You are on page 1of 62

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Lecture-10

Analysis and Design of


Two-way Slab Systems
(Two Way Joist Slabs & Two-way Slab
with Beams)

By: Prof Dr. Qaisar Ali


Civil Engineering Department
UET Peshawar
drqaisarali@nwfpuet.edu.pk

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 1

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Topics Addressed

 Two-Way Joist Slab


 Introduction

 Behavior

 Characteristics

 Basic Steps for Structural Design

 Example

2
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

1
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Topics Addressed

 Moment Coefficient Method for Two Way Slab with


Beams
 Introduction

 Cases

 Moment Coefficient Tables

 Reinforcement Requirements

 Steps

 Example

3
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist Slab

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 4

2
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Introduction
 A two-way joist system, or waffle slab, comprises evenly
spaced concrete joists spanning in both directions and a
reinforced concrete slab cast integrally with the joists.

Joist

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 5

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Introduction
 Like one-way joist system, a two way system will be called
as two-way joist system if clear spacing between ribs (dome
width) does not exceed 30 inches.

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 6

3
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Introduction

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 7

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Introduction
 The joists are commonly formed by using standard square
“dome” forms and the domes are omitted around the columns
to form the solid heads.
Solid Head

8
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

4
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist

 Introduction
 Standard Dome Data
 Generally the dome for waffle slab can be of any size. However the
commonly used standard domes are discussed as follows:

 30-inch × 30-inch square domes with 3-inch flanges; from which 6-


inch wide joist ribs at 36-inch centers are formed: these are
available in standard depths of 8, 10, 12, 14, 16 and 20 inches.

 19-inch × 19-inch square domes with 2 ½-inch flanges, from which


5-inch wide joist ribs at 24-inch centers are formed. These are
available in standard depths of 8, 10, 12, 14 and 16 inches.

9
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist

 Introduction
 Standard Dome Data

10
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

5
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Behavior
 The behavior of two-way joist slab is similar to a two way flat
Slab system.

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Characteristics
 Dome voids reduce dead load.

 Attractive ceiling (waffle like appearance).

 Electrical fixtures can be placed in the voids.

 Particularly advantageous where the use of longer spans


and/or heavier loads are desired without the use of
deepened drop panels or supported beams.

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

6
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Basic Steps for Structural Design
 Step No. 01 (Sizes): Sizes of all structural and non
structural elements are decided.

 Step No. 02 (Loads): Loads on structure are determined


based on occupational characteristics and functionality.

 Step No. 03 (Analysis): Effect of loads are calculated on all


structural elements.

 Step No. 04 (Design): Structural elements are designed for


the respective load effects following code provisions.

13
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Sizes
 Minimum Joist Depth
 For Joist depth determination, waffle slabs are considered as flat slab
(ACI 13.1.3, 13.1.4 & 9.5.3).

 The thickness of equivalent flat slab is taken from table 9.5 (c).

 The thickness of slab and depth of rib of waffle slab can be then
computed by equalizing the moment of inertia of equivalent flat slab to
that of waffle slab.

 However since this practice is time consuming, tables have been


developed to determine the size of waffle slab from equivalent flat slab
thickness.

14
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

7
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Sizes
 Minimum Joist Depth
 Equivalent Flat Slab Thickness

 ACI 318-05 – Sect. 9.5.3

 Minimum thickness = ln/33

15
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Sizes
 Minimum Joist Depth
 Slab and rib depth from equivalent flat slab thickness
Table 01: Waffle flat slabs (19" × 19" voids at 2'-0")-Equivalent thickness
Rib + Slab Depths (in.) Equivalent Thickness t e (in.)
8+3 8.89
8+4½ 10.11
10 + 3 10.51
10 + 4 ½ 11.75
12 + 3 12.12
12 + 4 ½ 13.38
14 + 3 13.72
14 + 4 ½ 15.02
16 + 3 15.31
16 + 4 ½ 16.64
Reference: Table 11-2 of CRSI Design Handbook 2002.
Note: Only first two columns of the table are reproduced here.

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 16

8
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Sizes
 Minimum Joist Depth
 Slab and rib depth from equivalent flat slab thickness
Table 02: Waffle flat slabs (30" × 30" voids at 3'-0")-Equivalent thickness
Rib + Slab Depths (in.) Equivalent Thickness te (in.)
8+3 8.61
8+4½ 9.79
10 + 3 10.18
10 + 4 ½ 11.37
12 + 3 11.74
12 + 4 ½ 12.95
14 + 3 13.3
14 + 4 ½ 14.54
16 + 3 14.85
16 + 4 ½ 16.12
20 + 3 17.92
20 + 4 ½ 19.26
Reference: Table 11-2 of CRSI Design Handbook 2002.
Note: Only first two columns of the table are reproduced here.

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 17

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Sizes
 Minimum Width of Rib
 ACI 8.11.2 states that ribs shall be not less than 4 inches in width.

 Maximum Depth of Rib


 ACI 8.11.2 also states that ribs shall have a depth of not more than 3
½ times the minimum width of rib.

 Minimum Slab Thickness


 ACI 8.11.6.1 states that slab thickness shall be not less than one-
twelfth the clear distance between ribs, nor less than 2 inch.

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 18

9
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Sizes
 Solid Head
 Dimension of solid head on either side of column centerline is equal to
l/6.

