DRW170805AE

Specifications Connections ※Shaded terminals is standard model.

Series TX4S TX4M TX4H TX4L TX4S Series TX4M Series TX4H, L Series
LCD Display PID Temperature Controller Power supply 100-240VAC 50/60Hz
OUT
Allowable voltage range 90 to 110% of rated voltage

TX SERIES
SSR
Power consumption Max. 8VA 12VDC±2V 20mA Max. 1 13
Display method 11-segments (PV: white, SV: green), other display (yellow) with LCD method※1 Current Communication
Character PV(W×H) 7.2×14mm 10.7×17.3mm 7.2×15.8mm 16×26.8mm DC0/4-20mA Output 2 14
INSTRUCTION MANUAL size SV(W×H) 3.9×7.6mm 6.8×11mm 6.2×13.7mm 10.7×17.8mm
Load 500ΩMax.
Relay 1 13 7
AL1 OUT:
250VAC 3A 1a
1 19 10 Transfer Output
DC4-20mA
3 15
RTD DPt100Ω, Cu50Ω (permissible line resistance max. 5Ω) 250VAC 3A 1a RESISTIVE LOAD 2 20 11 Communication
Input type 30VDC 3A 1a + Output
TC K (CA), J (IC), L (IC), T (CC), R (PR), S(PR) 2 14 8 RS485(A+) mA
RESISTIVE LOAD AL2 OUT:
- 4 16 Transfer Output
Display RTD ●At room temperature: (23℃±5℃): (PV ±0.3% or ±1℃, select the higher one) ±1-digit 250VAC 3A 1a 3 21 12 DC4-20mA
accuracy TC※2
●Out of room temperature: (PV ±0.5% or ±2℃, select the higher one) ±1-digit + + 3 +
RS485(A+) 15 9 RESISTIVE LOAD
OUT
RS485(B-)
5 17 +
mA OUT AL1 OUT: RS485(A+)
Relay 250VAC 3A, 30VDC 3A, 1a -
mA
- - A Current OUT 4 Relay 22 13 250VAC 3A 1a
mA
Control
SSR Max. 12VDC ±2V 20mA Max. 13VDC ±3V 20mA
4 RS485(B-) 16 10 DC4-20mA SSR 250VAC 3A 1a RESISTIVE LOAD 6 18 -
output Load 13VDC±3V 5 30VDC 3A 1a 23 14 AL2 OUT:
RS485(B-)
Current DC4-20mA or DC0-20mA (load resistance max. 500Ω) Communication B RESISTIVE LOAD
5 Output 17 11 + 500ΩMax. 20mA Max. 250VAC 3A 1a OUT
7 OUT
19 AL1 OUT:
Alarm output AL1, AL2: 250VAC 3A , 30VDC 3A 1a Transfer Output 6 24 15 RESISTIVE LOAD Current OUT Relay
Option B' + + DC4-20mA SSR 250VAC 3A 1a 250VAC 3A 1a
Trans. output DC4-20mA (load resistance max. 500Ω, output accuracy: ±0.3%F.S.) -
output SOURCE 6 DC4-20mA 18 12 mA
A Load 13VDC±3V 8 30VDC 3A 1a 20 RESISTIVE LOAD
Com. output RS485 communication output (Modbus RTU method) RTD TC - -
100-240VAC SENSOR
7 25 16 500ΩMax. 20mA Max. RESISTIVE LOAD AL2 OUT:
250VAC 3A 1a
Control method ON/OFF control, P, PI, PD, PID control 50/60Hz 8VA
B 9 21
+ + RESISTIVE LOAD
Hysteresis 1 to 100℃/℉ (0.1 to 50.0℃/℉) variable 8 26 17 + mA
A
Proportional band(P) 0.1 to 999.9℃/℉ ※Use terminals of size specified below. B'
- - 10 22
-
Integral time(I) 0 to 9999 sec SOURCE
9 27 18 RTD TC
a b a b B
Derivative time(D) 0 to 9999 sec 100-240VAC SENSOR 11 23 +
50/60Hz 8VA
Control period(T) 0.5 to 120.0 sec <Round> <Forked>
Thank you for choosing our Autonics product. Manual reset 0.0 to 100.0% a Min. 3.0mm Min. 3.0mm SOURCE 12 24 B'
RTD TC
-

Please read the following safety considerations before use. Sampling period 50ms b Max.5.8mm Max.5.8mm
100-240VAC
50/60Hz 8VA
SENSOR
Dielectric strength 3,000VAC 50/60Hz for 1 min (between primary circuit and secondary circuit)
Safety Considerations Vibration 0.75mm amplitude at frequency 5 to 55Hz (for 1 min) in each X, Y, Z direction for 2 hours

