You are on page 1of 273

GE Energy

________________________________________________________________________

Bernard W. Cable General Electric International, Inc.


Principal 1 River Road, Building 53-302B
Energy Consulting Schenectady, NY 12345
Tel: (518) 385-4664
e-mail: bernard.cable@ge.com

June 13, 2011

Andrzej Swarcewicz
GE Energy Services
53 Emilii Platter Suite 1200
Warsaw, Poland 00-113

Andrzej,

Attached are the following items, summarizing the results of the recently completed Sonelgaz M’Sila
Unit 25 Generator Protection Panel Relay Setting Calculations:

1. Setting tables for the GE Multilin UR G60 Generator Management Relays and UR T60
Transformer Management Relays installed in the Unit 25 Generator Protection Panel (GPP)
recently constructed for this site. Included on these tables are recommended settings for
the various “active” protection functions in the G60 and T60 relays (i.e., those protection
functions which have been placed into service). The Unit 25 M’Sila Generator Protection
Panel includes two G60 relays associated with gas-turbine generator G3. In addition, the
Unit 25 protection panel includes two T60 relays associated with the TP3 generator step-up
transformer.

2. Setting tables for the GE Multilin F650 Feeder Protection System Relays also installed in the
Unit 25 M’Sila Generator Protection Panel, summarizing recommended settings for the
various “active” protection functions in these F650 relays. The Unit 25 M’Sila Generator
Protection Panel includes one F650 relay associated with the gas-turbine generator G3
“TAM3” Auxiliary Transformer. In addition the Unit 25 M’Sila Generator Protection Panel
includes one F650 relay associated with the “TL2” Station Supply Transformer supplied from
the TP3 generator step-up transformer secondary main distribution bus.

3. Setting tables for the Basler BE1-59N Ground Fault Over-Voltage relay also installed in
conjunction with the Unit 25 M’Sila Generator Protection Panel. The BE1-59N relay is used to
provide Ground Fault protection for the Unit 25 11.5 kV step-up transformer secondary
supply bus.

4. Calculation sheets summarizing the philosophies and procedures used to determine the
recommended settings for the “active” protection functions in the M’Sila Generator G3 UR
G60 relays.
GE Energy
________________________________________________________________________

Andrzej Swarcewicz
June 13, 2011
Page 2

5. A discussion summarizing the philosophies used to determine the recommended settings for
the “active” protection functions in the UR T60 relays associated with the “TP3” step-up
transformer.

6. A discussion summarizing the philosophies used to determine the recommended settings for
the “active” protection functions in the F650 relay associated with the “TAM3” Auxiliary
Supply Transformer.

7. A discussion summarizing the philosophies used to determine the recommended settings for
the “active” protection functions in the F650 relay associated with the “TL2” Station Auxiliary
Transformer supplied from the TP3 GSU secondary main distribution bus.

8. A discussion summarizing the philosophies used to determine the recommended settings for
the BE1-59N relay associated with the Unit 25 11.5 kV main generator distribution bus.

9. Printouts summarizing in detail the recommended settings of the various Input/Output,


Protection, Control and Monitoring functions in the UR G60 relays, UR T60 relays and the
F650 relays evaluated in this analysis.

10. Copies of the Setpoint Files used to load the recommended settings into the subject UR G60
relays, the UR T60 relays and the F650 relays.

11. Copies of the Faceplate Templates created for the UR G60 and UR T60 relays. These
Faceplate Templates are contained within the UR G60 and UR T60 Setpoint Files (in the
section of the file labeled as “FRONT PANEL REPORT”) and can be printed on the supplied
faceplate inserts using the instructions included with the inserts.

12. Copies of the Faceplate Templates created for the F650 relays, supplied as Excel files.
GE Energy
________________________________________________________________________

Andrzej Swarcewicz
June 13, 2011
Page 3

The recommended UR G60, UR T60, F650 and BE1-59N relay settings summarized in this letter report
are based in general upon the data shown on the one-line diagram (Drawing 132E6199) and
generator protection/control panel drawings (Drawing 231D8388) supplied for this analysis. Copies
of this supplied data are not included with this letter report but can be provided if desired.

Thanks,

Bernie
GE Energy Services MCS
For
Sonelgaz Algeria
M’Sila Unit 25

Generator/Step-Up Transformer
Protection Panel
Relay Settings Study

June 13, 2011


Revision 0.0
GE Energy
________________________________________________________________________

Revision History
Rev Date Author(s) Significant Changes
0.0 13 June 2011 Bernie Cable Original Issue

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

Foreword
This report was prepared for GE Energy Services MCS by General Electric International Inc. – Energy
Consulting (GEII-EC) in Schenectady, NY. Questions concerning this report can be referred to:

Bernie Cable
General Electric International, Inc.
Building 53, Room 302B
Schenectady, New York 12345
Phone: (518) 385-4664
e-mail: bernard.cable@ge.com

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

Legal Notice

This report was prepared by General Electric International – Energy Consulting (GEII-EC) as an
account of work sponsored by GE Energy Services MCS. Neither GE Energy Services MCS nor GEII-
EC, nor any person acting on behalf of either:

1. Makes any warranty or representation, expressed or implied, with respect to the use of any
information contained in this report, or that the use of any information, apparatus, method, or
process disclosed in the report may not infringe privately owned rights; or

2. Assumes any liabilities with respect to the use of or damage resulting from the use of any
information, apparatus, method, or process disclosed in the report.

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

Table of Contents

1. G60 SETTING CALCULATIONS: SUMMARY OF SUPPLIED DATA/ASSUMPTIONS ............................................................1


1.1 INTRODUCTION........................................................................................................................................................................................................ 1
1.2 GENERATOR DATA .................................................................................................................................................................................................. 1
1.3 PROTECTIVE RELAY DATA ...................................................................................................................................................................................... 2
1.4 INPUT CT AND VT DATA (“PRIMARY” UR G60 RELAYS) ................................................................................................................................... 3
1.5 INPUT CT AND VT DATA (“BACKUP” UR G60 RELAYS) .................................................................................................................................... 4
1.6 CONTACT INPUT AND CONTACT OUTPUT DATA (“PRIMARY” UR G60 RELAYS) ............................................................................................. 6
1.7 CONTACT INPUT AND CONTACT OUTPUT DATA (“BACKUP” UR G60 RELAYS) .............................................................................................. 9
1.8 OBSERVATIONS/RECOMMENDATIONS................................................................................................................................................................ 12
2. T60 SETTING CALCULATIONS: SUMMARY OF SUPPLIED DATA/ASSUMPTIONS ......................................................... 17
2.1 INTRODUCTION...................................................................................................................................................................................................... 17
2.2 STEP-UP TRANSFORMER DATA........................................................................................................................................................................... 17
2.3 PROTECTIVE RELAY DATA .................................................................................................................................................................................... 18
2.4 INPUT CT AND VT DATA ...................................................................................................................................................................................... 19
2.5 INPUT CT AND VT DATA (“BACKUP” UR T60 RELAYS) ................................................................................................................................... 21
2.6 CONTACT INPUT AND CONTACT OUTPUT DATA (“PRIMARY” UR T60 RELAYS) ............................................................................................ 24
2.7 CONTACT INPUT AND CONTACT OUTPUT DATA (“BACKUP” UR T60 RELAY) ............................................................................................... 28
2.8 SETTING PHILOSOPHIES ....................................................................................................................................................................................... 32
2.9 PERCENT DIFFERENTIAL AND INST DIFFERENTIAL PROTECTION FUNCTIONS (87T, 87I) ............................................................................. 33
2.9.1 Percent Differential and Instantaneous Differential Settings (87T, 87I) ............................................................................ 33
2.10 SETTING PHILOSOPHIES: PRIMARY AND SECONDARY PHASE OVERCURRENT PROTECTION ....................................................................... 35
2.11 SECONDARY (11.5 KV GEN NEUTRAL, WINDING 2) PHASE OVERCURRENT PROTECTION (51S) .............................................................. 37
2.11.1 Winding 2 (Secondary) Phase Overcurrent Relay Settings (51S) ................................................................................... 37
2.12 PRIMARY PHASE OVERCURRENT PROTECTION FUNCTION (50/51P)............................................................................................................. 39
2.12.1 Winding 1 (Transformer Primary) Phase Overcurrent Relay Settings (50/51P)....................................................... 40
2.13 PRIMARY GROUND OVERCURRENT PROTECTION FUNCTION (51NP) ............................................................................................................ 43
2.13.1 Winding 1 (Transformer Primary) Ground Overcurrent Relay Settings (51NP) ....................................................... 43
2.14 SETTING PHILOSOPHIES: AUXILIARY TRANSFORMER PRIMARY PHASE OVERCURRENT PROTECTION ........................................................ 45
2.15 11.5 KV AUX TRANSFORMER (WINDING 3) PHASE OVERCURRENT PROTECTION (50/51 AUX) ............................................................... 46
2.15.1 Winding 3 (11.5 kV Aux Transformer) Phase Overcurrent Relay Settings (50/51 Aux) ........................................ 46
2.16 OVER-EXCITATION PROTECTION FUNCTION (24) ............................................................................................................................................. 48
2.16.1 Over-Excitation Trip Relay Settings (24) ................................................................................................................................... 48
2.17 BACKUP 11.5 KV BUS GROUND FAULT PROTECTION FUNCTION (64B) ...................................................................................................... 50
2.18 OBSERVATIONS/RECOMMENDATIONS................................................................................................................................................................ 51
3. F650 SETTING CALCULATIONS (800 KVA “TAM3” TURBINE AUX SUPPLY TRANSFORMERS) ..................................... 55
3.1 INTRODUCTION...................................................................................................................................................................................................... 55
3.2 “TAM3” GAS-TURBINE AUXILIARY SUPPLY TRANSFORMER DATA ................................................................................................................ 55
3.3 PROTECTIVE RELAY DATA .................................................................................................................................................................................... 56
3.4 INPUT CT AND VT DATA ...................................................................................................................................................................................... 57
3.5 CONTACT INPUT AND CONTACT OUTPUT DATA ............................................................................................................................................... 58
3.6 SETTING PHILOSOPHIES ....................................................................................................................................................................................... 60
3.7 SETTING PHILOSOPHIES: PRIMARY PHASE OVERCURRENT PROTECTION ...................................................................................................... 61
3.8 PRIMARY PHASE OVERCURRENT PROTECTION FUNCTION (50/51P)............................................................................................................. 61
3.8.1 Primary Phase Overcurrent Relay Settings (50/51P) ................................................................................................................ 61
3.8.2 Discussion .................................................................................................................................................................................................... 63
3.9 OBSERVATIONS/RECOMMENDATIONS................................................................................................................................................................ 65

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

4. F650 SETTING CALCULATIONS (3000 KVA “TL2” STATION AUX SUPPLY TRANSFORMER) ......................................... 66
4.1 INTRODUCTION...................................................................................................................................................................................................... 66
4.2 “TL2” STATION AUXILIARY SUPPLY TRANSFORMER DATA .............................................................................................................................. 66
4.3 PROTECTIVE RELAY DATA .................................................................................................................................................................................... 67
4.4 INPUT CT AND VT DATA ...................................................................................................................................................................................... 68
4.5 CONTACT INPUT AND CONTACT OUTPUT DATA ............................................................................................................................................... 69
4.6 SETTING PHILOSOPHIES ....................................................................................................................................................................................... 71
4.7 SETTING PHILOSOPHIES: PRIMARY PHASE OVERCURRENT PROTECTION ...................................................................................................... 72
4.8 PRIMARY PHASE OVERCURRENT PROTECTION FUNCTION (50/51P)............................................................................................................. 72
4.8.1 Primary Phase Overcurrent Relay Settings (50/51P) ................................................................................................................ 72
4.8.2 Discussion .................................................................................................................................................................................................... 74
4.9 OBSERVATIONS/RECOMMENDATIONS................................................................................................................................................................ 76
5. BE1-59N SETTING CALCULATIONS (11.5 KV MAIN DISTRIBUTION BUSES) .................................................................. 77
5.1 INTRODUCTION...................................................................................................................................................................................................... 77
5.2 BE1-59N RELAY DATA ....................................................................................................................................................................................... 77
5.3 CONTACT OUTPUT DATA ..................................................................................................................................................................................... 78
5.4 SETTING PHILOSOPHIES ....................................................................................................................................................................................... 78
5.4.1 Suggested Settings (64B)....................................................................................................................................................................... 78
6. RECOMMENDED PROTECTIVE DEVICE SETTING TABLES ................................................................................................ 79
6.1 INTRODUCTION...................................................................................................................................................................................................... 79
6.1.1 126.875 MVA, 11.5 kV Gen G3– UR G60 Generator Management Relay......................................................................... 81
6.1.2 GSU TP3 (125 MVA, 240.75/11.5 kV) – UR T60 Relay ................................................................................................................ 94
6.1.3 Station Aux Transformer TL2 (3000 kVA, 11.5/6.2 kV) – F650 Relay ............................................................................... 104
6.1.4 Gen Aux Transformer TAM3 (800 kVA, 11.5/0.4 kV) – F650 Relay ................................................................................... 109
6.1.5 11.5 kV Main Distribution Bus TP3S– BE1-59N Bus Ground Fault Relay ...................................................................... 114
7. APPENDIX 1: UR G60 SETTING CALCULATION SHEETS (GENERATOR G3) ................................................................. 115

8. APPENDIX 2: UR G60 SETTING FILE SUMMARY (GENERATOR G3)............................................................................... 116

9. APPENDIX 3 UR T60 SETTING FILE SUMMARY (STEP-UP TRANSFORMER TP3) ......................................................... 117

10. APPENDIX 4: F650 SETTING FILE SUMMARY (STATION AUXILIARY TRANSFORMER TL2) ................................... 118

11. APPENDIX 5: F650 SETTING FILE SUMMARY (GEN AUXILIARY TRANSFORMER TAM3) ....................................... 119

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


G60 Relay Application: 126.875 MVA Gas-Turbine Generator G3

1. G60 Setting Calculations: Summary of Supplied Data/Assumptions


1.1 Introduction
Attached to this letter report are calculation sheets summarizing the philosophies and procedures
used to determine recommended settings for the “Active” (in service) protection functions included
in the G60 Generator Management Relays being applied with the subject M’Sila Unit 25 126.875
MVA Gas-Turbine Generator. Included in this attachment and in the following discussions is a
summary of the significant assumptions used to determine these recommended settings.

1.2 Generator Data


The recommended G60 relay settings provided in this study are based upon the following known
and assumed data items for this Generator:

a) Generator Data:
 Nominal Output Ratings = 126.875 MVA, 0.80 p.f., 11.5 kV, 6370 Amps, 50 Hz (**)
 Phase Sequence = 1-2-3 (A significant assumption, should be verified).
 Direct-Axis Saturated Sub-Transient Reactance X”DV = 16.7% (**)
 Direct-Axis Saturated Transient Reactance X’DV = 24.3% (**)
 Direct-Axis Saturated Synchronous Reactance XDV = 197.8% (**)
 Short-Circuit Sub-Transient Time Constant T”D = 0.04 sec (**)
 Short-Circuit Transient Time Constant T’D = 0.866 sec (**)
 Armature DC Time-Constant = TA = 0.274 sec (**)
 Continuous Unbalanced Current Capability I2C = 8% (**)
 Rotor Short-Time Thermal Capacity I22t = 10 (**)

(**): All Generator parameters (summarized above) were taken from generator data sheets previously
supplied for the Tiaret 126.875 MVA Gas-Turbine Generators. For this analysis it is assumed that the
M’Sila 126.875 MVA generators are identical in design/Reactance’s/Time Constants, etc. as the Tiaret
generators. All Generator Reactance’s are assumed to be stated on the previously supplied Tiaret
data sheets on a 126.875 MVA, 11.5 kV Base.

Note that this represents an important assumption since settings of many of the active (in service)
G60 protection functions are based upon these generator electrical characteristics. If actual
characteristic data is available from station records for the M’Sila Unit 25 turbine-generator this
actual data can be used to verify or modify (as required) the G60 protection function settings.

PAGE 1

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


G60 Relay Application: 126.875 MVA Gas-Turbine Generator G3

1.3 Protective Relay Data


The recommended G60 relay settings provided in this study are based upon the following assumed
G60 Relay Order Code and Firmware Version:

 G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
 Version 5.7X

Before beginning relay testing/commissioning the UR G60 relay Order Code and Firmware Version
used to complete this analysis (and summarized above) should be compared against the actual (as
installed) UR G60 relay Order Code/Version. Modifications to the recommended relay settings and/or
the supplied UR G60 relay setting file may be required if the actual UR G60 Order Code/Firmware
Version is different than the Order Code/Version used in this analysis.

PAGE 2

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


G60 Relay Application: 126.875 MVA Gas-Turbine Generator G3

1.4 Input CT and VT Data (“Primary” UR G60 Relays)


The recommended “Primary” G60 relay settings are based upon the following assumptions
concerning the CT’s and VT’s which will be used to supply the relay:

Primary UR G60 Relays (associated with the 126.875 MVA Generator):


o Line-Side Phase CT’s (Inputs F1/F2/F3): These Line-Side Phase CT’s are connected in
Wye, and have a Ratio of 7500/1 Amperes. These line-side Phase CT’s are connected
to the F1c/b, F2c/b and F3c/b CT Inputs. Note that these same Phase CT’s are also
used to supply the Backup UR G60 Relay associated with this Generator/GSU
combination.

o Line-Side Neutral CT Input (Input F4): Not used in this application.

o Generator-Side Phase VT Inputs (Inputs F5/F6/F7): These Generator-Side Phase VT’s


are connected wye primary-wye secondary, and have a Ratio of 115/1. These
generator-side Phase VT’s are connected to the F5a/c, F6a/c and F7a/c VT Inputs.

o Neutral-Side Ground (Auxiliary) VT Input (Input F8): This input is connected to the
secondary winding of the (11500/3)/100 Volt single-phase Distribution
Transformer/Resistor combination (“NGT”) installed between the Generator Neutral
and Ground. The secondary of this NGT is connected to the F8a/c VT Input. Note that
this same NGT is also used to supply the Backup UR G60 Relay associated with this
Generator/GSU combination.

o Neutral-Side Phase CT Inputs (Inputs M1/M2/M3): These Neutral-Side Phase CT’s are
connected in Wye, and have a Ratio of 7500/1 Amperes. These neutral-side Phase
CT’s are connected to the M1c/b, M2c/b and M3c/b CT Inputs.

o Neutral-Side Ground CT Input (Input M4): Not used in this application.

o Bus-Side Phase VT Inputs (Inputs M5/M6/M7): These Bus-Side Phase VT’s are
connected wye primary-wye secondary, and have a Ratio of 115/1. These bus-side
Phase VT’s are connected to the M5a/c, M6a/c and M7a/c VT Inputs. Note that these
same Bus-Side VT’s are also used to supply the Backup UR G60 Relay associated with
this Generator/GSU combination.

o Bus-Side Auxiliary VT Input (Input M8): Not used in this application.

PAGE 3

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


G60 Relay Application: 126.875 MVA Gas-Turbine Generator G3

1.5 Input CT and VT Data (“Backup” UR G60 Relays)


The recommended “Backup” G60 relay settings are based upon the following assumptions
concerning the CT’s and VT’s which will be used to supply the relay:

Backup UR G60 Relays (associated with each of the 126.875 MVA Generators):
o Line-Side Phase CT’s (Inputs F1/F2/F3): These Line-Side Phase CT’s are connected in
Wye, and have a Ratio of 7500/1 Amperes. These line-side Phase CT’s are connected
to the F1c/b, F2c/b and F3c/b CT Inputs. Note that these same Phase CT’s are also
used to supply the Primary UR G60 Relay associated with this Generator/GSU
combination.

o Line-Side Neutral CT Input (Input F4): Not used in this application.

o Generator-Side Phase VT Inputs (Inputs F5/F6/F7): These Generator-Side Phase VT’s


are connected wye primary-wye secondary, and have a Ratio of 115/1. These
generator-side Phase VT’s are connected to the F5a/c, F6a/c and F7a/c VT Inputs.

o Neutral-Side Ground (Auxiliary) VT Input (Input F8): This input is connected to the
secondary winding of the (11500/3)/100 Volt single-phase Distribution
Transformer/Resistor combination (“NGT”) installed between the Generator Neutral
and Ground. The secondary of this NGT is connected to the F8a/c VT Input. Note that
this same NGT is also used to supply the Primary UR G60 Relay associated with this
Generator/GSU combination.

o Neutral-Side Phase CT Inputs (Inputs M1/M2/M3): These Neutral-Side Phase CT’s are
connected in Wye, and have a Ratio of 7500/1 Amperes. These neutral-side Phase
CT’s are connected to the M1c/b, M2c/b and M3c/b CT Inputs.

o Neutral-Side Ground CT Input (Input M4): Not used in this application.

o Bus-Side Phase VT Inputs (Inputs M5/M6/M7): These Bus-Side Phase VT’s are
connected wye primary-wye secondary, and have a Ratio of 115/1. These bus-side
Phase VT’s are connected to the M5a/c, M6a/c and M7a/c VT Inputs. Note that these
same Bus-Side VT’s are also used to supply the Primary UR G60 Relay associated with
this Generator/GSU combination.

o Bus-Side Auxiliary VT Input (Input M8): Not used in this application.

PAGE 4

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


G60 Relay Application: 126.875 MVA Gas-Turbine Generator G3

Based upon the supplied data, the nominal secondary voltage which will be applied to the
generator-side phase voltage inputs of each UR G60 relay = 100 Volts  = 57.7 Volts N, as
summarized below:

11500 Vph  ph  100Vph  ph  100 Vph  N  57.7Vph  N


Vrelay 
1151  3

Similarly, the nominal secondary voltage which will be applied to the bus-side phase voltage inputs
of each UR G60 relay will also = 100 Volts = 57.7 Volts N, as summarized below:

11500 Vph  ph  100Vph  ph  100 Vph  N  57.7Vph  N


Vrelay 
1151  3

As will be discussed further in a subsequent section of this report these secondary voltages should
be verified via comparison with other measurement devices during GPP commissioning and initial
generator startup. In addition, these secondary voltages should be further verified during unit
commissioning via actual measurement (using a multi-meter) at the relay VT input terminals when the
unit is operating at rated output voltage.

PAGE 5

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


G60 Relay Application: 126.875 MVA Gas-Turbine Generator G3

1.6 Contact Input and Contact Output Data (“Primary” UR G60 Relays)
The Primary and Backup G60 relays utilized in this application are also equipped with Digital
(Contact) inputs and Contact outputs which can (within certain restrictions) be assigned to perform
user-specified functions. The recommended “Primary” G60 relay settings provided in this analysis
are based upon the following assumptions for each of these Contact inputs and Contact outputs:

Primary UR G60 Relays (associated with the 126.875 MVA Generator):


o Assignable Digital (Contact) Input H7a: Connected to 52a contact in generator output
Circuit Breaker “52G”.
o Assignable Digital (Contact) Input H7c: Connected to 52b contact in generator output
Circuit Breaker “52G”.
o Assignable Digital (Contact) Input H8a: Connected to Contact Output “W7” of Backup
UR T60 relay (used to provide a C/B 52G Transfer Trip signal path from the backup UR
T60 relay).
o Assignable Digital (Contact) Input H8c: Connected to Contact Output “W7” of Primary
UR T60 relay (used to provide a C/B 52G Transfer Trip signal path from the primary UR
T60 relay).

It is important that both 52a and 52b position contacts be connected to the G60 relay Contact Inputs
shown above, as these contacts are used in selected portions of the G60 protection scheme to permit
(or in some cases) block operation of certain protection functions.

o Assignable Digital (Contact) Input P1a: Provides a “TP3 VT CB4 Open” indication.
o Assignable Digital (Contact) Input P1c: Used to provide a “Station Trip 52G” indication.
o Assignable Digital (Contact) Input P2a: Available for customer use if desired.
o Assignable Digital (Contact) Input P2c: Available for customer use if desired.
o Assignable Digital (Contact) Input P3a: Used to provide a “52LX1” position indication.
o Assignable Digital (Contact) Input P3c: Available for customer use if desired.
o Assignable Digital (Contact) Input P4a: Available for customer use if desired.
o Assignable Digital (Contact) Input P4c: Available for customer use if desired.
o Assignable Digital (Contact) Input P5a: Available for customer use if desired.
o Assignable Digital (Contact) Input P5c: Available for customer use if desired.
o Assignable Digital (Contact) Input P6a: Available for customer use if desired.
o Assignable Digital (Contact) Input P6c: Available for customer use if desired.
o Assignable Digital (Contact) Input P7a: Available for customer use if desired.
o Assignable Digital (Contact) Input P7c: Available for customer use if desired.
o Assignable Digital (Contact) Input P8a: Available for customer use if desired.
o Assignable Digital (Contact) Input P8c: Available for customer use if desired.

PAGE 6

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


G60 Relay Application: 126.875 MVA Gas-Turbine Generator G3

Contact Input Data and Contact Output Data (Primary UR G60 Relays) (Continued)

o Contact Output H1: Connected to Lockout Relay 86G1 Trip Circuit. (##)
o Contact Output H2: Connected to Generator C/B 52G Trip Circuit #1. (##)
o Contact Output H3: Connected to Generator C/B 52G Trip Circuit #2. (##)
o Contact Output H4: Connected to Lockout Relay 86T1 Trip Circuit. (##)
o Contact Output H5: Provides a “TP3 VT CB4 Open Trip” output indication.
o Contact Output H6: Provides a “Change Source 400V CCM” output.

(##) Note: Install external jumper between “a” and “b” terminals of output contact.

PAGE 7

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


G60 Relay Application: 126.875 MVA Gas-Turbine Generator G3

Contact Input Data and Contact Output Data (Primary UR G60 Relays) (Continued)

o Contact Output U1: Provides an “87ST Trip” output indication.


o Contact Output U2: Provides a “50P Trip” output indication.
o Contact Output U3: Provides a “51P Trip” output indication.
o Contact Output U4: Provides a “40 Trip” output indication.
o Contact Output U5: Provides a “46 Trip” output indication.
o Contact Output U6: Provides a “32 Trip” output indication.
o Contact Output U7: Provides a “95 (24) Trip” output indication.
o Contact Output U8: Provides a “27P Trip” output indication.
o Contact Output U9: Provides a “59P Trip” output indication.
o Contact Output U10: Provides a “50/27 Trip” output indication.
o Contact Output U11: Provides a “50/Offline Trip” output indication.
o Contact Output U12: Provides an “81 Trip” output indication.
o Contact Output U13: Provides a “64G Trip” output indication.
o Contact Output U14: Provides a “21/78 Trip” output indication.

o Contact Output W1: Provides an “All Trips” output indication.


o Contact Output W2: Provides an “All Alarms” output indication.
o Contact Output W3: Provides a “Turbine Normal Stop” output.
o Contact Output W4: Provides a “Turbine Trip Stop” output.
o Contact Output W5: Provides a “41EX Trip” output.
o Contact Output W6: Provides a “Change Source 6 kV” output.
o Contact Output W7: Connected to Backup T60 Relay Input H8a (used to provide a C/B
52L Transfer Trip signal path to the backup UR T60 relay).
o Contact Output W8: Connected to Primary T60 Relay Input H8c (used to provide a C/B
52L Transfer Trip signal path to the primary UR T60 relay).

PAGE 8

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


G60 Relay Application: 126.875 MVA Gas-Turbine Generator G3

1.7 Contact Input and Contact Output Data (“Backup” UR G60 Relays)
The recommended “Backup” G60 relay settings provided in this analysis are based upon the
following assumptions for each of these Contact inputs and Contact outputs:

Backup UR G60 Relays (associated with the 126.875 MVA Generator):


o Assignable Digital (Contact) Input H7a: Connected to 52a contact in generator output
Circuit Breaker “52G”.
o Assignable Digital (Contact) Input H7c: Connected to 52b contact in generator output
Circuit Breaker “52G”.
o Assignable Digital (Contact) Input H8a: Connected to Contact Output “W6” of Primary
UR T60 relay (used to provide a C/B 52G Transfer Trip signal path from the primary UR
T60 relay).
o Assignable Digital (Contact) Input H8c: Connected to Contact Output “W6” of Backup
UR T60 relay (used to provide a C/B 52G Transfer Trip signal path from the backup UR
T60 relay).

It is important that both 52a and 52b position contacts be connected to the G60 relay Contact Inputs
shown above, as these contacts are used in selected portions of the G60 protection scheme to permit
(or in some cases) block operation of certain protection functions.

o Assignable Digital (Contact) Input P1a: Provides a “TP3 VT CB4 Open” indication.
o Assignable Digital (Contact) Input P1c: Used to provide a “Station Trip 52G” indication.
o Assignable Digital (Contact) Input P2a: Available for customer use if desired.
o Assignable Digital (Contact) Input P2c: Available for customer use if desired.
o Assignable Digital (Contact) Input P3a: Used to provide a “52LX1” position indication.
o Assignable Digital (Contact) Input P3c: Available for customer use if desired.
o Assignable Digital (Contact) Input P4a: Available for customer use if desired.
o Assignable Digital (Contact) Input P4c: Available for customer use if desired.
o Assignable Digital (Contact) Input P5a: Available for customer use if desired.
o Assignable Digital (Contact) Input P5c: Available for customer use if desired.
o Assignable Digital (Contact) Input P6a: Available for customer use if desired.
o Assignable Digital (Contact) Input P6c: Available for customer use if desired.
o Assignable Digital (Contact) Input P7a: Available for customer use if desired.
o Assignable Digital (Contact) Input P7c: Available for customer use if desired.
o Assignable Digital (Contact) Input P8a: Available for customer use if desired.
o Assignable Digital (Contact) Input P8c: Available for customer use if desired.

PAGE 9

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


G60 Relay Application: 126.875 MVA Gas-Turbine Generator G3

Contact Input Data and Contact Output Data (Backup UR G60 Relays) (Continued)

o Contact Output H1: Connected to Lockout Relay 86G2 Trip Circuit. (##)
o Contact Output H2: Connected to Generator C/B 52G Trip Circuit #1. (##)
o Contact Output H3: Connected to Generator C/B 52G Trip Circuit #2. (##)
o Contact Output H4: Connected to Lockout Relay 86T2 Trip Circuit. (##)
o Contact Output H5: Provides a “TP3 VT CB4 Open Trip” output indication.
o Contact Output H6: Provides a “Change Source 400V CCM” output.

(##) Note: Install external jumper between “a” and “b” terminals of output contact.

PAGE 10

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


G60 Relay Application: 126.875 MVA Gas-Turbine Generator G3

Contact Input Data and Contact Output Data (Backup UR G60 Relays) (Continued)

o Contact Output U1: Provides an “87ST Trip” output indication.


o Contact Output U2: Provides a “50P Trip” output indication.
o Contact Output U3: Provides a “51P Trip” output indication.
o Contact Output U4: Provides a “40 Trip” output indication.
o Contact Output U5: Provides a “46 Trip” output indication.
o Contact Output U6: Provides a “32 Trip” output indication.
o Contact Output U7: Provides a “95 (24) Trip” output indication.
o Contact Output U8: Provides a “27P Trip” output indication.
o Contact Output U9: Provides a “59P Trip” output indication.
o Contact Output U10: Provides a “50/27 Trip” output indication.
o Contact Output U11: Provides a “50/Offline Trip” output indication.
o Contact Output U12: Provides an “81 Trip” output indication.
o Contact Output U13: Provides a “64G Trip” output indication.
o Contact Output U14: Provides a “21/78 Trip” output indication.

o Contact Output W1: Provides an “All Trips” output indication.


o Contact Output W2: Provides an “All Alarms” output indication.
o Contact Output W3: Provides a “Turbine Normal Stop” output.
o Contact Output W4: Provides a “Turbine Trip Stop” output.
o Contact Output W5: Provides a “41EX Trip” output.
o Contact Output W6: Provides a “Change Source 6 kV” output.
o Contact Output W7: Connected to Primary T60 Relay Input H8a (used to provide a
C/B 52L Transfer Trip signal path to the primary UR T60 relay).
o Contact Output W8: Connected to Backup T60 Relay Input H8c (used to provide a C/B
52L Transfer Trip signal path to the backup UR T60 relay).

