You are on page 1of 5

Electrical Maintenance (Rev 1/95)

CYCLE-SENTRY CHECK Electric Operation


Refer to the Cycle-Sentry V Operation and Diagnosis The defrost cycle on electric standby operation is
Manual for all operation and diagnosis procedures. similar to defrost on diesel operation. A heater
contactor, high temperature cutout switch and elec-
DEFROST SYSTEM tric heater strips are added for increased defrosting
capability. The electric heaters are energized along
CAUTION: C ycle•Sentry Equipped Units — Place the with the defrost relay, pilot solenoid, damper sole-
C ycle-Sentry switch in the CONTINUOUS position noids, and defrost light. The high temperature cutout
before performing any dtogtto5is and service operations switch must be closed to energize the heater
on the unit. The unit may start at any time without contactor.
prior warning if the On-Off switch is in the ON posi-
tion and the C ycle•Sentry switch is in the C'YCLE posi• Defrost Cycle Checkout Procedure
tion. CAUTION: Cycle-Sentry Equipped Units—Place the
The unit should be run through a defrost cycle C ycle-Sentry switch in the CONTINUOUS position be-
during Unit Pre-Load Operation and scheduled main- fore performing any diagnosis and service operations
tenance inspections to test defrost system compo- on the unit. The xnit may start at any time without
nents. To check the defrost cycle, run the unit on prior warning if the On-Off switch is in the ON posi-
cool and set the thermostat to drop the evaporator tion and the C ycle-Sentry SWitth is in the CYCLE posi-
coil temperature below 42.0 F (5.6 C). Press the tion.
manual defrost switch. The unit should shift from To check the defrost cycle, run the unit on cool until
the cool cycle to the defrost cycle. the evaporator coil temperature is below 42.0 F (5.6
If the unit continues to cool, double check the evap- C). Push the Manual Defrost switch.
orator coil temperature and refer to the defrost cycle If the unit shifts to defrost momentarily but shifts
checkout section. out of defrost when the switch is released, check the
The air switch setting should be checked annually. TG-V thermostat, and the 11 and 12 wires to the
Refer to the Air Switch Testing and Adjustment in TG-V.
the Electrical Maintenance section. If the unit will not shift to defrost, or if the defrost
cycle will not terminate, see the following defrost
Defrost Cycle Engine Operation checkout procedures.
The defrost cycle can be initiated by pressing the CAUTION: Do not forget to remove the jumper wires
Manual Defrost switch, by the air switch, or by the from the unit after checking or testing unit compo•
defrost timer in the TG-V when the defrost termina- nents.
tion switch is closed.
The initiation of the defrost cycle energizes the de- Unit Ooes Not defrost
frost relay, the pilot solenoid, damper solenoids, and 1. Check the evaporator temperature:
tan defrost indicator light. Make sure the evaporator temperature is actu—
The pilot solenoid causes the three-way valve to shift ally below 42.0 F (5.6 C) if the unit will not de-
and divert heated refrigerant vapor to the evaporator frost. Use a test thermometer to check the
coil, melting frost. The damper solenoids close the evaporator temperature.
damper in the discharge opening of the evaporator 2 Check the operation of the defrost termination
housing to hold the heat within the evaporator and switch:
prevent warm air from passing over the load.
If the unit fails to defrost, place a jumper wire
NOTE: The unit will not defrost during normal xnit between the 12 terminal and the CH terminal
operation unless the defrost c ycle is initiated while the on the switch panel circuit board. Press the
evaporator temperature is below 42.0 F (S.6 C). Manual Defrost switch. If the unit shifts to de-
frost, check the 12 wire to the defrost termina-
The defrost termination switch will open and de- tion switch for an open circuit and check for a
energize the defrost relay when the frost has melted defective defrost termination switch.
and the evaporator temperature rises above 52.0 F
(11. I C). This de-energizes the pilot solenoid and the If the unit still fails to defrost, move to step 3.
damper solenoids, and returns control of the three- Check the Manual Defrost switch:
way valve to the TG-V.
If the unit failed to defrost, place a jumper wire
between the 11 terminal and the CH terminal
on the switch panel circuit board. II the unit
shifts to defrost inn mediately, replace the Man-
ual Defrost switch. If the unit does not shift to
Defrost, move to step 4.

72
4. Check the defrost jumper: 5. Check the defrost fuse:
If the unit still fails to defrost, check to make If the unit still fails to defrost, check to make
sure that the defrost jumper is in place and is sure that the defrost fuse is in place and is not
positioned correctly. The defrost jumper blown. The defrost fuse is located near the
should connect the 1 slot (11 circuit) to the 2 defrost relay on the switch panel circuit board.
slot (1 lA circuit) on the defrost timer socket. The unit uses a 15 amp defrost fuse. The unit
The defrost timer socket is located on the will not defrost if this fuse is blown.
switch panel circuit board. If the unit does not shift to defrost with the
If the unit does not shift to defrost with the correct defrost fuse in place, move to step 6.
defrost jumper in place, move to step 5. 6. Check the defrost relay:
NOTE: The TG-V has an integral defro.st tim- If the unit fails to defrost, check the 8 termi-
er. The plug-in defrost timer cannot be used nal (8V terminal on the Cycle-Sentry switch
with the TG-V. The defrost jumper must be in panel) on the switch panel circuit board for 12
place and positioned correctly or the unit will volts dc. If the 8 or 8V terminal has 12 volts,
not defrost properly. the defrost relay is defective and should be re-
placed. A lack of voltage indicates an open
circuit in the 8 or 8V circuit.