※Please observe all safety considerations for safe and proper product operation to avoid hazards.
Relay
life cycle
Mechanical OUT, AL1/2: min 5,000,000 operations Dimensions (unit: mm)
Electrical OUT, AL1/2: min 200,000 (250VAC 3A resistance load)
※Safety considerations are categorized as follows. Insulation resistance Min. 100MΩ (at 500VDC megger) 51 Bracket
TX4S TX4M 51
Noise resistance Square shaped noise by noise simulator (pulse width 1㎲) ±2kV R-phase, S-phase ᆞ TX4S Series ᆞTX4M/H/L Series
Warning Failure to follow these instructions may result in serious injury or death. □48 6 45 72 6 45
Memory retention Approx. 10 years (non-volatile semiconductor memory type) 30.5
Caution Failure to follow these instructions may result in personal injury or product damage.

3.5
Environ- Ambient temp. -10 to 50℃, storage: -20 to 60℃ 48.6 20
※The symbols used on the product and instruction manual represent the following ment Ambient humi. 35 to 85%RH, storage: 35 to 85%RH 45 5
symbol represents caution due to special circumstances in which hazards may occur. Protection structure IP50 (front panel, IEC standards)

4
Insulation type Double insulation (mark: , dielectric strength between primary circuit and secondary circuit: 3kV)

44.8
Warning

44.9

36
Approval

16
46 8.5

67.5
Approx. 146.1g Approx. 233g Approx. 214g Approx. 290g
1. Fail-safe device must be installed when using the unit with machinery that may cause serious injury Weight※3 (approx. 86.7g) (approx. 143g) (approx. 133g) (approx. 206g)
or substantial economic loss. (e.g. nuclear power control, medical equipment, ships, vehicles,
※1: When using the unit at low temperature (below 0℃), display cycle is slow. 15
railways, aircraft, combustion apparatus, safety equipment, crime/disaster prevention devices, etc.)
Control output operates normally. 55 21

33
Failure to follow this instruction may result in fire, personal injury, or economic loss.
2. Install on a device panel to use. ※2: At room temperature(23℃±5℃)
Failure to follow this instruction may result in electric shock. TC R(PR), S(PR), below 200℃: (PV ±0.5% or ±3℃, select the higher one) ±1-digit
3. Do not connect, repair, or inspect the unit while connected to a power source. , over 200℃: (PV ±0.5% or ±2℃, select the higher one) ±1-digit
TC L(IC), RTD Cu50Ω: (PV ±0.5% or ±2℃, select the higher one) ±1-digit
11.9
Failure to follow this instruction may result in electric shock or fire.
Out of room temperature range 23.9
4. Check 'Connections' before wiring. 56
Failure to follow this instruction may result in fire. TC R(PR), S(PR): (PV ±1.0% or ±5℃, select the higher one) ±1-digit
TC L(IC), RTD Cu50Ω: (PV ±0.5% or ±3℃, select the higher one) ±1-digit
TX4H TX4L
5. Do not disassemble or modify the unit. 51 51
Failure to follow this instruction may result in electric shock or fire. ※3: The weight includes packaging. The weight in parenthesis is for unit only.
※Environment resistance is rated at no freezing or condensation.
48 6 45 96 6 45
Caution ●Panel cut-out
1. When connecting the power input and relay output, use AWG 20 (0.50mm2) cable or over and tighten Unit Description
the terminal screw with a tightening torque of 0.74 to 0.90N m. A
1. Measured value (PV) component:
When connecting the sensor input and communication cable without dedicated cable, use AWG 28 to RUN mode: Displays current measured value (PV).
16 cable and tighten the terminal screw with a tightening torque of 0.74 to 0.90N m. SETTING mode: Displays parameters.
Failure to follow this instruction may result in fire or malfunction due to contact failure.
2. Temperature unit(℃/℉) indicator: B
2. Use the unit within the rated specifications. 1
Failure to follow this instruction may result in fire or product damage. Displays the set temperature unit as temperature unit [UNIT] of D
parameter 2 group.

91.5
3. Use dry cloth to clean the unit, and do not use water or organic solvent.

