10 /2 dy = 150 - 20 - 10 - 10/2
= 125 mm in x- & = 115 mm in y- direction
Load on Slab
Density of concrete = 25 kN / m³
Self Weight of Slab = 0.15 x 25
= 3.750 kN / m²
Floor Finish = 1.400 kN / m²
Live Load = 0.75 kN / m²
other loads = 0.000 kN / m²
Total load, w = 3.75+1.4+0.75+0
= 5.900 kN / m²
Edge Condition : 4) Two adjacent edges discontinuous
Mx = ax w l x 2
My = ay w l x 2

ax (-ve) = 0.0874 ay (-ve) = 0.047 From Table 26 of IS:456-2000


ax (+ve) = 0.0660 ay (+ve) = 0.035 From Table 26 of IS:456-2000

w l x2 = 5.9 x 3.745^2
= 82.748 kN
Shorter Span Longer Span
At Midspan
Mx (+ve) = 0.0660 x 82.748 My (+ve) = 0.035 x 82.748
= 5.46 kNm = 2.90 kNm
Mu/bd2 (+ve) = (5.46 x 10^6 x 1.5)/(1000 x 125^2) Mu/bd2 (+ve) = (2.9x10^6x1.5)/(1000x115^2)
= 0.524 (with a load factor of 1.5) = 0.33 (with a load factor of 1.5)
From Table 2 of SP-16 From Table 2 of SP-16
Pt (+ve) = 0.124 Pt (+ve) = 0.077

Ast (+ve) = (0.124/100) x (1000 x 125) Ast (+ve) = (0.077/100) x (1000 x 115)
= 154.5 mm² = 88.38 mm²
Ast Min = 180.0 mm² Ast Min = 180.0 mm²
Hence provide 10 dia bars @ 130 c/c Hence provide 10 dia bars @ 130 c/c
Ast provided = 604.2 mm² Ast provide = 604.2 mm²
At Support
Mx (-ve) = 0.087 x 82.748 Mx (-ve) = 0.047 x 82.748
= 7.24 kNm = 3.89 kNm

Mu/bd2 (-ve) = (7.24 x 10^6 x 1.5)/(1000 x 125^2) Mu/bd2 (-ve) = (3.89x10^6x1.5)/(1000x115^2)


= 0.70 (with a load factor of 1.5) = 0.44 (with a load factor of 1.5)

From Table 3 of SP-16 From Table 3 of SP-16


Pt (-ve) = 0.165 Pt (-ve) = 0.104

Ast (-ve) = (0.165/100) x (1000 x 125) Ast (-ve) = (0.104/100) x (1000 x 115)
= 206.66 mm² = 119.17 mm²
Ast Min = 180.0 mm² Ast Min = 180.0 mm²
Hence provide 10 dia bars @ 130 c/c Hence provide 10 dia bars @ 130 c/c

Ast provided = 604.2 mm² Ast provide = 604.2 mm²

Check for Deflection


Actual lx / d = 3.745 / 0.125
= 29.96
Pt provided = (604.15 x 100)/(1000 x 125)
= 0.48 %
Steel Stress of service loads fs = 0.58 x fy x Ast req
Ast prov Fig. 4 - IS 456 : 2000
= 74.17 N/mm2

For continuous edges lx/d = 26 Clause 23.2.1 (a):IS 456

Modification factor = 2.00 Fig. 4 - IS 456 : 2000

lx/d = 2 x 26 Clause 23.2.1 (c):IS 456


= 52.00
Actual lx/d = 29.96 < 52.0
Hence safe