Defrost Relay Defrost Jumper


(P/N 44-9017)

Defrost Fuse

Circuit Board
Defrost Timer Socket

Terminal Strip
Circuit Breaker

Component Location-Switch Panel Without Cycle-Sentry

73
Electrical Maintenance (Rev 1/95)

7. If the defrost relay energizes, the defrost in- there will be a rise in suction pressure and a
dicator light comes on and the damper closes, drop in the discharge pressure. If the unit
but the unit continues to cool; check for a does not go into heat, refer to the procedure
stuck three-way valve, faulty pilot solenoid or described in TK 5984, Diagnosing the Thermo
open circuit in the 26 wire. King Refrigeration System.
To test the coil on the pilot solenoid valve,
turn the unit On-Off switch ON. Place a Unit Will Not Terminate Defrost
jumper wire with an ammeter in the circuit If the defrost termination switch does not terminate
between the 26 terminal and the 8 terminal on defrost less .than 45 minutes after it was initiated,
the switch panel circuit board. The pilot sole- the TG-V should terminate defrost, automatically.
noid should energize and the heat indicator
light should come on. If the unit does not The Standard TG-V (P/N 45-1450) and the
shift to heat, the pilot solenoid is not being Enhanced TG-V (P/N 45-1486) will record alarm
energized. Check the 26 wire for an open cir- code 14 to indicate that the defrost termination
cuit or replace the solenoid coil. If the sole- switch did not open, or that the 12 circuit is
noid is energized and the current draw is grounded.
greater than 1 ampere, there is a short in the The TG-V with Revision 4 Software (P/N 45-1579)
26 wire or the coil of the valve. will not record alarm code 14 unless the 11 circuit
To check the three-way valve, run the unit in stays grounded and the defrost termination on time
heat by setting the thermostat well above the limit is unsuccessful.
box temperature. If the unit goes into heat,

Defrost Relay Buzzer

- Circuit Board
Battery _

• @ ----•“ Terminal Strip

“---'
= — Defrost Fuse

Defrost Jumper "” Circuit Breaker


(P/N 44-9017) x

” Cycle-Sentry
Defrost Module
Timer Socket „

Terminal
Strip

Component Location—Switch Panel With Cycle-Sentry

74
Electrical Maintenance (Rev 1/95)

Unit Sticks On Defrost Indefinitely To check the refrigerant charge, refer to Refrig-
erant Charge in the Refrigeration Maintenance
If the unit remains stuck in defrost indefinitely, check
the defrost relay, the 11 circuit and the TG-V ther- section.
mostat. Failure of a damper solenoid may also delay or
NOTE: If the TG-V with Revision 4 Software {PIN 4S• prevent the evaporator coil temperature from
1579) itns recorded alarm code l4, check the II circuit rising. To test the damper operation, turn the
for a ground first. unit switch on. Make sure the unit is not in
defrost, and momentarily place a jumper
1. Check the defrost relay: between the 8 and 29 terminals on the switch
If the unit remains in defrost indefinitely, re- panel circuit board. The damper solenoids
move the defrost jumper from the defrost timer should both energize, and the damper should
socket. The relay should open (de-energize) im- close.
mediately. If the relay opens (de-energizes), 2. Check the operation of the defrost termination
move to step 2. If the relay fails to open, re- switch.
place the defrost relay.
If the unit will not come out of defrost, discon-
2. Check the 11 circuit for a ground: nect the 12 wire from the defrost termination
If the defrost relay opened (de-energized) when switch. If the unit shifts back to cool, the
the defrost jumper was removed, use an ohm- defrost termination switch is not opening and
meter to check the 11 wires for a ground. Re- should be replaced. If the unit remains in de-
pair the grounded wire. If no ground is found, frost, move to step 3.
move to step 3. 3. Check the 12 circuit for a ground:
3. Check the TG-V thermostat: If the unit remains in defrost, use an ohmmeter
The integral defrost timer in the TG-V thermo- to check the 12 circuit for a ground. If the 12
stat should terminate the defrost cycle after 45 circuit is grounded, find the grounded portion
minutes regardless of the evaporator tempera- and repair it.
ture or amount of frost or ice on the evaporator
coil. If not, test the TG-V and replace it if nec- TG-V Defrost Timer Bypass
essary.
If the integral defrost timer in the TG-V thermostat
fails, it can be bypassed temporarily using the follow-
Unit Continually Fails to Terminate Defrost ing procedure. However, the defective TG-V ther-
In Less than 45 Minutes mostat must be replaced as soon as possible.
NOTE: The Standard TG•V {PIN 4S•l450) and the 1. Open the control box cover to access the com-
Enhanced TG-V {P/N 45-1486) will record alarm code ponents inside the control box.
14 if defrost is termiNated on fne time limit. Alarm 2. Disconnect the 11 wire from the 11 terminal on
code 14 will not otcur on the TG•V with Revision 4 the back of the thermostat and tape off the 11
Software {PIN 45-1579) unless the II circxit stays wire.
grounded and the defrost termination on time limit is 3. Disconnect the 12 wire from the 12 terminal on
unsuccessful. the back of the thermostat and tape off the 12
If the unit continually fails to complete the defrost wire.
cycle in less than 45 minutes and cycles between cool 4. Place a jumper between the defrost jumper (P/N
and defrost, check the evaporator coil temperature, 44-9017) and the 3 slot in the defrost timer
three-way valve condenser seal, refrigerant charge, socket.
damper solenoids, defrost termination switch and the
12 circuit. NOTE: If a three pin TG•IV defrost jumper {P/N
44-7522) is available:
1. Check the Evaporator Temperature:
a. Remove the two pin TG-V defrost jumper (PIN
Make sure the evaporator temperature is actu- 44-9017) from the 1 and 2 slots in the de rOSt
ally above 52.0 F (11. 1 C) if the unit will not timer socket.
terminate defrost. Use a test thermometer to
check the temperature. If the evaporator tem- b. Insert the three pin TG-IV defrost jumper (P/N
perature does not rise enough to bring the unit 44-7522) into the 1, 2, and 3 slots in the de•
out of defrost. the condenser seal in the three- frost timer Socket.
way valve may be leaking. or the unit may be 5. Close the control box cover.
low on refrigerant.
After the defective TG-V thermostat is replaced.
To check the condenser seal in the three-way make sure:
valve or the condenser check valve, refer to the
procedures described in TK 5954. Diagnosing 1. That the two pin defrost jumper (P/N 44-9017)
the Thermo King Refrigeration System. is the only jumper in the defrost timer socket.