91.5
96
Failure to follow this instruction may result in electric shock or fire. 4 3. Setting value (SV) display component: C
4. Do not use the unit in the place where flammable/explosive/corrosive gas, humidity, direct sunlight, 5 2 RUN mode: Displays setting value(SV).
(unit: mm)
radiant heat, vibration, impact, or salinity may be present. SETTING mode: Displays setting value of parameter.
Failure to follow this instruction may result in fire or explosion. 6 3 4. Auto-tuning indicator:
Size A B C D
Model
5. Keep metal chip, dust, and wire residue from flowing into the unit. 9
Flashes during auto-tuning every 1 sec. TX4S Min. 65 Min. 65 45+0.6
0 45+0.6
0
Failure to follow this instruction may result in fire or product damage. 5. Control output (OUT1) indicator: Turns ON while control output is ON. TX4M Min. 90 Min. 90 68+0.7
0 68+0.7
0

※Turns ON when MV is over 3.0% at cycle/phase control of SSR drive TX4H Min. 115 Min. 65 +0.6
45 0 +0.8
92 0
Ordering Information 7 8
output method. TX4L Min. 115 Min. 115 +0.8
92 0 +0.8
92 0
6. Alarm output (AL1, AL2) indicator:
TX 4 S 1 4 R Turns ON when the corresponding alarm output turns ON.
10 Terminal cover (sold separately)
R Relay output
Control output 7. key: Enters parameter group, returns to RUN mode, moves parameters,
S SSR drive output ᆞRSA-COVER(48×48mm) ᆞRMA-COVER(72×72mm) ᆞRHA-COVER(48×96mm) ᆞRLA-COVER(96×96mm)
and saves the setting value.
C Selectable current output or SSR drive output 8. Setting value adjutment key: Enters SV setting mode and move digits.
3.8 47.2 9 3.8 94 10
Power supply 9. Digital input key: Press the + keys for 3 sec to execute the digital input key
4 100-240VAC 50/60Hz functions which is set at digital input key[DI-K]of parameter 2 group (RUN/STOP, 4 70 10
22
clear alarm output, auto-tuning). 3 48.4
1 Alarm output 1 13
10. PC loader port: It is for serial communication to set parameter and monitoring by
Option output 2 Alarm output 1+Alarm output 2 DAQMaster installed in PC. Use this for connection EXT-US (converter cable,
sold separately) + SCM-US (USB/Serial converter, sold separately).
A Alarm output 1+Alarm output 2+Trans. output

68.5

91.5
91.5
64
B Alarm output 1+Alarm output 2+RS485 com. output

86
86
41
45
Installation
S DIN W48×H48mm
Size TX4S (48×48mm) series ●Other series
M DIN W72×H72mm
H DIN W48×H96mm