 The depth of the solid head is equal to the depth of the combined
depth of ribs and top slab.

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 19

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Loads
 Floor dead load for two-way joist with certain dome size, dome depth can
be calculated from the table shown for two options of slab thicknesses (3
inches and 4 ½ inches).
Table 03: Standard Dome Dimensions and other Data
Floor Dead Load (psf) per slab
Dome Depth Volume of Void thickness
Dome Size
(inches) (ft3)
3 inches 4 ½ inches
8 3.98 71 90
10 4.92 80 99
12 5.84 90 109
30 inches
14 6.74 100 119
16 7.61 111 129
20 9.3 132 151
8 1.56 79 98
10 1.91 91 110
19 inches 12 2.25 103 122
14 2.58 116 134
16 2.9 129 148
Reference: Table 11-1, CRSI Design Handbook 2002

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 20

10
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Loads
 Floor dead load (wdj) for two-way joist can also be
calculated as follows:
Volume of solid: 36″
Vsolid = (36  36  11)/1728 = 8.24 ft3 3″

Volume of void: 8″
Vvoid = (30  30  8)/1728 = 4.166 ft3
30″
Total Load of joists per dome:
wdj = (Vsolid – Vvoid)  γconc
= ( 8.24 – 4.166)  0.15 = 0.61 kips/ dome

Total Load of joists per sq. ft:


wdj/ (dome area) = 0.61/ (3  3) = 0.0679 ksf
= 68 psf ≈ 71 psf (from table 03)
The difference is because sloped ribs are not considered. Plan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 21

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Loads
 Taking a panel out of the system:
l1
wdj + wsh wdj + wsh
wdj

a a
l1

l2

l2 b

wdj = Dead load at joist (load/ area)


wsh = Dead load of solid head (load/ area)
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 22

11
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Loads
 If the complete area l1 × l2 is assumed to occupy joists
alone, then the dead load in the area l1 × l2 will be wdj.

 However since there are solid head regions present,


therefore additional dead load due to solid head region shall
be:
 wdsh = hsolid  γconc - wdj

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 23

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Loads
 Factored loads can be calculated as:

 If wL = live load (load/area) wsh wj wsh

 wdj = dead load at joists, then


a a
 Factored load due to joists (wj)
l1
wuj = 1.2 wdj + 1.6wL

 Factored load due to solid head (wsh)

wush = 1.2(wdsh – wdj) l2 b

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 24

12
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Analysis
 ACI code allows use of DDM for analysis of waffle slabs (ACI
R13.1). In such a case, waffle slabs are considered as flat
slabs, with the solid head acting as drop panels (ACI 13.1.3).

25
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Analysis
 Static moment calculation for DDM analysis:
wuj
wush wush

ln a a
ln
Moj ln
Mosh

l2 b

Moj = wujl2ln2/8 Mosh = wushba2/2

Mo = Moj + Mosh
26
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

13
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Design
 Design of slab for punching shear
 The solid head shall be checked against punching shear.

 The critical section for punching shear is taken at a section d/2 from face
of the column, where d is the effective depth at solid head.

27
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Design
 Design of slab for
punching shear
 Load on tributary area will l1
cause punch out shear.

 Within tributary area, two


types of loads are acting:
 Solid head load

 Joist load
l2 d/2
 Both types shall be
considered while calculating
punching shear demand

28
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

14
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Design
 Design of slab for punching
shear
 Total area (At) = l1  l2 l1
 Solid head area = Asolid

 Critical perimeter area = Acp

 Vu =At  wuj + Asolid  (wish − wuj)

 Where,
l2 d/2

wuj = Factored load considering


joist alone

wsh = Factored solid head dead


load
29
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Design
 Shear Strength of Slab in Punching Shear:
 ΦVn = ΦVc + ΦVs

 ΦVc is least of:


 Φ4√ (fc′)bod

 (2 + 4/βc) √ (fc′)bod

 {(αsd/bo +2} √ (fc′)bod

βc = longer side of column/shorter side of column

αs = 40 for interior column, 30 for edge column, 20 for corner columns

30
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

15
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Design
 Design of Joist for Beam Shear:
 Beam Shear Demand

 Beam shear is not usually a problem in slabs including waffle slabs.


However for completion of design beam shear may also be
checked. Beam shear can cause problem in case where larger
spans and heavier loads with relatively shallow waffle slabs are
used.

 The critical section for beam shear is taken at a section d from face
of the column, where d is the effective depth at solid head.

31
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Design
 Design of Joist for Beam Shear:
 Beam shear capacity of concrete joist:

 ΦVn = ΦVc + ΦVs


Stirrup
 ΦVc is least of:
 Φ2√ (fc′)bribd

 ΦVs = ΦAvfy/bribs

 For joist construction, contribution of concrete to shear strength Vc shall be


permitted to be 10 percent more than that specified in Chapter 11.

 If required, one or two single legged stirrups are provided in the rib to
increase the shear capacity of waffle slab.
32
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

16
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Design
 Design for Flexure
 The design of waffle slab for flexure is done by usual procedures.

 However, certain reinforcement requirements apply discussed next.

33
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 ACI Recommendations on Reinforcement
Requirement of Waffle Slab:
 Recommendations for Ribs:
 ACI 10.6.7 states that if the effective depth d of a beam or joist
exceeds 36 inches, longitudinal skin reinforcement shall be provided as
per ACI section 10.6.7.