75
Electrical Maintenance (Rev 1/95)

2. That the two pin defrost jumper (P/N 44-9017) Defrost Termination Switch Bench Test
is inserted into the 1 and 2 slots in the defrost 1. Connect a test light between the screw terminal
timer socket. on the switch and the positive battery terminal.
Manual Defrost Switch NOTE: Anempting to test the elettronic defrost
The manual defrost switch is located on the unit termination switch with an ohmmeter is generally
switch panel. Pressing a manual defrost switch initi- not satisfattory because of the low voltage avail-
ates the defrost cycle if the defrost termination switch able at the meter leads.
is closed. 2. Connect the negative lead of the switch to the
negative battery terminal.
Defrost Termination Switch 3 Raise the temperature of the defrost termination
The electronic defrost termination switch uses solid switch above 52.0 F (11.1 C). The light should
state components to control the defrost circuit. The be off indicating an open switch.
switch is mounted in the evaporator and controls the 4. Cool the defrost termination switch below 42.0
defrost cycle in response to the evaporator coil tem- F (5.6 C). The light should come on indicating
perature. The switch is closed when the evaporator the switch has closed.
coil temperature is below 42.0 F (5.6 C), completing
the defrost circuit to ground and preparing the elec- NOTE: A flow adequate time for the temperature
trical system to the defrost cycle. change to saturate the switch before performing
When the unit does shift into a defrost cycle, the the test.
defrost damper blade closes, and heat from the hot
refrigerant gas melts the frost from the evaporator Defrost Relay
coil. The switch opens and terminates the defrost
cycle when the evaporator coil temperature rises to A defrost relay controls the operation of the unit on
52.0 F (11.1 C). the defrost cycle. When the air switch, the TG-V de-
frost timer, or the manual defrost switch complete
the circuit through the defrost termination switch to
ground, the defrost relay pulls in to initiate defrost
and energize the defrost light. A holding circuit in
the TG-V keeps the unit on defrost until the defrost
termination switch opens.

Pilot Solenoid
The pilot solenoid is an electrical valve that controls
the operation of the three-way valve in the refrigera-
tion system. When the pilot solenoid is energized, it
opens and allows refrigerant pressure to shift the
three-way valve, placing the unit on heat or defrost.

Air Switch
The air switch automatically places the unit on de-
Defrost Termination Switch frost when ice accumulation on the evaporator coil
builds up to a point where the air flow across the coil
is restricted.
Installation Restricted air flow results in a pressure difference be-
tween the evaporator coil inlet and outlet. The air
The proper polarity must be observed when installing switch senses the pressure differential across the coil
the defrost termination switch. The wire from the and initiates the defrost cycle.
defrost thermostat is negative and must be attached
to the chassis ground of the unit. This chassis ground The air switch is preset at the factory. Normally re-
wire must be grounded on a screw separate from the adjustment is not necessary unless the switch has been
switch mounting screws or an improper ground may tampered with or does not function properly due to
result. The 12 wire from the unit attaches to the ter- factors affecting air circulation, such as bulkhead con-
minal mounted solidly on the switch. If the polarity struction and duct work.
is reversed on the device, it will conduct continuously
and act like a switch that is stuck closed.

76

You might also like