Today's Discussion “ey
+ IEC 60909 Short circuit Analysis <\es
an . ‘i
Short Circuit Current Calculation “ey or]
» All electrical installations must be eet sein circuits
ionywhi
.
every time there is an electrical conngcti merally when
there is a change in conductor cross-s!
+ The short-circuit current valueymust be calculated at every stage of
installation for different my et worl (0) igurations.
* This is done to ee charac} ics of the equipment that
must withstand or set e fault ent.
+ In order to choose fs Soooosiehgevitching devices (cireuit-
breakers or a . set. the tection functions, four short-circuit
values _ wn: NY
The root meamsqua: wa}ue of the maximum short-circuit
current (ommetriegh iree-phase short-circuit)
+ The breaking capacity of the cireuit-breakers and fuses;
» The ‘empegene stress that the equipment must withstand.
irae ene Ses uoNV On eR CONgots
an . ‘i
Short Circuit Current Calculation “ey 7
‘The peak value of the maximum short-cir Sit cara ic of the
first peak of the transient period)
» The making capacity of the circuit-breakets and ies;
+ The electrodynamic withstand ofry wie
The minimum phase-to-phaselshort-circyit-eurrent
This must be known in orderjoxhoose t]
ping curve of the circuit-
breakers or fuses or set thé threshold
overcurrent protection
devices, especially me),
+ The cables are leg hen thApurce has a relatively high internal
impedance (9g. apbrator
+ Protection sien “ee pliaes overcurrent protective devices:
operating. This is egsdhttetly the case in low voltage network:
+ The network eae of protection selectivity.
The value of the phase-to-earth short-circuit current: It mainly
depends on thevearthing system and determines the setting of earth fault
irae ene Ses uoNV On eR CONShort Circuit Current Calculation “ey
a 3 ?p
=
mee
IEC 60365-1 TEC 60865-1
+ Switch-on capability «Protection measures
TEC 60265-1 touch voltages in L\-nstall
DIvoeoimaT
' cesenieps
Peak short-circuit current
(Maximal instantaneous value) 4 & a Feit
at stching inst fy)
ay
Further aspects
+ Touch and sep voltages
DIN VDE 0141
+ Imerference
DIN VDE 0228
«+ Surge arresiers
TEC 60099-4
+ Overvoltages
IEC 60071-1
EC 60071-2
«+ Neutral point earthing
DIN VDE 0141
Inslation e0-ordination
IEC 60071-1
TEC 60071-2
+ Surge aresters
TEC 600994ett
es
Short Circuit Current Calculation ‘Cr JZ
Attention shall be put on four parameters of nent cir rent:
+ ‘The total time duration of the sho ia of the
operating time of the protection nore) id the to’ eaking time of
the switchgear.
value of the short-circuit cur occurs
after the initiation of the s
proportional to the ins
circuit current is necedé
conductors and con:
The peak short-circuit aan is fhomaximal instantaneous
The r.m.s.-valuy ‘it current is decaying in this example
due to the deca: io: cataGpent, Currents through conductors will
heat the co himic losses. The r.m.s. value of the short-
circuit currentYcombi h the total time duration, is a measure for
the thermal eftects Short-circuit.
‘The short-circuit bréaking current is the r.m.s.-value of the short-
cireuit current at switching instant, i.e., at time of operating the cireuit-
breaker. WI ening the contacts of the circuit-breaker, the arc inside
the breakextrill heat up the installation, which depends obviously on
the bri ime as well.
irae eneShort Circuit Current Calculation
Regan Noe
feat cant voEO cima ano age malay
omy eT) Fan ‘poner fond
(095806) ey
auaa evar no — ity
a
om town) ania
Fenda Moretis
oi ey
‘ntoncpesed
ea) (Cprmitcwa toi
9 aan 3 Applicaton gudeforcacuance
ten SFocmettorcernrtn,
rr ‘Shon caerts Clon
to asst) orem
= = agents Stance Canon ot
NDEs
(0356-06) Pat Deion and alton etods
Enmple reece
Garen0— YDEOIO? —_Shiciniecunert cation
fiouy oot) eT) ee pte
Dr. M. RazaShort Circuit Current Calculation “ey
Table 1.1
Continued
TEC (year) EN(year) DIN; VDE (year)
60909-2 - oo 4 ical equipment
(1992) E 0102 for short-circuit current calculations
@ ce in accordance with IEC 909 (1998)
60909-3 vor dh 0" eo ‘current calculation in
wy QD an trope jee
Part 3: Currents during two separate
simultancous single-phase line-to-carth
short-cireuits and partial short-circuit
currents flowing through earth
60909-4 -—e Appendix 1 Examples for the calculation
(2000) VDE 0102 of short-circuit currents
(1992-09)
Dr. M. Raza"e,
Short Circuit Definitions a to ange No
Short circuit current (j,): The current tht\flows at More circuit
point for the duration of the short ci
AC short circuit current (i_): im frequency co Qe ont of the
short circuit current
Initial AC short circuit cur @, Or ue of the AC
component of current at ti tI set “ Ronen circuit.