34
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

17
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 ACI Recommendations on Reinforcement
Requirement of Waffle Slab:
 Recommendations for Slab:
 According to ACI 13.3.2, for cellular or ribbed construction reinforcement
shall not be less than the requirements of ACI 7.12.

 As per ACI 7.12, Spacing of top bars cannot exceed 5h or 18 inches.

35
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Other Important Points:
 The amount of reinforcement and, if necessary, the top slab
thickness can be changed to vary the load capacities for
different spans, areas, or floors of a structure.

 Each joist rib contains two bottom bars. Straight bars are
supplied over the column centerlines for negative factored
moment.

Bottom bar

36
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

18
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Other Important Points:
 For layouts that do not meet the standard 2-feet and 3-feet
modules, it is preferable that the required additional width be
obtained by increasing the width of the ribs framing into the
solid column head.

37
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Other Important Points:
 The designer should sketch out the spacing for a typical panel
and correlate with the column spacing as a part of the early
planning.

38
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

19
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Example: Design the slab system of hall shown in figure as waffle
slab, according to ACI 318. Use Direct Design Method for slab
analysis.
 fc′ = 4 ksi
 fy = 60 ksi
 Live load = 100 psf

39
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Solution:
 A 108′ × 144′ building, divided into twelve (12) panels, supported at
their ends on columns. Each panel is 36′ × 36′.

 The given slab system satisfies all the necessary limitations for Direct
Design Method to be applicable.

40
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

20
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 01: Sizes
 Columns
 Let all columns be 18″ × 18″.

 Slab
 Adopt 30″ × 30″ standard dome.

 Minimum equivalent flat slab thickness (hf) can be found using ACI Table
9.5 (c):
 Exterior panel governs. Therefore,
hf = ln/33
ln = 36 – (2 × 18/2)/12 = 34.5′
hf = (34.5/33) × 12 = 12.45″

41
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 01: Sizes
 Slab
 The closest depth of doom that will fulfill the requirement of equivalent
thickness of flat slab equal to 12.45″ is 12 in. with a slab thickness of 4 ½
in. for a dome size of 30-in.

Table: Waffle flat slabs (30" × 30" voids at 3'-0")-Equivalent thickness


Rib + Slab Depths (in.) Equivalent Thickness te (in.)
8+3 8.61
8+4½ 9.79
10 + 3 10.18
10 + 4 ½ 11.37
12 + 3 11.74
12 + 4 ½ 12.95
14 + 3 13.3
14 + 4 ½ 14.54
16 + 3 14.85
16 + 4 ½ 16.12
20 + 3 17.92
20 + 4 ½ 19.26

42
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

21
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
l = 36′-0″ = 432″
 Step No 01: Sizes Standard module = 36″  36″

 Planning of Joist layout No. of modules in 36′-0″:


n = 432/36 = 12

Planning:
First joist is placed on interior column
centerline with progressive placing of
other joists towards exterior ends of
panel. To flush the last joist with
external column, the width of exterior
joist comes out to be 15″ (6″+Column
size /2) as shown in plan view.

43
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 01: Sizes
 Solid Head
 Solid head dimension from column centerline = l/6 = 36/6 = 6′

 Total required length of solid head= 2  6 = 12′

 As 3′  3′ module is selected, therefore 4 voids including joist witdh will


make an interior solid head of 12.5′  12.5′. (Length of solid head = c/c
distance between rib + rib width )

 Depth of the solid head = Depth of standard module = 12 + 4.5 = 16.5′′

44
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

22
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 02: Loads
 Floor (joist) dead load (wdj) = 109 psf = 0.109 ksf

Table: Standard Dome Dimensions and other Data


Floor Dead Load (psf) per slab
Volume of Void thickness
Dome Size Dome Depth (in.)
(ft3)
3 inches 4 ½ inches
8 3.98 71 90
10 4.92 80 99
12 5.84 90 109
30-in
14 6.74 100 119
16 7.61 111 129
20 9.3 132 151
8 1.56 79 98
10 1.91 91 110
19-in 12 2.25 103 122
14 2.58 116 134
16 2.9 129 148
Reference: Table 11-1, CRSI Design Handbook 2002

45
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 02: Loads
 Floor (joist) dead load (wdj) = 109 psf = 0.109 ksf

 Solid Head dead load (wsh) = γchsh – wdj

= 0.15 ×{(12 + 4.5)/12} – 0.109 = 0.097 ksf

Wdj+sh wdj Wdj+sh

a a
l1

a = 5.25 ft l2 b
b = 12.5 ft

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 46

23
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 02: Loads wuj

 wL = 100 psf = 0.100 ksf

 Load due to joists plus LL (wuj) wush wush

wuj = 1.2 wdj + 1.6wL a a

= 1.2 0.109 + 1.60.100 l1

= 0.291 ksf
l2 b
 Load due to solid head dead load (wush)

wush = 1.2wsh

= 1.2  0.097 = 0.1164 ksf

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 47

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 03: Frame Analysis (E-W Interior Frame)
 Step 1: Marking E-W Interior Frame:

l2 = 36′

48
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

24
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 03: Frame Analysis (E-W Interior Frame)
 Step 2: Marking of Column and Middle Strips:

MS/2 = 9′
CS/2 = Least of l1/4 or l2/4
CS/2 = 9′
l2 = 36′
l2/4 = 36/4 = 9′ CS/2 = 9′
MS/2 = 9′

49
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 03: Frame Analysis (E-W Interior Frame)
 Step 03: Static Moment Calculation
 Moj (due to joists) = wojl2ln2/8

= 0.291 × 36 × 34.52/8 = 1557.56 ft-kip

Mosh (due to solid head excluding joists) = wush ba2/2

= 0.1164×12.5×5.252/2 = 20 ft-kip

Mo (total static moment) = Moj + Mosh = 1557.56 + 20 = 1577.56 ft-kip

Note: Since normally, Mosh is much smaller than Moj the former can be
conveniently ignored in design calculations.