PAGE 11

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


G60 Relay Application: 126.875 MVA Gas-Turbine Generator G3

1.8 Observations/Recommendations

a) The Ratios and Terminal Connections of all CT’s and VT’s connected to these G60 relays (as
previously listed under “Input CT and VT Data”) should be verified prior to Unit 25 generator
startup/operation. Modifications of recommended relay settings will be required if the
Terminal Connections or Ratios of any of the actual (installed) CT’s and/or VT’s are different
than the listed Connections/Ratios.

b) Following generator startup, the Connections and Ratios of the installed VT’s should be
further verified by comparing the generator-side and bus-side phase-to-phase and phase-
to-neutral voltages measured/displayed by each G60 relay (using the Actual Values
functions in the relay) with the corresponding phase-to-phase and phase-to-neutral voltages
measured by other devices. In addition, the Connections and Ratios of the installed CT’s
should be further verified by comparing the phase current values measured/displayed by
each G60 relay (using the Actual Values functions in the relay) with phase current values
measured by other devices.

c) The Contact Input and Contact Output assignments associated with these G60 relays (as
previously listed under “Contact Input and Contact Output Data”) should be verified prior to
Unit 25 generator startup/operation. Modifications of recommended relay settings will be
required if the actual Contact Input and/or Contact Output connections are different than
the listed Connections.

It is important that a field verification of actual (as installed) CT and VT Ratios, CT and VT connections
and Contact Input and Contact Output assignments as described in previous sections of this letter
report be completed prior to Unit 25 startup/operation. Providing and maintaining the desired
levels of protection to this turbine-generator by these installed G60 relays requires that the CT/VT
Ratios and connections along with the Contact Input and Contact Output assignments exactly
match the previously listed Ratios, connections and assignments.

PAGE 12

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


G60 Relay Application: 126.875 MVA Gas-Turbine Generator G3

d) Data on the actual Motoring (Reverse Power) requirements for this turbine-generator were
not available from the supplied data. For this reason a relatively low available Pickup setting
(2% of Generator Rated MVA * Rated p.f.) was selected for the Reverse Power protection
functions in these G60 relay applications. Note that because of the minimum operating
current requirements for the G60 relay the actual (in service) Trip operating points for the
relay may be higher than the programmed setpoints. The actual Trip operating points (in
primary MW’s) should be determined/verified through Test. In addition, actual required
Reverse Power (Motoring) data should be obtained for this unit from the turbine-generator
manufacturer if possible and compared to the actual Trip Pickup setpoints determined via
test. If the Reverse Power Pickup Trip operating points provided in this study are not suitable
for detecting the actual required Motoring Power for this unit setting changes or other
means (such as use of the Low Forward Power protection function) may be required to
reliably detect turbine-generator Motoring.

e) It is important that all VT Fuse Failures be addressed and corrected quickly, since several
important protection functions are presently blocked following detection of a VT Fuse Failure
(to prevent possible protection function mis-operation). Proper operation of the VT Fuse
Failure function in the G60 relay (and proper operation of the VT Fuse failure Alarm output)
should be verified through test prior to generator startup/operation. Examples of the
protection functions which are blocked following VT Fuse Failures are:

o Phase Time Overcurrent (51P)


o Loss of Excitation (40-1, 40-2)
o Reverse Power (Anti-Motoring) Trip (32T)
o Phase Under-Voltage (27P)

If desired by the client, VT Fuse Failure Blocking can be removed from some or all of the
protection functions listed above via field modification of the supplied G60 setpoint files.
However, removal of the VT Fuse Failure Blocking function can introduce the risk of false unit
tripping if a VT Fuse Failure does in fact occur.

PAGE 13

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


G60 Relay Application: 126.875 MVA Gas-Turbine Generator G3

f) In addition, proper operation of selected protection functions requires that both the 52a and
the 52b Status contacts from the generator output circuit breaker be wired to the G60 relays
as described in a previous section of this letter report and that both of these Status contacts
be functioning properly. Failure of either of these Status contacts can adversely affect
operation of selected protection functions (such as inadvertently remove a protection
function from service).

g) During normal operation, LED 31 on the G60 relay faceplate should not be illuminated (this
LED is labeled “VT Fuse Failure”). If this LED is illuminated during normal generator operation
the protection provided to the generator may be compromised, and further field
investigation of possible VT Fuse or supply VT failure is required.

h) During normal operation, LED 3 on the G60 relay faceplate should not be illuminated (this
LED is labeled “Gen C/B Trouble”). If this LED is illuminated during normal generator
operation the protection provided to the generator may be compromised, and further field
investigation of possible 52a and/or 52b contact input failure is required.

i) During normal operation, LED 12 on the G60 relay faceplate should be illuminated (this LED is
labeled “Setting Group 1 On”). If this LED is not illuminated during normal generator
operation the protection provided to the generator may be significantly compromised, and
further field investigation of UR G60 relay failure is required.

j) During normal operation, either LED 1 on the G60 relay faceplate (labeled as “Gen C/B Open”)
or LED 2 (labeled as “Gen C/B Closed”) should be illuminated, depending upon the status of
output circuit breaker 52G. If neither LED is illuminated during normal generator operation
further field investigation of the possible failure of the 52a and/or 52b contact inputs from
the 11.5 kV Generator C/B into the G60 relay is recommended.

PAGE 14

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


G60 Relay Application: 126.875 MVA Gas-Turbine Generator G3

k) During generator operation none of the following LED’s on the G60 relay faceplate should be
illuminated:

a. LED 24 (this LED is labeled “All Alarms”)


b. LED 25 (this LED is labeled “49/A Operate”)
c. LED 26 (this LED is labeled “24/A Operate”).
d. LED 27 (this LED is labeled “46/A Operate”)

If any of these LED’s are illuminated during generator operation further field investigation of
possible generator operational concerns/issues (such as possible generator current
overloads, excessive unbalanced current flows or excessive operating voltage or operating
V/Hz levels) may need to be investigated.

PAGE 15

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


G60 Relay Application: 126.875 MVA Gas-Turbine Generator G3

l) Note that the UR G60 relay has the ability to measure and display the Differential (operating)
and Restraint currents that the relay is using in the Stator Differential setting calculations.
Shown below is a copy of a portion of a page from the UR G60 Instruction Manual showing
the path available to view these currents.

When the Generator is normally operating and reasonably loaded each of the "Operate
Currents" values should be nearly zero and the "Restraint Currents" values should be non-zero.
It is recommended that the operate and restraint current values being measured by the UR
G60 relay be monitored during generator startup/operation. Measured Operate Current
values which are non-zero could indicate an error in CT connections and/or UR G60 relay
setup which should be resolved prior to continued operation of the generator.

If desired by the client, these measured Operate and Restraint Current values can also be
automatically displayed on the G60 Faceplate Display during startup and initial operation by
adding the appropriate descriptions and Mod Bus Addresses to the URPC setup file (under
\Product Setup\User Definable Displays). Once proper differential protection function
operation is verified these measured Operate and Restraint Current values can be eliminated if
desired.

PAGE 16

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

2. T60 Setting Calculations: Summary of Supplied Data/Assumptions


2.1 Introduction
Summarized in the following sections of this letter report are the philosophies and procedures used
to determine recommended settings for the “Active” (in service) protection functions in the UR T60
Transformer Management Relays being applied in conjunction with the 125 MVA, 240.75/11.5 kV
Unit 25 Two-Winding Generator Step-Up Transformer (TP3). This Generator Step-Up Transformer
(GSU) is associated with the 126.875 MVA Unit 25 Gas-Turbine Generator (G3) referenced in previous
sections of this study report. Also included in this section of the letter report is a summary of the
significant assumptions used to determine these recommended settings.

2.2 Step-Up Transformer Data


Manufacturers Test Reports for the subject step-up transformer were not available for this study.
The recommended UR T60 relay settings as described in this letter report are based upon the step-
up transformer ratings summarized below (assumed, based upon data utilized for the previously
completed Tiaret GPP settings studies):

 MVA Rating: 125 MVA ONAF.


 Rated Primary Voltage (phase-to-phase): 240.75 kV.
 Rated Secondary Voltage (phase-to-phase): 11.5 kV.
 Winding Connections (Primary/Secondary): /, 3, 50 Hz,  Primary Winding
operated solidly-grounded.
 Winding Phase Relationships (Primary/Secondary):  0/ -330 (NOTE: This is a
significant assumption relative to proper operation of Percent Differential protection
function and should be verified).
 System Phase Sequence = 1-2-3 (Also a significant assumption requiring verification).
 Rated Primary to Secondary Impedance ZPS = 13.2% on a 125 MVA base, 240.75 kV to
11.5 kV.

Obtaining (if possible) actual Nameplate data for this particular step-up transformer would allow for
more accurate relay setting calculations.

PAGE 17

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

2.3 Protective Relay Data


The recommended T60 relay settings provided in this study are based upon the following assumed
T60 Relay Order Code and Firmware Version:

 T60-J04-HMH-F8L-H6P-M8N-P6D-U4L-W6C
 Version 5.7X

Before beginning relay testing/commissioning the UR T60 relay Order Code and Firmware Version
used to complete this analysis (and summarized above) should be compared against the actual (as
installed) UR T60 relay Order Code/Version. Modifications to the recommended relay settings and/or
the supplied UR T60 relay setting file may be required if the actual UR T60 Order Code/Firmware
Version is different than the Order Code/Version used in this analysis.

PAGE 18

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

2.4 Input CT and VT Data


In addition to the above, the recommended Unit 25 T60 relay settings are based upon the following
assumptions concerning the CT’s and VT’s which will be used to supply the relay:

Primary UR T60 Relay (associated with the 125 MVA Unit 25 GSU):
o Primary (240.75 kV) Phase CT Inputs (Input F1/F2/F3): These Phase CT’s are connected in
Wye, and have a Ratio of 400/1 Amperes. These primary Phase CT’s are connected to the
F1c/b, F2c/b and F3c/b CT Inputs. Note that these same Phase CT’s are also used to
supply the Backup UR T60 Relay associated with this Generator/GSU combination.

o Primary (240.75 kV) Neutral CT Input (Input F4): Input F4c/b is connected into the neutral
(“residual”) circuit of the F1/F2/F3 Phase CT inputs.

o Secondary 1 (126.875 MVA Generator Neutral) Phase CT Inputs (Input M1/M2/M3): These
Generator Neutral Phase CT’s are connected in Wye, and have a Ratio of 7500/1
Amperes. These Phase CT’s are connected to the M1c/b, M2c/b and M3c/b CT Inputs.
Note that these same Phase CT’s are also used to supply the Backup UR T60 Relay
associated with this Generator/GSU combination.

o Secondary 1 (126.875 MVA Generator) Neutral CT Input (Input M4): Not used in this
application.

o Secondary 2 (3 MVA “TL2” Aux Transformer) Phase CT Inputs (Input M5/M6/M7): These TL
Aux Transformer Primary Phase CT’s are connected in Wye, and have a Ratio of 300/1
Amperes. These Phase CT’s are connected to the M5c/b, M6c/b and M7c/b CT Inputs.
Note that these same Phase CT’s are also used to supply the Backup UR T60 Relay
associated with this Generator/GSU combination.

o Secondary 2 (3 MVA “TL2” Aux Transformer) Neutral CT Input (Input M8): Not used in this
application.

PAGE 19

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

Input CT and VT Data (Continued)

o Phase VT Inputs (Input F5/F6/F7): These Phase VT’s are connected wye primary-wye
secondary, and have a Ratio of 115/1. These Phase VT’s are connected to the F5a/c,
F6a/c and F7a/c VT Inputs. Note that these same VT’s are also used to supply the Backup
UR T60 Relay associated with this Generator/GSU combination.

o Ground (Auxiliary) VT Input (Input F8): This single-phase Auxiliary VT input (F8a/c) is
connected to the secondary circuit of the (11500/3)/(100/3) Volt wye primary-broken
delta secondary VT’s also used to supply the BE1-59N over-voltage relay. Note that this
same VT signal is also used to supply the Backup UR T60 Relay associated with this
Generator/GSU combination.

PAGE 20

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

2.5 Input CT and VT Data (“Backup” UR T60 Relays)


The recommended T60 relay settings will be based upon the following assumptions concerning the
CT’s and VT’s which will be used to supply the relay:

Backup UR T60 Relay (associated with the 125 MVA Unit 25 GSU):
o Primary (240.75 kV) Phase CT Inputs (Input F1/F2/F3): These Phase CT’s are connected in
Wye, and have a Ratio of 400/1 Amperes. These primary Phase CT’s are connected to the
F1c/b, F2c/b and F3c/b CT Inputs. Note that these same Phase CT’s are also used to
supply the Primary UR T60 Relay associated with this Generator/GSU combination.

o Primary (240.75 kV) Neutral CT Input (Input F4): Input F4c/b is connected into the neutral
(“residual”) circuit of the F1/F2/F3 Phase CT inputs.

o Secondary 1 (126.875 MVA Generator Neutral) Phase CT Inputs (Input M1/M2/M3): These
Generator Neutral Phase CT’s are connected in Wye, and have a Ratio of 7500/1
Amperes. These Phase CT’s are connected to the M1c/b, M2c/b and M3c/b CT Inputs.
Note that these same Phase CT’s are also used to supply the Primary UR T60 Relay
associated with this Generator/GSU combination.

o Secondary 1 (126.875 MVA Generator) Neutral CT Input (Input M4): Not used in this
application.

o Secondary 2 (3 MVA “TL2” Aux Transformer) Phase CT Inputs (Input M5/M6/M7): These TL
Aux Transformer Primary Phase CT’s are connected in Wye, and have a Ratio of 300/1
Amperes. These Phase CT’s are connected to the M5c/b, M6c/b and M7c/b CT Inputs.
Note that these same Phase CT’s are also used to supply the Primary UR T60 Relay
associated with this Generator/GSU combination.

o Secondary 2 (3 MVA “TL2” Aux Transformer) Neutral CT Input (Input M8): Not used in this
application.

PAGE 21

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

Input CT and VT Data (Continued)

o Phase VT Inputs (Input F5/F6/F7): These Phase VT’s are connected wye primary-wye
secondary, and have a Ratio of 115/1. These Phase VT’s are connected to the F5a/c,
F6a/c and F7a/c VT Inputs. Note that these same VT’s are also used to supply the Primary
UR T60 Relay associated with this Generator/GSU combination.

o Ground (Auxiliary) VT Input (Input F8): This single-phase Auxiliary VT input (F8a/c) is
connected to the secondary circuit of the (11500/3)/(100/3) Volt wye primary-broken
delta secondary VT’s also used to supply the BE1-59N over-voltage relay. Note that this
same VT signal is also used to supply the Primary UR T60 Relay associated with this
Generator/GSU combination.

PAGE 22

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

Input CT and VT Data (Continued)


NOTE: The Ratios and connections assumed for the Primary, Secondary 1 and Secondary 2 Phase
CT’s represent significant assumptions relative to proper operation of the Percent Differential and
Primary/Secondary Phase Overcurrent protection functions and should be verified. In addition, the
Ratios and connections assumed for the Phase VT’s connected to the T60 relay represents a
significant assumption relative to proper operation of the Over-Excitation (V/Hz) protection function
and should be verified.

Based upon the supplied data, the nominal secondary voltage which will be applied to the phase
voltage inputs (Inputs F5, F6, F7) of each of the UR T60 relays = 100 Volts  (57.7 Volts N), as
summarized below:

11500 Vph  ph  100Vph  ph  100 Vph  N  57.7Vph  N


Vrelay 
1151  3

These secondary voltages should be verified during unit commissioning via actual measurement
(using a multi-meter) at the relay VT input terminals when the unit is operating at rated secondary
voltage.

PAGE 23

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

2.6 Contact Input and Contact Output Data (“Primary” UR T60 Relays)
The T60 relays utilized in this application are also equipped with Digital (Contact) inputs and Contact
outputs which can (within certain restrictions) be assigned to perform user-specified functions. The
recommended primary T60 relay settings provided in this analysis are based upon the following
assumptions for each of these Contact inputs and Contact outputs:

Primary UR T60 Relay (associated with the 125 MVA GSU):


o Assignable Digital (Contact) Input H7a: Connected to 52a contact in transformer
primary circuit breaker.
o Assignable Digital (Contact) Input H7c: Connected to 52b contact in transformer
primary circuit breaker.
o Assignable Digital (Contact) Input H8a: Connected to Contact Output “W7” of Backup
UR G60 relay (used to provide a C/B 52L Transfer Trip signal path from the backup UR
G60 relay).
o Assignable Digital (Contact) Input H8c: Connected to Contact Output “W8” of Primary
UR G60 relay (used to provide a C/B 52L Transfer Trip signal path from the primary UR
G60 relay).

PAGE 24

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

Contact Input Data and Contact Output Data (Primary UR T60 Relay) (Continued)

o Assignable Digital (Contact) Input P1a: Connected to 52a contact in generator main
circuit breaker.
o Assignable Digital (Contact) Input P1c: Connected to 52b contact in generator main
circuit breaker.
o Assignable Digital (Contact) Input P2a: Connected to 52a contact in “TL2” transformer
secondary main circuit breaker.
o Assignable Digital (Contact) Input P2c: Connected to 52b contact in “TL2” transformer
secondary main circuit breaker.
o Assignable Digital (Contact) Input P3a: Available for customer use if desired.
o Assignable Digital (Contact) Input P3c: Connected to a “DL91 225 kV Line Protection
Trip” contact output.
o Assignable Digital (Contact) Input P4a: Provides a “TP4 VT CB5 Open” indication.
o Assignable Digital (Contact) Input P4c: Connected to a “TP Refrig Fault” Status
Contact (normally open contact, closes when device operates).
o Assignable Digital (Contact) Input P5a: Connected to a “26TP Stage 1 (Temperature)”
Status Contact (normally open contact, closes when device operates).
o Assignable Digital (Contact) Input P5c: Connected to a “26TP Stage 2 (Temperature)”
Status Contact (normally open contact, closes when device operates).
o Assignable Digital (Contact) Input P6a: Connected to a “49TP Stage 1 (Image
Termique)” Status Contact (normally open contact, closes when device operates).
o Assignable Digital (Contact) Input P6c: Connected to a “49TP Stage 2 (Image
Termique)” Status Contact (normally open contact, closes when device operates).
o Assignable Digital (Contact) Input P7a: Connected to a “63TP Stage 1 (Bucholz)” Status
Contact (normally open contact, closes when device operates).
o Assignable Digital (Contact) Input P7c: Connected to a “63TP Stage 2 (Bucholz)” Status
Contact (normally open contact, closes when device operates).
o Assignable Digital (Contact) Input P8a: Connected to a “71TP (Oil Level)” Status
Contact (normally open contact, closes when device operates).
o Assignable Digital (Contact) Input P8c: Connected to a “45FTP (Fire Detection)” Status
Contact (normally open contact, closes when device operates).

PAGE 25

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

Contact Input Data and Contact Output Data (Primary UR T60 Relays) (Continued)

o Contact Output H1: Connected to Lockout Relay 86T1 Trip Circuit. (##)
o Contact Output H2: Connected to Lockout Relay 86G1 Trip Circuit. (##)
o Contact Output H3: Connected to 225 kV Transformer Primary Circuit Breaker Trip
Circuit #1. (##)
o Contact Output H4: Connected to 225 kV Transformer Primary Circuit Breaker Trip
Circuit #2. (##)
o Contact Output H5: Spare (not being utilized in this application).
o Contact Output H6: Provides a “Change Source 400V CCM” output.

(##) NOTE: Install external jumper between “a” and “b” terminals of output contact.

PAGE 26

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

Contact Input Data and Contact Output Data (Primary UR T60 Relays) (Continued)

o Contact Output U1: Provides an “87B (87T) Trip” output indication.


o Contact Output U2: Provides a “50P/51P Pri Trip” output indication.
o Contact Output U3: Provides a “51N Pri Trip” output indication.
o Contact Output U4: Provides a “51P Gen Trip” output indication.
o Contact Output U5: Provides a “51P Aux Trip” output indication.
o Contact Output U6: Provides a “24 Trip” output indication.
o Contact Output U7: Provides a “26TP Stage 2 Trip” output indication.
o Contact Output U8: Provides a “49TP Stage 2 Trip” output indication.
o Contact Output U9: Provides a “63TP Stage 2 Trip” output indication.
o Contact Output U10: Provides a “45F Trip” output indication.
o Contact Output U11: Provides a “21P Trip” output indication.
o Contact Output U12: Provides a “64B Backup Trip” output indication.
o Contact Output U13: Provides a “DL91 Trip” output indication.
o Contact Output U14: Available for customer use if desired.

o Contact Output W1: Provides an “All Trips” output indication.


o Contact Output W2: Provides an “All Alarms” output indication.
o Contact Output W3: Provides a “Turbine Normal Stop” output.
o Contact Output W4: Provides a “Change Source 6 kV” output.
o Contact Output W5: Provides a “41EX Trip” output.
o Contact Output W6: Connected to Backup G60 Relay Input H8a (used to provide a
C/B 52G Transfer Trip signal path to the backup UR G60 relay).
o Contact Output W7: Connected to Primary G60 Relay Input H8c (used to provide a
C/B 52G Transfer Trip signal path to the primary UR G60 relay).
o Contact Output W8: Normally Closed output connected in 225 kV Transformer
Primary Circuit Breaker 52L Close Circuit (provides “block closing” signal under
selected scenarios.

PAGE 27

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

2.7 Contact Input and Contact Output Data (“Backup” UR T60 Relay)
The T60 relays utilized in this application are also equipped with Digital (Contact) inputs and Contact
outputs which can (within certain restrictions) be assigned to perform user-specified functions. The
recommended backup T60 relay settings provided in this analysis are based upon the following
assumptions for each of these Contact inputs and Contact outputs:

Backup UR T60 Relay (associated with the 125 MVA GSU):


o Assignable Digital (Contact) Input H7a: Connected to 52a contact in transformer
primary circuit breaker.
o Assignable Digital (Contact) Input H7c: Connected to 52b contact in transformer
primary circuit breaker.
o Assignable Digital (Contact) Input H8a: Connected to Contact Output “W7” of Primary
UR G60 relay (used to provide a C/B 52L Transfer Trip signal path from the primary UR
G60 relay).
o Assignable Digital (Contact) Input H8c: Connected to Contact Output “W8” of Backup
UR G60 relay (used to provide a C/B 52L Transfer Trip signal path from the backup UR
G60 relay).

PAGE 28

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

Contact Input Data and Contact Output Data (Backup UR T60 Relays) (Continued)

o Assignable Digital (Contact) Input P1a: Connected to 52a contact in generator main
circuit breaker.
o Assignable Digital (Contact) Input P1c: Connected to 52b contact in generator main
circuit breaker.
o Assignable Digital (Contact) Input P2a: Connected to 52a contact in “TL2” transformer
secondary main circuit breaker.
o Assignable Digital (Contact) Input P2c: Connected to 52b contact in “TL2” transformer
secondary main circuit breaker.
o Assignable Digital (Contact) Input P3a: Available for customer use if desired.
o Assignable Digital (Contact) Input P3c: Connected to a “DL91 225 kV Line Protection
Trip” contact output.
o Assignable Digital (Contact) Input P4a: Provides a “TP4 VT CB5 Open” indication.
o Assignable Digital (Contact) Input P4c: Connected to a “TP Refrig Fault” Status
Contact (normally open contact, closes when device operates).
o Assignable Digital (Contact) Input P5a: Connected to a “26TP Stage 1 (Temperature)”
Status Contact (normally open contact, closes when device operates).
o Assignable Digital (Contact) Input P5c: Connected to a “26TP Stage 2 (Temperature)”
Status Contact (normally open contact, closes when device operates).
o Assignable Digital (Contact) Input P6a: Connected to a “49TP Stage 1 (Image
Termique)” Status Contact (normally open contact, closes when device operates).
o Assignable Digital (Contact) Input P6c: Connected to a “49TP Stage 2 (Image
Termique)” Status Contact (normally open contact, closes when device operates).
o Assignable Digital (Contact) Input P7a: Connected to a “63TP Stage 1 (Bucholz)” Status
Contact (normally open contact, closes when device operates).
o Assignable Digital (Contact) Input P7c: Connected to a “63TP Stage 2 (Bucholz)” Status
Contact (normally open contact, closes when device operates).
o Assignable Digital (Contact) Input P8a: Connected to a “71TP (Oil Level)” Status
Contact (normally open contact, closes when device operates).
o Assignable Digital (Contact) Input P8c: Connected to a “45FTP (Fire Detection)” Status
Contact (normally open contact, closes when device operates).

PAGE 29

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

Contact Input Data and Contact Output Data (Backup UR T60 Relays) (Continued)

o Contact Output H1: Connected to Lockout Relay 86T2 Trip Circuit. (##)
o Contact Output H2: Connected to Lockout Relay 86G2 Trip Circuit. (##)
o Contact Output H3: Connected to 225 kV Transformer Primary Circuit Breaker Trip
Circuit #1. (##)
o Contact Output H4: Connected to 225 kV Transformer Primary Circuit Breaker Trip
Circuit #2. (##)
o Contact Output H5: Spare (not being utilized in this application).
o Contact Output H6: Provides a “Change Source 400V CCM” output.

(##) NOTE: Install external jumper between “a” and “b” terminals of output contact.

PAGE 30

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

Contact Input Data and Contact Output Data (Backup UR T60 Relays) (Continued)

o Contact Output U1: Provides an “87B (87T) Trip” output indication.


o Contact Output U2: Provides a “50P/51P Pri Trip” output indication.
o Contact Output U3: Provides a “51N Pri Trip” output indication.
o Contact Output U4: Provides a “51P Gen Trip” output indication.
o Contact Output U5: Provides a “51P Aux Trip” output indication.
o Contact Output U6: Provides a “24 Trip” output indication.
o Contact Output U7: Provides a “26TP Stage 2 Trip” output indication.
o Contact Output U8: Provides a “49TP Stage 2 Trip” output indication.
o Contact Output U9: Provides a “63TP Stage 2 Trip” output indication.
o Contact Output U10: Provides a “45F Trip” output indication.
o Contact Output U11: Provides a “21P Trip” output indication.
o Contact Output U12: Provides a “64B Backup Trip” output indication.
o Contact Output U13: Provides a “DL91 Trip” output indication.
o Contact Output U14: Available for customer use if desired.

o Contact Output W1: Provides an “All Trips” output indication.


o Contact Output W2: Provides an “All Alarms” output indication.
o Contact Output W3: Provides a “Turbine Normal Stop” output.
o Contact Output W4: Provides a “Change Source 6 kV” output.
o Contact Output W5: Provides a “41EX Trip” output.
o Contact Output W6: Connected to Backup G60 Relay Input H8c (used to provide a
C/B 52G Transfer Trip signal path to the backup UR G60 relay).
o Contact Output W7: Connected to Primary G60 Relay Input H8a (used to provide a
C/B 52G Transfer Trip signal path to the primary UR G60 relay).
o Contact Output W8: Normally Closed output connected in 225 kV Transformer
Primary Circuit Breaker 52L Close Circuit (provides “block closing” signal under
selected scenarios.

PAGE 31

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

2.8 Setting Philosophies


For this UR T60 relay application, recommended settings were developed and implemented for the
following seven protection functions included in the relay:

o Percent Differential (87T)


o Instantaneous Differential (87I)
o Primary (240.75 kV) Phase Overcurrent (50/51P)
o Primary (240.75 kV) Ground Overcurrent (51NP)
o Secondary (11.5 kV Generator Neutral) Phase Overcurrent (51S)
o Over-Excitation (24)
o Backup 11.5 kV Bus Ground Fault (64B)

Included on the following pages of this letter report is a discussion of the philosophies used to
determine recommended settings for each of these protection functions.

PAGE 32

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

2.9 Percent Differential and Inst Differential Protection Functions (87T, 87I)
For this application, the Percent Differential and Instantaneous Differential protection functions
(87T, 87I) in the UR T60 Transformer Management Relay will utilize the following settings:

2.9.1 Percent Differential and Instantaneous Differential Settings (87T, 87I)


o Primary (240.75 kV, Winding 1) Phase CT Ratio = 400/1 Amperes
o Secondary (11.5 kV Generator Neutral, Winding 2) Phase CT Ratio = 7500/1 Amperes
o Aux Transformer (11.5 kV, Winding 3) Phase CT Ratio = 300/1 Amperes
o Transformer Type = / -330 (Wye-Delta, with HV Side Leading the LV Side by 330) (Assumed)
o System Phase Sequence = 1-2-3 (Assumed)

(NOTE: The Transformer Type and System Phase Sequence setpoints represent significant
assumptions relative to proper operation of the Percent Differential and Instantaneous Differential
protection functions and should be field verified).

2.9.1.1 Percent Differential (87T) Setpoint


o Percent Differential Pickup = 0.100 per-unit.
o Percent Differential Slope 1 = 20%.
o Percent Differential Break 1 = 2.000 per-unit.
o Percent Differential Break 2 = 30.000 per-unit.
o Percent Differential Slope 2 = 50%.

2.9.1.2 Harmonic Inhibit


o Harmonic Inhibit Function = Traditional 2ND Harmonic.
o Harmonic Inhibit Mode = Per-Phase.
o Harmonic Inhibit Level = 20% f0.

2.9.1.3 Instantaneous Deferential (87I) Setpoint


o Instantaneous Differential Pickup = 4.000 per-unit.

The recommended Percent Differential and Instantaneous Differential settings summarized above
are based upon past experience with other UR T60 relay applications (and upon past experience
with other Sonelgaz GPP installation projects), and attempt to provide reasonably sensitive settings
for this protection function while reducing the chances of protection function mis-operation during
disturbances (faults) outside of the T60 relay’s Zone of Protection.

PAGE 33

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

As shown on the previous page, the Harmonic Inhibit function was set to inhibit the Percent
Differential protection function in a particular phase if the level of 2ND Harmonic current flow in that
phase exceeds 20% f0. This is intended to inhibit operation of the percent Differential protection
function during transformer energization (inrush) when the inrush current can contain a large 2ND
Harmonic component.

Since it is not known at this time what the level of 2ND Harmonic current flow during energization of
this GSU design will be the “typical” (20% f0) Harmonic Inhibit Level setting has been recommended
for the initial UR T60 relay setup. For some transformer designs, the level of 2ND Harmonic current
flow during energization will not exceed 20% f0 in all three phases during all energization attempts.
In these cases, this Harmonic Inhibit function will not be enabled in every phase and the Percent
Differential protection function in the UR T60 relay may inadvertently operate during energization. In
this case, preventing inadvertent UR T60 operation during transformer energization may require a
reduction of the Harmonic Inhibit Level setting and/or a change in the algorithm used in the harmonic
inhibit calculation.

PAGE 34

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

2.10 Setting Philosophies: Primary and Secondary Phase Overcurrent Protection


The UR T60 relay settings provided with this letter report are based upon the assumption that each
of the M’Sila Generator Step-Up Transformers are two-winding units (one primary winding, one
secondary winding) rated 125 MVA (240.75/11.5 kV).

The recommended settings of the primary and secondary (generator neutral) phase overcurrent
protection functions associated with this step-up transformer will allow the associated generator to
continuously operate at (or slightly above) its 126.875 MVA rated output capability. To allow for
temporary overloads or increases in generator output (such as might occur following disturbances
in the 240.75 kV transmission system supply) the recommended settings of the secondary phase
overcurrent and primary phase overcurrent protection functions will also theoretically allow this
generator to operate at  150% of its 126.875 MVA rated output capability for  10.0 seconds and 
200% of its 126.875 MVA rated output capability for  4.4 seconds before initiating transformer
tripping.

For current flows above  250% of the rated output capability of the generator the primary and
secondary phase overcurrent protection functions associated with this step-up transformer will
utilize a 0.6 second Definite Time tripping delay. This tripping time delay will allow first-zone
(“instantaneous” tripping) or some second-zone (maximum 15 cycle delay) protective devices in the
240.75 kV transmission system to remove a multi-phase fault before initiating tripping of this step-
up transformer and the associated generator while still providing a reasonable level of overcurrent
(and through-fault) protection for this transformer.

In addition to the time delay type phase overcurrent protection functions described above, the
240.75 kV (primary) phase overcurrent protection function also includes recommended settings for
an instantaneous overcurrent trip. The recommended settings of this primary phase instantaneous
overcurrent protection function will allow energization (inrush) of this step-up transformer from the
240.75 kV transmission system supply while preventing tripping of this primary instantaneous
overcurrent protection function during multi-phase faults in its 11.5 kV transformer secondary
circuit.