Maximum asymmetri€al voren ee (I): The highest
possible instantang@ys dus value current following the occurrence
a peak value.
of the short ci ene is quot
Continuou: circuit ent (UJ: RMS value of the AC short
circuit currel shor the ly state.
Asymmetrical breakipg current (I,):
Symmetrical break current (I,): RMS value of the AC short circuit.
current foxgete a circuit breaker at the instant of the first contact
irae enefootw
‘
Short Circuit Definitions According to Shinde 7
Initial voltage (E”) [sub-transient volta: ARMS ve va Vine
effective voltage of a pugemen magi t of
initiation of a short circuit.
Nominal operating voltage UOnyPated ae line Voltage.
Initial AC short circuit pow 3k”): ‘of the initial AC short
circuit current (I,,”) with jominal ‘m voltage and the factor
ue x)
Minimum breaking delay (t,):, shortest possible time delay from
the initiation of ort cir 0 the first opening of the contact of
a circuit brgakdr pole. esse ‘sum of the minimum possible
response Uinle t the cles d the inherent delay of the circuit
breaker.
Positive sequence Se (Z,): Positive sequence impedance of a
three phase system seen from the short circuit point.
. °.. . .
Negative seGiuetice impedance (Z,): Negative sequence impedance of
a thr system seen from the short circuit point.
irae eneVe
Factors Effecting the Short Circuit Cumeny “ey 7
+ Zero sequence impedance (Z,): Zero sequeiice no Tra three
phase system seen from the short os
+ Short circuit in electrical systems bring about Q~ ges in the
operating levels. The transitioi the newcondition is associated
with electromagnetic and el Eeielwanian processes, on
which depend the magniti d tim Ation of the short circuit
current.
» The transient proce: Xsare infh ‘d also by the instant at which
the short circuit oceuys, the ayail le short circuit current sources,
the initial loadi ‘Onditions, location of the short circuit, its
duration, the stfuture oNhesystem, and the characteristics of
equipment inyalved.
* Short circuit cane ces are principally the synchronous
generator, asynchronéus generators and motors, motor converters
operating in inverter mode.
irae ene Ses uoNV On eR CONMethod of Calculation
Short-circuit current calculation accordin E Soe) og a
out based on the method of ‘equivalen: e short-
circuit location’,
®)Method of Calculation
‘The method is based on the presuppositions as‘ below: | v
6% sequence
Symmetrical short-circuits are represtefis} by thi
component;
Capacitances and parallel admitpgnces of notsrotating load of the
positive- (and negative-) or mponel neglected.
Capacitances and parallel admifiances,of fhe zero-sequence component
shalll be neglected, exce| stems with isolated neutral or wit
resonance earthing (sactop ‘vith Be’apyen coil) ae they have an
influence on fault ¢ in po
Impedance of th ( the shéybxircuit location is neglected.
The type of yor¥-circuit. gpiyRe system topology remain unchanged
shorpeireuit.
during the duation o
‘The tap-changers of QW Yansformers are assumed to be in main-position
(middle position).
All internal voltages of system feeders, generators and motors are short-
circuited and an equivalent voltage source with value cUn/\3 is
introduced
e a
he short circuit location. The voltage factor ¢ shall be
cordance with Table.
irae ene Ses uoNV On eR CONMethod of Calculation
Nominal system voltage Uj,
@ a. Minimal
vy s-c.cturént ——_s.-c. current
oO a
LV: 100 V up to 1000 0S d eS
(IEC 60038, meg
Voltage tolergne % 1.05 0.95
Voltage tolera HE 1.10 0.95
MV: >1 kV up to 35 a, fusive) 1.10 1.00
(IEC 60038, Table III)
HV: >35 kV (IEC 60038, Table IV) 1.10 1.00fe
. 4
Method of Calculation You 7
Depending on the task, the maximal or rae short; abt current
“cl
0
has to be calculated. The maximal sho,
design criteria for the rating of equipm‘ ‘it!
short-circuit currents. For the calculatior of maxit short-circuit
current, the items shall be ome, as belaw:
+ For the equivalent voltage at the Loeineut location the
voltage factor cmax as ee fe shall Yepsed.