18
L DIN W96×H96mm

22

13
Digit
4 9999(4-digit)

13
13
Item
TX LCD display PID temperature controller

Parameter 2 group
Input Type and Range (-) driver SV Setting Factory Default Parameter Factory default Parameter Factory default
Input type Decimal point Display Input range(℃) Input range(℉) ※To change set temperature from 210℃ to 250℃ IN-T KCaH AHYS 1
1 KCaH -50 to 1200 -58 to 2192 (-) driver
K (CA) ①RUN mode SV setting UNIT ?C LBaT 0
0.1 KCaL -50.0 to 999.9 -58.0 to 999.9
※Insert the unit into a panel, fasten the bracket by pushing with tools with a (-) driver. Parameter Factory default
1 JIcH -30 to 800 -22 to 1472 IN-B 0 LBaB 2
J (IC) 0
0.1 JIcL -30.0 to 800.0 -22.0 to 999.9 - MAvF )1 FS-L -50
1 LIcH -40 to 800 -40 to 1472
Thermocouple L (IC)
0.1 LIcL -40.0 to 800.0 -40.0 to 999.9 Comprehensive Device Management Program[DAQMaster] Parameter 1 group
L-SV -50 FS-H 1200
Press any key among , , , once. H-SV 1200 ADRS 1
1 TCcH -50 to 400 -58 to 752 DAQMaster is a comprehensive device management software for setting parameters and monitoring ③Completes SV
T (CC) Parameter Factory default O-FT HEAT BPS 96
0.1 TCcL -50.0 to 400.0 -58.0 to 752.0 processes. DAQMaster can be downloaded from our web site at www.autonics.com. ②SV setting mode setting
R (PR) 1 RPR 0 to 1700 32 to 3092 AL1 C-MD PID PRTY NONE
Item Minimum specifications 1250
S (PR) 1 SPR 0 to 1700 32 to 3092 AL2 OUT CURR STP 2
1 DPtH -100 to 400 -148 to 752 System IBM PC compatible computer with Pentium Ⅲ or above Change SV
DPt 100Ω Operations Windows 98/NT/XP/Vista/7/8/10 by , , key
AT OFF SSrM STND RSwT 20
0.1 DPtL -100.0 to 400.0 -148.0 to 752.0
RTD
1 CUsH -50 to 200 -58 to 392 Memory 256MB+
P 1)0 oMA 4-20 COMW EnA
Cu50Ω I 240 2)0 (Relay) DI-K STOP
0.1 CUsL -50.0 to 200.0 -58.0 to 392.0 Hard disk 1GB+ of available hard disk space
④Check SV
T
※The above specifications are subject to change and some models may be discontinued without notice. VGA Resolution: 1024×768 or higher D 49 @0(SSR drive) ErMV )0
※Be sure to follow cautions written in the instruction manual and the technical descriptions (catalog, Others RS232C serial port (9-pin), USB port ※If there is no key input for 3 sec while setting SV, the new setting is applied and the unit will return to REST 5)0 AL-1 AM!A LOC OFF
homepage). RUN mode. HYS 2 AL-2 AM@A
Parameter Groups ● Parameter 1 group Functions Digital input key( + 3 sec)[DI-K]
※1: : Press any key among , , . Input correction[IN-B] Parameter Operation
RUN mode ※2: Press the key once after changing the setting value, to save the setting Controller itself does not have errors but there may be error by external input temperature sensor. This function OFF OFF It does not use digital input key function.
RUN mode value and move to the next parameter is for correcting this error.
Press any key among Pauses control output. Auxiliary output (except loop break alarm, sensor break alarm)
2 sec 4 sec ※Hold the key for 3 sec to save the setting value and return to RUN mode Ex) If actual temperature is 80℃ but controller displays 78℃, set input correction value [IN-B] as '2' and
, , , once. 2 sec except Control output operates as setting. Hold the digital input keys for 3 sec to restart.
after changing the setting value. controller displays 80℃.
3 sec Digital input key
PAR1 ※ Dotted parameters may not appear by model type or other parameter ※As the result of input correction, if current temperature value (PV) is over each temperature range of input t t t t
SV setting Parameter 1 group[PAR1] Parameter 2 group[PAR2] sensor, it displays HHHH or LLLL.
RUN/STOP STOP (t: over 3 sec)
settings.
3 sec 3 sec Input digital filter[MAvF]
AL1 temperature RUN STOP RUN STOP RUN
※1 If current temperature (PV) is fluctuating repeatedly by rapid change of input signal, it reflects to MV and
※Order of parameter setup Parameter 2 group Parameter 1 group SV setting AL1 1250 Setting range: Deviation alarm(-[F.S] to [F.S]), stable control is impossible. Therefore, digital filter function stabilizes current temperature value.
Clears alarm output by force.
Absolute value alarm(temperature range) For example, set input digital filter value as 0.4 sec, and it applies digital filter to input values during 0.4 sec
●All parameters are related one another. Set the parameters as above order. and displays these values. Current temperature may be different by actual input value. (only when alarm option is alarm latch, or alarm latch and standby sequence 1/2 .)
※2 ※Does not appear when AL1/AL2 alarm operation[AL-1, AL-2] Clear alarm AlRE
※If there is no key input for 30 sec while setting parameters, the new settings are ignored, and the unit will This function is applied when present value is out of alarm operation range but alarm