50
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

25
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 03: Frame Analysis (E-W Interior Frame)
 Step 03: Static Moment Calculation.

l2 = 36′

51
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 03: Frame Analysis (E-W Interior Frame)
 Step 04: Longitudinal distribution of Total static moment (Mo).

Longitudinal 0.52 0.35 0.52


distribution l2 = 36′
0.26 0.70 0.65 0.65 0.70 0.26
factors (D.F)L
52
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

26
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 03: Frame Analysis (E-W Interior Frame)
 Step 04: Longitudinal distribution of Total static moment (Mo).

820 552 820


ML = Mo × (D.F)L l2 = 36′
410 1104 1025 1025 1104 410

Prof. Dr. Qaisar Ali CE 5115 Units: ft-kip


Advance Design of Reinforced Concrete Structures Fall 2011
53

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 03: Frame Analysis (E-W Interior Frame)
 Step 05: Lateral Distribution of Longitudinal moment (L.M).

Lateral
0.60 0.60 0.60
distribution l2 = 36′
1.00 0.75 0.75 0.75 0.75 1.00
factors (D.F)Lat

54
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

27
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 03: Frame Analysis (E-W Interior Frame)
 Step 05: Lateral Distribution of Longitudinal moment (L.M).

ML,ext- = 410 kip-ft


ML,ext+ = 820 kip-ft
ML,int- = 1104 kip-ft
ML,- = 1025 kip-ft
ML,+ = 552 kip-ft

0 328/2 276/2 256/2 221/2 256/2 276/2 328/2 0

492 331 492


MLat = ML × (D.F)Lat 410 828 769 769 828 410
l2 = 36′
0 328/2 276/2 256/2 221/2 256/2 276/2 328/2 0

55
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 03: Frame Analysis (E-W Interior Frame)
 Step 05: Lateral Distribution of Longitudinal moment (L.M).

ML,ext- = 410 kip-ft


ML,ext+ = 820 kip-ft
ML,int- = 1104 kip-ft
ML,- = 1025 kip-ft
ML,+ = 552 kip-ft

0 18.22 15.33 14.22 12.3 14.22 15.33 18.22 0

27.3 18.38 27.3


MLat per foot = Mlat/strip width 22.8 46 42.7 42.7 46 22.8
l2 = 36′
0 18.22 15.33 14.22 12.3 14.22 15.33 18.22 0

56
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

28
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 03: Frame Analysis (E-W Exterior Frame)
l2 = 18 + c/2
 Step 03: Static Moment Calculation = 18 + (18/12)/2
= 18.75′
 Moj (due to joists) = wojl2ln2/8 c = column dimension
= 0.291 × 18.75 × 34.52/8 = 811.78 ft-kip

Mosh (due to solid head excluding joists) = wush ba2/2

= 0.1164×7×5.252/2 = 12.83 ft-kip

Mo (total static moment) = Moj + Mosh = 811.78 + 12.83 = 825 ft-kip

Note: Since normally, Mosh is much smaller than Moj the former can be
conveniently ignored in design calculations.

57
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 03: Frame Analysis (E-W Exterior Frame)
 Step 03: Static Moment Calculation.

l2 = 18.75′
58
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

29
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 03: Frame Analysis (E-W Exterior Frame)
 Step 04: Longitudinal distribution of Total static moment (Mo).

Longitudinal
distribution
factors (D.F)L
0.52 0.35 0.52
0.26 0.70 0.65 0.65 0.70 0.26
59
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 03: Frame Analysis (E-W Exterior Frame)
 Step 04: Longitudinal distribution of Total static moment (Mo).

ML = Mo × (D.F)L
429 289 429
215 578 536 536 578 215
Prof. Dr. Qaisar Ali CE 5115 Units: ft-kip
Advance Design of Reinforced Concrete Structures Fall 2011
60

30
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 03: Frame Analysis (E-W Exterior Frame)
 Step 05: Lateral Distribution of Longitudinal moment (L.M).

Lateral
distribution
factors (D.F)Lat
0.60 0.60 0.60
1.00 0.75 0.75 0.75 0.75 1.00
61
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 03: Frame Analysis (E-W Exterior Frame)
 Step 05: Lateral Distribution of Longitudinal moment (L.M).

ML,ext- = 215 kip-ft


ML,ext+ = 429 kip-ft
ML,int- = 578 kip-ft
ML,- = 536 kip-ft
ML,+ = 289 kip-ft

MLat = ML × (D.F)Lat
215 257 434 402 173 769 402 257 215

0 172 144 134 116 134 144 172 0


62
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

31
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 03: Frame Analysis (E-W Exterior Frame)
 Step 05: Lateral Distribution of Longitudinal moment (L.M).