PAGE 35

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

Note that under some scenarios (for example generator output current flows between 175% and
250% of rated and/or multi-phase faults which result in generator terminal voltages significantly
lower than nominal) it is quite possible that the generator supplied from a GSU will be tripped by the
phase overcurrent protection function (51P) in the G60 relay(s) associated with the unit before the
GSU is tripped by its T60 relay(s). No attempt was made to coordinate the phase overcurrent
protection functions in the G60 and T60 relays associated with this GSU/Generator combination,
since achieving phase overcurrent coordination would likely have required higher G60 protection
function time delay (time multiplier) settings, reducing the phase overcurrent protection provided to
the generator by its associated G60 relays.

PAGE 36

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

2.11 Secondary (11.5 kV Gen Neutral, Winding 2) Phase Overcurrent Protection (51S)
As stated previously, the step-up transformer secondary winding is rated 125,000 kVA ONAF, which
corresponds to an output current rating of  6276 Amperes at the rated secondary voltage of 11.5
kV. In addition, the generator connected to the step-up transformer secondary winding is rated
126,875 kVA, which corresponds to an output current rating of  6370 Amperes at the rated output
voltage of 11.5 kV.

Based upon the above and the setting philosophies described on previous pages, the Winding 2
Secondary Phase Overcurrent protection function (51S) in the UR T60 Transformer Management
Relays will utilize the following settings:

2.11.1 Winding 2 (Secondary) Phase Overcurrent Relay Settings (51S)


Supply Phase CT Ratio = 7500/1 Ampere

o PHASE TOC3 Pickup = 1.020 per-unit (7650 Amperes, or  122% of the 125,000 kVA winding
rating or  120% of the 126,875 kVA generator output current rating)
o PHASE TOC3 Curve Shape = IEEE Moderately Inverse
o PHASE TOC3 Multiplier = 0.86

o PHASE IOC3 Pickup = 2.120 per-unit (15900 Amperes, or  253% of the 125,000 kVA winding
rating or  250% of the 126,875 kVA generator output current rating)
o PHASE IOC3 Delay = 0.60 seconds

Below is a summary of equations which can be used to describe the shape of the Winding 2
(Secondary) Phase Overcurrent characteristic curve:

  
 0.0515  
T  M    0.114  , 1.020  I < 2.120 Amps

 I
 1.02
 0. 02
1



T  0.6 , I  2.120 Amps

NOTES:
T = Trip Time (seconds)
I = Relay Input Current (Amps)
M = Curve Multiplier = 0.86

In the above equations, the value of I (relay input current) is shown in CT Secondary Amps.

PAGE 37

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

Application of the Phase TOC3 and Phase IOC3 settings summarized on the previous page will result
in the following approximate relay tripping times at various values of % Rated Current. Here, note
that “Rated Current” is being defined as the generator output current rating (6370 Amps) and not
the ONAF rating of the step-up transformer secondary winding (6276 Amps).

% of Rated Current Time


125 55.5 sec
150 10.0 sec
175 5.96 sec
200 4.42 sec
225 3.60 sec
250 3.10 sec
>250 0.6 sec

Where the Rated Current = 6370 Primary (System) Amperes, or 0.85 Secondary (Relay) Amperes.

Note that for primary current flows less than 15900 Amperes only the PHASE TOC3 protection
function is effectively in service, since the minimum operating (Pickup) current of the PHASE IOC3
protection function is 15900 Primary Amperes. For primary current flows equal to or above 15900
Amperes both the PHASE TOC3 protection function and the PHASE IOC3 protection function are
effectively in service. However the PHASE IOC3 protection function will normally respond first and
provide a trip output before the PHASE TOC3 protection function, since the PHASE IOC3 protection
function utilizes a faster (Definite Time, 0.60 second) trip characteristic.

PAGE 38

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

2.12 Primary Phase Overcurrent Protection Function (50/51P)


For current flows < 250% of the rated output of the generator associated with this step-up
transformer the Primary Phase Overcurrent protection function (50/51P) in the UR T60 relays was
set to provide similar tripping times as the previously described secondary (generator neutral) phase
overcurrent protection function (51S). For current flows from 250% of the rated output up to the
maximum “through-fault” current flow into the step-up transformer the primary phase overcurrent
protection function was also set to provide similar (here, 0.60 second Definite Time) tripping times as
the previously described secondary phase overcurrent protection function. Coordination between
the primary and secondary phase overcurrent protection functions was sacrificed to allow the T60
relays to provide better (faster tripping times) through-fault current withstand protection for this
step-up transformer. In addition, achieving selectivity between the primary and secondary phase
overcurrent protection functions in this T60 application does not appear to provide any significant
operational benefits, since this step-up transformer is associated with only a single generator.

As stated previously, the step-up transformer primary winding is rated 125,000 kVA, which
corresponds to an output current rating of  300 Amperes at the rated primary voltage of 240.75 kV.
In addition, the generator connected to this step-up transformer is rated 126,875 kVA, which
corresponds to an output current rating of  304 Amperes at the 240.75 kV rated primary voltage.

PAGE 39

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

Based upon the above and the setting philosophies described on previous pages, the Primary Phase
Overcurrent protection function (50/51P) in the UR T60 Transformer Management Relays will utilize
the following settings:

2.12.1 Winding 1 (Transformer Primary) Phase Overcurrent Relay Settings (50/51P)


Supply Phase CT Ratio = 400/1 Ampere

o PHASE TOC1 Pickup = 0.910 per-unit (364 Amperes, or  121% of the 125,000 kVA winding
rating or  120% of the 126,875 kVA generator output current rating)
o PHASE TOC1 Curve Shape = IEEE Moderately Inverse
o PHASE TOC1 Multiplier = 0.88

o PHASE IOC1 Pickup = 1.900 per-unit (760 Amperes, or  254% of the 125,000 kVA winding
rating or  250% of the 126,875 kVA generator output current rating)
o PHASE IOC1 Delay = 0.60 seconds

o PHASE IOC2 Pickup = 9.250 per-unit (3700 Primary Amperes)


o PHASE IOC2 Delay = 0.00 seconds

PAGE 40

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

Below is a summary of equations which can be used to describe the shape of the Transformer
Primary Phase Overcurrent characteristic curve:

  
 0.0515  
T  M    0.114  , 0.910  I < 1.900 Amps

 I
 0.91
 0. 02
1



T  0.6 , 1.900  I < 9.250 Amps
T  Inst , I  9.25 Amps

NOTES:
T = Trip Time (seconds)
I = Relay Input Current (Amps)
M = Curve Multiplier = 0.88

In the above equations, the value of I (relay input current) is shown in CT Secondary Amps.

Application of the Phase TOC1, Phase IOC1 and Phase IOC2 settings summarized above and on the
previous page will result in the following approximate relay tripping times at various values of %
Rated Current. Here, note that “Rated Current” is being defined as the 126,875 kVA generator
output current rating (304 Amps) and not the 125,000 kVA rating of the step-up transformer primary
winding (300 Amps).

% of Rated Current Time


125 51.7 sec
150 10.1 sec
175 6.04 sec
200 4.49 sec
225 3.67 sec
250 3.16 sec
>253 and <1216 0.6 sec
1216 “Inst”

Where the Rated Current = 304 Primary (System) Amperes, or 0.76 Secondary (Relay) Amperes.
Note: “Inst” signifies no intentional time delay.

PAGE 41

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

Note that for primary current flows less than 760 Amperes only the PHASE TOC1 protection
function is effectively in service, since the minimum operating (Pickup) current of the PHASE IOC1
protection function is 760 Primary Amperes. For primary current flows equal to or above 760
Amperes but less than 3700 Amperes both the PHASE TOC1 protection function and the PHASE
IOC1 protection function are effectively in service. However the PHASE IOC1 protection function will
normally respond first and provide a trip output before the PHASE TOC1 protection function, since
the PHASE IOC1 protection function utilizes a faster (Definite Time, 0.60 second) trip characteristic.
For primary current flows equal to or above 3700 Amperes the PHASE TOC1 protection function,
the PHASE IOC1 protection function and the PHASE IOC2 protection functions are all effectively in
service. However the PHASE IOC2 protection function will normally respond first and provide a trip
output before either the PHASE TOC1 or the PHASE IOC1 protection function, since the PHASE IOC2
protection function utilizes a faster (“Instantaneous” or no intentional time delay) trip characteristic.

As shown, the recommended Winding 1 (Primary) Phase TOC1 and Phase IOC1 settings summarized
on the previous pages will result in UR T60 relay tripping times similar to the Winding 2 (Phase TOC3
and Phase IOC3) settings described previously at equivalent “% Rated Current” values. The Winding
1 Phase IOC2 protection function is set above the maximum “through-fault” current flow into the
step-up transformer (the current that would flow through the transformer for a bolted 3 fault at
the transformer secondary terminals) and is also set above the assumed maximum transformer
inrush current flow. For this analysis, the maximum expected through-fault current flow value for
this step-up transformer is calculated to be  2270 RMS symmetrical Amperes @ the 240.75 kV
primary voltage level, while the maximum Inrush current flow is  3597 Amperes @ 240.75 kV
(based upon a typical assumption that the maximum IINRUSH  12*IFL).

Note that the maximum expected through-fault current flow was calculated assuming an infinite
primary source, using the assumed primary winding to secondary winding Impedance (13.2% on a
125,000 kVA base). The actual maximum available through-fault current flow through this unit is
expected to be less than this calculated maximum value. In addition, note that the Phase
Instantaneous Overcurrent protection functions in the T60 relay will respond essentially only to the
fundamental (50 Hz) component of Inrush current flow. Since the fundamental component of
transformer inrush current flow is generally only a fraction of the total (RMS) inrush current value
setting the PHASE IOC2 protection function in this manner should not result in T60 relay tripping
during transformer energization.

PAGE 42

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

2.13 Primary Ground Overcurrent Protection Function (51NP)


The recommended settings of the Primary (240.75 kV) Ground Overcurrent protection function in
these T60 relays is based upon maintaining a protection function tripping time  0.6 seconds for
any practical level of current flow through the protection function during a phase-to-ground fault in
the 240.75 kV transmission system supplying this generator/GSU combination. Maintaining a
minimum protection function tripping time  0.6 seconds should allow first-zone and some
second-zone (maximum 15 cycle delay) protective devices installed in the 240.75 kV transmission
system the opportunity to remove a 240.75 kV transmission system disturbance before GSU tripping
is initiated.

2.13.1 Winding 1 (Transformer Primary) Ground Overcurrent Relay Settings (51NP)


Supply Neutral CT Ratio = 400/1 Ampere

o GROUND TOC1 Pickup = 0.125 per-unit (50 Primary Amperes)


o GROUND TOC1 Curve Shape = IEEE Moderately Inverse
o GROUND TOC1 Multiplier = 1.00

o GROUND IOC1 Pickup = 0.375 per-unit (150 Primary Amperes)


o GROUND IOC1 Delay = 0.60 seconds

Below is a summary of equations which can be used to describe the shape of the Winding 1
(Primary) Ground Overcurrent characteristic curve:

  
 0.0515  
T  M    0.114  , 0.125  I < 0.375 Amps

 I
 0.125
 0.02
1



T  0.6 , I  0.375 Amps

NOTES:
T = Trip Time (seconds)
I = Relay Input Current (Amps)
M = Curve Multiplier = 1.00

In the above equations, the value of I (relay input current) is shown in CT Secondary Amps.

PAGE 43

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

Application of the Ground TOC1 settings summarized above and on the previous page will result in
the following approximate relay tripping times at the various Multiplies of Pickup Current shown.

Multiples of Primary (System) Trip


Pickup Current Current Time
1.5 75 Amps 6.44 sec
1.75 87.5 Amps 4.69 sec
2 100 Amps 3.80 sec
2.25 112.5 Amps 3.26 sec
2.5 125 Amps 2.90 sec
2.75 137.5 Amps 2.63 sec
2.95 147.5 Amps 2.47 sec
3 150 Amps 0.60 sec

Where the Pickup Current = 50 Primary (System) Amperes, or 0.125 Secondary (Relay) Amperes.

Note that for primary current flows less than 150 Amperes only the GROUND TOC1 protection
function is effectively in service, since the minimum operating (Pickup) current of the GROUND IOC1
protection function is 150 Primary Amperes. For primary current flows above 150 Amperes both
the GROUND TOC1 protection function and the GROUND IOC1 protection function are effectively in
service. However the GROUND IOC1 protection function will normally respond first and provide a
trip output before the GROUND TOC1 protection function, since the GROUND IOC1 protection
function utilizes a faster (Definite Time, 0.60 second) trip characteristic.

In theory, for primary current flows above 7500 Amperes the GROUND TOC1 protection function
would start to respond first and provide a trip output before the GROUND IOC1 protection function,
which would then result in protection function tripping times less than 0.60 seconds. However, this
7500 Ampere ground fault current flow (where tripping times less than 0.60 seconds would
theoretically be possible) appears based upon supplied data to be well above the maximum
possible current flow through this protection function for any practical 240.75 kV phase-to-ground
transmission system fault. Therefore, the recommended Winding 1 (Primary) Ground TOC1 and
IOC1 settings summarized on the previous pages should result in UR T60 relay tripping times 
0.60 seconds for all practical current flows through the 51TN protection function.

PAGE 44

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

2.14 Setting Philosophies: Auxiliary Transformer Primary Phase Overcurrent Protection


In addition to the primary and secondary (generator neutral) phase overcurrent protection functions
described previously, the UR T60 relays being applied in conjunction with this generator step-up
transformer also have the capability of providing backup primary phase overcurrent protection for
the “TL2” Auxiliary Transformer being supplied from the GSU, utilizing phase overcurrent protection
functions associated with the Winding 3 (11.5 kV Aux Transformer) Phase CT inputs.

The philosophies used to determine recommended settings for the F650 Feeder Protection System
Relay being applied in conjunction with this 3000 kVA, “TL2” Auxiliary Supply Transformer will be
described in a subsequent section of this report. This F650 relay will provide the desired primary
phase overcurrent protection for this “TL2” auxiliary transformer. For current flows  300% of the
rated output capability of the auxiliary supply transformer the Winding 3 (11.5 kV Aux Transformer)
phase overcurrent protection function in the T60 relays applied with this GSU will be set to be
selective with the phase overcurrent protection function in the F650 Feeder Protection System
Relay, allowing the F650 relay the opportunity to detect and respond to overload/low-level
overcurrent flows into the auxiliary supply transformer first. For current flows above  300% of the
rated output capability of the auxiliary supply transformer the Winding 3 phase overcurrent
protection functions in these T60 relays will be set to provide similar or identical tripping time delays
as the associated F650 relay.

PAGE 45

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

2.15 11.5 kV Aux Transformer (Winding 3) Phase Overcurrent Protection (50/51 Aux)
Based upon the above and the setting philosophies described in Section 4 of this letter report , the
Winding 3 Aux Transformer Phase Overcurrent protection function (50/51 Aux) in the UR T60
Transformer Management Relays will utilize the following settings:

2.15.1 Winding 3 (11.5 kV Aux Transformer) Phase Overcurrent Relay Settings (50/51 Aux)
Supply Phase CT Ratio = 300/1 Ampere

o PHASE TOC5 Pickup = 0.600 per-unit (180 Primary Amperes, or  120% of the winding rating)
o PHASE TOC5 Curve Shape = IEEE Extremely Inverse
o PHASE TOC5 Multiplier = 3.60

o PHASE IOC5 Pickup = 1.500 per-unit (450 Primary Amperes, or  299% of the winding rating)
o PHASE IOC5 Delay = 0.60 seconds

o PHASE IOC6 Pickup = 9.000 per-unit (2700 Primary Amperes)


o PHASE IOC6 Delay = 0.00 seconds

  
 28.2  
T  M    0.1217 , 0.600  I < 1.500 Amps

 I
 0.60
 2
1



T  0.6 , 1.500  I < 9.000 Amps
T  Inst , I  9.000 Amps

NOTES:
T = Trip Time (seconds)
I = Relay Input Current (Amps)
M = Curve Multiplier = 3.60

In the above equations, the value of I (relay input current) is shown in CT Secondary Amps.

PAGE 46

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

Application of the Phase TOC5, Phase IOC5 and Phase IOC6 settings summarized on the previous
page will result in the following approximate relay tripping times at various values of % Rated
Current. Here, note that “Rated Current” is defined as the Auxiliary Supply transformer output
current rating (151 Amps at 11.5 kV).

% of Rated Current Time


150 177 sec
175 89.2 sec
200 56.8 sec
250 30.5 sec
299 19.7 sec
>299 and <1793 0.6 sec
>1793 “Inst”

Where the Rated Current = 151 Primary (System) Amperes, or 0.50 Secondary (Relay) Amperes.
Note: “Inst” signifies no intentional time delay.

Comparing the above calculated tripping times with the corresponding times shown in the tripping
time table included in Section 4.8.1 of this report, note that selectivity will exist between this Winding
3 phase overcurrent protection function and the phase overcurrent protection function enabled in
the F650 relay associated with this “TL2” Auxiliary Supply Transformer for current flows  300% of
the rated output capability of the aux supply transformer. For current flows above  300% of the
rated output capability of this auxiliary transformer the Winding 3 phase overcurrent protection
function tripping times will be essentially identical to the corresponding F650 tripping times.

PAGE 47

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

2.16 Over-Excitation Protection Function (24)


Based upon typical application practices for generator step-up transformers and past experience at
similar facilities, the Over-Excitation Trip protection function (24) in the UR T60 Transformer
Management Relays associated with this Unit 25 GSU will utilize the following settings:

2.16.1 Over-Excitation Trip Relay Settings (24)


Supply Phase VT Ratio = 115/1 Volts

Volts-Per-Hertz 1 (24T1) Setpoint


Volts-Per-Hertz 1 Pickup = 1.10 per-unit V/Hz.
Volts-Per-Hertz 1 Curve Shape = Definite Time
Volts-Per-Hertz 1 Delay (D) = 42.0 seconds.

Volts-Per-Hertz 2 (24T2) Setpoint


Volts-Per-Hertz 2 Pickup = 1.17 per-unit V/Hz.
Volts-Per-Hertz 2 Curve Shape = Definite Time
Volts-Per-Hertz 2 Delay (D) = 1.85 seconds.

Below is a summary of the equation which can be used to describe the shape of the Over-Excitation
Trip (Volts-Per-Hertz) characteristic curve:

T  42 , 110  V< 117 Volts @ 50 Hz

T  1.85 , V 117 Volts @ 50 Hz

NOTES:
T = Trip Time (seconds)
V = Input Voltage @ 50 Hz

PAGE 48

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

Application of the Volts-Per-Hertz settings summarized on the previous page will result in the
following approximate relay tripping times at various values of % Primary Voltage (at 50 Hz).

% of Rated Voltage
(Frequency = 50 Hz) Time
106 Continuous (no Trip)
108 Continuous (no Trip)
109.9 Continuous (no Trip)
110 42.0 sec (Trip)
112 42.0 sec (Trip)
114 42.0 sec (Trip)
116 42.0 sec (Trip)
116.9 42.0 sec (Trip)
117 1.85 sec (Trip)

Where the Rated Voltage = 11500 Primary Volts, or 100.0 Secondary Volts.

PAGE 49

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

2.17 Backup 11.5 kV Bus Ground Fault Protection Function (64B)


The Backup 11.5 kV Bus Ground Fault (64B) protection function in the UR T60 Transformer
Management Relays are set to provide similar protection characteristics as the Basler BE1-59N Bus
Ground Fault Relay associated with the Unit 25 11.5 kV Main Distribution Bus. The philosophies
used to determine recommended settings for the BE1-59N relay are described in a subsequent
section of this letter report.

PAGE 50

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

2.18 Observations/Recommendations

a) The Ratios and Terminal Connections of all CT’s and VT’s connected to these T60 relays (as
previously listed under “Input CT and VT Data”) should be verified prior to transformer
startup/operation. Modifications of recommended relay settings will be required if the
Terminal Connections or Ratios of any of the actual (installed) CT’s and/or VT’s are different
than the listed Connections/Ratios.

b) Following transformer startup, the Connections and Ratios of the installed Phase VT’s should
be further verified by comparing the generator-side and bus-side phase-to-phase and
phase-to-neutral voltages measured/displayed by each T60 relay (using the Actual Values
functions in the relay) with the corresponding phase-to-phase and phase-to-neutral voltages
measured by other devices. In addition, the Connections and Ratios of the installed Phase
CT’s should be further verified by comparing the phase current values measured/displayed
by each T60 relay (using the Actual Values functions in the relay) with phase current values
measured by other devices.

c) The Contact Input and Contact Output assignments associated with each of these T60 relays
(as previously listed under “Contact Input and Contact Output Data”) should be verified prior
to transformer startup/operation. Modifications of recommended relay settings will be
required if the actual Contact Input and/or Contact Output connections are different than
the listed Connections.

It is important that a field verification of actual (as installed) CT and VT Ratios, CT and VT connections
and Contact Input and Contact Output assignments as described in previous sections of this letter
report be completed prior to transformer startup/operation. Providing and maintaining the desired
levels of protection to this transformer by these installed T60 relays requires that the CT/VT Ratios
and connections along with the Contact Input and Contact Output assignments exactly match the
previously listed Ratios, connections and assignments.

PAGE 51

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

a) During normal operation, LED 25, LED 26 and LED 27 on each of the T60 relay faceplates
should not be illuminated (these LED’s are labeled “Ph A 2nd Har Rest”, “Ph B 2nd Har Rest”,
Ph C 2nd Har Rest”). These LED’s may be illuminated for a short period of time during
transformer energization. If any of these LED’s are illuminated during normal transformer
operation the Phase Differential protection (87T) provided to the transformer may be
significantly compromised, and further evaluation will be required to determine if relay
setting modifications or other corrective actions are required.

b) During normal operation, LED 36 on each of the T60 relay faceplates should not be
illuminated (this LED is labeled “VT/VT Fuse Failure”). If this LED is illuminated during normal
operation the Over-Excitation protection (24) provided to the transformer may be
compromised, and further field investigation of possible VT Fuse or supply VT failure is
required.

c) It is important that all VT/VT Fuse Failures be addressed and corrected quickly. Proper
operation of the VT/VT Fuse Failure function in the T60 relays (and proper operation of the
VT/VT Fuse failure Alarm output) should be verified through test prior to Transformer
startup/operation.

d) During normal operation, LED 12 on each of the T60 relay faceplates should be illuminated
(this LED is labeled “Setting Group 1 On”). If this LED is not illuminated during normal
transformer operation the protection provided to the transformer may be significantly
compromised, and further field investigation of possible UR T60 relay failure is required.

e) During normal operation, LED 3, LED 7 and LED 11 on each of the T60 relay faceplates should
not be illuminated (these LED are labeled “Primary CB Trouble”, “CB 52G Trouble” and “TL Sec
CB Trouble” respectively). Further field investigation of possible 52a and/or 52b contact
input failure is required if any of these LED’s are illuminated during normal operation.

f) During normal operation, either LED 1 on each of the T60 relay faceplates (labeled as
“Primary CB Open”) or LED 2 (labeled as “Primary CB Closed”) should be illuminated,
depending upon the status of the 240.75 kV transformer primary circuit breaker. If neither
LED is illuminated during normal transformer operation further field investigation of the
possible failure of the 52a and/or 52b contact inputs from the 240.75 kV Primary C/B into the
T60 relays is recommended.

PAGE 52

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

g) During normal operation, either LED 5 on each of the T60 relay faceplates (labeled as “CB
52G Open”) or LED 6 (labeled as “CB 52G Closed”) should be illuminated, depending upon the
status of 11.5 kV CB 52G. If neither LED is illuminated during normal transformer operation
further field investigation of the possible failure of the 52a and/or 52b contact inputs from
CB 52G into the T60 relays is recommended.

h) During normal operation, either LED 9 on each of the T60 relay faceplates (labeled as “TL Sec
CB Open”) or LED 10 (labeled as “TL Sec CB Closed”) should be illuminated, depending upon
the status of the 6 kV “TL2” Auxiliary transformer secondary main breaker. If neither LED is
illuminated during normal “TL2” Aux transformer operation further field investigation of the
possible failure of the 52a and/or 52b contact inputs from the 6 kV “TL2” Auxiliary secondary
main C/B into the T60 relays is recommended.

PAGE 53

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


T60 Relay Application: 125 MVA Generator Step-Up Transformer TP3

i) Note that the UR T60 relay has the ability to measure and display the Differential (operating)
and Restraint currents that the relay is using in the Percent Differential setting calculations.
Shown below is a copy of a portion of a page from the UR T60 Instruction Manual showing
the path available to view these currents.

When the GSU is normally operating and reasonably loaded each of the "Differential Currents"
values should be nearly zero and the "Restraint Currents" values should be non-zero. It is
recommended that the differential and restraint current values being measured by each of the
UR T60 relays be monitored during GSU startup/operation. Measured Differential Current
values which are non-zero could indicate an error in CT connections and/or UR T60 relay
setup which should be resolved prior to continued operation of the GSU.

PAGE 54

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


F650 Relay Application: 800 kVA Gas-Turbine Auxiliary Supply Transformer TAM3

3. F650 Setting Calculations (800 kVA “TAM3” Turbine Aux Supply Transformers)
3.1 Introduction
Summarized in the following sections of this letter report are the philosophies and procedures used
to determine recommended settings for the “Active” (in service) protection functions in the F650
Feeder Protection System Relay being applied in conjunction with the 800 kVA, 11.5/0.40 kV Unit 25
“TAM3” Auxiliary Supply Transformer. This Auxiliary Supply Transformer is associated with the
126.875 MVA Gas-Turbine Generator referenced in previous sections of this study report. Also
included in this section of the letter report is a summary of the significant assumptions used to
determine these recommended settings.

3.2 “TAM3” Gas-Turbine Auxiliary Supply Transformer Data


A Manufacturers Test Report for the subject gas-turbine auxiliary supply transformer was not
available for this study. The recommended F650 relay settings as described in this letter report are
based upon the transformer ratings summarized below (assumed, based upon data utilized for the
previously completed Tiaret GPP settings studies):

 kVA Rating: 800 kVA.


 Rated Primary Voltage (phase-to-phase): 11.5 kV.
 Rated Secondary Voltage (phase-to-phase): 0.40 kV.
 Winding Connections (Primary/Secondary): /, 3, 50 Hz,  Winding operated
Solidly Grounded (Note: Solidly-Grounded Operation Assumed).
 System Phase Sequence = 1-2-3
 Rated Primary to Secondary Impedance ZPS  4.5% on an 800 kVA base, 11.5 kV to
0.40 kV.

Obtaining (if possible) actual Nameplate data for this particular auxiliary supply transformer would
allow for more accurate relay setting calculations.

PAGE 55

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


F650 Relay Application: 800 kVA Gas-Turbine Auxiliary Supply Transformer TAM3

3.3 Protective Relay Data


The recommended F650 relay settings provided for the “TAM3” auxiliary supply transformer feeder
circuit is based upon the following assumed F650 Relay Order Code:

 F650-B-A-B-F-2-G-1-HI-F-6
 Version 5.40

Before beginning relay testing/commissioning the F650 relay Order Code and Firmware Version used
to complete this analysis (and summarized above) should be compared against the actual (as
installed) F650 relay Order Code/Version. Modifications to the recommended relay settings and/or the
supplied F650 relay setting file may be required if the actual F650 Order Code/Firmware Version is
different than the Order Code/Version used in this analysis.

PAGE 56

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


F650 Relay Application: 800 kVA Gas-Turbine Auxiliary Supply Transformer TAM3

3.4 Input CT and VT Data


In addition to the above, the recommended F650 relay settings are based upon the following
assumptions concerning the CT’s and VT’s which will be used to supply the relay:

F650 Relay (associated with the 800 kVA Unit 25 “TAM3” Aux Supply Transformer):
o Phase CT Inputs (Input B1/B2, B3/B4, B5/B6): These Phase CT’s are connected in Wye,
and have a Ratio of 100/1 Amperes. These Phase CT’s are connected to the B1/B2,
B3/B4 and B5/B6 CT Inputs.
o Ground CT Input (B9/B10): This CT input (Input B9/B10) is connected into the neutral
(“residual”) circuit of the B1/B2, B3/B4, B5/B6 Phase CT inputs. Due to the fact that
this turbine-generator is operated High-Resistance Grounded this Ground CT input
signal is not used in this application.

o Phase VT Inputs (Input A5/A6, A7/A8, A9/A10): These Phase VT’s are connected wye
primary-wye secondary, and have a Ratio of 115/1. These Phase VT’s are connected
to the A5/A6, A7/A8 and A9/A10 VT Inputs.
o Auxiliary VT Input (A11/A12): Not used in this application.

Based upon the supplied data, the nominal secondary voltage which will be applied to the F650
relay = 100 Volts  (57.7 Volts N), as summarized below:

11500 Vph  ph  100Vph  ph  100 Vph  N  57.7Vph  N


Vrelay 
1151  3

These secondary voltages should be verified during unit commissioning via actual measurement
(using a multi-meter) at the relay VT input terminals when the unit is operating at rated secondary
voltage.

PAGE 57

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


F650 Relay Application: 800 kVA Gas-Turbine Auxiliary Supply Transformer TAM3

3.5 Contact Input and Contact Output Data


The F650 relay utilized in this application are also equipped with Digital (Contact) inputs and Contact
outputs which can (within certain restrictions) be assigned to perform user-specified functions. The
recommended F650 relay settings provided in this analysis are based upon the following
assumptions for each of these Contact inputs and Contact outputs:

F650 Relay (associated with the 800 kVA Unit 25 “TAM3” Aux Supply Transformer):
o Assignable Digital (Contact) Input F1/F2: Not utilized in this application.
o Assignable Digital (Contact) Input F3/F4: Not utilized in this application.
o Assignable Digital (Contact) Input F5/F9: Externally connect “b” Status contacts from
the 86/T1 and 86/T2 Lockout relays (normally closed contacts, open when L/O
operates) in series. This series combination is then connected into this input.
o Assignable Digital (Contact) Input F6/F9: Connect an “a” Status contact from the
86/T1 Lockout relay into this input (normally open contact, closes when L/O operates).
o Assignable Digital (Contact) Input F7: Connect an “a” Status contact from the 86/T2
Lockout relay into this input (normally open contact, closes when L/O operates).
o Assignable Digital (Contact) Input F8: Not utilized in this application.
o Assignable Digital (Contact) Input F11: Not utilized in this application.
o Assignable Digital (Contact) Input F12: Not utilized in this application.
o Assignable Digital (Contact) Input F13: Not utilized in this application.
o Assignable Digital (Contact) Input F14: Not utilized in this application.
o Assignable Digital (Contact) Input F15/F16: Not utilized in this application.
o Assignable Digital (Contact) Input F17/F18: Not utilized in this application.

o Contact Output “O1” (F19/F20): Provides a “26TAM Stage 1” output indication.


o Contact Output “O2” (F21/F22): Provides a “26TAM Stage 2” output indication.
o Contact Output “O3” (F23/F24): Provides a “63TAM” output indication.
o Contact Output “O4” (F25/F26): Provides a “71TAM” output indication.
o Contact Output “O5” (F27/F28): Provides a “45FTAM” output indication.
o Contact Output “O6” (F29/F30): Provides a “41EX” Trip Output.
o Contact Output “O7” (F31/F33): Connected to 86/T1 Lockout Relay Trip Circuit.
o Contact Output “O8” (F34/F36): Connected to C/B 52L Trip Circuit.