return to RUN mode with previous settings. AL2 temperature of parameter 2 group is set as AM)_/SBa /LBa .
SSR drive output method (SSRP function)[SSrM] output is ON. Alarm operates normally right after clearing alarm.
AL2 1250 ※Only alarm output 2 models have [AL2].
※When returning to RUN mode by holding the key for over 3 sec, press the key within 1 sec to ㆍSSRP function is selectable one of standard ON/OFF control, cycle control, phase control by Starts/Stops auto-tuning. This function is same as auto-tuning[AT] of parameter 1
re-enter the first parameter of previous parameter group. utilizing standard SSR drive output. group. (You can start auto-tuning [AT] of parameter 1 group and stop it by digital input
※Hold the + + keys for 5 sec in RUN mode, to enter re-set parameter menu. Select 'YES' and all ㆍThis function parameter appears only in SSR drive output model (TX4 - 4S). key.)
parameters are reset as factory default. Auto-tuning ※When setting as ON, the unit starts auto-tuning. After ㆍRealizing high accuracy and cost effective temperature control with both current output (4-20mA) Auto-tuning AT
※This parameter AT appears only when control method [C-MD] parameter 2 group
AT completing, OFF is automatically set. and linear output(cycle control and phase control)
OFF ON is set as PID. When control method [C-MD] parameter 2 group is set as ONOF, this
※During auto-tuning, the auto-tuning indicator ㆍSelect one of standard ON/OFF control [STND], cycle control [CYCL] , phase control [PHAS] at SSrM
● Parameter 2 group ※1: : Press any key among , , . flashes (every 1 sec). parameter of parameter 2 group. For cycle control, connect a zero cross turn-on SSR or random parameter is changed as OFF.
※2: Press the key once after changing the setting value, to save the setting turn-on SSR. For phase control, connect random turn-on SSR. Control output MV for input break[ErMV]
RUN mode ※1
value and move to the next parameter Proportional band SSR voltage output SSR module When input sensor is break, set control output MV.
3 sec 4 sec ※Hold the key for 3 sec to save the setting value and return to RUN mode P 1)0 Setting range: 0.1 to 999.9℃/℉ (TX4S: 12VDC
Load
after changing the setting value. TX4M/H/L: 13VDC) When control method[C-MD] of parameter 2 group is set as ONOF, set control output MV as )0(OFF)
PAR2 ※ Dotted parameters may not appear by model type or other parameter
Temperature controller or10)0(ON). When control method[C-MD] is set as PID, setting range for control output MV is )0 to 10)0.
settings. (TX Series)
Setting range: Refer to '▣ Input Type And Range'. Integral time Setting range: 0 to 9999 sec
Input sensor IN-T KCaH ※When changing the setting value, SV, [IN-B, H-SV/L-SV, I 240 ※Integral operation will be OFF
when the setting value is '0'
※Only appears when control Communication Setting
※2 AL1, AL2, LBaB, AHYS] parameters of parameter 2 group are method [C-MD] of parameter It is for parameter setting and monitoring via external devices (PC, PLC, etc.).
reset. 2 group is set as PID. Power Applicable for models with RS485 communication output through option output(TX4 -B4 ).
※When changing the setting value, SV, [IN-B, H-SV/ Derivative time
Temp. unit UNIT ?C ?F Setting range: 0 to 9999 sec 100-240VAC Please refer to ' Ordering Information'.
L-SV, AL1, AL2, LBaB, AHYS] parameters of
D 49 ※Derivative operation will be OFF 50/60Hz Interface
parameter 2 group are reset.
when the setting value is '0' Comm. protocol Modbus RTU Comm. speed 4800, 9600 (default), 19200, 38400, 115200 bps
Input ※When selecting cycle or phase control mode, the power supply for a load and a temperature
IN-B 0 Setting range: -999 to 999℃/℉(-199.9 to 999.9℃/℉) Connection type RS485 Response waiting time 5 to 99ms (default: 20ms)
correction controller must be the same.
Manual reset Setting range: 0.0 to 100.0% Application standard EIA RS485 Compliance with Start bit 1-bit (fixed)
※Control cycle[T] is able to set only when control method[C-MD]of parameter group 2 is set as PID and SSR
Input digital REST 5)0 ※Only appears in P, PD control. drive output method [SSrM] is set as STND. Max. connection 31 units (address: 01 to 127) Data bit 8-bit (fixed)
MAvF )1 Setting range: 0.1 to 120.0 sec Synchronous method Asynchronous Parity bit None (default), Odd, Even
filter ※In case of selectable current output or SSR drive output model(TX4 - 4C), this parameter does not appear.
Standard ON/OFF control by SSR is only available. Comm. method Two-wire half duplex Stop bit 1-bit, 2-bit (default)
SV low-limit Comm. effective range Max. 800m
L-SV -50 Hysteresis Setting range: 1 to 100℃/℉ (0.1 to 50.0℃/℉) 1)Standard ON/OFF control [STND]
value AC