ML,ext- = 215 kip-ft


ML,ext+ = 429 kip-ft
ML,int- = 578 kip-ft
ML,- = 536 kip-ft
ML,+ = 289 kip-ft

MLat per foot = Mlat/strip width

23.8 28.6 48.2 44.7 19.2 44.7 48.2 28.6 23.8

0 17.64 14.76 13.74 11.89 13.74 14.76 17.64 0


63
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 03: Frame Analysis
 Analysis of N-S Interior and Exterior Frame will be same as E-W respective
frames due to square panels.

N-S
Interior
Frame
l2 = 36′-0″

N-S
Exterior
Frame
l2 = 18′-9″
64
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

32
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 04: Design
 For E-W Interior Slab Strip:

Selective values
are used for design.

0 18.22 15.33 14.22 12.3 14.22 15.33 18.22 0

27.3 18.38 27.3


22.8 46 42.7 42.7 46 22.8
l2 = 36′
0 18.22 15.33 14.22 12.3 14.22 15.33 18.22 0

65
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 04: Design
 E-W Exterior Frame.

Selective values
are used for
design

23.8 28.6 48.2 19.2 48.2 28.6 23.8

0 17.64 14.76 11.89 14.76 17.64 0


66
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

33
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 04: Design
 Design of N-S Interior and Exterior Frame will be same as E-
W respective frames due to square panels and also for the
reason that davg is used in design.

 davg = 16.5 – (0.75 inch (cover) + ¾ inch (Assumed bar


diameter) = 15 inch

 This will be used for both directions positive as well as


negative reinforcement.

67
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 05: Detailing (E-W Frames)

Negative Reinforcement in
E-W direction
For M = 46 ft-k =46 x12
= 552 in-k
d = 15
fy = 60 ksi
As = 0.7 in2
#6 @ 12″ #6 @ 6″ #6 @ 6″ #6 @ 12″

#6 @ 18″ #6 @ 18″ #6 @ 18″ #6 @ 18″

#6 @ 12″ #6 @ 6″ #6 @ 6″ #6 @ 12″
68
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

34
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 05: Detailing (N-S Frames)

#6 @ 12″ #6 @ 18″ #6 @ 12″

#6 @ 6″ #6 @ 18″ #6 @ 6″
Negative Reinforcement
in N-S direction

#6 @ 6″ #6 @ 18″ #6 @ 6″

69
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 05: Detailing (N-S Frames)
 Positive reinforcement
 For M = 27 ft-k =27x12 = 324in-k

 d = 15

 fy = 60 ksi

 As = 0.373 in2 This is per foot reinforcement. For 18 feet col strip, this will
be equal to 0.373 x 18 = 6.714 in2

 There are 6 joists in 18 feet with. Therefore per rib reinforcement = 1.12

 Using # 7 bars, 2 bars per joist rib will be provided.

70
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

35
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 05: Detailing (E-W Interior Frame)
18′-0″
#6 @ 6″ c/c

Column Strip (Interior Frame); section taken over support


2 #7 Bars
#6 @ 12″ c/c

2 #7 Bars Column Strip (Exterior Frame); section taken over support


71
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 05: Detailing (E-W Interior Frame)
18′-0″
#6 @ 18″ c/c

Middle Strip (Interior Frame); Section taken over column line


2 #7 Bars
#6 @ 18″ c/c

2 #7 Bars Middle Strip (Exterior Frame); Section taken over column line
72
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

36
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 05: Detailing (E-W Exterior Frame)
9′-0″
#6 @ 6″ c/c

2 #7 Bars Column Strip (Interior Frame); section over support


#6 @ 12″ c/c

2 #7 Bars Column Strip (Exterior Frame); section over support


73
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 05: Detailing (E-W Exterior Frame)
9′-0″
#6 @ 18″ c/c

2 #7 Bars Middle Strip (Interior Frame) ; section over support


#6 @ 18″ c/c

2 #7 Bars Middle Strip (Exterior Frame); section over support


74
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

37
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two-Way Joist
 Step No 04: Design
 Note: For the completion of design problem, the waffle slab
should also be checked for beam shear and punching shear.

75
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Moment Coefficient
Method

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 76

38
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method (Introduction)


 The Moment Coefficient Method included for the first time in
1963 ACI Code is applicable to two-way slabs supported on
four sides of each slab panel by walls, steel beams relatively
deep, stiff, edge beams (h = 3hf).

 Although, not included in 1977 and later versions of ACI code,


its continued use is permissible under the ACI 318-08 code
provision (13.5.1). Visit ACI 13.5.1.

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 77

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs


Ma,neg

la
 Moment Coefficient Method Ma,pos
Mb,neg Mb,pos Mb,neg
 Moments:
Ma, neg = Ca, negwula2 lb Ma,neg

Mb, neg = Cb, negwulb2

Ma, pos, (dl + ll) = M a, pos, dl + M a, pos, ll = Ca, pos, dl × wu, dl × la2 + Ca, pos, ll × wu, ll × la2

Mb, pos, (dl + ll) = Mb, pos, dl + Mb, pos, ll = Cb, pos, dl × wu, dl × lb2 + Cb, pos, ll × wu, ll × lb2

 Where Ca, Cb = Tabulated moment coefficients

wu = Ultimate uniform load, psf

la, lb = length of clear spans in short and long directions respectively.