PAGE 58

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


F650 Relay Application: 800 kVA Gas-Turbine Auxiliary Supply Transformer TAM3

Contact Input Data and Contact Output Data (TAM F650 Relays) (Continued)

o Assignable Digital (Contact) Input G1: Connected to a “26TAM Stage 1 (Temperature)”


Status Contact (normally open contact, closes when device operates).
o Assignable Digital (Contact) Input G2: Connected to a “26TAM Stage 2 (Temperature)”
Status Contact (normally open contact, closes when device operates).
o Assignable Digital (Contact) Input G3: Connected to a “63TAM (Bucholz)” Status
Contact (normally open contact, closes when device operates).
o Assignable Digital (Contact) Input G4: Connected to a “71TAM (Oil Level)” Status
Contact (normally open contact, closes when device operates).
o Assignable Digital (Contact) Input G5: Connected to a “45FTAM (Fire Detection)” Status
Contact (normally open contact, closes when device operates).
o Assignable Digital (Contact) Input G6: Available for customer use if desired.
o Assignable Digital (Contact) Input G7: Connected to “Change Source 6 kV” from G60
(Primary and Backup), T60 (Primary and Backup), 64B and F650 relays.
o Assignable Digital (Contact) Input G8: Available for customer use if desired.
o Assignable Digital (Contact) Input G11: Available for customer use if desired.
o Assignable Digital (Contact) Input G12: Available for customer use if desired.
o Assignable Digital (Contact) Input G13: Available for customer use if desired.
o Assignable Digital (Contact) Input G14: Available for customer use if desired.
o Assignable Digital (Contact) Input G15: Available for customer use if desired.
o Assignable Digital (Contact) Input G16: Available for customer use if desired.
o Assignable Digital (Contact) Input G17: Available for customer use if desired.
o Assignable Digital (Contact) Input G18: Available for customer use if desired.

o Contact Output “O1” (G20/G21): Provides a “Change Source 6 kV NC” output.


o Contact Output “O2” (G22/G23/G24): Connected to C/B 52G Trip Circuit.
o Contact Output “O3” (G25/G26): Provides a “TAM 50/51P Trip” output indication.
o Contact Output “O4” (G27/G28): Provides an “F650 Alarm” output indication.
o Contact Output “O5” (G29/G30): Provides a “Change Source 400V CCM” output.
o Contact Output “O6” (G31/G32): Connected to 86/T2 Lockout Relay Trip Circuit.
o Contact Output “O7” (G33/G34): Provides a “Turbine Normal Stop” output.
o Contact Output “O8” (G35/G36): Provides a “Change Source 6 kV NO” output.

PAGE 59

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


F650 Relay Application: 800 kVA Gas-Turbine Auxiliary Supply Transformer TAM3

3.6 Setting Philosophies


For this Gas-Turbine Auxiliary Supply Transformer F650 relay application, recommended settings
were developed and implemented for the following protection functions included in the relay:

o Primary (11.5 kV) Phase Overcurrent (50/51P)

Included on the following pages of this letter report is a discussion of the philosophies used to
determine recommended settings for this protection function.

PAGE 60

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


F650 Relay Application: 800 kVA Gas-Turbine Auxiliary Supply Transformer TAM3

3.7 Setting Philosophies: Primary Phase Overcurrent Protection


The recommended settings of the F650 primary phase overcurrent protection functions associated
with the 800 kVA Gas-Turbine Auxiliary Supply Transformer will;

1. allow the auxiliary supply transformer to continuously operate at its 800 kVA rated output
capability.
2. allow successful energization of the 800 kVA supply transformer.
3. provide the level of through-fault current withstand protection for the supply transformer
described in the ANSI C57 transformer protection standards.

3.8 Primary Phase Overcurrent Protection Function (50/51P)


As stated previously, the “TAM3” Auxiliary Supply Transformer is rated 800 kVA, which corresponds
to an output current rating of  40.2 Amperes at the rated primary voltage of 11.5 kV. Based upon
the previous discussion, the Primary Phase Overcurrent protection function (50/51P) in the F650
Feeder Protection System Relay will utilize the following settings:

3.8.1 Primary Phase Overcurrent Relay Settings (50/51P)


Supply Phase CT Ratio = 100/1 Amperes

o Phase TOC High 1 Pickup = 0.50 A (50 Primary Amperes, or  125% of the winding rating)
o Phase TOC High 1 Curve Shape = IEEE Extremely Inverse
o Phase TOC High 1 Multiplier = 3.20

o Phase IOC High 1 Pickup = 9.80 A (980 Primary Amperes)


o Phase IOC High 1 Trip Delay = 0.00 seconds

o Phase IOC Low 1 Pickup = 1.20 A (120 Primary Amperes, or  299% of the winding rating)
o Phase IOC Low 1 Trip Delay = 0.60 seconds

PAGE 61

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


F650 Relay Application: 800 kVA Gas-Turbine Auxiliary Supply Transformer TAM3

Below is a summary of equations which can be used to describe the shape of the Primary Phase
Overcurrent characteristic curve:

  
 28.2  
T  M    0.1217 , 0.50  I < 1.20 Amps

 I
 0.50
 2
1



T  0.6 , 1.20  I < 9.80 Amps
T  " Inst" , I  9.80 Amps
NOTES:
T = Trip Time (seconds)
I = Relay Input Current (Amps)
M = Curve Multiplier = 3.20

In the above equations, the value of I (relay input current) is shown in CT Secondary Amps.

Application of the Phase TOC High 1, Phase IOC High 1 and Phase IOC Low 1 settings summarized
above and on the previous page will result in the following approximate relay tripping times at
various values of % Rated Current. Here, note that “Rated Current” is defined as the Auxiliary Supply
transformer output current rating (40.2 Amps at 11.5 kV).

% of Rated Current Time


150 200 sec
175 92.8 sec
200 57.5 sec
250 30.1 sec
299 19.3 sec
>299 and <2440 0.6 sec
>2440 “Inst”

Where the Rated Current = 40.2 Primary (System) Amperes, or 0.402 Secondary (Relay) Amperes.
Note: “Inst” signifies no intentional time delay.

PAGE 62

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


F650 Relay Application: 800 kVA Gas-Turbine Auxiliary Supply Transformer TAM3

3.8.2 Discussion
The data supplied for this analysis did not include any information (types, settings, time versus
current tripping characteristics, etc.) for the 0.40 kV secondary main/feeder circuit breakers
presently installed in conjunction with this gas-turbine auxiliary supply transformer. In addition, the
study Workscope did not include performing any time versus current coordination analyses for this
“TAM3” 11.5/0.40 kV Gas-Turbine Auxiliary distribution system. As stated previously, the
recommended settings provided for the 11.5 kV primary phase overcurrent protection functions
were based upon; (a) allowing the gas-turbine auxiliary supply transformer to continuously operate
at its 800 kVA rated output capability, (b) allowing successful energization of the 800 kVA supply
transformer and (c) providing the level of through-fault current withstand protection for the 800 kVA
gas-turbine supply transformer described in the ANSI C57 transformer protection standards.
Depending upon the time versus current tripping characteristics of the presently installed 0.40 kV
transformer secondary protective devices these recommended primary phase overcurrent
protection function settings may also provide some coordination (selectivity) with these secondary
protective devices.

Note that for primary current flows less than 120 Amperes only the Phase TOC High 1 protection
function is effectively in service, since the minimum operating (Pickup) current of the Phase IOC Low
1 protection function is 120 Primary Amperes. For primary current flows equal to or above 120
Amperes but less than 980 Amperes both the Phase TOC High 1 protection function and the Phase
IOC Low 1 protection functions are effectively in service. However the Phase IOC 1 Low protection
function will normally respond first and provide a trip output before the Phase TOC High 1
protection function, since the Phase IOC Low 1 protection function utilizes a faster (Definite Time,
0.60 second) trip characteristic. For primary current flows equal to or above 980 Amperes the
Phase TOC High 1, the Phase IOC Low 1 and the Phase IOC High 1 protection functions are all
effectively in service. However the Phase IOC High 1 protection function will normally respond first
and provide a trip output before either the Phase TOC High 1 or the Phase IOC Low 1 protection
function, since the Phase IOC High 1 protection function utilizes a faster (“Instantaneous” or no
intentional time delay) trip characteristic.

PAGE 63

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


F650 Relay Application: 800 kVA Gas-Turbine Auxiliary Supply Transformer TAM3

Note that the Phase IOC High 1 protection function is set slightly above the maximum expected
“through-fault” current flow into the 800 kVA auxiliary supply transformer (the current that would
flow through the transformer for a bolted 3 fault at the transformer secondary terminals) and is
also set above the assumed maximum transformer inrush current flow. For this analysis, the
maximum expected through-fault current flow value for the 800 kVA auxiliary supply transformer is
calculated to be  893 RMS symmetrical Amperes @ the 11.5 kV primary voltage level, while the
maximum Inrush current flow is  321 Amperes @ 11.5 kV (based upon a typical assumption that
the maximum IINRUSH  8*IFL). Note that the maximum expected through-fault current flow was
calculated assuming an Infinite primary source, using the previously summarized winding
Impedance (4.5% on an 800 kVA base).

PAGE 64

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


F650 Relay Application: 800 kVA Gas-Turbine Auxiliary Supply Transformer TAM3

3.9 Observations/Recommendations

a) The Ratios and Connections of all Phase CT’s and Phase VT’s connected to this F650 relay (as
previously listed under “Input CT and VT Data”) should be verified prior to auxiliary supply
transformer startup/operation. Modifications of recommended relay settings will be
required if the Connections or Ratios of any of the actual (installed) CT’s and/or VT’s are
different than the listed Connections/Ratios.

b) Following “TAM3” auxiliary supply transformer energization, the Connections and Ratios of
the installed Phase VT’s should be further verified by comparing the phase-to-phase and
phase-to-neutral voltages measured/displayed by this F650 relay (using the Metering
functions in the relay) with phase-to-phase and phase-to-neutral voltages measured by
other devices. In addition, the Connections and Ratios of the installed Phase CT’s should be
further verified by comparing the phase current values measured/displayed by this F650
relay (using the metering functions in the relay) with phase current values measured by other
devices.

c) The Contact Input and Contact Output assignments associated with this F650 relay (as
previously listed under “Contact Input and Contact Output Data”) should be verified prior to
gas-turbine auxiliary transformer startup/operation. Modifications of recommended relay
settings will be required if the actual Contact Input and/or Contact Output connections are
different than the listed Connections.

It is important that a field verification of actual (as installed) CT and VT Ratios, CT and VT connections
and Contact Input and Contact Output assignments as described in previous sections of this letter
report be completed prior to gas-turbine auxiliary transformer startup/operation. Providing and
maintaining the desired levels of protection to these transformers by the installed F650 relay
requires that the CT/VT Ratios and connections along with the Contact Input and Contact Output
assignments exactly match the previously listed Ratios, connections and assignments.

d) During normal operation, the “READY” LED on the relay faceplate should be illuminated. If
this LED is not illuminated during normal transformer operation the protection provided to
the transformer may be significantly compromised, and further field investigation of F650
relay failure is required.

PAGE 65

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


F650 Relay Application: 3000 kVA Station Auxiliary Supply Transformer TL2

4. F650 Setting Calculations (3000 kVA “TL2” Station Aux Supply Transformer)
4.1 Introduction
Summarized in the following sections of this letter report are the philosophies and procedures used
to determine recommended settings for the “Active” (in service) protection functions in the F650
Feeder Protection System Relay being applied in conjunction with the 3000 kVA, 11.5/6.2 kV “TL2”
Station Auxiliary Supply Transformer. This Station Auxiliary Supply Transformer is associated with
the 126.875 MVA Unit 25 Gas-Turbine Generator referenced in previous sections of this study report.
Also included in this section of the letter report is a summary of the significant assumptions used to
determine these recommended settings.

4.2 “TL2” Station Auxiliary Supply Transformer Data


A Manufacturers Test Report for the subject station auxiliary supply transformer was not available
for this study. The recommended F650 relay settings as described in this letter report are based
upon the transformer ratings summarized below (assumed, based upon data utilized for the
previously completed Tiaret GPP settings studies):

 kVA Rating: 3000 kVA.


 Rated Primary Voltage (phase-to-phase): 11.5 kV.
 Rated Secondary Voltage (phase-to-phase): 6.2 kV.
 Winding Connections (Primary/Secondary): /, 3, 50 Hz,  Winding operated
Solidly Grounded (Note: Solidly-Grounded Operation Assumed).
 System Phase Sequence = 1-2-3
 Rated Primary to Secondary Impedance ZPS  6.0% on a 3000 kVA base, 11.5 kV to 6.2
kV.

Obtaining (if possible) actual Nameplate data for this particular station auxiliary supply transformer
would allow for more accurate relay setting calculations.

PAGE 66

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


F650 Relay Application: 3000 kVA Station Auxiliary Supply Transformer TL2

4.3 Protective Relay Data


The recommended F650 relay settings provided for the “TL2” supply transformer feeder circuits are
based upon the following assumed F650 Relay Order Code:

 F650-B-A-B-F-2-G-1-HI-F-6
 Version 5.40

Before beginning relay testing/commissioning the F650 relay Order Code and Firmware Version used
to complete this analysis (and summarized above) should be compared against the actual (as
installed) F650 relay Order Code/Version. Modifications to the recommended relay settings and/or the
supplied F650 relay setting file may be required if the actual F650 Order Code/Firmware Version is
different than the Order Code/Version used in this analysis.

PAGE 67

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


F650 Relay Application: 3000 kVA Station Auxiliary Supply Transformer TL2

4.4 Input CT and VT Data


In addition to the above, the recommended F650 relay settings are based upon the following
assumptions concerning the CT’s and VT’s which will be used to supply the relay:

F650 Relay (associated with the 3000 kVA Unit 25 “TL2” Aux Supply Transformer):
o Phase CT Inputs (Input B1/B2, B3/B4, B5/B6): These Phase CT’s are connected in Wye,
and have a Ratio of 300/1 Amperes. These Phase CT’s are connected to the B1/B2,
B3/B4 and B5/B6 CT Inputs.
o Ground CT Input (B9/B10): This CT input (Input B9/B10) is connected into the neutral
(“residual”) circuit of the B1/B2, B3/B4, B5/B6 Phase CT inputs. Due to the fact that
this turbine-generator is operated High-Resistance Grounded this Ground CT input
signal is not used in this application.

o Phase VT Inputs (Input A5/A6, A7/A8, A9/A10): These Phase VT’s are connected wye
primary-wye secondary, and have a Ratio of 115/1. These Phase VT’s are connected
to the A5/A6, A7/A8 and A9/A10 VT Inputs.
o Auxiliary VT Input (A11/A12): Not used in this application.

Based upon the supplied data, the nominal secondary voltage which will be applied to the F650
relay = 100 Volts  (57.7 Volts N), as summarized below:

11500 Vph  ph  100Vph  ph  100 Vph  N  57.7Vph  N


Vrelay 
1151  3

These secondary voltages should be verified during unit commissioning via actual measurement
(using a multi-meter) at the relay VT input terminals when the unit is operating at rated secondary
voltage.

PAGE 68

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


F650 Relay Application: 3000 kVA Station Auxiliary Supply Transformer TL2

4.5 Contact Input and Contact Output Data


The F650 relay utilized in this application is also equipped with Digital (Contact) inputs and Contact
outputs which can (within certain restrictions) be assigned to perform user-specified functions. The
recommended F650 relay settings provided in this analysis are based upon the following
assumptions for each of these Contact inputs and Contact outputs:

a) F650 Relay (associated with each of the 3000 kVA “TL2” Station Aux Supply Transformers):
o Assignable Digital (Contact) Input F1/F2: Not utilized in this application.
o Assignable Digital (Contact) Input F3/F4: Not utilized in this application.
o Assignable Digital (Contact) Input F5/F9: Externally connect “b” Status contacts from
the 86/T1 and 86/T2 Lockout relays (normally closed contacts, open when L/O
operates) in series. This series combination is then connected into this input.
o Assignable Digital (Contact) Input F6/F9: Connect an “a” Status contact from the
86/T1 Lockout relay into this input (normally open contact, closes when L/O operates).
o Assignable Digital (Contact) Input F7: Connect an “a” Status contact from the 86/T2
Lockout relay into this input (normally open contact, closes when L/O operates).
o Assignable Digital (Contact) Input F8: Not utilized in this application.
o Assignable Digital (Contact) Input F11: Not utilized in this application.
o Assignable Digital (Contact) Input F12: Not utilized in this application.
o Assignable Digital (Contact) Input F13: Not utilized in this application.
o Assignable Digital (Contact) Input F14: Not utilized in this application.
o Assignable Digital (Contact) Input F15/F16: Not utilized in this application.
o Assignable Digital (Contact) Input F17/F18: Not utilized in this application.

o Contact Output “O1” (F19/F20): Provides a “26TL Alarm” output indication.


o Contact Output “O2” (F21/F22): Provides a “63TL Stage 1” output indication.
o Contact Output “O3” (F23/F24): Provides a “63TL Stage 2” output indication.
o Contact Output “O4” (F25/F26): Provides a “71TL” output indication.
o Contact Output “O5” (F27/F28): Provides a “45FTL” output indication.
o Contact Output “O6” (F29/F30): Provides a “41EX” Trip Output.
o Contact Output “O7” (F31/F33): Connected to 86/T1 Lockout Relay Trip Circuit.
o Contact Output “O8” (F34/F36): Connected to C/B 52L Trip Circuit.

PAGE 69

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


F650 Relay Application: 3000 kVA Station Auxiliary Supply Transformer TL2

Contact Input Data and Contact Output Data (TL F650 Relays) (Continued)

o Assignable Digital (Contact) Input G1: Connected to a “26TL Stage 1 (Temperature)”


Status Contact (normally open contact, closes when device operates).
o Assignable Digital (Contact) Input G2: Connected to a “26TL Stage 2 (Temperature)”
Status Contact (normally open contact, closes when device operates).
o Assignable Digital (Contact) Input G3: Connected to a “63TL Stage 1 (Bucholz)” Status
Contact (normally open contact, closes when device operates).
o Assignable Digital (Contact) Input G4: Connected to a “63TL Stage 2 (Bucholz)” Status
Contact (normally open contact, closes when device operates).
o Assignable Digital (Contact) Input G5: Connected to a “71TL (Oil Level)” Status Contact
(normally open contact, closes when device operates).
o Assignable Digital (Contact) Input G6: Connected to a “45FTL (Fire Detection)” Status
Contact (normally open contact, closes when device operates).
o Assignable Digital (Contact) Input G7: Available for customer use if desired.
o Assignable Digital (Contact) Input G8: Available for customer use if desired.
o Assignable Digital (Contact) Input G11: Available for customer use if desired.
o Assignable Digital (Contact) Input G12: Available for customer use if desired.
o Assignable Digital (Contact) Input G13: Available for customer use if desired.
o Assignable Digital (Contact) Input G14: Available for customer use if desired.
o Assignable Digital (Contact) Input G15: Available for customer use if desired.
o Assignable Digital (Contact) Input G16: Available for customer use if desired.
o Assignable Digital (Contact) Input G17: Available for customer use if desired.
o Assignable Digital (Contact) Input G18: Available for customer use if desired.

o Contact Output “O1” (G20/G21): Available for customer use if desired.


o Contact Output “O2” (G22/G23/G24): Connected to C/B 52G Trip Circuit.
o Contact Output “O3” (G25/G26): Provides a “TL 50/51P Trip” output indication.
o Contact Output “O4” (G27/G28): Provides an “F650 Alarm” output indication.
o Contact Output “O5” (G29/G30): Provides a “Change Source 400V CCM” output.
o Contact Output “O6” (G31/G32): Connected to 86/T2 Lockout Relay Trip Circuit.
o Contact Output “O7” (G33/G34): Provides a “Turbine Normal Stop” output.
o Contact Output “O8” (G35/G36): Provides a “Change Source 6 kV” NO output to the
TAM F650 relay input.

PAGE 70

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


F650 Relay Application: 3000 kVA Station Auxiliary Supply Transformer TL2

4.6 Setting Philosophies


For these Station Auxiliary Supply Transformer F650 relay applications, recommended settings were
developed and implemented for the following protection functions included in each relay:

o Primary (11.5 kV) Phase Overcurrent (50/51P)

Included on the following pages of this letter report is a discussion of the philosophies used to
determine recommended settings for this protection function.

PAGE 71

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


F650 Relay Application: 3000 kVA Station Auxiliary Supply Transformer TL2

4.7 Setting Philosophies: Primary Phase Overcurrent Protection


The recommended settings of the primary phase overcurrent protection functions associated with
the 3000 kVA Unit 25 Station Auxiliary Supply Transformer will;

1. allow the auxiliary supply transformer to continuously operate at its 3000 kVA rated output
capability.
2. allow successful energization of the 3000 kVA station auxiliary supply transformer.
3. provide the level of through-fault current withstand protection for the station auxiliary
supply transformer described in the ANSI C57 transformer protection standards.

4.8 Primary Phase Overcurrent Protection Function (50/51P)


As stated previously, the “TL2” Station Auxiliary Supply Transformer is rated 3000 kVA, which
corresponds to an output current rating of  151 Amperes at the rated primary voltage of 11.5 kV.
Based upon the previous discussion, the Primary Phase Overcurrent protection function (50/51P) in
the F650 Feeder Protection System Relay will utilize the following settings:

4.8.1 Primary Phase Overcurrent Relay Settings (50/51P)


Supply Phase CT Ratio = 300/1 Amperes

o Phase TOC High 1 Pickup = 0.60 A (180 Primary Amperes, or  120% of the winding rating)
o Phase TOC High 1 Curve Shape = IEEE Extremely Inverse
o Phase TOC High 1 Multiplier = 3.50

o Phase IOC High 1 Pickup = 9.00 A (2700 Primary Amperes)


o Phase IOC High 1 Trip Delay = 0.00 seconds

o Phase IOC Low 1 Pickup = 1.50 A (450 Primary Amperes, or  299% of the winding rating)
o Phase IOC Low 1 Trip Delay = 0.60 seconds

PAGE 72

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


F650 Relay Application: 3000 kVA Station Auxiliary Supply Transformer TL2

Below is a summary of equations which can be used to describe the shape of the Primary Phase
Overcurrent characteristic curve:

  
 28.2  
T  M    0.1217 , 0.60  I < 1.50 Amps

 I
 0.60
 2
1



T  0.6 , 1.50  I < 9.00 Amps
T  " Inst" , I  9.00 Amps
NOTES:
T = Trip Time (seconds)
I = Relay Input Current (Amps)
M = Curve Multiplier = 3.50

In the above equations, the value of I (relay input current) is shown in CT Secondary Amps.

Application of the Phase TOC High 1, Phase IOC High 1 and Phase IOC Low 1 settings summarized
above and on the previous page will result in the following approximate relay tripping times at
various values of % Rated Current. Here, note that “Rated Current” is defined as the Station
Auxiliary Supply transformer output current rating (151 Amps at 11.5 kV).

% of Rated Current Time


150 172 sec
175 86.7 sec
200 55.2 sec
250 29.7 sec
299 19.2 sec
>299 and <1793 0.6 sec
>1793 “Inst”

Where the Rated Current = 151 Primary (System) Amperes, or 0.502 Secondary (Relay) Amperes.
Note: “Inst” signifies no intentional time delay.

PAGE 73

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


F650 Relay Application: 3000 kVA Station Auxiliary Supply Transformer TL2

4.8.2 Discussion
The data supplied for this analysis did not include any information (types, settings, time versus
current tripping characteristics, etc.) for the 6.2 kV secondary main/feeder circuit breakers presently
installed in conjunction with this station auxiliary supply transformer. In addition, the study
Workscope did not include performing any time versus current coordination analyses for this “TL2”
11.5/6.2 kV Station Auxiliary distribution system. As stated previously, the recommended settings
provided for the 11.5 kV primary phase overcurrent protection functions were based upon; (a)
allowing the station auxiliary supply transformer to continuously operate at its 3000 kVA rated
output capability, (b) allowing successful energization of the 3000 kVA supply transformer and (c)
providing the level of through-fault current withstand protection for the station auxiliary supply
transformer described in the ANSI C57 transformer protection standards. Depending upon the time
versus current tripping characteristics of the presently installed 6.2 kV transformer secondary
protective devices these recommended primary phase overcurrent protection function settings may
also provide some coordination (selectivity) with these secondary protective devices.

Note that for primary current flows less than 450 Amperes only the Phase TOC High 1 protection
function is effectively in service, since the minimum operating (Pickup) current of the Phase IOC Low
1 protection function is 450 Primary Amperes. For primary current flows equal to or above 450
Amperes but less than 2700 Amperes both the Phase TOC High 1 protection function and the
Phase IOC Low 1 protection functions are effectively in service. However the Phase IOC 1 Low
protection function will normally respond first and provide a trip output before the Phase TOC High
1 protection function, since the Phase IOC Low 1 protection function utilizes a faster (Definite Time,
0.60 second) trip characteristic. For primary current flows equal to or above 2700 Amperes the
Phase TOC High 1, the Phase IOC Low 1 and the Phase IOC High 1 protection functions are all
effectively in service. However the Phase IOC High 1 protection function will normally respond first
and provide a trip output before either the Phase TOC High 1 or the Phase IOC Low 1 protection
function, since the PHASE IOC High 1 protection function utilizes a faster (“Instantaneous” or no
intentional time delay) trip characteristic.

PAGE 74

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


F650 Relay Application: 3000 kVA Station Auxiliary Supply Transformer TL2

Note that the Phase IOC High 1 protection function is set slightly above the maximum “through-
fault” current flow into the 3000 kVA station auxiliary supply transformer (the current that would
flow through the transformer for a bolted 3 fault at the transformer secondary terminals) and is
also set above the assumed maximum transformer inrush current flow. For this analysis, the
maximum expected through-fault current flow value for the station auxiliary supply transformer is
calculated to be  2510 RMS symmetrical Amperes @ the 11.5 kV primary voltage level, while the
maximum Inrush current flow is  1807 Amperes @ 11.5 kV (based upon a typical assumption that
the maximum IINRUSH  12*IFL). Note that the maximum expected through-fault current flow was
calculated assuming an Infinite primary source, using the previously summarized winding
Impedance (6.0% on a 3000 kVA base).

PAGE 75

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


F650 Relay Application: 3000 kVA Station Auxiliary Supply Transformer TL2

4.9 Observations/Recommendations

a) The Ratios and Connections of all Phase CT’s and Phase VT’s connected to this F650 relay (as
previously listed under “Input CT and VT Data”) should be verified prior to station auxiliary
supply transformer startup/operation. Modifications of recommended relay settings will be
required if the Connections or Ratios of any of the actual (installed) CT’s and/or VT’s are
different than the listed Connections/Ratios.

b) Following “TL2” auxiliary supply transformer energization, the Connections and Ratios of the
installed Phase VT’s should be further verified by comparing the phase-to-phase and phase-
to-neutral voltages measured/displayed by this F650 relay (using the Metering functions in
the relay) with phase-to-phase and phase-to-neutral voltages measured by other devices.
In addition, the Connections and Ratios of the installed Phase CT’s should be further verified
by comparing the phase current values measured/ displayed by this F650 relay (using the
metering functions in the relay) with phase current values measured by other devices.

c) The Contact Input and Contact Output assignments associated with this F650 relay (as
previously listed under “Contact Input and Contact Output Data”) should be verified prior to
station auxiliary supply transformer startup/operation. Modifications of recommended relay
settings will be required if the actual Contact Input and/or Contact Output connections are
different than the listed Connections.

It is important that a field verification of actual (as installed) CT and VT Ratios, CT and VT connections
and Contact Input and Contact Output assignments as described in previous sections of this letter
report be completed prior to transformer startup/operation. Providing and maintaining the desired
levels of protection to this transformer by the installed F650 relay requires that the CT/VT Ratios and
connections along with the Contact Input and Contact Output assignments exactly match the
previously listed Ratios, connections and assignments.

d) During normal operation, the “READY” LED on the relay faceplate should be illuminated. If
this LED is not illuminated during normal station auxiliary supply transformer operation the
protection provided to the transformer may be significantly compromised, and further field
investigation of F650 relay failure is required.

PAGE 76

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


BE1-59N Relay Application: 11.5 kV Main Distribution Bus

5. BE1-59N Setting Calculations (11.5 kV Main Distribution Buses)


5.1 Introduction
Summarized in the following sections of this letter report are the philosophies and procedures used
to determine recommended settings for Basler BE1-59N Ground Fault Over-Voltage Relay being
applied in conjunction with the TP3 11.5 kV main distribution bus referenced in previous sections of
this study report. Also included in this section of the letter report is a summary of the significant
assumptions used to determine these recommended settings.

5.2 BE1-59N Relay Data


The recommended BE1-59N ground fault over-voltage relay settings provided in this study are
based upon the following assumed BE1-59N Order Code:

Style Number:
BE1-59N, Style A1E-E1J-D0N1F

Adjustment Ranges:
Time Over-Voltage: 1-20 Volts, 0.1-99.9 sec Definite Time Delay

Supply VT Ratio: (11500/3)/(100/3) Volts (Wye- Broken Delta)

Modifications to the recommended device settings may be required if the actual BE1-59N Order
Code is different than the assumed Order Code summarized above.

PAGE 77

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


BE1-59N Relay Application: 11.5 kV Main Distribution Bus

5.3 Contact Output Data


The BE1-59N relay utilized in this application is also equipped with contact outputs which can be
assigned (wired) to perform user-specified functions. Shown below is a summary of the BE1-59N
output contact assignment utilized in this application:

1. Contact Outputs
a. Trip Contact Output (Terminals 1/10): Connected to Auxiliary Relay 64BX Trip Circuit.
b. Auxiliary NO Contact Output (Terminals 5/8): Provides a “BE1-59N Trip” output
indication.

5.4 Setting Philosophies


The recommended settings for this BE1-59N relay are based upon past experience with application
of bus ground fault relays at similar installations (such as other Sonelgaz facilities), and attempt to
provide reasonably sensitive phase-to-ground fault protection for the 11.5 kV distribution bus
associated with this Generator/GSU combination while also providing some security against false
tripping.

The recommended BE1-59N relay settings are also based upon an interpretation of existing setting
data supplied for the previously completed Tiaret Unit 6 GPP settings study. This supplied data
seemed to indicate that an existing 64B relay (type/model unknown) utilized the following settings:

“20% Un, 0.47 s, Un=100/3”

Based upon the indicated value for Un (100/3 or 57.7 Volts), a setting of 20% Un would imply a
Pickup setting of  (0.20)*(57.7) Volts or 11.6 Volts (12 Volts), with an indicated tripping time delay of
0.47 seconds (0.5 seconds).

Based upon the above, the BE1-59N Ground Fault Over-Voltage Relay will utilize the following
settings:

5.4.1 Suggested Settings (64B)

o Time Over-Voltage Pickup = 12 Volts


o Definite Time Delay = 0.50 seconds

PAGE 78

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


Recommended Protective Device Setting Tables

6. Recommended Protective Device Setting Tables


6.1 Introduction
Following this introduction are tables of recommended settings for the “active” (in service)
protection functions in the following protective relays associated with the new M’Sila Unit 25
Generator Protection Panel (GPP):

1. The G3 UR G60 Generator Management Primary and Backup Relays.


2. The UR T60 Transformer Management Primary and Backup Relays associated with the TP3
125 MVA Generator Step-Up Transformer.
3. The F650 Feeder Protection System Relay associated with the TL2 3000 kVA Station Auxiliary
Supply Transformer.
4. The F650 Feeder Protection System Relay associated with the TAM3 800 kVA Gas-Turbine
Auxiliary Supply Transformer.
5. The BE1-59N Neutral Over-Voltage Relay associated with the TP3 11.5 kV Secondary Main
Distribution Bus.

The recommended UR G60, UR T60 and F650 settings have been implemented in the URPC and
EnerVista 650PC setting files included with this transmittal.

PAGE 79

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


Recommended Protective Device Setting Tables

As shown, one or more Test Points (shown in Green) have been provided for each of the active
overcurrent, under-voltage, over-voltage and over-excitation protection functions in each of these
relays. These Test Points summarize expected relay tripping times (in seconds) for various values of
relay input current (In Amperes) or input voltage (in Volts). The listed Test Points should be used
during relay calibration/test to verify the performance of each protective relay. Any discrepancies
between the tripping times shown on the attached setting tables and the actual tripping times
determined during relay testing should be resolved before these relays are placed into service.

Each setting sheet also includes one or more reference Notes. Some of the more significant setting
Notes are shown in Red, Dark Red or Violet on these sheets.

In addition, note that the “active” (in-service) Phase Time Overcurrent protection functions in the UR
G60 and UR T60 relays utilize Timed-Type Reset characteristics. In order to obtain accurate tripping
times during relay calibration, these Reset characteristics may need to be temporarily changed to
the Instantaneous type during testing/commissioning. Once relay calibration is completed this
Reset characteristic should be changed back to the Timed type prior to placing the relay in service.

Similarly, the Reset Rates associated with the Over-Excitation (24T) Trip protection functions in the
UR G60 and UR T60 relays may need to be temporarily changed to 0 seconds during relay
calibration to allow accurate tripping times to be obtained during testing of these protection
functions. Once relay calibration is completed the Reset Rates associated with these functions
should be returned to the originally programmed values.