* Short-circuit imped. ofsystem rs shall be minimal
(ZQmin), so that the eeptributiop othe short-circuit current is
maximal. o
* The contributi mot CO be assessed and eventually be
taken into on
+ Resistance of nse calculated for a temperature of 20°C.
* Operation of power pants and system feeders shall be in such a way
that the contribution to short-circuit currents will be maximal.
+ System topglogy leading to the maximal short-circuit currents shall
be takenintyaccount.
cy
irae ene Ses uoNV On eR CON(i
Initial symmetrical short-circuit current ne “ey .
wee.
> The initial symmetrical short-circuit o t a is tea for
balanced short-circuits based on the gquiv. source at the
short-circuit location and the short-citguit i ‘mpé seen from the
short-circuit location, which has to be “ ‘with the system of
symmetrical components.
irae enePeak short-circuit current ip
» Depending on the feeding source of the pois 42
considerations have to be taken to the, Agsore circuit
current.
* The peak short-circuit current, ich is a: 7 value, can be
calculated for the different, te if short- Gapuite based on the
initial short-circuit curre 8. Ka
ip3 = K ® v2. 2N3 =
c= 1m sogiCrinnng® & TS
Or
we
YLae
soleate a
Calculation of factor k Ae JZ
» Uniform (smallest) ratio R/X. The factoy x ) a ha based on
the smallest ratio R/X of all ke
* Only those branches need to be taken into accou! ee contribute
to the short-circuit current in t] ower sygtem corresponding to the
short-circuit location, respectt
transformers to the moa ign The results are always on
the safe-side, however tl
+ Ratio RX at short-ixduit lo . Based on the ratio R/X of the
total system impedance at tras -circuit location, the factor K is
calculated ie ecount of of a SGitety factor of 1.15 to allow for
deviations fe Rs ratios R/X in the different branches.
a =1.15%*«
* The factor 1.15 $x should not exceed the value of 1.8 in LV-systems
and shall exceed 2.0 in HV-systems. The safety factor 1.15 is
neglected.whén R/X < 0.3
irae eneCalculation of factor k
if
+ Equivalent frequency fe. The factor x = ace based on the
ratio R/X:
ie
o@i*y io
» Re and Xc are the scien tance and reactance at
the short-cireuit het equivalegddrequency fe which is
fe = 20 Hz (aomifal powdp system frequency 50 Hz)
fe = 24 Seen al poke system frequency 60 Hz)
» The caleulatiap ‘of the ads lent impedance at equivalent frequency
fe is to be carfied out Sey to the calculation of impedance at.
nominal power systemh frequency
irae enefoe
. . (ay
Accuracy of k factor calculation A “ey 7
Results obtained by the method of unift (small: 8 tatho R/X are
always on the safe side, if all brancl nbributi he short-
circuit current are taken into accounts
Errors can reach in rare cases Rye 100 cent. If only those
branches are considered, whi ntribu to 80 per cent to the
short-circuit current, and ay
tthe ratte RE are ipa wll ean results can even be on the
unsafe side. The mi Red/thereh 11 be applied only if the ratios
R/X are in a small bandwidth, If R/X < 0.3.
The metho raiGRIX eee arcu location (safety factor 1.15)
will lead to’ ‘Its on t] ‘e and unsafe side. Applying the method
to ratios 0.003 s R/X the error will be in the range +10 to -5
per cent.
‘The method of equivalent frequency has an accuracy of +5 per cent,
if the ratio R/X @f each branch is in the range of 0.005 < R/X < 5.0.
irae eneQ
Decaying (aperiodic) component ide “ey
0.25 S
~
irae eneSymmetrical short-circuit breaking current I
SOY
: 19
‘Minimum OD
09
06 s 0.258
irae ene®
Symmetrical short-circuit breaking current Hey 7
» where Ik’G is the initial symmetrical s| circuit gurrant of the
generator, IrG is the rated current ener tmin is the
minimal time delay of the protection, auxiliaries,
that is, minimal time for switching the short-circvfit current off.