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 78

39
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method: Cases


 Depending on the support conditions, several cases are possible:

4 spans @ 25′-0″

3 spans @ 20′-0″
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 79

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method: Cases


 Depending on the support conditions, several cases are possible:

4 spans @ 25′-0″
3 spans @ 20′-0″

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 80

40
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method: Cases


 Depending on the support conditions, several cases are possible:

4 spans @ 25′-0″

3 spans @ 20′-0″
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 81

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method: Cases


 Depending on the support conditions, several cases are possible:

4 spans @ 25′-0″
3 spans @ 20′-0″

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 82

41
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Tables:

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 83

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Tables:

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 84

42
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Tables:

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 85

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Tables:

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 86

43
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Tables:

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 87

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Tables:

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 88

44
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Load Coefficient Table:

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 89

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Maximum Spacing and Minimum Reinforcement


Requirement:
 Maximum spacing (ACI 13.3.2):
smax = 2 hf in each direction.

 Minimum Reinforcement (ACI 7.12.2.1):


Asmin = 0.0018 b hf for grade 60.

Asmin = 0.002 b hf for grade 40 and 50.

90
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

45
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Special Reinforcement at Exterior Corner of Slab


 The reinforcement at exterior ends of the slab shall be provided as per ACI
13.3.6 in top and bottom layers as shown.

 The positive and negative reinforcement in any case, should be of a size and
spacing equivalent to that required for the maximum positive moment (per foot
of width) in the panel.

91
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method


 Steps
 Find hmin = perimeter/ 180 = 2(la + lb)/180

 Calculate loads on slab (force / area)

 Calculate m = la/ lb

 Decide about case of slab,

 Use table to pick moment coefficients,

 Calculate moments and then design.

 Apply reinforcement requirements (smax = 2hf, ACI 13.3.2)

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 92

46
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method: Example 1


 A 100′  60′, 3-storey commercial building is to be designed.
The grids of column plan are fixed by the architect.

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 93

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method: Example 1


 Complete analysis of the slab is done by analyzing four panels

4 spans @ 25′-0″

Panel I Panel III Panel III Panel I


3 spans @ 20′-0″

Panel II Panel IV Panel IV Panel II

Panel I Panel III Panel III Panel I

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 94

47
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method: Example 1

 A 100′  60′, 3-storey commercial building: Sizes and Loads.


 Sizes:
 Minimum slab thickness = perimeter/180 = 2 (20+25)/180 = 6″

However, for the purpose of comparison, take hf = 7″

 Columns = 14″  14″ (assumed)

 Beams = 14″  20″ (assumed)

 Loads:
 S.D.L = Nil ; Self Weight = 0.15 x (7/12) = 0.0875 ksf

 L.L = 144 psf ; wu = 0.336 ksf


Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 95

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method: Example 1


 Panels are analyzed using Moment Coefficient Method
4 spans @ 25′-0″
Case = 4 Ma,neg
m = la/lb = 0.8 Mb,neg Mb,pos Mb,neg
Ma,pos
3 spans @ 20′-0″

Ma,neg

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 96

48
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method: Example 1


 Panels are analyzed using Moment Coefficient Method
Case = 4
m = la/lb = 0.8

Ca,neg = 0.071
Cb,neg = 0.029
Ca,posLL = 0.048
Cb,posLL = 0.020
Ca,posDL = 0.039
Cb,posDL = 0.016

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 97

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method: Example 1


 Panels are analyzed using Moment Coefficient Method
Case = 4
m = la/lb = 0.8

Ca,neg = 0.071
Cb,neg = 0.029
Ca,posLL = 0.048
Cb,posLL = 0.020
Ca,posDL = 0.039
Cb,posDL = 0.016

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 98

49
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method: Example 1


 Panels are analyzed using Moment Coefficient Method
Case = 4
m = la/lb = 0.8

Ca,neg = 0.071
Cb,neg = 0.029
Ca,posLL = 0.048
Cb,posLL = 0.020
Ca,posDL = 0.039
Cb,posDL = 0.016

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 99

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method: Example 1


 Panels are analyzed using Moment Coefficient Method
Case = 4
m = la/lb = 0.8

Ca,neg = 0.071
Cb,neg = 0.029
Ca,posLL = 0.048
Cb,posLL = 0.020
Ca,posDL = 0.039
Cb,posDL = 0.016

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 100

50
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method: Example 1


 Panels are analyzed using Moment Coefficient Method
Case = 4
m = la/lb = 0.8

Ca,neg = 0.071
Cb,neg = 0.029
Ca,posLL = 0.048
Cb,posLL = 0.020
Ca,posDL = 0.039
Cb,posDL = 0.016

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 101

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method: Example 1


 Panels are analyzed using Moment Coefficient Method
Case = 4
m = la/lb = 0.8

Ca,neg = 0.071
Cb,neg = 0.029
Ca,posLL = 0.048
Cb,posLL = 0.020
Ca,posDL = 0.039
Cb,posDL = 0.016

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 102

51
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method: Example 1


 Panels are analyzed using Moment Coefficient Method
Case = 4 4 spans @ 25′-0″
m = la/lb = 0.8 Panel I
Ma,neg
Mb,neg Mb,pos Mb,neg
Ca,neg = 0.071
Cb,neg = 0.029 Ma,pos