PAGE 80

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: G60 Generator Management Primary and Backup Relays

6.1.1 126.875 MVA, 11.5 kV Gen G3– UR G60 Generator Management Relay
Protective Device Description
Circuit Identification Relay Ranges Recommended Settings Protection
C/B Circuit Gen ANSI Relay CT VT Time Function
Number Identification Rating Dev. No. Mfg. Model No. Time Inst. Ratio Ratio Tap Amp Dial Inst. Amp Trips Reference
52G Tie to Generator 126875 kVA 87S UR G60-J04-HMH- -- 0.05- 7500/1 -- Pickup = 0.060 pu H1 STATOR DIFF OP
G5 11500 Volts G60 F8L-H6P-M8L- 1.00 pu (F1-F3) Slope 1 = 10%, Break 1 = 1.15 pu U1
6370 Amps P6D-U4L-W6C Slope 2 = 20%, Break 2 = 30.00 pu W1
7500/1
(M1-M3)
51P UR G60-J04-HMH- 0.000- -- 7500/1 115/1 Pickup = 1.189 pu (8918 Primary A) H1 PHASE TOC1 OP
G60 F8L-H6P-M8L- 30.00 pu (F1-F3) (F5-F7) Input Type = RMS U3 (**)
P6D-U4L-W6C IEEE Moderately Inverse Curve, Timed Reset W1
Multiplier = 0.42, Voltage Restraint Enabled
Test Point 1: 1.8 Amps, 100 Volts, 2.65 sec
Test Point 2: 5.2 Amps, 100 Volts, 0.77 sec

NOTES
Output Contact H1 Trips L/O Relay 86/G1 (for “Primary” G60 Relay) or L/O Relay 86/G2 (for “Backup” G60 Relay).
Output Contact U1 provides an “87ST Trip” Output Indication.
Output Contact U3 provides a “51P Trip” Output Indication.
Output Contact W1 provides an “All Trips” Output Indication.
(**) – Protection Function blocked following VT Fuse Failure

PAGE 81

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: G60 Generator Management Primary and Backup Relays

126.875 MVA, 11.5 kV Generator G3 – UR G60 Generator Management Relay (Continued)


Protective Device Description
Circuit Identification Relay Ranges Recommended Settings Protection
C/B Circuit Gen ANSI Relay CT VT Time Function
Number Identification Rating Dev. No. Mfg. Model No. Time Inst. Ratio Ratio Tap Amp Dial Inst. Amp Trips Reference
52G Tie to Generator 126875 kVA 50P UR G60-J04-HMH- -- 0.000- 7500/1 -- Protection Function Not Utilized in This PHASE IOC1 OP
G5 11500 Volts G60 F8L-H6P-M8L- 30.00 (F1-F3) Application.
6370 Amps P6D-U4L-W6C pu
50/27 UR G60-J04-HMH- -- 0.000- 7500/1 115/1 O/C Pickup = 0.050 pu (375 Primary A) H1 ACCDNT ENGR OP
G60 F8L-H6P-M8L- 3.000 (F1-F3) (F5-F7) U/V Pickup = 0.800 pu U10
P6D-U4L-W6C pu Arming Mode = “U/V and OFFLINE” W1

NOTES
Output Contact H1 Trips L/O Relay 86/G1 (for “Primary” G60 Relay) or L/O Relay 86/G2 (for “Backup” G60 Relay).
Output Contact U10 provides a “50/27 Trip” Output Indication.
Output Contact W1 provides an “All Trips” Output Indication.

PAGE 82

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: G60 Generator Management Primary and Backup Relays

126.875 MVA, 11.5 kV Generator G3 – UR G60 Generator Management Relay (Continued)


Protective Device Description
Circuit Identification Relay Ranges Recommended Settings Protection
C/B Circuit Gen ANSI Relay CT VT Time Function
Number Identification Rating Dev. No. Mfg. Model No. Time Inst. Ratio Ratio Tap Amp Dial Inst. Amp Trips Reference
52G Tie to Generator 126875 kVA 46 UR G60-J04-HMH- 7500/1 -- Inom = 0.849 pu (6368 Primary A)
G5 11500 Volts G60 F8L-H6P-M8L- (F1-F3)
6370 Amps P6D-U4L-W6C Alarm: Alarm: Alarm:
0.00-100.00% Inom Pickup = 4.48% Inom Alarm GEN UNBAL STG2
0.0-1000.0 sec Delay = 6.0 sec LED OP
W2

Trip:
0.00-100.00% Inom Trip: W7 Trip:
K = 0.00-100.00 Pickup = 6.40% Inom W8 GEN UNBAL STG1
0.000-50.000 sec K = 8.00 U5 OP
0.0-1000.0 sec Tmin = 0.010 sec W1
0.0-1000.0 sec Tmax = 120.0 sec
K-Reset = 900.0 sec

NOTES
Output Contact U5 provides a “46 Trip” Output Indication.
Output Contact W1 provides an “All Trips” Output Indication.
Output Contact W2 provides an “All Alarms” Output Indication.
Output Contact W7 Trips C/B 52L via Backup UR T60 Relay. Output Contact W8 Trips C/B 52L via Primary UR T60 Relay.

PAGE 83

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: G60 Generator Management Primary and Backup Relays

126.875 MVA, 11.5 kV Generator G3 – UR G60 Generator Management Relay (Continued)


Protective Device Description
Circuit Identification Relay Ranges Recommended Settings Protection
C/B Circuit Gen ANSI Relay CT VT Time Function
Number Identification Rating Dev. No. Mfg. Model No. Time Inst. Ratio Ratio Tap Amp Dial Inst. Amp Trips Reference
52G Tie to Generator 126875 kVA 64G UR G60-J04-HMH- -- 0.000- -- 66.4/1 Pickup = 0.040 pu (266 Primary V) H2 AUX OV1
G5 11500 Volts G60 F8L-H6P-M8L- 3.000 (F8) Delay = 0.28 seconds H3 OP
6370 Amps P6D-U4L-W6C pu Reset Delay = 0.10 sec W5
Test Point 1: 4.5 Volts, 0.28 sec U13
Test Point 2: 100 Volts, 0.28 sec W1
27PA UR G60-J04-HMH- 0.00- -- -- 115/1 Pickup = 0.720 pu (8280 Primary V) Alarm PHASE UV2 OP
G60 F8L-H6P-M8L- 3.00 pu (F5-F7) Signal Source = Phase-to-Phase LED (**)
P6D-U4L-W6C Definite Time Curve, Delay = 2.50 W2
Test Point 1: 70 Volts , 2.50 sec W7
Test Point 2: 10 Volts , 2.50 sec W8
27PT UR G60-J04-HMH- 0.00- -- -- 115/1 Pickup = 0.720 pu (8280 Primary V) H2 PHASE UV1 OP
G60 F8L-H6P-M8L- 3.00 pu (F5-F7) Signal Source = Phase-to-Phase H3 (**)
P6D-U4L-W6C Definite Time Curve, Delay = 2.80 U8
Test Point 3: 70 Volts , 2.80 sec W1
Test Point 4: 10 Volts , 2.80 sec H6
NOTES
Output Contact H2 Trips Gen C/B 52G, Trip Circuit #1. Output Contact H3 Trips Gen C/B 52G, Trip Circuit #2.
Output Contact H6 Performs a “Change Source 400 V CCM” Operation.
Output Contact U8 provides a “27PT” Output Indication.
Output Contact U13 provides a “64G Trip” Output Indication.
Output Contact W1 provides an “All Trips” Output Indication.
Output Contact W2 provides an “All Alarms” Output Indication.
Output Contact W5 Provides a 41EX Output Signal.
Output Contact W7 Trips C/B 52L via Backup UR T60 Relay. Output Contact W8 Trips C/B 52L via Primary UR T60 Relay.

PAGE 84

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: G60 Generator Management Primary and Backup Relays

126.875 MVA, 11.5 kV Generator G3 – UR G60 Generator Management Relay (Continued)


Protective Device Description
Circuit Identification Relay Ranges Recommended Settings Protection
C/B Circuit Gen ANSI Relay CT VT Time Function
Number Identification Rating Dev. No. Mfg. Model No. Time Inst. Ratio Ratio Tap Amp Dial Inst. Amp Trips Reference
52G Tie to Generator 126875 kVA 59P1 UR G60-J04-HMH- 0.00- -- -- 115/1 Pickup = 1.20 pu (13800 Primary V) H1 FLEXELMT 5 OP
G5 11500 Volts (Trip) G60 F8L-H6P-M8L- 3.00 pu (F5-F7) Delay = 3.60 sec U9 FLEXELMT 6 OP
6370 Amps P6D-U4L-W6C Reset Delay = 0.10 sec W1 FLEXELMT 7 OP
Trip Mode = (VAB) + (VBC) + (VCA)
(Any Phase-to-Phase Over-Voltage)
Test Point 1: 122 Volts , applied to any
phase-to-phase input, 3.60 sec
59P2 UR G60-J04-HMH- 0.00- -- -- 115/1 Pickup = 1.300 pu (14950 Primary V) H1 PHASE OV1 OP
(Trip) G60 F8L-H6P-M8L- 3.00 pu (F5-F7) Definite Time, Delay = 0.00 sec U9
P6D-U4L-W6C Reset Delay = 0.10 sec W1
Test Point 2: 132 Volts , “Inst”

NOTES
Output Contact H1 Trips L/O Relay 86/G1 (for “Primary” G60 Relay) or L/O Relay 86/G2 (for “Backup” G60 Relay).
Output Contact U9 provides a “59P Trip” Output Indication.
Output Contact W1 provides an “All Trips” Output Indication.

Typically Over-Voltage protection functions do not utilize “Instantaneous” (no intentional time delay) Tripping Time delays. In this application the 59P2 protection function has been enabled with an
Instantaneous tripping delay based upon customer request/requirements provided for the Tiaret GPP setting calculation studies. However a relatively short (0.10 second) tripping time delay is suggested as
an alternative for consideration by the customer.

PAGE 85

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: G60 Generator Management Primary and Backup Relays

126.875 MVA, 11.5 kV Generator G3 – UR G60 Generator Management Relay (Continued)


Protective Device Description
Circuit Identification Relay Ranges Recommended Settings Protection
C/B Circuit Gen ANSI Relay CT VT Time Function
Number Identification Rating Dev. No. Mfg. Model No. Time Inst. Ratio Ratio Tap Amp Dial Inst. Amp Trips Reference
52G Tie to Generator 126875 kVA 95(24)T1 UR G60-J04-HMH- 0.80-4.00 -- -- 115/1 Pickup = 1.10 pu H2 VOLTS PER
G5 11500 Volts (Trip) G60 F8L-H6P-M8L- pu V/Hz (F5-F7) Definite Time, Delay = 42.0 sec H3 HERTZ 1 OP
6370 Amps P6D-U4L-W6C T Reset = 900.0 sec U7
Test Point 1: 110 Volts , 50 Hz, 42.0 sec W1
Test Point 2: 116 Volts , 50 Hz, 42.0 sec W5
95(24)T2 UR G60-J04-HMH- 0.80-4.00 -- -- 115/1 Pickup = 1.17 pu H2 VOLTS PER
(Trip) G60 F8L-H6P-M8L- pu V/Hz (F5-F7) Definite Time, Delay = 1.85 sec H3 HERTZ 2 OP
P6D-U4L-W6C T Reset = 10.0 sec U7
Test Point 3: 117 Volts , 50 Hz, 1.85 sec W1
Test Point 4: 135 Volts , 50 Hz, 1.85 sec W5
95(24)A UR G60-J04-HMH- -- -- 115/1 Pickup = 1.07 pu Alarm FLEXELEMENT
(Alarm) G60 F8L-H6P-M8L- (F5-F7) Definite Time, Delay = 10.000 sec LED 4 OP
P6D-U4L-W6C T Reset = 0.000 sec W2
Test Point 5: 107 Volts , 50 Hz, 10.00 sec
NOTES
Output Contact H2 Trips Gen C/B 52G, Trip Circuit #1. Output Contact H3 Trips Gen C/B 52G, Trip Circuit #2.
Output Contact U7 provides a “24 Trip” Output Indication.
Output Contact W1 provides an “All Trips” Output Indication.
Output Contact W2 provides an “All Alarms” Output Indication.
Output Contact W5 Provides a 41EX Output Signal.

PAGE 86

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: G60 Generator Management Primary and Backup Relays

126.875 MVA, 11.5 kV Generator G3 – UR G60 Generator Management Relay (Continued)


Protective Device Description
Circuit Identification Relay Ranges Recommended Settings Protection
C/B Circuit Gen ANSI Relay CT VT Time Function
Number Identification Rating Dev. No. Mfg. Model No. Time Inst. Ratio Ratio Tap Amp Dial Inst. Amp Trips Reference
52G Tie to Generator 126875 kVA 40-1 UR G60-J04-HMH- 0.10-300.0 Ohms 7500/1 115/1 Trip #1: Center=55.32 , Radius=47.06  H2 LOSS EXCIT
G5 11500 Volts G60 F8L-H6P-M8L- (Center, Radius) (F1-F3) (F5-F7) Pickup Delay = 0.060 sec H3 STG1 OP
6370 Amps P6D-U4L-W6C 0-65.535 sec Delay UV Supervision = Disabled U4 (**)
W1
W5
40-2 UR G60-J04-HMH- 0.10-300.0 Ohms 7500/1 115/1 Trip #2: Center=75.49 , Radius=67.23  H2 LOSS EXCIT
G60 F8L-H6P-M8L- (Center, Radius) (F1-F3) (F5-F7) Pickup Delay = 0.600 sec H3 STG2 OP
P6D-U4L-W6C 0-65.535 sec Delay UV Supervision = Disabled U4 (**)
W1
W5

NOTES
Output Contact H2 Trips Gen C/B 52G, Trip Circuit #1. Output Contact H3 Trips Gen C/B 52G, Trip Circuit #2.
Output Contact U4 provides a “40 Trip” Output Indication.
Output Contact W1 provides an “All Trips” Output Indication.
Output Contact W5 Provides a 41EX Output Signal.
(**) – Protection Function blocked following VT Fuse Failure

Typically operation of Loss of Excitation protection functions Trip the 86G Lockout Relay associated with the unit. Based upon customer request/requirements provided for the Tiaret GPP setting calculation
studies the Loss of Excitation protection functions associated with this unit will instead trip the generator output circuit breaker (C/B 52G) and also provide a “41EX” Trip signal.

PAGE 87

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: G60 Generator Management Primary and Backup Relays

126.875 MVA, 11.5 kV Generator G3 – UR G60 Generator Management Relay (Continued)


Protective Device Description
Circuit Identification Relay Ranges Recommended Settings Protection
C/B Circuit Gen ANSI Relay CT VT Time Function
Number Identification Rating Dev. No. Mfg. Model No. Time Inst. Ratio Ratio Tap Amp Dial Inst. Amp Trips Reference
52G Tie to Generator 126875 kVA 81U/ UR G60-J04-HMH- 20.00-65.00 Hz -- 115/1 Trip #1: W7
G5 11500 Volts Trip 1 G60 F8L-H6P-M8L- 0.000-65.535 sec (F5-F7) Pickup = 47.80 Hz W8 UNDERFREQ 1
6370 Amps P6D-U4L-W6C Delay = 0.300 sec U12 OP
Reset Delay = 0.100 sec W1
81U/ UR G60-J04-HMH- 20.00-65.00 Hz -- 115/1 Trip #2: W3
Trip 2 G60 F8L-H6P-M8L- 0.000-65.535 sec (F5-F7) Pickup = 47.50 Hz H2 UNDERFREQ 2
P6D-U4L-W6C Delay = 0.000 sec H3 OP
Reset Delay = 0.100 sec W5
U12
W1
NOTES
Output Contact H2 Trips Gen C/B 52G, Trip Circuit #1. Output Contact H3 Trips Gen C/B 52G, Trip Circuit #2.
Output Contact U12 provides an “81 Trip” Output Indication.
Output Contact W1 provides an “All Trips” Output Indication.
Output Contact W5 Provides a 41EX Output Signal.
Output Contact W7 Trips C/B 52L via Backup UR T60 Relay. Output Contact W8 Trips C/B 52L via Primary UR T60 Relay.

Note – 81U/Trip 1 and 81U/Trip 2 are blocked from operation if C/B 52G is open, as indicated by the C/B 52G “b” position contact being closed. This is done to prevent possible protection function mis-
operation during unit startup.

Typically Under-Frequency protection functions do not utilize “Instantaneous” (no intentional time delay) Tripping Time delays. In this application the 81U/Trip 2 and 81U/Trip 4 protection functions have
been enabled with an Instantaneous tripping delay based upon customer request/requirements provided for the Tiaret GPP setting calculation studies. However a relatively short (0.10 second) tripping time
delay is suggested as an alternative for consideration by the customer.

PAGE 88

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: G60 Generator Management Primary and Backup Relays

126.875 MVA, 11.5 kV Generator G3 – UR G60 Generator Management Relay (Continued)


Protective Device Description
Circuit Identification Relay Ranges Recommended Settings Protection
C/B Circuit Gen ANSI Relay CT VT Time Function
Number Identification Rating Dev. No. Mfg. Model No. Time Inst. Ratio Ratio Tap Amp Dial Inst. Amp Trips Reference
52G Tie to Generator 126875 kVA 81U/ UR G60-J04-HMH- 20.00-65.00 Hz -- 115/1 Trip #3: H4
G5 11500 Volts Trip 3 G60 F8L-H6P-M8L- 0.000-65.535 sec (F5-F7) Pickup = 47.00 Hz U12 UNDERFREQ 3
6370 Amps P6D-U4L-W6C Delay = 20.000 sec W1 OP
Reset Delay = 0.100 sec
81U/ UR G60-J04-HMH- 20.00-65.00 Hz -- 115/1 Trip #4: H4
Trip 4 G60 F8L-H6P-M8L- 0.000-65.535 sec (F5-F7) Pickup = 46.00 Hz U12 UNDERFREQ 4
P6D-U4L-W6C Delay = 0.000 sec W1 OP
Reset Delay = 0.100 sec

NOTES
Output Contact H4 Trips L/O Relay 86/T1 (for “Primary” G60 Relay) or L/O Relay 86/T2 (for “Backup” G60 Relay).
Output Contact U12 provides an “81 Trip” Output Indication.
Output Contact W1 provides an “All Trips” Output Indication.

Note – 81U/Trip 3 and 81U/Trip 4 are blocked from operation if C/B 52G is open, as indicated by the C/B 52G “b” position contact being closed. This is done to prevent possible protection function mis-
operation during unit startup.

Typically Under-Frequency protection functions do not utilize “Instantaneous” (no intentional time delay) Tripping Time delays. In this application the 81U/Trip 2 and 81U/Trip 4 protection functions have
been enabled with an Instantaneous tripping delay based upon customer request/requirements provided for the Tiaret GPP setting calculation studies. However a relatively short (0.10 second) tripping time
delay is suggested as an alternative for consideration by the customer.

PAGE 89

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: G60 Generator Management Primary and Backup Relays

126.875 MVA, 11.5 kV Generator G3 – UR G60 Generator Management Relay (Continued)


Protective Device Description
Circuit Identification Relay Ranges Recommended Settings Protection
C/B Circuit Gen ANSI Relay CT VT Time Function
Number Identification Rating Dev. No. Mfg. Model No. Time Inst. Ratio Ratio Tap Amp Dial Inst. Amp Trips Reference
52G Tie to Generator 126875 kVA 81O/ UR G60-J04-HMH- 20.00-65.00 Hz -- 115/1 Trip #1: H2
G5 11500 Volts Trip 1 G60 F8L-H6P-M8L- 0.000-65.535 sec (F5-F7) Pickup = 51.00 Hz H3 OVERFREQ 2 OP
6370 Amps P6D-U4L-W6C Delay = 20.000 sec U12
Reset Delay = 0.100 sec W1
W3
W5
W7
W8
81O/ UR G60-J04-HMH- 20.00-65.00 Hz -- 115/1 Trip #2: H2
Trip 2 G60 F8L-H6P-M8L- 0.000-65.535 sec (F5-F7) Pickup = 52.00 Hz H3 OVERFREQ 3 OP
P6D-U4L-W6C Delay = 0.300 sec U12
Reset Delay = 0.100 sec W1
W3
W5
W7
W8

NOTES
Output Contact H2 Trips Gen C/B 52G, Trip Circuit #1.
Output Contact H3 Trips Gen C/B 52G, Trip Circuit #2.
Output Contact U12 provides an “81 Trip” Output Indication.
Output Contact W1 provides an “All Trips” Output Indication.
Output Contact W3 Provides a Turbine Normal Stop Output Signal.
Output Contact W5 Provides a 41EX Output Signal.
Output Contact W7 Trips C/B 52L via Backup UR T60 Relay. Note – In this case Output Contact W7 will only be enabled if Input P3a (52LX1) is closed.
Output Contact W8 Trips C/B 52L via Primary UR T60 Relay. Note – In this case Output Contact W8 will only be enabled if Input P3a (52LX1) is closed.

PAGE 90

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: G60 Generator Management Primary and Backup Relays

126.875 MVA, 11.5 kV Generator G3 – UR G60 Generator Management Relay (Continued)


Protective Device Description
Circuit Identification Relay Ranges Recommended Settings Protection
C/B Circuit Gen ANSI Relay CT VT Time Function
Number Identification Rating Dev. No. Mfg. Model No. Time Inst. Ratio Ratio Tap Amp Dial Inst. Amp Trips Reference
52G Tie to Generator 126875 kVA 32 UR G60-J04-HMH- -1.200 to 1.200 pu 7500/1 115/1 Trip: H2 Trip:
G5 11500 Volts G60 F8L-H6P-M8L- 0.00-600.00 sec (F1-F3) (F5-F7) Relay Characteristic Angle = 180 Degrees H3 DIR POWER 1
6370 Amps P6D-U4L-W6C Calibration Angle = 0 Degrees U6 STG1 OP
Pickup = 0.014 pu, Delay = 2.20 sec W1 (**)
50/Offline UR G60-J04-HMH- 7500/1 -- Protection Function Not Utilized in This
G60 F8L-H6P-M8L- (M1-M3) Application.
P6D-U4L-W6C

NOTES
Output Contact H2 Trips Gen C/B 52G, Trip Circuit #1.
Output Contact H3 Trips Gen C/B 52G, Trip Circuit #2.
Output Contact U6 provides a “32 Trip” Output Indication.
Output Contact W1 provides an “All Trips” Output Indication.
(**) – Protection Function blocked following VT Fuse Failure

Typically operation of the Reverse Power protection function Trips the 86G Lockout Relay associated with the unit. Based upon customer request/requirements provided for the Tiaret GPP setting
calculation studies the Reverse Power protection functions associated with this unit will instead trip the generator output circuit breaker (C/B 52G).

o Verify Correct Operating Direction of 32 Protection Function (Active Power flow into Generator).

PAGE 91

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: G60 Generator Management Primary and Backup Relays

126.875 MVA, 11.5 kV Generator G3 – UR G60 Generator Management Relay (Continued)


Protective Device Description
Circuit Identification Relay Ranges Recommended Settings Protection
C/B Circuit Gen ANSI Relay CT VT Time Function
Number Identification Rating Dev. No. Mfg. Model No. Time Inst. Ratio Ratio Tap Amp Dial Inst. Amp Trips Reference
52G Tie to Generator 126875 kVA 21 UR G60-J04-HMH- 0.02-250.00 Ohms 7500/1 115/1 Zone 2: Relay Forward Reach = 10.02  H4 PH DIST Z2 OP
G5 11500 Volts G60 F8L-H6P-M8L- 30-90 Degrees (F1-F3) (F5-F7) Time Delay = 0.600 seconds H6 (**)
6370 Amps P6D-U4L-W6C Supervision = 0.849 pu (6368 Primary Amps) W6
U14
W1
49 UR G60-J04-HMH- 7500/1 -- Pickup = 0.977 pu (7328 Primary Amps) Alarm FLEXELMT 1 OP
G60 F8L-H6P-M8L- (F1-F3) Delay = 5.00 sec LED FLEXELMT 2 OP
P6D-U4L-W6C W2 FLEXELMT 3 OP

NOTES
Output Contact H4 Trips L/O Relay 86/T1 (for “Primary” G60 Relay) or L/O Relay 86/T2 (for “Backup” G60 Relay).
Output Contact H6 Performs a “Change Source 400 V CCM” Operation
Output Contact W6 Performs a “Change Source 6 kV” Operation
Output Contact U14 provides a “21 Trip” Output Indication.
Output Contact W1 provides an “All Trips” Output Indication.
Output Contact W2 provides an “All Alarms” Output Indication.
(**) – Protection Function blocked following VT Fuse Failure

o Verify Correct Operating Direction of 21 Protection Function (Forward or towards Step-Up Transformer Winding)
o Verify Current Supervision Function (21 Protection Function will operate for phase current flows greater than or equal to 6368 Primary Amps or  0.85 secondary Amps but will not operate for phase
current flows less than this value).

PAGE 92

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: G60 Generator Management Primary and Backup Relays

126.875 MVA, 11.5 kV Generator G3 – UR G60 Generator Management Relay (Continued)


Protective Device Description
Circuit Identification Relay Ranges Recommended Settings Protection
C/B Circuit Gen ANSI Relay CT VT Time Function
Number Identification Rating Dev. No. Mfg. Model No. Time Inst. Ratio Ratio Tap Amp Dial Inst. Amp Trips Reference
52G Tie to Generator 126875 kVA 78 UR G60-J04-HMH- 7500/1 115/1 Forward Reach = 13.66  H2 POWER SWING
G5 11500 Volts G60 F8L-H6P-M8L- (F1-F3) (F5-F7) Reverse Reach = 33.04  H3 TRIP
6370 Amps P6D-U4L-W6C Outer Right Blinder Reach = 40.08  W5 (**)
Inner Right Blinder Reach = 13.36  U14
Outer Left Blinder Reach = 40.80  W1
Inner Left Blinder Reach = 13.60 

NOTES
Output Contact H2 Trips Gen C/B 52G, Trip Circuit #1.
Output Contact H3 Trips Gen C/B 52G, Trip Circuit #2.
Output Contact W5 Provides a 41EX Output Signal.
Output Contact U14 provides a “78 Trip” Output Indication.
Output Contact W1 provides an “All Trips” Output Indication.
(**) – Protection Function blocked following VT Fuse Failure

PAGE 93

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: T60 Transformer Management Primary and Backup Relays

6.1.2 GSU TP3 (125 MVA, 240.75/11.5 kV) – UR T60 Relay


Protective Device Description
Circuit Identification Relay Ranges Recommended Settings Protection
Unit Xfmr ANSI Relay CT VT Time Function
Number Identification Rating Dev. No. Mfg. Model No. Time Inst. Ratio Ratio Tap Amp Dial Inst. Amp Trips Reference
Tie to Step-Up 125000 kVA 87T UR T60-J04-HMH- 0.050-1.000 pu 400/1 -- Pickup = 0.100 pu H1 XFMR PCNT
Transformer 240.75 kV  Pri T60 F8L-H6P-M8N- 15-100% (F1-F3) Slope 1 = 20% W1 DIFF OP
TP5 11.5 kV  Sec P6D-U4L-W6C 1.000-2.000 pu Break 1 = 2.000 pu U1
Z=13.2% 2.000-30.000 pu 7500/1 Break 2 = 30.000 pu W4
50%-100% (M1-M3) Slope 2 = 50% H6

300/1 Inrush Inhibit Function = Traditional 2ND


(M5-M7) Inrush Inhibit Mode = Per Phase
1% to 40% fo (%%) Inrush Inhibit Level = 20.0% fo

NOTES
Output Contact H1 Trips L/O Relay 86/T1 (for “Primary” T60 Relay) or L/O Relay 86/T2 (for “Backup” T60 Relay).
Output Contact W1 provides an “All Trips” Output Indication.
Output Contact U1 provides an “87B (87T) Trip” Output Indication.
Output Contact W4 Performs a “Change Source 6 kV” Operation
Output Contact H6 Performs a “Change Source 400 V CCM” Operation
(%%) – 300/1 Ampere Phase CT inputs (associated with “TL2” Auxiliary Transformer) used in conjunction with Step-Up Transformer TP3.

PAGE 94

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: T60 Transformer Management Primary and Backup Relays

Step-up Transformer TP3 (125 MVA, 240.75/11.5 kV) – UR T60 Transformer Management Relay (Continued)
Protective Device Description
Circuit Identification Relay Ranges Recommended Settings Protection
Unit Xfmr ANSI Relay CT VT Time Function
Number Identification Rating Dev. No. Mfg. Model No. Time Inst. Ratio Ratio Tap Amp Dial Inst. Amp Trips Reference
Tie to Step-Up 125000 kVA 87I UR T60-J04-HMH- 2.000-30.000 pu 400/1 Pickup = 4.000 pu H1 XFMR INST
Transformer 240.75 kV  Pri T60 F8L-H6P-M8N- (F1-F3) W1 DIFF OP
TP5 11.5 kV  Sec P6D-U4L-W6C U1
Z=13.2% 7500/1 W4
(M1-M3) H6

300/1
(M5-M7)
(%%)

NOTES
Output Contact H1 Trips L/O Relay 86/T1 (for “Primary” T60 Relay) or L/O Relay 86/T2 (for “Backup” T60 Relay).
Output Contact W1 provides an “All Trips” Output Indication.
Output Contact U1 provides an “87B (87T) Trip” Output Indication.
Output Contact W4 Performs a “Change Source 6 kV” Operation
Output Contact H6 Performs a “Change Source 400 V CCM” Operation
(%%) – 300/1 Ampere Phase CT inputs (associated with “TL2” Auxiliary Transformer) used in conjunction with Step-Up Transformer TP3.