HYS 2 ※Only appears when control method [C-MD] of parameter 2 group is Controls ON (100% output)/OFF ● Application of system organization ※Only for RS485 communication output model.
SV high-limit Setting range: Within temperature range of each sensor [H-SV≥(L-SV+1digit)] set as ONOF. (0% output) as same as standard RS232C/
H-SV 1200 When changing the setting value, and SV>H-SV, SV is reset as OUT Terminating resistance
value ※ H-SV. relay output. ON OFF ON OFF USB/Wi-Fi RS485
(100 to 120Ω)
2)Cycle control [CYCL] B (-) RS485
Control
output mode
O-FT HEAT COOL Alarm[AL-1/ AL-2] Set both alarm operation and alarm option by combining.
Controls the load by repeating
output ON / OFF according to the A (+)
DEVICE
#31
Each alarm operates individually in two alarm output models.
rate of output within setting cycle
Control
method
C-MD PID ONOF
※When changing the setting value, [ErMV] is reset as )0,
[DI-K] is reset as OFF.
AM!A When the current temperature is out of alarm range, alarm
clears automatically. If alarm option is alarm latch or alarm latch based on certain period (50-cycle).
Control accuracy is almost the
AC Comm.
converter
B (-)
A (+) B (-) A (+) B (-) A (+) B (-)
Alarm and standby sequence 1/2, press digital input key( + 3 sec, RS485 RS485 RS485
Control Alarm digital input key[DI-K] of parameter 2 group set as AlRE), or same with phase control’s.
※Appears only in selectable current output or SSR drive operation OUT DEVICE DEVICE DEVICE
output OUT CURR SSR option turn OFF the power and turn ON to clear alarm. This control has improved ON/ Computer #1 #2 #30
output model(TX4 - 4C). 50 Cycle 50 Cycle ON OFF
selection Alarm operation OFF noise than phase control’s
SSR drive due to zero cross type which turns 50% 80% A (+)
※Appears only in SSR drive output model Mode Name Alarm operation Description ON/OFF at zero point of AC.
output SSrM STND CYCL PHAS ※It is recommended to use Autonics communication converter; SCM-WF48 (Wi-Fi to RS485·USB wireless
method (TX4 - 4S). AM)_ - - No alarm output 3)Phase control [PHAS]
communication converter, sold separately), SCM-US48I (USB to RS485 converter, sold separately), SCM-38I
Current Controls the load by controlling AC
OFF H ON OFF H ON If deviation between PV and SV as (RS232C to RS485 converter, sold separately), SCM-US (USB to Serial converter, sold separately).
output oMA 4-20 0-20 ※Appears only when control output[OUT] is set as CURR. Deviation the phase within AC half cycle.
Please use twisted pair wire, which is suitable for RS485 communication, for SCM-WF48, SCM-US48I and
range high-limit is higher than set value Serial control is available.
AM! high-limit SV PV PV SV of deviation temperature, the alarm SCM-38I.
alarm 100℃ 110℃ 90℃ 100℃ Must use random turn-on SSR for OUT
Setting range: 0.5 to 120.0 sec output will be ON. 10% 50%
Control High-limit deviation: Set as 10℃ High-limit deviation: Set as -10℃ this mode.
T 2)0 ※Appears only when control method[C-MD] is PID.
cycle
※Does not appear when SSR drive output is set as CYCL, or PHAS. ON H OFF ON H OFF If deviation between PV and SV as Current output range[oMA] Manual
Deviation For the detail information and instructions of communication setting and Modbus mapping table, please refer
low-limit is higher than set value of In case of selectable current output or SSR drive output model(TX4S- 4C), when control output [OUT]
AM@ low-limit PV SV SV PV deviation temperature, the alarm to user manual for communication, and be sure to follow cautions written in the technical descriptions (catalog,
AL1 alarm 90℃ 100℃ parameter 2 group is set as [CURR], you can select high/low-limit range, 4-20mA [4-20] or 0-20mA [0-20] of
AL-1 AM!A LBaA AM!A AM!B ※When changing the
100℃ 110℃
output will be ON. current output. homepage).
operation Low-limit deviation: Set as 10℃ Low-limit deviation: Set as -10℃ Visit our homepage (www.autonics.com) to download manuals.
setting value,
※Alarm operation ※ Alarm option Deviation ON H OFF H ON If deviation between PV and SV Hysteresis[HYS]
[AL1, AL2]
※Press the key to switch 'Alarm operation' parameter of AM#
high/low-
limit PV SV PV
as high/low-limit is higher than set
value of deviation temperature, the
Set interval between ON and OFF of control output for ON/OFF
control. Error
'Alarm option' setting. parameter 1 group 90℃ 100℃ 110℃
alarm alarm output will be ON. ●If hysteresis is too narrow, hunting(oscillation, chattering) could Display Description Troubleshooting
AL2 ※Set method is same as AL1 alarm is reset. High, Low-limit deviation: Set as 10℃ occur due to external noise. Heating operation
AL-2 AM@A operation[AL-1]. Control OPEN Flashes when input sensor is disconnected or sensor is not connected. Check input sensor status.
operation Deviation OFF H ON H OFF ●In case of ON / OFF control mode, even if PV reaches stable
