1. An open tank contains a liquid of varying density and the level within the tank must be
accurately measured. The best choice of measurements system would be:
a. Bubble tube
b. Diaphragm box
c. Float and cable
d. Head type with differential pressure transmitter
Answer: c
InstrumentationTools.com
Instrumentation Tools
Learn Instrumentation and Control Engineering. Inst Tools covers topics of Industrial
Instrumentation, PLC, DCS, SCADA, Field Instruments, Analyzers and so on.
https://instrumentationtools.com
a. 10 psi
b. 25 psi
c. 5 psi
d. 15 psi
Answer: c
3. A pressurized tank contains a líquid, SG = 1.0, and the level measuring pressure taps
are 100 inches apart. A pneumatic differential pressure transmitter is used to measure
om
level. The leg that connects the top of the tank to the transmitter is filled with tank líquid.
.c
The top tap should be connected to:
s
a. The low-pressure tap on the transmitter.
ol
b. The high-pressure tap on the transmitter.
c. Either the high- or the low-pressure tap. To
d. The high-pressure tap but through a seal chamber
on
Answer: a
i
at
transmitter is calibrated 0 to 100 inches, when the tank is full will be:
me
d. A measure of density
In
Answer: b
5. A plant has a water tower mounted on top of an 80-foot platform. The tank is 30 feet
high. What is the height of water in the tank if a pressure gauge on the second floor,
height 15 feet, reads 40 psi.
a. Full
b. 12.42 feet
c. 4.74 feet
d. 27.42 feet
Answer: d
a. 11.3 pound
b. 426.3 pounds
c. 35.5 pounds
d. 1.47 pounds
InstrumentationTools.com
Instrumentation Tools
Learn Instrumentation and Control Engineering. Inst Tools covers topics of Industrial
Instrumentation, PLC, DCS, SCADA, Field Instruments, Analyzers and so on.
https://instrumentationtools.com
Answer: a
7. A closed tank level (Sa = 0.83) is measured with a differential pressure transmitter.The
level may vary from 10 to 100 inches.The high-pressure tap is 10 inches above the
transmitter and a water seal fluid is used. A pressure repeater is used for the top tank
pressure. The differential pressure transmitter should be calibrated
a. 10 to 100 inches
b. 10 to 84.7 inches
om
c. 8.3 to 74.7 inches
.c
d. 8.3 to 98.3 inches
s
Answer: b
ol
To
on
8. To resist the corrosive effects of a very unusual, highly explosive chemical, a storaget
i
ank is lead-lined.L evel measuremenist difficult because the material also solid if lies
at
once it enter a measuring tap. To measure the level with accuracy the best choice would
be:
nt
me
a. Weigh the tank and its contents and zero out the tare weight of the tank.
b. Use a radioactive level measurement.
ru
Answer: a
a. 0.6
b. 0.8
c. 1.0
d. 1.6
Answer: c
10. A density measuring system is set up as shown in Figure. The H distance is 100
inches and the lower transmitter is calibrated to a 120-inch span. If the transmitter is
pneumatic and delivering a 12-psi signal, the specific gravity of the tank’s contents is:
InstrumentationTools.com
Instrumentation Tools
Learn Instrumentation and Control Engineering. Inst Tools covers topics of Industrial
Instrumentation, PLC, DCS, SCADA, Field Instruments, Analyzers and so on.
https://instrumentationtools.com
om
s .c
ol
To
i on
at
nt
me
ru
Fig : In an open or closed tank with varying level and/or pressure where seal fluid or purge is
not suitable, a pressure repeater can be used.
st
In
a. 1.0
b. 0.83
c. 0.9
d. 1.2
Answer: c