PAGE 95

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: T60 Transformer Management Primary and Backup Relays

Step-up Transformer TP3 (125 MVA, 240.75/11.5 kV) – UR T60 Transformer Management Relay (Continued)
Protective Device Description
Circuit Identification Relay Ranges Recommended Settings Protection
C/B Circuit Xfmr ANSI Relay CT VT Time Function
Number Identification Rating Dev. No. Mfg. Model No. Time Inst. Ratio Ratio Tap Amp Dial Inst. Amp Trips Reference
Tie to Step-Up 125000 kVA 51 Pri UR T60-J04-HMH- 0.000- -- 400/1 -- Pickup = 0.910 pu (364 Primary A) H1 PHASE TOC1
Transformer 240.75 kV  Pri T60 F8L-H6P-M8N- 30.00 pu (F1-F3) IEEE Moderately Inverse Curve, Timed Reset W1 OP
TP5 11.5 kV  Sec P6D-U4L-W6C Multiplier = 0.88, Voltage Restraint Disabled U2
Z=13.2% Test Point 1: 1.20 Amps, 8.27 sec W4
Test Point 2: 1.80 Amps, 3.40 sec H6
50-1 Pri UR T60-J04-HMH- -- 0.000- 400/1 -- Pickup = 1.900 pu (760 Primary A) H1 PHASE IOC1 OP
T60 F8L-H6P-M8N- 30.00 (F1-F3) Delay = 0.60 sec W1
P6D-U4L-W6C pu Reset Delay = 0.10 sec U2
Test Point 3: 2.0 Amps, 0.60 sec W4
Test Point 4: 9.0 Amps, 0.60 sec H6
50-2 Pri UR T60-J04-HMH- -- 0.000- 400/1 -- Pickup = 9.250 pu (3700 Primary A) H1 PHASE IOC2 OP
T60 F8L-H6P-M8N- 30.00 (F1-F3) Delay = 0.00 sec W1
P6D-U4L-W6C pu Reset Delay = 0.10 sec U2
Test Point 5: 9.50 Amps, “Inst” W4
Test Point 6: 40.0 Amps, “Inst” H6
NOTES
Output Contact H1 Trips L/O Relay 86/T1 (for “Primary” T60 Relay) or L/O Relay 86/T2 (for “Backup” T60 Relay).
Output Contact W1 provides an “All Trips” Output Indication.
Output Contact U2 provides an “50P/51P Pri Trip” Output Indication.
Output Contact W4 Performs a “Change Source 6 kV” Operation
Output Contact H6 Performs a “Change Source 400 V CCM” Operation

PAGE 96

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: T60 Transformer Management Primary and Backup Relays

Step-up Transformer TP3 (125 MVA, 240.75/11.5 kV) – UR T60 Transformer Management Relay (Continued)
Protective Device Description
Circuit Identification Relay Ranges Recommended Settings Protection
C/B Circuit Xfmr ANSI Relay CT VT Time Function
Number Identification Rating Dev. No. Mfg. Model No. Time Inst. Ratio Ratio Tap Amp Dial Inst. Amp Trips Reference
Tie to Step-Up 125000 kVA 51N Pri UR T60-J04-HMH- 0.000- -- 400/1 -- Pickup = 0.125 pu (50 Primary A) H1 GROUND TOC1
Transformer 240.75 kV  Pri T60 F8L-H6P-M8N- 30.00 pu (F4) IEEE Moderately Inverse Curve, Inst Reset W1 OP
TP5 11.5 kV  Sec P6D-U4L-W6C Multiplier = 1.00 U3
Z=13.2% Test Point 1: 0.19 Amps, 6.24 sec W4
Test Point 2: 0.35 Amps, 2.59 sec H6
50N Pri UR T60-J04-HMH- -- 0.000- 400/1 -- Pickup = 0.375 pu (150 Primary A) H1 GROUND IOC1
T60 F8L-H6P-M8N- 30.00 (F4) Delay = 0.60 sec W1 OP
P6D-U4L-W6C pu Reset Delay = 0.10 sec U3
Test Point 3: 0.40 Amps, 0.60 sec W4
Test Point 4: 10 Amps, 0.60 sec H6

NOTES
Output Contact H1 Trips L/O Relay 86/T1 (for “Primary” T60 Relay) or L/O Relay 86/T2 (for “Backup” T60 Relay).
Output Contact W1 provides an “All Trips” Output Indication.
Output Contact U3 provides an “50N/51N Pri Trip” Output Indication.
Output Contact W4 Performs a “Change Source 6 kV” Operation
Output Contact H6 Performs a “Change Source 400 V CCM” Operation

PAGE 97

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: T60 Transformer Management Primary and Backup Relays

Step-up Transformer TP3 (125 MVA, 240.75/11.5 kV) – UR T60 Transformer Management Relay (Continued)
Protective Device Description
Circuit Identification Relay Ranges Recommended Settings Protection
C/B Circuit Xfmr ANSI Relay CT VT Time Function
Number Identification Rating Dev. No. Mfg. Model No. Time Inst. Ratio Ratio Tap Amp Dial Inst. Amp Trips Reference
Tie to Step-Up 125000 kVA 51S UR T60-J04-HMH- 0.000- -- 7500/1 -- Pickup = 1.020 pu (7650 Primary A) H1 PHASE TOC3
Transformer 240.75 kV  Pri T60 F8L-H6P-M8N- 30.00 pu (M1-M3) IEEE Moderately Inverse Curve, Timed Reset W1 OP
TP5 11.5 kV  Sec P6D-U4L-W6C Multiplier = 0.86, Voltage Restraint Disabled U4
Z=13.2% Test Point 1: 1.20 Amps, 13.7 sec W4
Test Point 2: 1.80 Amps, 3.97 sec H6
50S UR T60-J04-HMH- -- 0.000- 7500/1 -- Pickup = 2.120 pu (15900 Primary A) H1 PHASE IOC3 OP
T60 F8L-H6P-M8N- 30.00 (M1-M3) Delay = 0.60 sec W1
P6D-U4L-W6C pu Reset Delay = 0.10 sec U4
Test Point 3: 2.2 Amps, 0.60 sec W4
Test Point 3: 6.5 Amps, 0.60 sec H6

NOTES
Output Contact H1 Trips L/O Relay 86/T1 (for “Primary” T60 Relay) or L/O Relay 86/T2 (for “Backup” T60 Relay).
Output Contact W1 provides an “All Trips” Output Indication.
Output Contact U4 provides an “51P Gen Trip” Output Indication.
Output Contact W4 Performs a “Change Source 6 kV” Operation
Output Contact H6 Performs a “Change Source 400 V CCM” Operation

PAGE 98

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: T60 Transformer Management Primary and Backup Relays

Step-up Transformer TP3 (125 MVA, 240.75/11.5 kV) – UR T60 Transformer Management Relay (Continued)
Protective Device Description
Circuit Identification Relay Ranges Recommended Settings Protection
C/B Circuit Xfmr ANSI Relay CT VT Time Function
Number Identification Rating Dev. No. Mfg. Model No. Time Inst. Ratio Ratio Tap Amp Dial Inst. Amp Trips Reference
Tie to Step-Up 3000 kVA 51 TL Aux UR T60-J04-HMH- 0.000- -- 300/1 -- Pickup = 0.600 pu (180 Primary A) H1 PHASE TOC5
Transformer 11.5 kV  Pri T60 F8L-H6P-M8N- 30.00 pu (M5-M7) IEEE Extremely Inverse Curve, Timed Reset W1 OP
TP5 6.2 kV  Sec P6D-U4L-W6C Multiplier = 3.60, Voltage Restraint Disabled U5
Z=6% Test Point 1: 0.90 Amps, 81.6 sec W4
Test Point 2: 1.40 Amps, 23.3 sec H6
50-1 TL UR T60-J04-HMH- -- 0.000- 300/1 -- Pickup = 1.500 pu (450 Primary A) H1 PHASE IOC5 OP
Aux T60 F8L-H6P-M8N- 30.00 (M5-M7) Delay = 0.60 sec W1
P6D-U4L-W6C pu Reset Delay = 0.10 sec U5
Test Point 3: 1.60 Amps, 0.60 sec W4
Test Point 4: 8.50 Amps, 0.60 sec H6
50-2 TL UR T60-J04-HMH- -- 0.000- 300/1 -- Pickup = 9.000 pu (2700 Primary A) H1 PHASE IOC6 OP
Aux T60 F8L-H6P-M8N- 30.00 (M5-M7) Delay = 0.00 sec W1
P6D-U4L-W6C pu Reset Delay = 0.10 sec U5
Test Point 5: 10.0 Amps, “Inst” W4
Test Point 6: 40.0 Amps, “Inst” H6
NOTES
Output Contact H1 Trips L/O Relay 86/T1 (for “Primary” T60 Relay) or L/O Relay 86/T2 (for “Backup” T60 Relay).
Output Contact W1 provides an “All Trips” Output Indication.
Output Contact U5 provides an “50P/51P Aux Trip” Output Indication.
Output Contact W4 Performs a “Change Source 6 kV” Operation
Output Contact H6 Performs a “Change Source 400 V CCM” Operation

PAGE 99

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: T60 Transformer Management Primary and Backup Relays

Step-up Transformer TP3 (125 MVA, 240.75/11.5 kV) – UR T60 Transformer Management Relay (Continued)
Protective Device Description
Circuit Identification Relay Ranges Recommended Settings Protection
C/B Circuit Xfmr ANSI Relay CT VT Time Function
Number Identification Rating Dev. No. Mfg. Model No. Time Inst. Ratio Ratio Tap Amp Dial Inst. Amp Trips Reference
Tie to Step-Up 125000 kVA 24T1 UR T60-J04-HMH- 0.80-4.00 -- -- 115/1 Pickup = 1.10 pu H1 VOLTS PER
Transformer 240.75 kV  Pri T60 F8L-H6P-M8N- pu V/Hz (F5-F7) Definite Time, Delay = 42.0 sec W1 HERTZ 1 OP
TP5 11.5 kV  Sec P6D-U4L-W6C T Reset = 900.0 sec U6
Z=13.2% Test Point 1: 110 Volts , 50 Hz, 42.0 sec W4
Test Point 2: 116 Volts , 50 Hz, 42.0 sec H6
24T2 UR T60-J04-HMH- 0.80-4.00 -- -- 115/1 Pickup = 1.17 pu H1 VOLTS PER
T60 F8L-H6P-M8N- pu V/Hz (F5-F7) Definite Time, Delay = 1.85 sec W1 HERTZ 2 OP
P6D-U4L-W6C T Reset = 10.0 sec U6
Test Point 3: 117 Volts , 50 Hz, 1.85 sec W4
Test Point 4: 135 Volts , 50 Hz, 1.85 sec H6
64B UR T60-J04-HMH- -- 0.000- -- (&&) Pickup = 0.070 pu H1 AUX OV1
T60 F8L-H6P-M8N- 3.000 (F8) Delay = 0.50 seconds W1 OP
P6D-U4L-W6C pu Reset Delay = 0.10 sec U12
Test Point 1: 12.5 Volts, 0.50 sec W4
Test Point 2: 170 Volts, 0.50 sec H6

NOTES
Output Contact H1 Trips L/O Relay 86/T1 (for “Primary” T60 Relay) or L/O Relay 86/T2 (for “Backup” T60 Relay).
Output Contact W1 provides an “All Trips” Output Indication.
Output Contact U6 provides an “24 Trip” Output Indication.
Output Contact U12 provides a “64B Trip” Output Indication.
Output Contact W4 Performs a “Change Source 6 kV” Operation
Output Contact H6 Performs a “Change Source 400 V CCM” Operation

(&&) – (11500/3)/(100/3) Volts, Wye Primary to Broken Delta Secondary

PAGE 100

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: T60 Transformer Management Primary and Backup Relays

Step-up Transformer TP3 (125 MVA, 240.75/11.5 kV) – UR T60 Transformer Management Relay (Continued)
Summary of Output Relays Enabled By Each External Protective Device Input
Protective Device Description
Circuit Identification
Unit Xfmr External Protective Device Inputs and Associated
Number Identification Rating Output Relay Operations
Tie to Step-Up 125000 kVA 26TP STAGE 1 (INPUT P5A)
Transformer 240.75 kV  Pri
TP5 11.5 kV  Sec
Z=13.2%
26TP STAGE 2 (INPUT P5C)
Operates Output U7 (Alarm Indication)
Operates Output W3 (Turbine Normal Stop)
Operates Output W6 (C/B 52G Trip Via Backup G60 Rly)
Operates Output W7 (C/B 52G Trip Via pri G60 Rly)
49TP STAGE 1 (INPUT P6A)

49TP STAGE 2 (INPUT P6C)


Operates Output U8 (Alarm Indication)
Operates Output W3 (Turbine Normal Stop)
Operates Output W6 (C/B 52G Trip Via Backup G60 Rly)
Operates Output W7 (C/B 52G Trip Via pri G60 Rly)
Operates Output W5 (Trip 41EX)
Operates Output W4 (Change Source 6 kV)
Operates Output H6 (Change Source 400 V CCM)

NOTES

PAGE 101

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: T60 Transformer Management Primary and Backup Relays

Step-up Transformer TP3 (125 MVA, 240.75/11.5 kV) – UR T60 Transformer Management Relay (Continued)
Summary of Output Relays Enabled By Each External Protective Device Input
Protective Device Description
Circuit Identification
Unit Xfmr External Protective Device Inputs and Associated
Number Identification Rating Output Relay Operations
Tie to Step-Up 125000 kVA 63TP STAGE 1 (INPUT P7A)
Transformer 240.75 kV  Pri
TP5 11.5 kV  Sec
Z=13.2%
63TP STAGE 2 (INPUT P7C)
Operates Output U9 (Alarm Indication)
Operates Output H1 (L/O 86T Trip)
Operates Output W4 (Change Source 6 kV)
Operates Output H6 (Change Source 400 V CCM)
71TP (INPUT P8A)

45FTP (INPUT P8C)


Operates Output U10 (Alarm Indication)
Operates Output H1 (L/O 86T Trip)
Operates Output W4 (Change Source 6 kV)
Operates Output H6 (Change Source 400 V CCM)

NOTES

PAGE 102

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: T60 Transformer Management Primary and Backup Relays

Step-up Transformer TP3 (125 MVA, 240.75/11.5 kV) – UR T60 Transformer Management Relay (Continued)
Summary of Output Relays Enabled By Each External Protective Device Input
Protective Device Description
Circuit Identification
Unit Xfmr External Protective Device Inputs and Associated
Number Identification Rating Output Relay Operations
Tie to Step-Up 125000 kVA TP4 VT CB5 OPEN (INPUT P4A)
Transformer 240.75 kV  Pri
TP5 11.5 kV  Sec
Z=13.2%
TP REFRIG FAULT (INPUT P4C)

DL91 TRIP (INPUT P3C)


Operates Output U13 (DL91 Trip Indication)
Operates Output W6 (C/B 52G Trip Via Backup G60 Rly)
Operates Output W7 (C/B 52G Trip Via pri G60 Rly)
Operates Output H3 (C/B 52L Trip)
Operates Output H4 (C/B 52L Trip)
Operates Output W4 (Change Source 6 kV)
Operates Output H6 (Change Source 400 V CCM)

NOTES

PAGE 103

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: F650 Feeder Protection System Relays

6.1.3 Station Aux Transformer TL2 (3000 kVA, 11.5/6.2 kV) – F650 Relay
Protective Device Description
Circuit Identification Relay Ranges Recommended Settings Protection
Unit Xfmr ANSI Relay CT VT Time Function
Number Identification Rating Dev. No. Mfg. Model No. Time Inst. Ratio Ratio Tap Amp Dial Inst. Amp Trips Reference
Tie to Station Aux 3000 kVA 51 Pri F650 F650-B-A-B-F-2- 0.05- -- 300/1 -- Pickup = 0.600 Amps (180 Primary A) F31/33 Phase TOC
Transformer 11.5 kV  Pri G-1-HI-F-6 160.00 A (B1-B6) IEEE Extremely Inverse Curve, Inst Reset G31/32 High 1 OP
TL7 6.2 kV  Sec Multiplier = 3.50, Voltage Restraint Disabled F29/30
Z=6% Test Point 1: 0.90 Amps, 79.4 sec F34/36
Test Point 2: 1.40 Amps, 22.6 sec G22/24
G25/26
G29/30
G33/34
G35/36

NOTES
Output Contact F31/F33 (F07) Trips Lockout Relay 86/T1. Output Contact G31/G32 (G06) Trips Lockout Relay 86/T2.
Output Contact F29/F30 (F06) Performs a “Trip Device 41EX” Operation.
Output Contact F34/F36 (F08) Trips C/B 52L. Output Contact G22/G24 (G02) Trips C/B 52G.
Output Contact G25/G26 (G03) Provides a “TL 50/51P Operate” Alarm Indication.
Output Contact G29/G30 (G05) Performs a “Change Source 400 V CCM” Operation.
Output Contact G33/G34 (G07) Performs a “Turbine Normal Stop” Operation.
Output Contact G35/G36 (G08) Performs a “Change Source 6 kV NO” Operation.

Note 1: Output Contacts F07 and G06 were removed from service (not programmed) during Tiaret GPP Testing/Commissioning. These output contacts have been programmed to operate as indicated
above in the supplied F650 setting files, but may be removed from service by the Purchaser if desired.

Note 2: Output Contact G01 (Formerly designated as “Change Source 6 kV NO”) has not been programmed in the supplied settings file, but may be added to the F650 program if desired by the Purchaser.

PAGE 104

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: F650 Feeder Protection System Relays

Station Aux Transformer TL2 (3000 kVA, 11.5/6.2 kV) – F650 Feeder Protection System Relay (Continued)
Protective Device Description
Circuit Identification Relay Ranges Recommended Settings Protection
Unit Xfmr ANSI Relay CT VT Time Function
Number Identification Rating Dev. No. Mfg. Model No. Time Inst. Ratio Ratio Tap Amp Dial Inst. Amp Trips Reference
Tie to Station Aux 3000 kVA 50-1 Pri F650 F650-B-A-B-F-2- -- 0.05- 300/1 -- Pickup = 1.500 Amps (450 Primary A) F31/33 Phase IOC Low
Transformer 11.5 kV  Pri G-1-HI-F-6 160.00 (B1-B6) Delay = 0.60 sec G31/32 1 OP
TL7 6.2 kV  Sec A Reset Delay = 0.00 sec F29/30
Z=6% Test Point 3: 1.60 Amps, 0.60 sec F34/36
Test Point 4: 8.50 Amps, 0.60 sec G22/24
G25/26
G29/30
G33/34
G35/36

NOTES
Output Contact F31/F33 (F07) Trips Lockout Relay 86/T1. Output Contact G31/G32 (G06) Trips Lockout Relay 86/T2.
Output Contact F29/F30 (F06) Performs a “Trip Device 41EX” Operation.
Output Contact F34/F36 (F08) Trips C/B 52L. Output Contact G22/G24 (G02) Trips C/B 52G.
Output Contact G25/G26 (G03) Provides a “TL 50/51P Operate” Alarm Indication.
Output Contact G29/G30 (G05) Performs a “Change Source 400 V CCM” Operation.
Output Contact G33/G34 (G07) Performs a “Turbine Normal Stop” Operation.
Output Contact G35/G36 (G08) Performs a “Change Source 6 kV NO” Operation.

Note 1: Output Contacts F07 and G06 were removed from service (not programmed) during Tiaret GPP Testing/Commissioning. These output contacts have been programmed to operate as indicated
above in the supplied F650 setting files, but may be removed from service by the Purchaser if desired.

Note 2: Output Contact G01 (Formerly designated as “Change Source 6 kV NO”) has not been programmed in the supplied settings file, but may be added to the F650 program if desired by the Purchaser.

PAGE 105

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: F650 Feeder Protection System Relays

Station Aux Transformer TL2 (3000 kVA, 11.5/6.2 kV) – F650 Feeder Protection System Relay (Continued)
Protective Device Description
Circuit Identification Relay Ranges Recommended Settings Protection
Unit Xfmr ANSI Relay CT VT Time Function
Number Identification Rating Dev. No. Mfg. Model No. Time Inst. Ratio Ratio Tap Amp Dial Inst. Amp Trips Reference
Tie to Station Aux 3000 kVA 50-2 Pri F650 F650-B-A-B-F-2- -- 0.05- 300/1 -- Pickup = 9.000 Amps (2700 Primary A) F31/33 Phase IOC
Transformer 11.5 kV  Pri G-1-HI-F-6 160.00 (B1-B6) Delay = 0.00 sec G31/32 High 1 OP
TL7 6.2 kV  Sec A Reset Delay = 0.00 sec F29/30
Z=6% Test Point 5: 10.0 Amps, “Inst” F34/36
Test Point 6: 40.0 Amps, “Inst” G22/24
G25/26
G29/30
G33/34
G35/36

NOTES
Output Contact F31/F33 (F07) Trips Lockout Relay 86/T1. Output Contact G31/G32 (G06) Trips Lockout Relay 86/T2.
Output Contact F29/F30 (F06) Performs a “Trip Device 41EX” Operation.
Output Contact F34/F36 (F08) Trips C/B 52L. Output Contact G22/G24 (G02) Trips C/B 52G.
Output Contact G25/G26 (G03) Provides a “TL 50/51P Operate” Alarm Indication.
Output Contact G29/G30 (G05) Performs a “Change Source 400 V CCM” Operation.
Output Contact G33/G34 (G07) Performs a “Turbine Normal Stop” Operation.
Output Contact G35/G36 (G08) Performs a “Change Source 6 kV NO” Operation.

Note 1: Output Contacts F07 and G06 were removed from service (not programmed) during Tiaret GPP Testing/Commissioning. These output contacts have been programmed to operate as indicated
above in the supplied F650 setting files, but may be removed from service by the Purchaser if desired.

Note 2: Output Contact G01 (Formerly designated as “Change Source 6 kV NO”) has not been programmed in the supplied settings file, but may be added to the F650 program if desired by the Purchaser.

PAGE 106

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: F650 Feeder Protection System Relays

Station Aux Transformer TL2 (3000 kVA, 11.5/6.2 kV) – F650 Feeder Protection System Relay (Continued)
Summary of Output Relays Enabled By Each External Protective Device Input
Protective Device Description
Circuit Identification
Unit Xfmr External Protective Device Inputs and Associated
Number Identification Rating Output Relay Operations
Tie to Station Aux 3000 kVA 26TL STAGE 1 (INPUT G1)
Transformer 11.5 kV  Pri Operates Output F19/F20 (F01) (Alarm Indication)
TL7 6.2 kV  Sec
Z=6%
26TL STAGE 2 (INPUT G3)
Operates Out G35/G36 (G08) Change Source 6 kV NO)

63TL STAGE 1 (INPUT G3)


Operates Output F21/F22 (F02) (Alarm Indication)

63TL STAGE 2 (INPUT G4)


Operates Output F23/F24 (F03) (Alarm Indication)
Operates Output G33/G34 (G07) (Turbine Normal Stop)
Operates Output G22/G24 (G02) (C/B 52G Trip)
Operates Output F34/F36 (F08) (C/B 52L Trip)
Operates Out G35/G36 (G08) Change Source 6 kV NO)
71TL (INPUT G3)
Operates Output F25/F26 (F04) (Alarm Indication)

NOTES

PAGE 107

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: F650 Feeder Protection System Relays

Station Aux Transformer TL2 (3000 kVA, 11.5/6.2 kV) – F650 Feeder Protection System Relay (Continued)
Summary of Output Relays Enabled By Each External Protective Device Input (Continued)
Protective Device Description
Circuit Identification
Unit Xfmr External Protective Device Inputs and Associated
Number Identification Rating Output Relay Operations
Tie to Station Aux 3000 kVA 45FTL (INPUT G6)
Transformer 11.5 kV  Pri Operates Output F27/F28 (F05) (Alarm Indication)
TL7 6.2 kV  Sec Operates Output G33/G34 (G07) (Turbine Normal Stop)
Z=6% Operates Output G22/G24 (G02) (C/B 52G Trip)
Operates Output F34/F36 (F08) (C/B 52L Trip)
Operates Output F29/F30 (F06) (Trip 41EX)
Operates Out G35/G36 (G08) Change Source 6 kV NO)
Operates Out G29/G30 (G05) (Chg Source 400 V CCM)

NOTES

PAGE 108

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: F650 Feeder Protection System Relays

6.1.4 Gen Aux Transformer TAM3 (800 kVA, 11.5/0.4 kV) – F650 Relay
Protective Device Description
Circuit Identification Relay Ranges Recommended Settings Protection
Unit Xfmr ANSI Relay CT VT Time Function
Number Identification Rating Dev. No. Mfg. Model No. Time Inst. Ratio Ratio Tap Amp Dial Inst. Amp Trips Reference
Tie to Gen Aux 800 kVA 51 Pri F650 F650-B-A-B-F-2- 0.05- -- 100/1 -- Pickup = 0.50 Amps (50 Primary A) F31/33 Phase TOC
Transformer 11.5 kV  Pri G-1-HI-F-6 160.00 A (B1-B6) Input Type = RMS G31/32 High 1 OP
TAM3 0.4 kV  Sec IEEE Extremely Inverse Curve, Inst Reset F29/30
Z=4.5% Multiplier = 3.20, Voltage Restraint Disabled F34/36
Test Point 1: 0.80 Amps, 58.2 sec G20/21
Test Point 2: 1.10 Amps, 23.9 sec G22/24
G25/26
G29/30
G33/34
G35/36

NOTES
Output Contact F31/F33 (F07) Trips Lockout Relay 86/T1. Output Contact G31/G32 (G06) Trips Lockout Relay 86/T2.
Output Contact F29/F30 (F06) Performs a “Trip Device 41EX” Operation.
Output Contact F34/F36 (F08) Trips C/B 52L. Output Contact G22/G24 (G02) Trips C/B 52G.
Output Contact G20/G21 (G01) Performs a “Change Source 6 kV NC” Operation
Output Contact G25/G26 (G03) Provides a “TAM 50/51P Operate” Alarm Indication
Output Contact G29/G30 (G05) Performs a “Change Source 400 V CCM” Operation
Output Contact G33/G34 (G07) Performs a “Turbine Normal Stop” Operation.
Output Contact G35/G36 (G08) Performs a “Change Source 6 kV NO” Operation

Note: Output Contacts F07 and G06 were removed from service (not programmed) during Tiaret GPP Testing/Commissioning. These output contacts have been programmed to operate as indicated above
in the supplied F650 setting files, but may be removed from service by the Purchaser if desired.

PAGE 109

GE ENERGY FOR SONELGAZ TIARET LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: F650 Feeder Protection System Relays

Generator Aux Transformer TAM3 (800 kVA, 11.5/0.400 kV) – F650 Feeder Protection System Relay (Continued)
Protective Device Description
Circuit Identification Relay Ranges Recommended Settings Protection
Unit Xfmr ANSI Relay CT VT Time Function
Number Identification Rating Dev. No. Mfg. Model No. Time Inst. Ratio Ratio Tap Amp Dial Inst. Amp Trips Reference
Tie to Gen Aux 800 kVA 50-1 Pri F650 F650-B-A-B-F-2- -- 0.05- 100/1 -- Pickup = 1.20 Amps (120 Primary A) F31/33 Phase IOC Low
Transformer 11.5 kV  Pri G-1-HI-F-6 160.00 (B1-B6) Input Type = Phasor G31/32 1 OP
TAM3 0.4 kV  Sec A Trip Delay = 0.60 sec F29/30
Z=4.5% Reset Delay = 0.00 sec F34/36
Test Point 3: 1.30 Amps, 0.60 sec G20/21
Test Point 4: 9.5 Amps, 0.60 sec G22/24
G25/26
G29/30
G33/34
G35/36

NOTES
Output Contact F31/F33 (F07) Trips Lockout Relay 86/T1. Output Contact G31/G32 (G06) Trips Lockout Relay 86/T2.
Output Contact F29/F30 (F06) Performs a “Trip Device 41EX” Operation.
Output Contact F34/F36 (F08) Trips C/B 52L. Output Contact G22/G24 (G02) Trips C/B 52G.
Output Contact G20/G21 (G01) Performs a “Change Source 6 kV NC” Operation
Output Contact G25/G26 (G03) Provides a “TAM 50/51P Operate” Alarm Indication
Output Contact G29/G30 (G05) Performs a “Change Source 400 V CCM” Operation
Output Contact G33/G34 (G07) Performs a “Turbine Normal Stop” Operation.
Output Contact G35/G36 (G08) Performs a “Change Source 6 kV NO” Operation

Note: Output Contacts F07 and G06 were removed from service (not programmed) during Tiaret GPP Testing/Commissioning. These output contacts have been programmed to operate as indicated above
in the supplied F650 setting files, but may be removed from service by the Purchaser if desired.

PAGE 110

GE ENERGY FOR SONELGAZ TIARET LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: F650 Feeder Protection System Relays

Generator Aux Transformer TAM3 (800 kVA, 11.5/0.400 kV) – F650 Feeder Protection System Relay (Continued)
Protective Device Description
Circuit Identification Relay Ranges Recommended Settings Protection
Unit Xfmr ANSI Relay CT VT Time Function
Number Identification Rating Dev. No. Mfg. Model No. Time Inst. Ratio Ratio Tap Amp Dial Inst. Amp Trips Reference
Tie to Gen Aux 800 kVA 50-2 Pri F650 F650-B-A-B-F-2- -- 0.05- 100/1 -- Pickup = 9.80 Amps (980 Primary A) F31/33 Phase IOC
Transformer 11.5 kV  Pri G-1-HI-F-6 160.00 (B1-B6) Input Type = Phasor G31/32 High 1 OP
TAM3 0.4 kV  Sec A Trip Delay = 0.00 sec F29/30
Z=4.5% Reset Delay = 0.00 sec F34/36
Test Point 5: 10.0 Amps, “Inst” G20/21
Test Point 6: 40.0 Amps, “Inst” G22/24
G25/26
G29/30
G33/34
G35/36

NOTES
Output Contact F31/F33 (F07) Trips Lockout Relay 86/T1. Output Contact G31/G32 (G06) Trips Lockout Relay 86/T2.
Output Contact F29/F30 (F06) Performs a “Trip Device 41EX” Operation.
Output Contact F34/F36 (F08) Trips C/B 52L. Output Contact G22/G24 (G02) Trips C/B 52G.
Output Contact G20/G21 (G01) Performs a “Change Source 6 kV NC” Operation
Output Contact G25/G26 (G03) Provides a “TAM 50/51P Operate” Alarm Indication
Output Contact G29/G30 (G05) Performs a “Change Source 400 V CCM” Operation
Output Contact G33/G34 (G07) Performs a “Turbine Normal Stop” Operation.
Output Contact G35/G36 (G08) Performs a “Change Source 6 kV NO” Operation

Note: Output Contacts F07 and G06 were removed from service (not programmed) during Tiaret GPP Testing/Commissioning. These output contacts have been programmed to operate as indicated above
in the supplied F650 setting files, but may be removed from service by the Purchaser if desired.

PAGE 111

GE ENERGY FOR SONELGAZ TIARET LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: F650 Feeder Protection System Relays

Generator Aux Transformer TAM3 (800 kVA, 11.5/0.400 kV) – F650 Feeder Protection System Relay (Continued)
Summary of Output Relays Enabled By Each External Protective Device Input
Protective Device Description
Circuit Identification
Unit Xfmr External Protective Device Inputs and Associated
Number Identification Rating Output Relay Operations
Tie to Gen Aux 800 kVA 26TAM STAGE 1 (INPUT G1)
Transformer 11.5 kV  Pri Operates Output F19/F20 (F01) (Alarm Indication)
TAM3 0.4 kV  Sec
Z=4.5%
26TAM STAGE 2 (INPUT G3)
Operates Output F21/F22 (F02) (Alarm Indication)
Operates Out G29/G30 (G05) (Chg Source 400 V CCM)

63TAM STAGE 2 (INPUT G3)


Operates Output F23/F24 (F03) (Alarm Indication)
Operates Output G33/G34 (G07) (Turbine Normal Stop)
Operates Output G22/G24 (G02) (C/B 52G Trip)
Operates Output F34/F36 (F08) (C/B 52L Trip)
Operates Output F29/F30 (F06) (Trip 41EX)
Operates Out G29/G30 (G05) (Chg Source 400 V CCM)
71TAM (INPUT G4)
Operates Output F25/F26 (F04) (Alarm Indication)

NOTES

PAGE 112

GE ENERGY FOR SONELGAZ TIARET LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Tables: F650 Feeder Protection System Relays

Generator Aux Transformer TAM3 (800 kVA, 11.5/0.400 kV) – F650 Feeder Protection System Relay (Continued)
Summary of Output Relays Enabled By Each External Protective Device Input (Continued)
Protective Device Description
Circuit Identification
Unit Xfmr External Protective Device Inputs and Associated
Number Identification Rating Output Relay Operations
Tie to Gen Aux 800 kVA 45FTAM (INPUT G3)
Transformer 11.5 kV  Pri Operates Output F27/F28 (F05) (Alarm Indication)
TAM3 0.4 kV  Sec Operates Output G33/G34 (G07) (Turbine Normal Stop)
Z=4.5% Operates Output G22/G24 (G02) (C/B 52G Trip)
Operates Output F34/F36 (F08) (C/B 52L Trip)
Operates Output F29/F30 (F06) (Trip 41EX)
Operates Out G20/G21 (G01) (Change Source 6 kV NC)
Operates Out G35/G36 (G08) Change Source 6 kV NO)
Operates Out G29/G30 (G05) (Chg Source 400 V CCM)
CHANGE SOURCE 6 KV (INPUT G3)
Operates Out G20/G21 (G01) (Change Source 6 kV NC)
Operates Out G35/G36 (G08) Change Source 6 kV NO)

NOTES

PAGE 113

GE ENERGY FOR SONELGAZ TIARET LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
__________________________________________________________________________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25 GPP


Recommended Protective Device Setting Table: BE1-59N Bus Ground Fault Relay

6.1.5 11.5 kV Main Distribution Bus TP3S– BE1-59N Bus Ground Fault Relay
Protective Device Description
Circuit Identification Relay Ranges Recommended Settings Protection
C/B Circuit ANSI Relay CT VT Time Function
Number Identification Dev. No. Mfg. Model No. Time Inst. Ratio Ratio Tap Amp Dial Inst. Amp Trips Reference
TP3 11.5 kV 64B-TP3S Bas BE1-59N/ 1-20 V -- (&&) Pickup = 12 Volts Aux Rly
Secondary A1E-E1J-D0N1F 0.1-99.9 sec Delay = 0.50 sec 64BX
Main Bus

NOTES
(&&) – (11500/3)/(100/3) Volts, Wye Primary to Broken Delta Secondary

PAGE 114

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


Study Appendix

7. Appendix 1: UR G60 Setting Calculation Sheets (Generator G3)

PAGE 115

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Energy For Sonelgaz M'Sila G3
g
GE Energy
GE UR G60 Generator Management Relay
Setting Calculations

Setting Calculation Sheet


Phase Distance Protection (Function 21)

A) System Data
Generator: 126.875 MVAG 11.50 kVG 0.8 pf 24.3% X'dv
System: 240.75 kVS
GSU Xfmr: 125 MVAT 240.75 kVpri,kVsec 11.5 13.20% Zt, X/R 40

CT Ratio (CT R): 7,500 / 1 = 7,500 :1


PT Ratio (PT R): 11,500 / 100 = 115 :1

Note: GSU X/R Ratio Assumed

B) 21 Function Data
PHASE DISTANCE ZONE 2 DIRECTION: Forward/Reverse
PHASE DISTANCE ZONE 2 SHAPE: Mho (Fixed)
PHASE DISTANCE ZONE 2 REACH: 0.02 - 500.00  in steps of 0.01
PHASE DISTANCE ZONE 2 ANGLE: 30 to 90° in steps of 1
PHASE DISTANCE ZONE 2 SUPERVISION: 0.050 - 30.000 pu in steps of 0.001
PHASE DISTANCE ZONE 2 DELAY: 0.000 - 65.535 s in steps of 0.001

21

GENERAL ELECTRIC INTERNATIONAL, INC. - ENERGY CONSULTING


GE Energy For Sonelgaz M'Sila G3
g
GE Energy
GE UR G60 Generator Management Relay
Setting Calculations

Setting Calculation Sheet


Phase Distance Protection (Function 21)

C) Settings Calculations
1. Calculate impedances in relay ohms on generator base with the CT and VT at the generator terminals:

Transformer:
Zt (primary ohms) = (%Zt/100)*[(MVA G/MVAT)[(kVG*kVG)/MVAG)] = 0.140 ohms

Zt (relay ohms) = Zt (primary ohms) * (CT Ratio/PT Ratio) = 9.11 ohms


Angle = Arc Tangent (X/R) = 89 °

Generator:
Xg (primary ohms) = (%X'dv/100)*(Zbase) = (%X'dv/100)*[(kV G*kVG)/MVAG)] = 0.253 ohms

Xg (relay ohms) = Xg (primary ohms) * (CT Ratio/PT Ratio) = 16.52 ohms

2. Backup distance relay (21) setting philosophy: Set relay reach for 110% of the Impedance of the
Generator Step-up Transformer (GSU), with a 0.6 second time delay. This setting is similar to the setting of
the existing "21P" relays applied in conjunction with the Tiaret GPP's. Set current supervision at 6370
Primary Amps, to prevent operation due to generator load current flow.

