Optimizing Energy Efficiency With VRV Heat Recovery Hot Water System For Hotel Application - T SJ
Optimizing Energy Efficiency With VRV Heat Recovery Hot Water System For Hotel Application - T SJ
• There are various systems or methods to generate hot water for hotel
but today we will only discuss for 3 systems:
HR unit
or
Water Heating Condenser Unit Heat exchanger Condenser Unit Hydro box
Heatpump
i ii iii
2
Notes
• Heat recovery in hot water system here means harvesting waste heat from
condenser unit and stored in hot water tank. The hot water is used for shower etc.
3
1. Water Heating Heatpump
May/2020
4
Water Heating Heatpump
Evaporator
Water outlet
30~65oC
Heat Pump
Hot Water Ambient
Large Capacity Air 35oC
Plate Heat q
Exchanger
Compressor
+
+
Compressor
Water inlet & outlet Compressor
Work,
Work,
W
W
Water outlet Water inlet Incoming Water inlet
30~65oC 25~55oC Water 25~55oC
25~30oC
5
Water Heating Heatpump
6
Water Heating Heatpump
• Equivalent water heating capacity (mdot x c x dT) include ring line losses 20%
= 12,800L/day/3600s x 4.18kJ/kg.K x (333.15-300.15)K x 120%
= 589kWh/day
• Assume the Heatpump operate 10hrs/day to produce 589kWh/day, heat pump size
= 589kWh/day divide by 10hrs
= 58.9kW
• Each day hot water usage has 2 peaks or 4hours (7am-9am; 6pm-8pm), each peak
= 589kWh/2 peaks
= 294.5kW/peak
7
2. Water Heating via Heat Recovery
May/2020
8
Water Heating via Heat Recovery
9
Water Heating via Heat Recovery
R410a P-h chart Schematic
Q1
Incoming water
P Compressor discharge Condenser 20oC - 55oC
temperature 75oC - 95oC
Q1
Close
Q2
Q2 Q2
Heat Exchanger
EXV
w w
q
Evaporator
h
q
• Heat available for recovery is the heat that is removed from the room
or space, q + heat available due to the compression of the
refrigerant in the compressor. It would be desirable to reclaim this
heat in a usable form. The best form of heat recovery is for heating
water.
10
Water Heating via Heat Recovery
VRV-HRHW
Serpentine Heat
Exchanger
Hot refrigerant/
compressor discharge
11
Water Heating via Heat Recovery
Hot Water
Tank
Circulation pump
Note: Above illustration water piping is reverse return concept with centralize pump, other design is possible depends on site requirements.
12
Centralized Hot Water System
13
Hybrid Centralized Hot Water System
Heatpump
14
Water Heating via Heat Recovery
recovery:
• Calculation for heat recovery (100 rooms business hotel dual occupancy)
• Equivalent water heating capacity (mdot x c x dT) include ring line losses 20%
= 589kWh/day
16
Water Heating via Heat Recovery
• Daily hot water requirement
= 12,800L/day
• Each day hot water usage has 2 peaks (7am-9am; 6pm-8pm), each peak
= 294.5kW/peak
Heat
Recovery Hot water
39.36kWh tank
5760L/
220.7kWh Return line
Water pumps Electric heater
34.4kWh
During Peak Incoming water around 27oC
7am-9am
2 hrs* 17
Comparison
• Example 100 rooms hotel dual occupancy with 24hp fresh air and
24hp for lobby & corridor.
18
Comparison
• Example 100 rooms hotel dual occupancy with 24hp fresh air and
24hp for lobby & corridor.
19
Appendix
VRV Power Consumption:
• RWHQ24TASYM: (558.32+61.92)kWh x 365days x RM0.509/kWh = RM103,727.5
• RXQ24AMYM: (523.7+61.92)kWh x 365days x RM0.509/kWh = RM97,295.6
20
Summary
21
Project
References
Hotel with VRV-
HRHW
Palm Hotel
Ipoh
• Total HP : 60 HP (3 modules)
• Completion : 2017
: VRV HRHW
• Completion : 2019
Fresh Air AHU and VRV HRHW is use for heat recovery due
to 24hours operation and high heat load from ambient.
The heat recovery mechanism provide free energy to hot
water tank thus reduce electricity usage for hot water
system.
Park Inn Hotel
Selangor
• Model : VRV A
: VRV HRHW
• Completion : 2020
The hotel is using VRV A and VRV HRHW for heat recovery
(Lobby, Meeting Room and FA unit). VRV system used due
to energy saving and comfort (VRT Technology).
Salam Hospital
Senawang
• Model : VRV A
: VRV HRHW
• Completion : 2020