Professional Documents
Culture Documents
DATE
PROJECT: CHILIME-TRISHULI 220 kV TRANSMISSION LINE PROJECT
15/11/20
TITLE: 33 KV INDOOR SWITCHGEAR BUILDING SLAB
ly / lx 7.015 / 3.745
=
w l x2 = 5.9 x 3.745^2
= 82.748 kN
Shorter Span Longer Span
At Midspan
Mx (+ve) = 0.0660 x 82.748 My (+ve) = 0.035 x 82.748
= 5.46 kNm = 2.90 kNm
Mu/bd2 (+ve) = (5.46 x 10^6 x 1.5)/(1000 x 125^2) Mu/bd2 (+ve) = (2.9x10^6x1.5)/(1000x115^2)
= 0.524 (with a load factor of 1.5) = 0.33 (with a load factor of 1.5)
From Table 2 of SP-16 From Table 2 of SP-16
Pt (+ve) = 0.124 Pt (+ve) = 0.077
Ast (+ve) = (0.124/100) x (1000 x 125) Ast (+ve) = (0.077/100) x (1000 x 115)
= 154.5 mm² = 88.38 mm²
Ast Min = 180.0 mm² Ast Min = 180.0 mm²
Hence provide 10 dia bars @ 130 c/c Hence provide 10 dia bars @ 130 c/c
Ast provided = 604.2 mm² Ast provide = 604.2 mm²
At Support
Mx (-ve) = 0.087 x 82.748 Mx (-ve) = 0.047 x 82.748
= 7.24 kNm = 3.89 kNm
Ast (-ve) = (0.165/100) x (1000 x 125) Ast (-ve) = (0.104/100) x (1000 x 115)
= 206.66 mm² = 119.17 mm²
Ast Min = 180.0 mm² Ast Min = 180.0 mm²
Hence provide 10 dia bars @ 130 c/c Hence provide 10 dia bars @ 130 c/c