3 spans @ 20′-0″
Ca,posLL = 0.048 Ma,neg
Cb,posLL = 0.020
Ca,posDL = 0.039
Cb,posDL = 0.016
Ma,neg = 9.5 k-ft
Ma,pos = 6.1 k-ft
Mb,neg = 6.1 k-ft
Mb,pos = 3.9 k-ft
For slab supported on Spandrals, Mneg,ext = 1/3Mpos
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 103

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method: Example 1


 Panels are analyzed using Moment Coefficient Method
Case = 9 4 spans @ 25′-0″
m = la/lb = 0.8 Panel II

Ca,neg = 0.075
Cb,neg = 0.017
3 spans @ 20′-0″

Ma,neg
Ca,posLL = 0.042
Mb,neg Mb,pos Mb,neg
Cb,posLL = 0.017
Ca,posDL = 0.029 Ma,pos
Cb,posDL = 0.010
Ma,neg
Ma,neg = 10.1 k-ft
Ma,pos = 5.1 k-ft
Mb,neg = 3.6 k-ft
Mb,pos = 3.1 k-ft
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 104

52
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method: Example 1


 Panels are analyzed using Moment Coefficient Method
Case = 8
4 spans @ 25′-0″
m = la/lb = 0.8 Ma,neg
Panel III
Mb,neg Mb,pos Mb,neg
Ca,neg = 0.055
Cb,neg = 0.041 Ma,pos

3 spans @ 20′-0″
Ca,posLL = 0.044
Ma,neg
Cb,posLL = 0.019
Ca,posDL = 0.032
Cb,posDL = 0.015
Ma,neg = 7.4 k-ft
Ma,pos = 5.4 k-ft
Mb,neg = 8.6 k-ft
Mb,pos = 3.7 k-ft

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 105

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method: Example 1


 Panels are analyzed using Moment Coefficient Method
Case = 2 4 spans @ 25′-0″
m = la/lb = 0.8
Panel IV
Ca,neg = 0.065
Cb,neg = 0.027
3 spans @ 20′-0″

Ma,neg
Ca,posLL = 0.041
Cb,posLL = 0.017 Mb,neg Mb,pos Mb,neg
Ca,posDL = 0.026 Ma,pos
Cb,posDL = 0.011
Ma,neg = 8.7 k-ft Ma,neg
Ma,pos = 4.9 k-ft
Mb,neg = 5.7 k-ft
Mb,pos = 3.2 k-ft

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 106

53
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method: Example 1


 Slab analysis summary
4 spans @ 25′-0″

9.5 7.4
3.9 3.7
6.1 6.1 6.1 8.6 5.4 8.6

3 spans @ 20′-0″
9.5 7.4
10.1 8.7

3.2 3.2
3.6 3.6 5.7 5.7
5.1 4.9
10.1 8.7

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 107

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method: Example 1


 Slab Reinforcement Details
4 spans @ 25′-0″

C C
A A
B B C B C
3 spans @ 20′-0″

C C
A= #4 @ 12″
A A B = #4 @ 6″
A B B
B B C = #4 @ 4″
C C

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 108

54
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method: Example 1


 Load On Beams from coefficient tables
4 spans @ 25′-0″
B2
Table: Load on beam in panel I, using
Coefficients Panel I

3 spans @ 20′-0″
(wu = 0.336 ksf) B1
Width
(bs) of Load
slab due to
Bea B1
Length panel Wa Wb slab,
m
(ft) support Wwubs
ed by (k/ft)
beam B2
B1 25 10 0.71 - 2.39
B2 25 10 0.71 - 2.39
B4 B3 B3 B3 B4
B3 20 12.5 - 0.29 1.22
B4 20 12.5 - 0.29 1.22

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 109

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method: Example 1


 Load On Beams from coefficient tables
4 spans @ 25′-0″
B2
Table: Load on beam in panel I, using
Coefficients Panel I
3 spans @ 20′-0″

(wu = 0.336 ksf) B1


Width
(bs) of Load
slab due to
Bea B1
Length panel Wa Wb slab,
m
(ft) support Wwubs
ed by (k/ft)
beam B2
B1 25 10 0.71 - 2.39
B2 25 10 0.71 - 2.39
B4 B3 B3 B3 B4
B3 20 12.5 - 0.29 1.22
B4 20 12.5 - 0.29 1.22

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 110

55
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method: Example 1


 Load On Beams from coefficient tables
4 spans @ 25′-0″
B2

3 spans @ 20′-0″
Table: Load on beam in panel I, using
Coefficients B1
(wu = 0.336 ksf)
Width Panel II
(bs) of Load B1
slab due to
Bea
Length panel Wa Wb slab,
m
(ft) support Wwubs
ed by (k/ft) B2
beam
B1 25 10 0.83 - 2.78
B4 B3 B3 B3 B4
B3 20 12.5 - 0.17 0.714
B4 20 12.5 - 0.17 0.714

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 111

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method: Example 1


 Load On Beams from coefficient tables
4 spans @ 25′-0″
B2
3 spans @ 20′-0″

Table: Load on beam in panel I, using


Coefficients B1
(wu = 0.336 ksf)
Width Panel II
(bs) of Load B1
slab due to
Bea
Length panel Wa Wb slab,
m
(ft) support Wwubs
ed by (k/ft) B2
beam
B1 25 10 0.83 - 2.78
B4 B3 B3 B3 B4
B3 20 12.5 - 0.17 0.714
B4 20 12.5 - 0.17 0.714

