You are on page 1of 1

Draft Version, P+F

NON HAZARDOUS AREA

DCS PANEL / Control Room

DCI - Tx - d -ER/LPR - A/H DC Supply 15Watt


DCIA-05
KFD2-STC5-Ex2 85-264VAC
24VDC 50/60 Hz
1 0.6A
+24V + 4 +
2 -
GND -
5
DATA(4-20mA)

24 to GND 24 to Data
4-20mA+HART
3
14
+
Connect This
if DCIA-06
15 - not present
Po : 0.6 Watt
Pi : 0.8 Watt
x
CORROSION RATE
8
0.254 Ii : 35 mA Io : 24 mA
4-20mA
7
Ui : 24 VDC Uo : 24 VDC
CH Input

250 ohm
Ci : 4.7nF Ci : 4.7nF
Li : 0 uH Lo : 0 uH
COM
0.254

Corrosion Meter Analog Input Module


PLC/ Receiver
DCIA-06

Probe
Po : 50 mW
Io : 10 mA
Uo : 5 VDC
Co : 2.7nF Ground of transmitter must be connected to 2&5 terminal of P+F
cable 10m Lo : 0 uH

: vendor Scope

You might also like