+ The factor p is valid for high, Keo sync jous generators,
excited by rotating machi rectifi the excitation system is
not known the factor shi set to re
+ In the case of far-fr erato; -circuits, the symmetrical
short-circuit breaking current 46 equal to the initial short-circuit
current Ik” as th ac. Rey is not decaying.
irae ene Ses uoNV On eR CONgt
Steady-state short-circuit current Ik “ey 7
» The steady-state short-circuit current dk eee cast A far-to-
generator short-circuits depends pay eee has
saturation effects, power factor of ge zotyphtors, mag of system
topology due to operation of srs etc, and ca therefore only be
determined with a certain ina
+ The method as per IEC 60909,determipps lower and upper limits
only when one synchronaudaiiachin: ig €eeding the short circuit.
* The calculation is b; mn the tor-rated current assuming a
factor \ which ‘eng on thi of initial symmetrical short-
circuit current ed currel the generator and on the
saturated sync ous reretam:
maximal symmetr‘ ort-circuit breaking current
* Maximal exeitati gerne machine leads to the
Tigmax = Amax * 1:6
irae ene Ses uoNV On eR CONSteady-state short-circuit current Ik
‘The minimal symmetrical short-circuit brgaking cu EVs
calculated for constant no-load excitapion ofthe tor with the
factor Amin.
Tk min ics * Bo
IrG: Rated current oe Bre
1k’G: Initial syne 4 short Got os current of the generator
Xdsat: Saturat O. wGSactance of the generator, equal to
the reciprogal ofthe shortcirtuit ratio of the generator
In the case of far-fro erator short-circuits, the symmetrical
short-circuit breaking current Ib is equal to the initial short-circuit
current Ik” as the a.c. component is not decaying.
irae enefe
. . bs}
Steady-state short-circuit current Ik “ey
A wee.
(a) 28
26.
24:
a2:
20.
13;
16:
—>
412.
104
08.
06.
04:
02:
irae ene
(b) or
144
phase short circuit JigiMig >
Qe:
x Te Tos
: = 24 6
Javax [18
22 S70
20 a 22.
y
2.0| &
22 i
4 — ttt ft
ay" 12-4
I i
i 10
i in ool tf | =
1 1 Pt
|_t |
ie Sir
I 0277
7 0
01g 3745678 12345678
Three-phase short circuit [hg lug >
SUB aCOn NOTH UCONNi
mat
Influence of motors Al 7
» Asynchronous motors and synchronous métors hav. V2 taken into
account in MV-systems and in auxiligry supply s of power
plants and industrial networks for the leulai maximal short-
circuit currents.
* They contribute to the initial etricat Ae rt-circuit current, to
the peak short-circuit curre’ ‘0 the s; ypypetrical short-circuit
breaking current.
+ Synchronous motors Xxe/modellgdhvs generators and asynchronous
generators are credteg as asy) ous motors.
» Motors fed by Cie restire Seed to be considered in the case of
three-phasé reine ly, if they are able to transfer energy
for deceleratidn for = ‘ation of the short-circuit, as they
contribute to the ii ‘symmetrical and to the peak short-circuit
current.
irae ene Ses uoNV On eR CONInfluence of motors “ey
Wi en Be Ne EK Ce = 7
‘rcuit ee
cures
Peak ipa = euVEER tone Oe ip = eM 2MCing
short-cireuit
ata
eee - ‘active power per pole-pair <1 MW
CaS 0Aoffor active power per pole-pair =1 MW
rotors ms Aen ‘cables
=13 = 0.42)
Symmetrical gy 4 Team Elio fom ® Nang
short-circuit
freaking 4.10, q as per Figure 4.13
current
Steady-state 7 1A
fom = Fiiby —im ~Kine
Pye®
Soa
Asynchronous motors in public supply on are co ax. when
* the sum of the rated currents is greaterthan veg of the initial
symmetrical short-circuit current i out motor:
Influence of motors
* the contribution to the initia! Coinetric wt-circuit current with
motors is greater or equal to per conv: initial symmetrical
short-cireuit current withOys tnotors
OS
irae eneMinimal short-circuit currents
TEES
ral
In order to calculate the minimal pas current, tHe voltage
3
factor emin according to the Table uivi tage source
at the short-circuit location has to be epnsider thermore,
System topology, generator dis} h and short-circuit power of
feeding networks have to etapa d in su way that the minimal
short-circuit current is ay “ey
Motors are to be neal &
Resistances of oveyfiead lines cables shall be calculated with the
maximal permigajbte-temperéftire at the end of the short-circuit,
e.g., 80°C es ltage sig .
irae enefoe
ox
4
aa es
Calculatio gs nite and System
meeefe
oO
Soo!
Oe 3
eal
xy
Tanke a time
4"