※Appears only in alarm output 2 models. high/low- If deviation between PV and SV status, there still occurs hunting. It could be due to hysteresis output Flashes when measured value is higher than input range. When input is within the
ON OFF HHHH
as high/low-limit is higher than set [HYS] setting value, load’s response characteristics or sensor’s
Alarm AM$ limit PV SV PV value of deviation temperature, the rated input range, this display
output AHYS 1 Setting range: 1 to 100℃/℉(0.1 to 50.0℃/℉) 90℃ 100℃ 110℃ location. In order to reduce hunting to a minimum, it is required Hysteresis LLLL Flashes when measured value is lower than input range.
reserve alarm output will be OFF. [HYS] disappears.
hysteresis ※Does not appear when AL1/AL2 alarm operation[AL-1, AL-2] is set alarm High, Low-limit deviation: Set as 10℃ to take into following factors consideration when designing temp. Temp.
LBA as AM)_/SBa /LBa . controlling; proper Hysteresis [HYS], heater’s capacity, thermal SV
OFF H ON
monitoring
time
LBaT 0 Setting range: 0 to 9999 sec (automatically set during auto-tuning)
※Appears only when alarm operation[AL-1, AL-2] is set as LBa .
Absolute
OFF H ON
If PV is higher than the absolute
characteristics, sensor’s response and location.
Cautions during Use
AM% value high PV SV SV PV value, the output will be ON. 1. Follow instructions in 'Cautions during Use'. Otherwise, It may cause unexpected accidents.
LBA Setting range: 0 to 999℃/℉ (0.0 to 999.9℃/℉) limit alarm 90℃ 100℃ 100℃ 110℃
detection LBaB Loop break alarm(LBA) 2. Check the polarity of the terminals before wiring the temperature sensor.
2 (automatically set during auto-tuning) Alarm absolute-value: Set as 90℃ Alarm absolute-value: Set as 110℃
band It checks control loop and outputs alarm by temperature change of the subject. For heating control(cooling For RTD temperature sensor, wire it as 3-wire type, using cables in same thickness and length.
※Appears only when alarm operation [AL-1, AL-2] is set as LBa ON H OFF ON H OFF control), when control output MV is 100%(0% for cooling control) and PV is not increased over than LBA For thermocouple (CT) temperature sensor, use the designated compensation wire for extending wire.
Trans. Absolute 3. Keep away from high voltage lines or power lines to prevent inductive noise.
output low- FS-L -50 and [LBaT] is not set as 0. If PV is lower than the absolute detection band [LBaB] during LBA monitoring time [LBaT], or when control output MV is 0%(100% for cooling
AM^ value low PV SV SV PV value, the output will be ON. control) and PV is not decreased below than LBA detection band [LBaB] during LBA monitoring time [LBaT], In case installing power line and input signal line closely, use line filter or varistor at power line and shielded
limit value Setting range: Refer to '▣ Input Type and Range'. limit alarm 90℃ 100℃ 100℃ 110℃ alarm output turns ON. wire at input signal line.
Trans. output ※Appears only in transmission output model(TX4 -A4 ). Alarm absolute-value: Set as 90℃ Alarm absolute-value: Set as 110℃ Do not use near the equipment which generates strong magnetic force or high frequency noise.
high-limit FS-H 1200
value Sensor It will be ON when it detects sensor 4. Do not apply excessive power when connecting or disconnecting the connectors of the product.
SBa break alarm
- disconnection. 5. Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting the
Comm. power.
ADRS 1 Setting range: 1 to 127 Loop break It will be ON when it detects loop
address LBa alarm
- break. 6. Do not use the unit for other purpose (e.g. voltmeter, ammeter), but temperature controller.
7. When changing the input sensor, turn off the power first before changing.
Comm. Setting range: 24, 48, 96, 192, 384 bps ※ H: Alarm output hysteresis [AHYS] After changing the input sensor, modify the value of the corresponding parameter.
BPS 96 8. Do not overlapping communication line and power line.
speed Multiply 100 to read the setting value.
Alarm option Use twisted pair wire for communication line and connect ferrite bead at each end of line to reduce the effect
Comm. Option Name Description of external noise.
PRTY NONE EVEN ODD ※Appears in RS485 9. Make a required space around the unit for radiation of heat.
parity-bit
communication output Standard If it is an alarm condition, alarm output is ON. If it is a clear alarm condition, alarm output For accurate temperature measurement, warm up the unit over 20 min after turning on the power.
AM .A alarm is OFF.
Comm. model(TX4 -B4 ). 10. Make sure that power supply voltage reaches to the rated voltage within 2 sec after supplying power.
STP 2 1 If it is an alarm condition, alarm output is ON and maintains ON status. 11. Do not wire to terminals which are not used.