This function will be blocked for a VT Fuse Failure (VTFF).

Set Zone 2 Reach equal to 125% of the GSU Impedance = 10.02 relay 
Set Zone 2 Angle equal to GSU Impedance Angle = 89 °
Set Zone 2 Direction = Forward
Set Zone 2 Operating Time Delay = 0.600 seconds
Set Zone 2 Current Supervision = 0.849 per-unit

21

GENERAL ELECTRIC INTERNATIONAL, INC. - ENERGY CONSULTING


GE Energy For Sonelgaz M'Sila G3
g
GE Energy
GE UR G60 Generator Management Relay
Setting Calculations

Setting Calculation Sheet


Power Swing Detection Function (ANSI Device 78)

Out-of-Step (78) Relay Setting Philosophy - the application follows the approach outlined in GE technical
reference GER-3179, Out-of-Step Protection for Generators. This approach utilizes two impedance relays
(OUTER unit and INNER unit) to track the impedance locus of the generator during an out-of-step swing. The
objective is to detect that the generator is going out of step and initiate separation from the system during the
first swing. Traditionally, a 120° separation has been considered the criterion to define an out-of-step condition.
° °
The INNER unit is set at the points at which the generator and system are 130 and 260 apart. The OUTER
unit is set to avoid tripping on stable swings, and to initiate separation when the generator voltage approaches
°
295 with respect to the system. This assures that the maximum voltage angle across the breaker at the time
°
that it opens will be 65 or less.

The impedance locus of most out-of-step swings passes through the generator step-up (GSU) transformer,
or the generator itself (relatively closer to the line-side terminals). For this reason, GER-3179 suggests that with
the relay applied at the generator terminals and polarized to look toward the system, the reverse reach into the
machine should be two to three times the generator transient reactance (X'dv). The forward reach into the
system should extend well past the high-voltage terminals of the GSU, and forward reach settings typically fall
in the range of one to two times the GSU leakage impedance.

78

GENERAL ELECTRIC INTERNATIONAL, INC. - ENERGY CONSULTING


GE Energy For Sonelgaz M'Sila G3
g
GE Energy
GE UR G60 Generator Management Relay
Setting Calculations

Setting Calculation Sheet


Power Swing Detection Function (ANSI Device 78)

A
a. Zt = 25.63  sec @ 89.5 ° = RCA
X
b. Forward Reach (Z F) = 1.5Zt = 13.66 ohms sec. Z
forward

c. Reverse Reach (Z R) = 2X'dv = 33.04 ohms sec.


O
The line OC is the lateral reach of the relay. For the
settings to be secure, the apparent impedance
associated with an output equal to the rating of the Z
Zreverse C
machine must be less than OC.

Y
B Figure A
Z AB  Z forward  Z reverse = 46.70 

Z AB / 2
OC 
tan( Z / 2)

d. Outer Right Blinder Reach (Z = 60°) = OC[1-cos(RCA)] = 40.08 ohms secondary

e. Inner Right Blinder Reach (Z = 120°) = OC[1-cos(RCA)] = 13.36 ohms secondary

f. Outer Left Blinder Reach (Z = 60°) = OC[1+cos(RCA)] = 40.80 ohms secondary

g. Inner Left Blinder Reach (Z = 120°) = OC[1+cos(RCA)] = 13.60 ohms secondary

78

GENERAL ELECTRIC INTERNATIONAL, INC. - ENERGY CONSULTING


GE Energy For Sonelgaz M'Sila G3
g
GE Energy
GE UR G60 Generator Management Relay
Setting Calculations

Setting Calculation Sheet


Stator Differential (Function 87S)

A) Generator Data
Generator Data: 126.875 MVAG, 11.50 kV, 0.8 pf
Generator Base Current: 6369 A
B) Relay Data
87S Relay Ranges: Pickup: 0.050 - 1.000 pu in steps of 0.001
Slope: 1 - 100% in steps of 1%
Break 1: 1.00 - 1.50 pu in steps of 0.01
Break 2: 1.50 - 30.00 pu in steps of 0.01

CT Ratio (CT R): 7,500 / 1 = 7,500 :1

C) Settings Calculations
Relay Setting Philosophy: The 87S function provides primary phase fault
protection for the generator. The recommended settings shown below
are based upon previous experience at similar Generator installations
and upon setting guidelines suggested by the relay manufacturer.
Relatively low Pickup (0.050 pu), Slope 1 (10%) and Break 1 (1.15 pu) settings are used to
provide reasonably sensitive internal fault protection at or near normal operating
current levels. The Slope 2 (20%) and Break 2 (30.00 pu) setpoints
are used to provide additional restraint against false tripping
during high-magnitude external faults due to possible CT saturation.

Set 87G pickup: 0.060 pu


Set 87G Slope 1: 10 %
Set 87G Break 1: 1.15 pu
Set 87G Slope 2: 20 %
Set 87G Break 2: 30.00 pu

87S

GENERAL ELECTRIC INTERNATIONAL, INC. - ENERGY CONSULTING


GE Energy For Sonelgaz M'Sila G3
g
GE Energy
GE UR G60 Generator Management Relay
Setting Calculations

Setting Calculation Sheet


Stator Differential (Function 87S)

87S

GENERAL ELECTRIC INTERNATIONAL, INC. - ENERGY CONSULTING


GE Energy For Sonelgaz M'Sila G3
g
GE Energy
GE UR G60 Generator Management Relay
Setting Calculations

Setting Calculation Sheet


Generator Unbalance (Functions 46A & 46T)

A) Generator Data
Generator Data: 126.875 MVAG, 11.50 kV, 0.8 pf
Generator Full Load Current (IFL): 6369 Amperes
0.85 secondary amperes
0.170 pu CT rating

Continuous Unbalanced Current (I2C) Capability: 8%


2
I2 t Capability (K): 10

B) Relay Data
46A [STG2] Relay Ranges: Pickup: 0.00 - 100.00% in steps of 0.01
Delay: 0.0 to 1000.0 seconds in steps of 0.1

46T [STG1] Relay Ranges: Pickup: 0.00 - 100.00% in steps of 0.01


K-value: 0.00 - 100.00 in steps of 0.01
TMIN: 0.000 - 50.000 seconds in steps of 0.001
TMAX: 0.0 - 1000.0 seconds in steps of 0.1
K-Reset: 0.0 - 1000.0 seconds in steps of 0.1

CT Ratio (CT R): 7,500 / 1 = 7500 :1

C) Settings Calculations
Relay Setting Philosophy:

To provide some conservatism, the recommended 46T [Stage 1] Pickup and K-Values are set at
approximately 80% of the defined continuous unbalanced current (I2C) Capability and the defined
2
I2 t Capability (K) of the machine respectively.

The 46A [Stage 2] Alarm Pickup is set at approximately 70% of the 46T [Stage 1] Trip Pickup Setting,
with an Alarm Time Delay of 6 seconds.

I nominal: 0.849 pu CT rating

Recommended 46T [STG1] Pickup Setting: 6.40%


Recommended 46T [STG1] K-Value: 8.00
Recommended 46T [STG1] Min Operate Time (TMIN): 0.010 seconds
Recommended 46T [STG1] Max Operate Time (TMAX): 120.0 seconds
Recommended 46T [STG1] K-Reset: 900.0 seconds

Recommended 46A [STG2] Pickup Setting: 4.48%


Recommended 46A [STG2] Delay: 6.0 seconds

46A & 46T

GENERAL ELECTRIC INTERNATIONAL, INC. - ENERGY CONSULTING


GE Energy For Sonelgaz M'Sila G3
g
GE Energy
GE UR G60 Generator Management Relay
Setting Calculations

Setting Calculation Sheet


Generator Unbalance (Functions 46A & 46T)

Generator I22t Capacity vs Protection

1000.000

100.000

10.000
Time in Seconds

Machine, K = 10
1.000 46T, K = 8
46A

0.100

0.010

0.001
0.01 0.1 1 10 100
Per Unit I2

46A & 46T

GENERAL ELECTRIC INTERNATIONAL, INC. - ENERGY CONSULTING


GE Energy For Sonelgaz M'Sila G3
g
GE Energy
GE UR G60 Generator Management Relay
Setting Calculations

Setting Calculation Sheet


Loss of Excitation (Functions 40-1 & 40-2)

A) Generator Data
Generator Data: 126.875 MVAG, 11.50 kV, 0.8 pf
XDV = 1.978 per unit
X’DV = 0.243 per unit

B) Relay Data
40-1,2 Relay Ranges: 0.10-300.00  Center & Radius
0.000-65.535 seconds Time delay

CT Ratio (CT R): 7,500 / 1 = 7,500 :1


PT Ratio (PT R): 11,500 / 100 = 115 :1
CTR/PTR: 65.22

C) Settings Calculations
Relay Setting Philosophy: During loss of excitation, these relay functions will
detect Reactive Power flow from the system into the generator, provided that
a suitable source of Reactive Power (such as a utility tie) is available. An offset setting
of X’ DV / 2 is used to avoid misoperations during system faults. The 40-1 circle is set
at a Diameter of 0.7*XDV (time delay = 0.06 seconds) in order to detect loss of excitation at
full and moderate load, while not tripping for stable swings or regulator undershoot.
The 40-2 circle is set at a Diameter of XDV with a time delay of 0.6 seconds to provide tripping
for loss of excitation under a wider range of loading conditions or open circuit field,
while not tripping for stable swings.

This function will be blocked for a VT Fuse Failure (VTFF).

Convert X’ DV and X DV from per unit on gen. MVA and kV bases to relay ohms:
ZBASE (Generator Relay Base Impedance) = ((kV*kV)/MVA G)*(CTR/PTR) = 67.98 
X’DV-RELAY = (X’ DV) * (Z BASE) = 16.519 
70% X DV-RELAY = 0.70 * (X DV) * (Z BASE) = 94.13 
XDV-RELAY = (X DV) * (Z BASE) = 134.47 

Set 40-STG1 Center = (X’ DV-RELAY + 70% X DV-RELAY) / 2 = 55.32 


Set 40-1 Radius = (70% X DV-RELAY / 2) = 47.06 
Set 40-STG1 Delay = 0.060 seconds

Set 40-STG2 Center = (X’ DV-RELAY + X DV-RELAY) / 2 = 75.49 


Set 40-2 Radius = (X DV-RELAY / 2) = 67.23 
Set 40-STG2 Delay = 0.600 seconds
Set 40-STG1 & 40-STG2 UV Supervision = Disable

40-1 & 40-2

GENERAL ELECTRIC INTERNATIONAL, INC. - ENERGY CONSULTING


GE Energy For Sonelgaz M'Sila G3
g
GE Energy
GE UR G60 Generator Management Relay
Setting Calculations

Setting Calculation Sheet


Loss of Excitation (Functions 40-1 & 40-2)

40-1 40-2
Loss of Excitation Protection (40)

-10

-20

-30

-40

-50
X (relay ohms)

-60

-70

-80

-90

-100

-110

-120

-130

-140

-150
-75 -65 -55 -45 -35 -25 -15 -5 5 15 25 35 45 55 65 75

R (relay ohms)

40-1 & 40-2

GENERAL ELECTRIC INTERNATIONAL, INC. - ENERGY CONSULTING


GE Energy For Sonelgaz M'Sila G3
g
GE Energy
GE UR G60 Generator Management Relay
Setting Calculations

Setting Calculation Sheet


Anti-Motoring (Function 32)

A) Generator Data
Generator Data: 126.875 MVAG, 11.5 kV, 0.8 pf
Generator Base kW Rating: 101.5 MW

B) Relay Data
32-STG1,32-STG2 Relay Ranges: -1.200 to 1.200 pu in steps of 0.001
0 to 600.00 seconds in steps of 0.01

CT Ratio (CT R): 7,500 / 1 = 7,500 :1


PT Ratio (PT R): 11,500 / 100 = 115 :1

C) Settings Calculations
Relay Setting Philosophy: The amount of Motoring Power which will be required by this particular
Turbine-Generator application was not available for these setting calculations. For the initial
turbine-generator startup, a reasonably conservative Pickup setting of 2% of the Gen MVA * p.f. Rating
will be utilized, with a Trip Time Delay of 2.2 seconds (to match existing Tiaret GPP "32P" function trip time dela
This setting can be adjusted in the future if actual data becomes available or if operating requirements dictate

The magnitude of Motoring Power (in Primary MW) required to operate this protection function
must be verified by testing during relay commissioning.

This function will be blocked for a VT Fuse Failure (VTFF).

32-STG1 pickup set for 2.00% of machine MVA * P.F. rating = 2.030 MW

Sensitive Directional Power Element


Dir. Power 1 Char Angle: 180 °
Directional Power 1 Calibration: 0 °
Directional Power 1 STG1 SMIN: 0.014 pu
Directional Power 1 STG1 Delay: 2.20 seconds

32

GENERAL ELECTRIC INTERNATIONAL, INC. - ENERGY CONSULTING


GE Energy For Sonelgaz M'Sila G3
g
GE Energy
GE UR G60 Generator Management Relay
Setting Calculations

Setting Calculation Sheet


Overcurrent Voltage Restrained (Function 51P)

A) Generator Data
Generator Data: 126.875 MVAG, 11.5 kV, 0.8 pf
Generator Base kW Rating: 101.5 MW
X"dv = 0.167 T"d = 0.04 IFG = 2123 A, FL Field
X'dv = 0.243 T'd = 0.866 IF = 748 A, NL Field
Xdv = 1.98 Ta = 0.274 IFG / I F = 2.8
ZGSU = 13.2 %Z
@ 125 MVA
B) Relay Data
51P Relay Ranges: 0.000 to 30.000 pu pickup range in steps of 0.001
0.00 to 600.00 TD multiplier range in steps of 0.01

CT Ratio (CT R): 7,500 / 1 = 7,500 :1


PT Ratio (PT R): 11,500 / 100 = 115 :1

C) Settings Calculations
Relay Setting Philosophy: This function provides backup system phase overcurrent protection
and is set to pick-up at 140% of rated current and operate in approximately 0.60 seconds for a GSU
High-Side fault based upon the calculated generator fault decrement curve. These pickup and time delay
setpoints were selected based upon past experience and typical application practices.

These setpoints will provide the generator with some ability to continue to operate
during periods of increased output current flows which might occur during otherwise stable system swings
while also providing some tripping time delay at high output (fault) current levels to allow downstream
phase fault protective devices the opportunity to remove a fault before generator tripping is initiated.
Note that the 51P protection function operating times shown on the curve following this discussion
are approximate, due to the varying (decaying) characteristic of the generator output current following
a three-phase terminal fault.

This function will be blocked for a VT Fuse Failure (VTFF).

Recommended 51V pickup (I PU) =I FL * 1.4 = 8917 Amperes


1.19 Secondary Amps

Recommended 51V pickup (I PU) = 1.189 pu CT rating


Curve Type: IEEE Moderately Inverse
Recommended Time Dial Multiplier = 0.42
.
Generator fault current @ 0.6 second (I) = 21505 Amperes
(per generator decrement curve) 2.87 secondary amps
Generator terminal voltage for GSU high-side fault = 0.355 pu V

Generator terminal voltage for close-in fault  0.1 pu V ; V/VNOM = 0.1

51P

GENERAL ELECTRIC INTERNATIONAL, INC. - ENERGY CONSULTING


GE Energy For Sonelgaz M'Sila G3
g
GE Energy
GE UR G60 Generator Management Relay
Setting Calculations

Setting Calculation Sheet


Overcurrent Voltage Restrained (Function 51P)

10
Coordination
Point: 51V GSU
High Side SC &
Gen Dec. Curve at
approx. 0.60 sec

1
Gen. Decrement
51V GEN SC
51V GSU HS SC
Time (sec)

0.1

0.01
1,000 10,000 100,000
Current (Amps)

NOTE: Decrement Curve shown is approximate. Values indicated in Red (previous page) are assumed.

51P

GENERAL ELECTRIC INTERNATIONAL, INC. - ENERGY CONSULTING


GE Energy For Sonelgaz M'Sila G3
g
GE Energy
GE UR G60 Generator Management Relay
Setting Calculations

Setting Calculation Sheet


Stator Ground Fault (Function 64G)

A) Generator Data
Generator Data: 126.875 MVAG, 11.5 kV, 0.8 pf
Neutral Grounding Transformer Ratio (NGT R): 6640 /100 = 66.40 :1
Neutral Grounding Transformer Resistor Impedance (Z RES): 664 

B) Relay Data
Auxiliary OV1 Relay Ranges: 0.000 to 3.000 pu pickup range in steps of 0.001
0.00 to 600.00 seconds pickup delay in steps of 0.01

C) Settings Calculations
Relay Setting Philosophy: Set 64G pickup to provide approximately 96% or higher stator ground
fault coverage, with a tripping time delay of 0.28 seconds. These pickup and time delay
setpoints were selected based upon the supplied settings for the existing Tiaret GPP "64G" protection function.

IGMAX = V L-N / (Z RES) = 10.00 amps

Neutral Grounding Transformer Secondary Voltage at I GMAX:


VMAX SEC = (I GMAX * Z RES)/NGTR = 100.0 Volts

Recommended 64G Pickup Setting (V SET) : 4 Volts = 0.040 pu


Approximate Stator Ground Fault Coverage = (1 -V SET MAX SEC) * 100 =
/V 96.0%

Recommended 64G Time Delay Setting: 0.28 seconds

64G

GENERAL ELECTRIC INTERNATIONAL, INC. - ENERGY CONSULTING


GE Energy For Sonelgaz M'Sila G3
g
GE Energy
GE UR G60 Generator Management Relay
Setting Calculations

Setting Calculation Sheet


Overexcitation (Functions 24A & 24T)

A) Generator Data
Generator Data: 126.875 MVAG, 11.5 kV, 0.8 pf

B) Relay Data
24T Relay Ranges: DT, Inverse A-C, Flexcurve A,B curve settings
0.80 to 4.00 per unit Volts/Hertz pickup range in steps of 0.01
0.05 to 600.00 TD multiplier range in steps of 0.01
0.0 to 1000.0 second T-Reset settings range in steps of 0.1

PT Ratio (PT R): 11,500 / 100 = 115 :1

C) Settings Calculations

Relay Setting Philosophy: The 24A function is intended to alarm prior


to a trip. Typically, generators are capable of continuous operation at 1.05 per unit V/Hz,
therefore, a 1.07 per unit V/Hz alarm setting with a 10 second delay to avoid
nuisance alarms will be used. Corrective action must be taken by the operator to prevent continuous
operation of the machine above 105% V/Hz.

The Pickup, Curve Type and Time Multiplier settings selected for the 24T
protection function were based upon past experience and typical application practices,
and will operate at the V/Hz versus operating time values shown on the following curve.
As shown, the V/Hz protection function will operate in approximately 1.85 seconds at 117% V/Hz and
will operate in approximately 42 seconds at 110% V/Hz.

Volts/Hertz Element 1 (Trip)


Set 24T1 curve type : Def Time
Set 24T1 pickup : 1.10 per unit V/Hz
Set 24T1 TD multiplier : 42.00
Set 24T1 T-Reset: 900.0 seconds

Volts/Hertz Element 2 (Trip)


Set 24T2 curve type : Def Time
Set 24T2 pickup : 1.17 per unit V/Hz
Set 24T2 TD multiplier : 1.85 seconds
Set 24T2 T-reset : 10.0 seconds

Volts/Hertz Element 3 (FlexElement 4) (Alarm)


24T3 curve type : Def Time
Set 24T3 pickup : 1.07 per unit V/Hz
Set 24T3 time delay : 10.000 seconds
Set 24T3 T-reset : 0.000 seconds

24

GENERAL ELECTRIC INTERNATIONAL, INC. - ENERGY CONSULTING


GE Energy For Sonelgaz M'Sila G3
g
GE Energy
GE UR G60 Generator Management Relay
Setting Calculations

Setting Calculation Sheet


Overexcitation (Functions 24A & 24T)

V/Hz Protection (24)

1.4000

1.3500

1.3000

1.2500
V/Hz in Per Unit

24T
1.2000

1.1500

1.1000

1.0500

1.0000
1.00 10.00 100.00
Time in Seconds

24

GENERAL ELECTRIC INTERNATIONAL, INC. - ENERGY CONSULTING


GE Energy For Sonelgaz M'Sila G3
g
GE Energy
GE UR G60 Generator Management Relay
Setting Calculations

Setting Calculation Sheet


Phase Overvoltage (Function 59P)

A) Generator Data
Generator Data: 126.875 MVAG, 11.5 kV, 0.8 pf

B) Relay Data
59P Relay Ranges: 0.000 to 3.000 pu pickup range in steps of 0.001
0.00 to 600.00 second pickup time delay range in steps of 0.01
0.00 to 600.00 second reset delay range in steps of 0.01

PT Ratio (PT R): 11,500 / 100 = 115 :1

C) Settings Calculations
Relay Setting Philosophy: The recommended settings for the 59P-1 and 59P-2 protection functions were
based upon the previously supplied settings for the existing Tiaret GPP "59P" protection functions.

Nominal voltage = 100 volts

Recommended 59P-1 pickup = 1.200 per-unit volts


= 120.0 volts

Recommended 59P-1 Time Delay = 3.60 seconds


Recommended 59P-1 Reset Delay = 0.10 seconds

Recommended 59P-2 pickup = 1.300 per-unit volts


= 130.0 volts

Recommended 59P-2 Time Delay = 0.00 seconds


Recommended 59P-2 Reset Delay = 0.10 seconds

59P

GENERAL ELECTRIC INTERNATIONAL, INC. - ENERGY CONSULTING


GE Energy For Sonelgaz M'Sila G3
g
GE Energy
GE UR G60 Generator Management Relay
Setting Calculations

Setting Calculation Sheet


Under/Overfrequency (Functions 81U & 81O)

A) Generator Data
Generator Data: 126.875 MVAG, 11.5 kV, 0.8 pf
Nominal Frequency: 50 Hz
B) Relay Data
81 Relay Ranges: 0.10-1.25 pu min Volts/Amps
20.00 - 65.00 Hz Set Points (81-1U, 81-2U, 81-3U)
20.00 - 65.00 Hz Set Points (81-1O, 81-2O, 81-3O)
0.000 - 65.535 second delay time range

PT Ratio (PT R): 11,500 / 100 = 115 :1

C) Settings Calculations
Relay Setting Philosophy: The recommended settings of the 81U and 81O protection functions are
based upon the supplied settings for the existing Tiaret GPP "81U" and "81O" protection functions.

Applying the settings summarized below requires that the generator has the capability of continuously
operating at an output frequency between 47.80 and 51.00 Hz without damage.

Recommended Min Volts/Amps (under-frequency setpoints) = 0.10 pu

Recommended 81U-1 pickup = 47.80 Hz


Recommended 81U-1 delay = 0.300 seconds (Trip)
Recommended 81U-1 reset = 0.100 seconds
Recommended 81U-2 pickup = 47.50 Hz
Recommended 81U-2 delay = 0.000 seconds (Trip)
Recommended 81U-2 reset = 0.100 seconds
Recommended 81U-3 pickup = 47.00 Hz
Recommended 81U-3 delay = 20.000 seconds (Trip)
Recommended 81U-3 reset = 0.100 seconds
Recommended 81U-4 pickup = 46.00 Hz
Recommended 81U-4 delay = 0.000 seconds (Trip)
Recommended 81U-4 reset = 0.100 seconds

Recommended 81O-2 pickup = 51.00 Hz


Recommended 81O-2 delay = 20.000 seconds (Trip)
Recommended 81O-2 reset = 0.100 seconds
Recommended 81O-3 pickup = 52.00 Hz
Recommended 81O-3 delay = 0.300 seconds (Trip)
Recommended 81O-3 reset = 0.100 seconds

81-U/O

GENERAL ELECTRIC INTERNATIONAL, INC. - ENERGY CONSULTING


GE Energy For Sonelgaz M'Sila G3
g
GE Energy
GE UR G60 Generator Management Relay
Setting Calculations

Setting Calculation Sheet


Phase Undervoltage (Function 27P)

A) Generator Data
Generator Data: 126.875 MVAG, 11.5 kV, 0.8 pf

B) Relay Data
27P Relay Ranges: 0.000 to 3.000 pu pickup range in steps of 0.001
0.00 to 600.00 second pickup time delay range in steps of 0.01
0.000 to 3.000 pu minimum voltage setpoint in steps of 0.001
Inverse Time Characteristic or Definite Time

PT Ratio (PT R): 11,500 / 100 = 115 :1

C) Settings Calculations
Relay Setting Philosophy: The recommended settings for the 27P-1 and 27P-2 protection functions were
based upon the supplied settings for the existing Tiaret GPP "27P" protection functions.

Nominal voltage = 100 volts

Recommended 27P-1 (Trip) pickup = 0.720 per-unit volts


= 72.0 volts

Recommended 27P-1 Time Delay = 2.80 seconds

Recommended 27P-2 (Alarm) pickup = 0.720 per-unit volts


= 72.0 volts

Recommended 27P-2 Time Delay = 2.50 seconds

27P

GENERAL ELECTRIC INTERNATIONAL, INC. - ENERGY CONSULTING


GE Energy For Sonelgaz M'Sila G3
g
GE Energy
GE UR G60 Generator Management Relay
Setting Calculations

Setting Calculation Sheet


Inadvertent Generator Energization (Function 50/27)

A) Generator Data
Generator Data: 126.875 MVAG, 11.5 kV, 0.8 pf

B) Relay Data
50/27 Function Ranges: U/V and/or Offline (Arming Mode)
0.000 to 3.000 pu overcurrent pickup range in steps of 0.001
0.000 to 3.000 pu undervoltage pickup range in steps of 0.001

CT Ratio (CT R): 7,500 / 1 = 7,500 :1


PT Ratio (PT R): 11,500 / 100 = 115 :1

C) Settings Calculations
Relay Setting Philosophy: This function provides protection against accidental
closing of the circuit breaker when the unit is offline. The function is armed
when the voltage falls below 0.80 pu V and the unit is offline (52b contact
closed indicates that the generator circuit breaker is open).

Recommended 50/27 Arming Mode: U/V and Offline

Recommended 50/27 O/C Pickup Setting: 0.050 pu

Recommended 50/27 U/V Pickup Setting: 0.800 pu

50/27

GENERAL ELECTRIC INTERNATIONAL, INC. - ENERGY CONSULTING


GE Energy For Sonelgaz M'Sila G3
g
GE Energy
GE UR G60 Generator Management Relay
Setting Calculations

Setting Calculation Sheet


Generator Overcurrent Alarm (Function 49G)

A) Generator Data
Generator Data: 126.875 MVAG, 11.5 kV, 0.8 pf

B) Relay Data

CT Ratio (CT R): 7500 / 1 = 7500 :1

C) Settings Calculations
Relay Setting Philosophy: This overcurrent alarm function utilizes FlexElements to
monitor and respond to the generator phase current flows.

The Generator Overcurrent Alarm function is set to operate when the generator output current
is equal to or greater than approximately 7325 Amps (approximately 115% of nominal),
with an operating time delay of 5 seconds.