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 112

56
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method: Example 1


 Load On Beams from coefficient tables
4 spans @ 25′-0″
B2

Panel III

3 spans @ 20′-0″
Table: Load on beam in panel I, using
B1
Coefficients
(wu = 0.336 ksf)
Width
(bs) of Load B1
slab due to
Bea
Length panel Wa Wb slab,
m
(ft) support Wwubs
B2
ed by (k/ft)
beam
B1 25 10 0.55 - 1.84 B4 B3 B3 B3 B4
B3 20 12.5 - 0.45 1.89

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 113

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method: Example 1


 Load On Beams from coefficient tables
4 spans @ 25′-0″
B2

Panel III
3 spans @ 20′-0″

Table: Load on beam in panel I, using


B1
Coefficients
(wu = 0.336 ksf)
Width
(bs) of Load B1
slab due to
Bea
Length panel Wa Wb slab,
m
(ft) support Wwubs
B2
ed by (k/ft)
beam
B1 25 10 0.55 - 1.84 B4 B3 B3 B3 B4
B3 20 12.5 - 0.45 1.89

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 114

57
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method: Example 1


 Load On Beams from coefficient tables
4 spans @ 25′-0″
B2

Table: Load on beam in panel I, using

3 spans @ 20′-0″
Coefficients
(wu = 0.336 ksf) B1
Width
(bs) of Load Panel IV
slab due to B1
Bea
Length panel Wa Wb slab,
m
(ft) support Wwubs
ed by (k/ft)
B2
beam
B1 25 10 0.71 - 2.39
B3 20 12.5 - 0.29 1.22 B4 B3 B3 B3 B4

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 115

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method: Example 1


 Load On Beams from coefficient tables
4 spans @ 25′-0″
B2

Table: Load on beam in panel I, using


3 spans @ 20′-0″

Coefficients
(wu = 0.336 ksf) B1
Width
(bs) of Load Panel IV
slab due to B1
Bea
Length panel Wa Wb slab,
m
(ft) support Wwubs
ed by (k/ft)
beam B2
B1 25 10 0.71 - 2.39
B3 20 12.5 - 0.29 1.22
B4 B3 B3 B3 B4

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 116

58
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs


 Moment Coefficient Method: Example 1
 Load On Beams 4 spans @ 25′-0″

B2
2.39 k/ft 1.84 k/ft

1.22 k/ft 1.22 k/ft 1.89 k/ft 1.89 k/ft

2.39 k/ft 1.84 k/ft

3 spans @ 20′-0″
B1
2.77 k/ft 2.39 k/ft

0.71 k/ft 0.71 k/ft 1.22 k/ft 1.22 k/ft

2.77 k/ft 2.39 k/ft


B1

B2

B4 B3 B3 B3 B4
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 117

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs


 Moment Coefficient Method: Example 1
 Load On Beams 4 spans @ 25′-0″

B2
2.62 k/ft 2.07 k/ft

1.45 k/ft 3.34 k/ft


Loads
including self
3 spans @ 20′-0″

weight of B1
5.39 k/ft 4.46 k/ft
beams 0.23
kip/ft 0.94 k/ft 2.16 k/ft

B1

B2

B4 B3 B3 B3 B4
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 118

59
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method: Example 2


 Similarly, slab analysis results of 25′ × 20′ structure.

4 spans @ 25′-0″
Slab thickness = 6″

Panel I Panel III Panel III Panel I SDL = 40 psf


LL = 60 psf

3 spans @ 20′-0″
fc′ =3 ksi
fy = 40 ksi
Panel II Panel IV Panel IV Panel II
wu = 0.234 ksf

Panel I Panel III Panel III Panel I

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 119

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method: Example 2


 Slab analysis summary
4 spans @ 25′-0″

6.6 5.1
2.6 2.4
4.2 4.0 4.2 6.0 3.5 6.0
3 spans @ 20′-0″

6.6 5.1
7 6.1
1.9 2.0
2.5 2.5 3.9 3.0 3.9
3.2
7 6.1

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 120

60
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method: Example 3


 Similarly, slab analysis results of 20′ × 15′ structure.

4 spans @ 20′-0″
Slab thickness = 6″

Panel I Panel III Panel III Panel I SDL = 40 psf


LL = 60 psf

3 spans @ 15′-0″
fc′ =3 ksi
fy = 40 ksi
Panel II Panel IV Panel IV Panel II
wu = 0.234 ksf

Panel I Panel III Panel III Panel I

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 121

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

Two Way Slabs

 Moment Coefficient Method: Example 3


 Slab analysis summary
4 spans @ 25′-0″

4 3.2
1.3 1.3
2.2 2.5 2.2 3.4 2.2 3.4
3 spans @ 20′-0″

4 3.2
4.1 3.6
0.9 1.0
1.3 1.3 2.1 1.8 2.1
2.0
4.1 3.6

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 122

61
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

References

 CRSI Design Handbook


 ACI 318
 Design of Concrete Structures 13th Ed. by Nilson, Darwin and
Dolan.

Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 123

Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

The End

124
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

62

You might also like