stop-bit AM .B Alarm latch Time
(Alarm output HOLD) 12. This unit may be used in the following environments.
Comm.
First alarm condition is ignored and from second alarm condition, standard alarm ①Indoors (in the environment condition rated in 'Specifications') ②Altitude max. 2,000m
response RSwT 20 Setting range: 5 to 99ms Standby operates. When power is supplied and it is an alarm condition, this first alarm condition is ③Pollution degree 2 ④Installation category II
AM .C sequence 1
waiting time ignored and from the second alarm condition, standard alarm operates.
Comm. Start control When control output MV is 100%, PV is increased over than LBA detection band [LBaB] during
Alarm latch If it is an alarm condition, it operates both alarm latch and standby sequence. When
write
COMW EnA DIsA
AM .D and standby power is supplied and it is an alarm condition, this first alarm condition is ignored and to LBA monitoring time [LBaT]. Major Products
※AT does not appear when sequence 1 from the second alarm condition, alarm latch operates. to The status of changing control output MV (LBA monitoring time is reset.) Photoelectric Sensors Temperature Controllers
Digital control method [C-MD] is set First alarm condition is ignored and from second alarm condition, standard alarm Fiber Optic Sensors Temperature/Humidity Transducers
DI-K STOP AlRE AT OFF Standby When control output MV is 0% and PV is not decreased below than LBA detection band [LBaB] Door Sensors SSR/Power Controllers
input key as ONOF. AM .E sequence 2 operates. When re-applied standby sequence and if it is alarm condition, alarm output to
during LBA monitoring time [LBaT], loop break alarm (LBA) turns ON after LBA monitoring time. Door Side Sensors Counters
does not turn ON. After clearing alarm condition, standard alarm operates.
Control Setting range: 0.0 to 100.0% to Control output MV is 0% and loop break alarm (LBA) turns and maintains ON. Area Sensors Timers
※Only )0(OFF)/10)0(ON) appear when control method Basic operation is same as alarm latch and standby sequence 1. It operates not only by Proximity Sensors Panel Meters
output MV Alarm latch
ErMV )0 [C-MD] is set as ONOF. power ON/OFF, but also alarm setting value, or alarm option changing. When re-applied to The status of changing control output MV (LBA monitoring time is reset.) Pressure Sensors Tachometer/Pulse(Rate)Meters
for input AM .F and standby standby sequence and if it is alarm condition, alarm output does not turn ON. After
※When control method [C-MD] is changing PID↔ONOF and the setting sequence 2 Rotary Encoders Display Units
break clearing alarm condition, alarm latch operates. When control output MV is 100% and PV is not increased over than LBA detection band [LBaB] Connector/Sockets Sensor Controllers
value is below 10)0, it is reset as )0. to
during LBA monitoring time [LBaT], loop break alarm (LBA) turns ON after LBA monitoring time. Switching Mode Power Supplies
※Condition of re-applied standby sequence for standby sequence 1, alarm latch and standby sequence 1: Power ON http://www.autonics.com
Condition of re-applied standby sequence for standby sequence 2, alarm latch and standby sequence 2: Power ON, When control output MV is 100% and PV is increased over than LBA detection band [LBaB] Control Switches/Lamps/Buzzers
Lock LOC OFF LOC1 LOC2 LOC3 to I/O Terminal Blocks & Cables
changing set temperature, alarm temperature [AL1, AL2] or alarm operation [AL-1, AL-2], switching STOP mode during LBA monitoring time [LBaT], loop break alarm (LBA) turns OFF after LBA monitoring time. HEADQUARTERS:
to RUN mode. Stepper Motors/Drivers/Motion Controllers 18, Bansong-ro 513beon-gil, Haeundae-gu, Busan,
Setting range: OFF Unlock to The status of changing control output MV (LBA monitoring time is reset.) Graphic/Logic Panels South Korea, 48002
Sensor break alarm Field Network Devices
LOC1 Parameter 2 group lock The function that alarm output will be ON when sensor is not connected or when sensor's disconnection is TEL: 82-51-519-3232
※When executing auto-tuning, LBA detection band[LBaB] and LBA monitoring time are automatically set based Laser Marking System(Fiber, Co₂, Nd:yag) E-mail: sales@autonics.com
LOC2 Parameter 1,2 group lock detected during temperature controlling. You can check whether the sensor is connected with buzzer or other on auto tuning value. When alarm operation mode [AL-1, AL-2] is set as loop break alarm(LBA)[LBa ], LBA Laser Welding/Cutting System
LOC3 Parameter 1,2 group, SV setting lock units using alarm output contact. It is selectable between standard alarm [SBaA] or alarm latch [SBaB]. detection band [LBaB] and LBA monitoring time [LBaT] parameter is displayed. DRW170805AE