Recommended 49G Pickup Setting: 0.977 (7328 Amps)


Recommended 49G Operating Time Delay: 5.000 seconds

49G

GENERAL ELECTRIC INTERNATIONAL, INC. - ENERGY CONSULTING


GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


Study Appendix

8. Appendix 2: UR G60 Setting File Summary (Generator G3)

PAGE 116

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 1

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

PRODUCT SETUP
SECURITY
Command Password 0
Setting Password 0
Command Password Access Timeout 5 min
Setting Password Access Timeout 30 min
Invalid Password Attempts 3
Password Lockout Duration 5 min
Password Access Events Disabled
Local Setting Authorized ON
Remote Setting Authorized ON
Access Authorized Timeout 30 min

DISPLAY PROPERTIES
Language French
Flash Message Time 4.0 s
Default Message Timeout 24 s
Default Message Intensity (VFD Only) 25 %
Screen Saver Feature (LCD Only) Disabled
Screen Saver Wait Time (LCD Only) 30 min
Current Cutoff Level 0.002 pu
Voltage Cutoff Level 1.0 V

COMMUNICATIONS
SERIAL PORTS
COM2 Selection RS485
RS485 Com2 Baud Rate 115200
RS485 Com2 Parity None
RS485 Com2 Response Min Time 0 ms

NETWORK
IP Address 192.168.101. 82
IP Subnet Mask 255.255.255. 0
Gateway IP Address 192.168.101. 15
Ethernet Operation Mode Full-Duplex
OSI Network Address (NSAP) 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 49 00 00 00

MODBUS PROTOCOL
Modbus Slave Address 254
Modbus TCP Port Number 502

IEC 61850
GSSE / GOOSE CONFIGURATION
TRANSMISSION
GENERAL
Default GSSE/GOOSE Update Time 60 s

GSSE
Function Enabled
ID GSSEOut
Destination MAC 00 00 00 00 00 00

TX CONFIGURABLE GOOSE
GOOSEOut 1 Function Enabled
GOOSEOut 1 ID GOOSEOut_1
GOOSEOut 1 Destination MAC 00 00 00 00 00 00
GOOSEOut 1 VLAN Priority 4
GOOSEOut 1 VLAN ID 0
GOOSEOut 1 ETYPE APPID 0
GOOSEOut 1 ConfRev 1
GOOSEOut 1 Retransmission Curve Relaxed
GOOSEOut 2 Function Enabled
GOOSEOut 2 ID GOOSEOut_2
GOOSEOut 2 Destination MAC 00 00 00 00 00 00
GOOSEOut 2 VLAN Priority 4
GOOSEOut 2 VLAN ID 0
GOOSEOut 2 ETYPE APPID 0
GOOSEOut 2 ConfRev 1
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 2

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

TX CONFIGURABLE GOOSE (continued from last page)


GOOSEOut 2 Retransmission Curve Relaxed
GOOSEOut 3 Function Enabled
GOOSEOut 3 ID GOOSEOut_3
GOOSEOut 3 Destination MAC 00 00 00 00 00 00
GOOSEOut 3 VLAN Priority 4
GOOSEOut 3 VLAN ID 0
GOOSEOut 3 ETYPE APPID 0
GOOSEOut 3 ConfRev 1
GOOSEOut 3 Retransmission Curve Relaxed
GOOSEOut 4 Function Enabled
GOOSEOut 4 ID GOOSEOut_4
GOOSEOut 4 Destination MAC 00 00 00 00 00 00
GOOSEOut 4 VLAN Priority 4
GOOSEOut 4 VLAN ID 0
GOOSEOut 4 ETYPE APPID 0
GOOSEOut 4 ConfRev 1
GOOSEOut 4 Retransmission Curve Relaxed
GOOSEOut 5 Function Enabled
GOOSEOut 5 ID GOOSEOut_5
GOOSEOut 5 Destination MAC 00 00 00 00 00 00
GOOSEOut 5 VLAN Priority 4
GOOSEOut 5 VLAN ID 0
GOOSEOut 5 ETYPE APPID 0
GOOSEOut 5 ConfRev 1
GOOSEOut 5 Retransmission Curve Relaxed
GOOSEOut 6 Function Enabled
GOOSEOut 6 ID GOOSEOut_6
GOOSEOut 6 Destination MAC 00 00 00 00 00 00
GOOSEOut 6 VLAN Priority 4
GOOSEOut 6 VLAN ID 0
GOOSEOut 6 ETYPE APPID 0
GOOSEOut 6 ConfRev 1
GOOSEOut 6 Retransmission Curve Relaxed
GOOSEOut 7 Function Enabled
GOOSEOut 7 ID GOOSEOut_7
GOOSEOut 7 Destination MAC 00 00 00 00 00 00
GOOSEOut 7 VLAN Priority 4
GOOSEOut 7 VLAN ID 0
GOOSEOut 7 ETYPE APPID 0
GOOSEOut 7 ConfRev 1
GOOSEOut 7 Retransmission Curve Relaxed
GOOSEOut 8 Function Enabled
GOOSEOut 8 ID GOOSEOut_8
GOOSEOut 8 Destination MAC 00 00 00 00 00 00
GOOSEOut 8 VLAN Priority 4
GOOSEOut 8 VLAN ID 0
GOOSEOut 8 ETYPE APPID 0
GOOSEOut 8 ConfRev 1
GOOSEOut 8 Retransmission Curve Relaxed

SERVER CONFIGURATION
IEDName IEDName
Logical Device Instance LDInst
LPHD DC PhyNam location Location
MMS TCP Port Number 102

MMXU DEADBANDS
MMXU1: TotW Deadband 10.000 %
MMXU1: TotVAr Deadband 10.000 %
MMXU1: TotVA Deadband 10.000 %
MMXU1: TotPF Deadband 10.000 %
MMXU1: Hz Deadband 10.000 %
MMXU1: PPV phsAB Deadband 10.000 %
MMXU1: PPV phsBC Deadband 10.000 %
MMXU1: PPV phsCA Deadband 10.000 %
MMXU1: PhV phsA Deadband 10.000 %
MMXU1: PhV phsB Deadband 10.000 %
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 3

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

MMXU DEADBANDS (continued from last page)


MMXU1: PhV phsC Deadband 10.000 %
MMXU1: A phsA Deadband 10.000 %
MMXU1: A phsB Deadband 10.000 %
MMXU1: A phsC Deadband 10.000 %
MMXU1: A neut Deadband 10.000 %
MMXU1: W phsA Deadband 10.000 %
MMXU1: W phsB Deadband 10.000 %
MMXU1: W phsC Deadband 10.000 %
MMXU1: VAr phsA Deadband 10.000 %
MMXU1: VAr phsB Deadband 10.000 %
MMXU1: VAr phsC Deadband 10.000 %
MMXU1: VA phsA Deadband 10.000 %
MMXU1: VA phsB Deadband 10.000 %
MMXU1: VA phsC Deadband 10.000 %
MMXU1: PF phsA Deadband 10.000 %
MMXU1: PF phsB Deadband 10.000 %
MMXU1: PF phsC Deadband 10.000 %
MMXU2: TotW Deadband 10.000 %
MMXU2: TotVAr Deadband 10.000 %
MMXU2: TotVA Deadband 10.000 %
MMXU2: TotPF Deadband 10.000 %
MMXU2: Hz Deadband 10.000 %
MMXU2: PPV phsAB Deadband 10.000 %
MMXU2: PPV phsBC Deadband 10.000 %
MMXU2: PPV phsCA Deadband 10.000 %
MMXU2: PhV phsA Deadband 10.000 %
MMXU2: PhV phsB Deadband 10.000 %
MMXU2: PhV phsC Deadband 10.000 %
MMXU2: A phsA Deadband 10.000 %
MMXU2: A phsB Deadband 10.000 %
MMXU2: A phsC Deadband 10.000 %
MMXU2: A neut Deadband 10.000 %
MMXU2: W phsA Deadband 10.000 %
MMXU2: W phsB Deadband 10.000 %
MMXU2: W phsC Deadband 10.000 %
MMXU2: VAr phsA Deadband 10.000 %
MMXU2: VAr phsB Deadband 10.000 %
MMXU2: VAr phsC Deadband 10.000 %
MMXU2: VA phsA Deadband 10.000 %
MMXU2: VA phsB Deadband 10.000 %
MMXU2: VA phsC Deadband 10.000 %
MMXU2: PF phsA Deadband 10.000 %
MMXU2: PF phsB Deadband 10.000 %
MMXU2: PF phsC Deadband 10.000 %
MMXU3: TotW Deadband 10.000 %
MMXU3: TotVAr Deadband 10.000 %
MMXU3: TotVA Deadband 10.000 %
MMXU3: TotPF Deadband 10.000 %
MMXU3: Hz Deadband 10.000 %
MMXU3: PPV phsAB Deadband 10.000 %
MMXU3: PPV phsBC Deadband 10.000 %
MMXU3: PPV phsCA Deadband 10.000 %
MMXU3: PhV phsA Deadband 10.000 %
MMXU3: PhV phsB Deadband 10.000 %
MMXU3: PhV phsC Deadband 10.000 %
MMXU3: A phsA Deadband 10.000 %
MMXU3: A phsB Deadband 10.000 %
MMXU3: A phsC Deadband 10.000 %
MMXU3: A neut Deadband 10.000 %
MMXU3: W phsA Deadband 10.000 %
MMXU3: W phsB Deadband 10.000 %
MMXU3: W phsC Deadband 10.000 %
MMXU3: VAr phsA Deadband 10.000 %
MMXU3: VAr phsB Deadband 10.000 %
MMXU3: VAr phsC Deadband 10.000 %
MMXU3: VA phsA Deadband 10.000 %
MMXU3: VA phsB Deadband 10.000 %
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 4

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

MMXU DEADBANDS (continued from last page)


MMXU3: VA phsC Deadband 10.000 %
MMXU3: PF phsA Deadband 10.000 %
MMXU3: PF phsB Deadband 10.000 %
MMXU3: PF phsC Deadband 10.000 %
MMXU4: TotW Deadband 10.000 %
MMXU4: TotVAr Deadband 10.000 %
MMXU4: TotVA Deadband 10.000 %
MMXU4: TotPF Deadband 10.000 %
MMXU4: Hz Deadband 10.000 %
MMXU4: PPV phsAB Deadband 10.000 %
MMXU4: PPV phsBC Deadband 10.000 %
MMXU4: PPV phsCA Deadband 10.000 %
MMXU4: PhV phsA Deadband 10.000 %
MMXU4: PhV phsB Deadband 10.000 %
MMXU4: PhV phsC Deadband 10.000 %
MMXU4: A phsA Deadband 10.000 %
MMXU4: A phsB Deadband 10.000 %
MMXU4: A phsC Deadband 10.000 %
MMXU4: A neut Deadband 10.000 %
MMXU4: W phsA Deadband 10.000 %
MMXU4: W phsB Deadband 10.000 %
MMXU4: W phsC Deadband 10.000 %
MMXU4: VAr phsA Deadband 10.000 %
MMXU4: VAr phsB Deadband 10.000 %
MMXU4: VAr phsC Deadband 10.000 %
MMXU4: VA phsA Deadband 10.000 %
MMXU4: VA phsB Deadband 10.000 %
MMXU4: VA phsC Deadband 10.000 %
MMXU4: PF phsA Deadband 10.000 %
MMXU4: PF phsB Deadband 10.000 %
MMXU4: PF phsC Deadband 10.000 %

GGIO1 STATUS CONFIGURATION


Number of Status Points 8

GGIO2 CONTROL CONFIGURATION


SPCSO 1 ctlModel 1
SPCSO 2 ctlModel 1
SPCSO 3 ctlModel 1
SPCSO 4 ctlModel 1
SPCSO 5 ctlModel 1
SPCSO 6 ctlModel 1
SPCSO 7 ctlModel 1
SPCSO 8 ctlModel 1
SPCSO 9 ctlModel 1
SPCSO 10 ctlModel 1
SPCSO 11 ctlModel 1
SPCSO 12 ctlModel 1
SPCSO 13 ctlModel 1
SPCSO 14 ctlModel 1
SPCSO 15 ctlModel 1
SPCSO 16 ctlModel 1
SPCSO 17 ctlModel 1
SPCSO 18 ctlModel 1
SPCSO 19 ctlModel 1
SPCSO 20 ctlModel 1
SPCSO 21 ctlModel 1
SPCSO 22 ctlModel 1
SPCSO 23 ctlModel 1
SPCSO 24 ctlModel 1
SPCSO 25 ctlModel 1
SPCSO 26 ctlModel 1
SPCSO 27 ctlModel 1
SPCSO 28 ctlModel 1
SPCSO 29 ctlModel 1
SPCSO 30 ctlModel 1
SPCSO 31 ctlModel 1
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 5

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

GGIO2 CONTROL CONFIGURATION (continued from last page)


SPCSO 32 ctlModel 1
SPCSO 33 ctlModel 1
SPCSO 34 ctlModel 1
SPCSO 35 ctlModel 1
SPCSO 36 ctlModel 1
SPCSO 37 ctlModel 1
SPCSO 38 ctlModel 1
SPCSO 39 ctlModel 1
SPCSO 40 ctlModel 1
SPCSO 41 ctlModel 1
SPCSO 42 ctlModel 1
SPCSO 43 ctlModel 1
SPCSO 44 ctlModel 1
SPCSO 45 ctlModel 1
SPCSO 46 ctlModel 1
SPCSO 47 ctlModel 1
SPCSO 48 ctlModel 1
SPCSO 49 ctlModel 1
SPCSO 50 ctlModel 1
SPCSO 51 ctlModel 1
SPCSO 52 ctlModel 1
SPCSO 53 ctlModel 1
SPCSO 54 ctlModel 1
SPCSO 55 ctlModel 1
SPCSO 56 ctlModel 1
SPCSO 57 ctlModel 1
SPCSO 58 ctlModel 1
SPCSO 59 ctlModel 1
SPCSO 60 ctlModel 1
SPCSO 61 ctlModel 1
SPCSO 62 ctlModel 1
SPCSO 63 ctlModel 1
SPCSO 64 ctlModel 1

GGIO4 ANALOG CONFIGURATION


IEC61850 GGIO4 Analogs 4
IEC61850 GGIO4 Analog 1 Value OFF
IEC61850 GGIO4 Analog 1 db 100.000 %
IEC61850 GGIO4 Analog 1 min 0.000
IEC61850 GGIO4 Analog 1 max 1000000.000
IEC61850 GGIO4 Analog 2 Value OFF
IEC61850 GGIO4 Analog 2 db 100.000 %
IEC61850 GGIO4 Analog 2 min 0.000
IEC61850 GGIO4 Analog 2 max 1000000.000
IEC61850 GGIO4 Analog 3 Value OFF
IEC61850 GGIO4 Analog 3 db 100.000 %
IEC61850 GGIO4 Analog 3 min 0.000
IEC61850 GGIO4 Analog 3 max 1000000.000
IEC61850 GGIO4 Analog 4 Value OFF
IEC61850 GGIO4 Analog 4 db 100.000 %
IEC61850 GGIO4 Analog 4 min 0.000
IEC61850 GGIO4 Analog 4 max 1000000.000
IEC61850 GGIO4 Analog 5 Value OFF
IEC61850 GGIO4 Analog 5 db 100.000 %
IEC61850 GGIO4 Analog 5 min 0.000
IEC61850 GGIO4 Analog 5 max 1000000.000
IEC61850 GGIO4 Analog 6 Value OFF
IEC61850 GGIO4 Analog 6 db 100.000 %
IEC61850 GGIO4 Analog 6 min 0.000
IEC61850 GGIO4 Analog 6 max 1000000.000
IEC61850 GGIO4 Analog 7 Value OFF
IEC61850 GGIO4 Analog 7 db 100.000 %
IEC61850 GGIO4 Analog 7 min 0.000
IEC61850 GGIO4 Analog 7 max 1000000.000
IEC61850 GGIO4 Analog 8 Value OFF
IEC61850 GGIO4 Analog 8 db 100.000 %
IEC61850 GGIO4 Analog 8 min 0.000
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 6

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

GGIO4 ANALOG CONFIGURATION (continued from last page)


IEC61850 GGIO4 Analog 8 max 1000000.000
IEC61850 GGIO4 Analog 9 Value OFF
IEC61850 GGIO4 Analog 9 db 100.000 %
IEC61850 GGIO4 Analog 9 min 0.000
IEC61850 GGIO4 Analog 9 max 1000000.000
IEC61850 GGIO4 Analog 10 Value OFF
IEC61850 GGIO4 Analog 10 db 100.000 %
IEC61850 GGIO4 Analog 10 min 0.000
IEC61850 GGIO4 Analog 10 max 1000000.000
IEC61850 GGIO4 Analog 11 Value OFF
IEC61850 GGIO4 Analog 11 db 100.000 %
IEC61850 GGIO4 Analog 11 min 0.000
IEC61850 GGIO4 Analog 11 max 1000000.000
IEC61850 GGIO4 Analog 12 Value OFF
IEC61850 GGIO4 Analog 12 db 100.000 %
IEC61850 GGIO4 Analog 12 min 0.000
IEC61850 GGIO4 Analog 12 max 1000000.000
IEC61850 GGIO4 Analog 13 Value OFF
IEC61850 GGIO4 Analog 13 db 100.000 %
IEC61850 GGIO4 Analog 13 min 0.000
IEC61850 GGIO4 Analog 13 max 1000000.000
IEC61850 GGIO4 Analog 14 Value OFF
IEC61850 GGIO4 Analog 14 db 100.000 %
IEC61850 GGIO4 Analog 14 min 0.000
IEC61850 GGIO4 Analog 14 max 1000000.000
IEC61850 GGIO4 Analog 15 Value OFF
IEC61850 GGIO4 Analog 15 db 100.000 %
IEC61850 GGIO4 Analog 15 min 0.000
IEC61850 GGIO4 Analog 15 max 1000000.000
IEC61850 GGIO4 Analog 16 Value OFF
IEC61850 GGIO4 Analog 16 db 100.000 %
IEC61850 GGIO4 Analog 16 min 0.000
IEC61850 GGIO4 Analog 16 max 1000000.000
IEC61850 GGIO4 Analog 17 Value OFF
IEC61850 GGIO4 Analog 17 db 100.000 %
IEC61850 GGIO4 Analog 17 min 0.000
IEC61850 GGIO4 Analog 17 max 1000000.000
IEC61850 GGIO4 Analog 18 Value OFF
IEC61850 GGIO4 Analog 18 db 100.000 %
IEC61850 GGIO4 Analog 18 min 0.000
IEC61850 GGIO4 Analog 18 max 1000000.000
IEC61850 GGIO4 Analog 19 Value OFF
IEC61850 GGIO4 Analog 19 db 100.000 %
IEC61850 GGIO4 Analog 19 min 0.000
IEC61850 GGIO4 Analog 19 max 1000000.000
IEC61850 GGIO4 Analog 20 Value OFF
IEC61850 GGIO4 Analog 20 db 100.000 %
IEC61850 GGIO4 Analog 20 min 0.000
IEC61850 GGIO4 Analog 20 max 1000000.000
IEC61850 GGIO4 Analog 21 Value OFF
IEC61850 GGIO4 Analog 21 db 100.000 %
IEC61850 GGIO4 Analog 21 min 0.000
IEC61850 GGIO4 Analog 21 max 1000000.000
IEC61850 GGIO4 Analog 22 Value OFF
IEC61850 GGIO4 Analog 22 db 100.000 %
IEC61850 GGIO4 Analog 22 min 0.000
IEC61850 GGIO4 Analog 22 max 1000000.000
IEC61850 GGIO4 Analog 23 Value OFF
IEC61850 GGIO4 Analog 23 db 100.000 %
IEC61850 GGIO4 Analog 23 min 0.000
IEC61850 GGIO4 Analog 23 max 1000000.000
IEC61850 GGIO4 Analog 24 Value OFF
IEC61850 GGIO4 Analog 24 db 100.000 %
IEC61850 GGIO4 Analog 24 min 0.000
IEC61850 GGIO4 Analog 24 max 1000000.000
IEC61850 GGIO4 Analog 25 Value OFF
IEC61850 GGIO4 Analog 25 db 100.000 %
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 7

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

GGIO4 ANALOG CONFIGURATION (continued from last page)


IEC61850 GGIO4 Analog 25 min 0.000
IEC61850 GGIO4 Analog 25 max 1000000.000
IEC61850 GGIO4 Analog 26 Value OFF
IEC61850 GGIO4 Analog 26 db 100.000 %
IEC61850 GGIO4 Analog 26 min 0.000
IEC61850 GGIO4 Analog 26 max 1000000.000
IEC61850 GGIO4 Analog 27 Value OFF
IEC61850 GGIO4 Analog 27 db 100.000 %
IEC61850 GGIO4 Analog 27 min 0.000
IEC61850 GGIO4 Analog 27 max 1000000.000
IEC61850 GGIO4 Analog 28 Value OFF
IEC61850 GGIO4 Analog 28 db 100.000 %
IEC61850 GGIO4 Analog 28 min 0.000
IEC61850 GGIO4 Analog 28 max 1000000.000
IEC61850 GGIO4 Analog 29 Value OFF
IEC61850 GGIO4 Analog 29 db 100.000 %
IEC61850 GGIO4 Analog 29 min 0.000
IEC61850 GGIO4 Analog 29 max 1000000.000
IEC61850 GGIO4 Analog 30 Value OFF
IEC61850 GGIO4 Analog 30 db 100.000 %
IEC61850 GGIO4 Analog 30 min 0.000
IEC61850 GGIO4 Analog 30 max 1000000.000
IEC61850 GGIO4 Analog 31 Value OFF
IEC61850 GGIO4 Analog 31 db 100.000 %
IEC61850 GGIO4 Analog 31 min 0.000
IEC61850 GGIO4 Analog 31 max 1000000.000
IEC61850 GGIO4 Analog 32 Value OFF
IEC61850 GGIO4 Analog 32 db 100.000 %
IEC61850 GGIO4 Analog 32 min 0.000
IEC61850 GGIO4 Analog 32 max 1000000.000

REPORT CONTROL CONFIGURATION


REPORT 1 (GGIO1.BR): RptID
REPORT 1 (GGIO1.BR): OptFlds 0
REPORT 1 (GGIO1.BR): BufTm 0
REPORT 1 (GGIO1.BR): TrgOps 0
REPORT 1 (GGIO1.BR): IntgPd 0
REPORT 2 (GGIO1.BR01): RptID
REPORT 2 (GGIO1.BR01): OptFlds 0
REPORT 2 (GGIO1.BR01): BufTm 0
REPORT 2 (GGIO1.BR01): TrgOps 0
REPORT 2 (GGIO1.BR01): IntgPd 0
REPORT 3 (GGIO1.RP): RptID
REPORT 3 (GGIO1.RP): OptFlds 0
REPORT 3 (GGIO1.RP): BufTm 0
REPORT 3 (GGIO1.RP): TrgOps 0
REPORT 3 (GGIO1.RP): IntgPd 0
REPORT 4 (GGIO4.RP): RptID
REPORT 4 (GGIO4.RP): OptFlds 0
REPORT 4 (GGIO4.RP): BufTm 0
REPORT 4 (GGIO4.RP): TrgOps 0
REPORT 4 (GGIO4.RP): IntgPd 0
REPORT 5 (MMXU1.BR): RptID
REPORT 5 (MMXU1.BR): OptFlds 0
REPORT 5 (MMXU1.BR): BufTm 0
REPORT 5 (MMXU1.BR): TrgOps 0
REPORT 5 (MMXU1.BR): IntgPd 0
REPORT 6 (MMXU1.RP): RptID
REPORT 6 (MMXU1.RP): OptFlds 0
REPORT 6 (MMXU1.RP): BufTm 0
REPORT 6 (MMXU1.RP): TrgOps 0
REPORT 6 (MMXU1.RP): IntgPd 0
REPORT 7 (MMXU2.BR): RptID
REPORT 7 (MMXU2.BR): OptFlds 0
REPORT 7 (MMXU2.BR): BufTm 0
REPORT 7 (MMXU2.BR): TrgOps 0
REPORT 7 (MMXU2.BR): IntgPd 0
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 8

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

REPORT CONTROL CONFIGURATION (continued from last page)


REPORT 8 (MMXU2.RP): RptID
REPORT 8 (MMXU2.RP): OptFlds 0
REPORT 8 (MMXU2.RP): BufTm 0
REPORT 8 (MMXU2.RP): TrgOps 0
REPORT 8 (MMXU2.RP): IntgPd 0
REPORT 9 (MMXU3.BR): RptID
REPORT 9 (MMXU3.BR): OptFlds 0
REPORT 9 (MMXU3.BR): BufTm 0
REPORT 9 (MMXU3.BR): TrgOps 0
REPORT 9 (MMXU3.BR): IntgPd 0
REPORT 10 (MMXU3.RP): RptID
REPORT 10 (MMXU3.RP): OptFlds 0
REPORT 10 (MMXU3.RP): BufTm 0
REPORT 10 (MMXU3.RP): TrgOps 0
REPORT 10 (MMXU3.RP): IntgPd 0
REPORT 11 (MMXU4.BR): RptID
REPORT 11 (MMXU4.BR): OptFlds 0
REPORT 11 (MMXU4.BR): BufTm 0
REPORT 11 (MMXU4.BR): TrgOps 0
REPORT 11 (MMXU4.BR): IntgPd 0
REPORT 12 (MMXU4.RP): RptID
REPORT 12 (MMXU4.RP): OptFlds 0
REPORT 12 (MMXU4.RP): BufTm 0
REPORT 12 (MMXU4.RP): TrgOps 0
REPORT 12 (MMXU4.RP): IntgPd 0

XCBR CONFIGURATION
XCBR1 ST.Loc Operand OFF
XCBR2 ST.Loc Operand OFF
XCBR3 ST.Loc Operand OFF
XCBR4 ST.Loc Operand OFF
Clear XCBR1 OpCnt No
Clear XCBR2 OpCnt No
Clear XCBR3 OpCnt No
Clear XCBR4 OpCnt No

XSWI CONFIGURATION
XSWI1 ST.Loc Operand OFF
XSWI2 ST.Loc Operand OFF
XSWI3 ST.Loc Operand OFF
XSWI4 ST.Loc Operand OFF
XSWI5 ST.Loc Operand OFF
XSWI6 ST.Loc Operand OFF
XSWI7 ST.Loc Operand OFF
XSWI8 ST.Loc Operand OFF
XSWI9 ST.Loc Operand OFF
XSWI10 ST.Loc Operand OFF
XSWI11 ST.Loc Operand OFF
XSWI12 ST.Loc Operand OFF
XSWI13 ST.Loc Operand OFF
XSWI14 ST.Loc Operand OFF
XSWI15 ST.Loc Operand OFF
XSWI16 ST.Loc Operand OFF
Clear XSWI1 OpCnt No
Clear XSWI2 OpCnt No
Clear XSWI3 OpCnt No
Clear XSWI4 OpCnt No
Clear XSWI5 OpCnt No
Clear XSWI6 OpCnt No
Clear XSWI7 OpCnt No
Clear XSWI8 OpCnt No
Clear XSWI9 OpCnt No
Clear XSWI10 OpCnt No
Clear XSWI11 OpCnt No
Clear XSWI12 OpCnt No
Clear XSWI13 OpCnt No
Clear XSWI14 OpCnt No
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 9

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

XSWI CONFIGURATION (continued from last page)


Clear XSWI15 OpCnt No
Clear XSWI16 OpCnt No

HTTP
HTTP TCP Port Number 80

TFTP
TFTP Main UDP Port Number 69
TFTP Data UDP Port Number 1 0
TFTP Data UDP Port Number 2 0

EGD PROTOCOL
FAST PRODUCER EXCHANGE
Function Enabled
Destination 192.168.101.255
Data Rate 50 ms
Data Item 1 5416
Data Item 2 5417
Data Item 3 5418
Data Item 4 5419
Data Item 5 5420
Data Item 6 5421
Data Item 7 0
Data Item 8 0
Data Item 9 0
Data Item 10 0
Data Item 11 0
Data Item 12 0
Data Item 13 0
Data Item 14 0
Data Item 15 0
Data Item 16 0
Data Item 17 0
Data Item 18 0
Data Item 19 0
Data Item 20 0

REAL TIME CLOCK


IRIG-B Signal Type DC Shift
Real Time Clock Events Enabled
Time Zone Offset 0.0 hr
DST Function Enabled
DST Start Month January
DST Start Day Sunday
DST Start Day Instance First
DST Start Hour 2
DST Stop Month January
DST Stop Day Sunday
DST Stop Day Instance First
DST Stop Hour 2

OSCILLOGRAPHY
Number Of Records 15
Trigger Mode Automatic Overwrite
Trigger Position 25 %
Trigger Source Osc Initiate On (VO8)
AC Input Waveforms 32 samples/cycle
Digital Channel 1 52a CB 52G On(H7a)
Digital Channel 2 52b CB 52G On(H7c)
Digital Channel 3 52a CB 52G Off(H7a)
Digital Channel 4 52b CB 52G Off(H7c)
Digital Channel 5 86G Trip On (VO71)
Digital Channel 6 52G Trip On (VO72)
Digital Channel 7 All Trips On (VO73)
Digital Channel 8 H1 Operate On (VO21)
Digital Channel 9 H2 Operate On (VO22)
Digital Channel 10 H3 Operate On (VO23)
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 10

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

OSCILLOGRAPHY (continued from last page)


Digital Channel 11 H4 Operate On (VO24)
Digital Channel 12 H5 Operate On (VO25)
Digital Channel 13 H6 Operate On (VO26)
Digital Channel 14 49/A Oper On (VO42)
Digital Channel 15 24/A Oper On (VO43)
Digital Channel 16 46/A Oper On (VO44)
Digital Channel 17 32/A Oper On (VO45)
Digital Channel 18 81O/A Oper On (VO46)
Digital Channel 19 81U/A Oper On (VO47)
Digital Channel 20 VTFF Operate On (VO49)
Digital Channel 21 87S/T Oper On (VO50)
Digital Channel 22 51P/T Oper On (VO51)
Digital Channel 23 50P/T Oper On (VO52)
Digital Channel 24 64G/T Oper On (VO53)
Digital Channel 25 50/27T Oper On (VO54)
Digital Channel 26 50OFF/T Oper On (VO55)
Digital Channel 27 40/T Oper On (VO56)
Digital Channel 28 46/T Oper On (VO57)
Digital Channel 29 32/T Oper On (VO58)
Digital Channel 30 24/T Oper On (VO59)
Digital Channel 31 27P/T Oper On (VO60)
Digital Channel 32 59P/T Oper On (VO61)
Digital Channel 33 81U/T Oper On (VO62)
Digital Channel 34 81O/T Oper On (VO63)
Digital Channel 35 21 Oper On (VO64)
Digital Channel 36 STATOR DIFF OP A
Digital Channel 37 STATOR DIFF OP B
Digital Channel 38 STATOR DIFF OP C
Digital Channel 39 PHASE TOC1 OP A
Digital Channel 40 PHASE TOC1 OP B
Digital Channel 41 PHASE TOC1 OP C
Digital Channel 42 PHASE IOC1 OP A
Digital Channel 43 PHASE IOC1 OP B
Digital Channel 44 PHASE IOC1 OP C
Digital Channel 45 ACCDNT ENRG OP
Digital Channel 46 GEN UNBAL STG1 OP
Digital Channel 47 GEN UNBAL STG2 OP
Digital Channel 48 AUX OV 1 OP
Digital Channel 49 PHASE UV1 OP
Digital Channel 50 PHASE OV1 OP
Digital Channel 51 VOLTS PER HERTZ 1 OP
Digital Channel 52 VOLTS PER HERTZ 2 OP
Digital Channel 53 LOSS EXCIT STG1 OP
Digital Channel 54 LOSS EXCIT STG2 OP
Digital Channel 55 UNDERFREQ 1 OP
Digital Channel 56 UNDERFREQ 2 OP
Digital Channel 57 UNDERFREQ 3 OP
Digital Channel 58 OVERFREQ 1 OP
Digital Channel 59 OVERFREQ 2 OP
Digital Channel 60 OVERFREQ 3 OP
Digital Channel 61 DIR POWER 1 STG1 OP
Digital Channel 62 DIR POWER 2 STG1 OP
Digital Channel 63 PH DIST Z2 OP
Analog Channel 1 SRC1 Ia Mag
Analog Channel 2 SRC1 Ib Mag
Analog Channel 3 SRC1 Ic Mag
Analog Channel 4 SRC2 Ia Mag
Analog Channel 5 SRC2 Ib Mag
Analog Channel 6 SRC2 Ic Mag
Analog Channel 7 SRC1 Vab Mag
Analog Channel 8 SRC1 Vbc Mag
Analog Channel 9 SRC1 Vca Mag
Analog Channel 10 SRC3 Vx Mag
Analog Channel 11 SRC1 I_1 Mag
Analog Channel 12 SRC1 I_2 Mag
Analog Channel 13 SRC2 I_1 Mag
Analog Channel 14 SRC2 I_2 Mag
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 11

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

OSCILLOGRAPHY (continued from last page)


Analog Channel 15 SRC1 V_1 Mag
Analog Channel 16 Tracking Frequency

DATA LOGGER
Data Logger Mode Continuous
Data Logger Trigger OFF
Rate 60000 msec
Channel 1 SRC1 Ia RMS
Channel 2 SRC1 Ib RMS
Channel 3 SRC1 Ic RMS
Channel 4 SRC2 Ia RMS
Channel 5 SRC2 Ib RMS
Channel 6 SRC2 Ic RMS
Channel 7 SRC1 Vab RMS
Channel 8 SRC1 Vbc RMS
Channel 9 SRC1 Vca RMS
Channel 10 SRC3 Vx RMS
Channel 11 SRC1 I_1 Mag
Channel 12 SRC1 V_1 Mag
Channel 13 SRC1 P
Channel 14 SRC1 Q
Channel 15 SRC1 S
Channel 16 Tracking Frequency

USER-PROGRAMMABLE LEDS
LED TEST
Function Enabled
Control CONTROL PUSHBUTTON 3 ON

TRIP AND ALARMS LEDS


Trip LED Input Trip LED In On (VO7)
Alarm LED Input Alrm LED In On (VO6)

USER PROGRAMMABLE LEDS


LED 1: OPERAND Gen C/B Open On (VO11)
LED 1: TYPE Self-Reset
LED 2: OPERAND Gen C/B Clos On (VO12)
LED 2: TYPE Self-Reset
LED 3: OPERAND Gen C/B Trbl On (VO14)
LED 3: TYPE Self-Reset
LED 12: OPERAND SETTING GROUP ACT 1
LED 12: TYPE Self-Reset
LED 13: OPERAND H1 Operate On (VO21)
LED 13: TYPE Latched
LED 14: OPERAND H2 Operate On (VO22)
LED 14: TYPE Latched
LED 15: OPERAND H3 Operate On (VO23)
LED 15: TYPE Latched
LED 16: OPERAND H4 Operate On (VO24)
LED 16: TYPE Latched
LED 17: OPERAND W8 Operate On (VO88)
LED 17: TYPE Latched
LED 18: OPERAND W7 Operate On (VO87)
LED 18: TYPE Latched
LED 23: OPERAND W1 Operate On (VO81)
LED 23: TYPE Latched
LED 24: OPERAND W2 Operate On (VO82)
LED 24: TYPE Self-Reset
LED 25: OPERAND 49/A Oper On (VO42)
LED 25: TYPE Self-Reset
LED 26: OPERAND 24/A Oper On (VO43)
LED 26: TYPE Self-Reset
LED 27: OPERAND 46/A Oper On (VO44)
LED 27: TYPE Self-Reset
LED 31: OPERAND VTFF Operate On (VO49)
LED 31: TYPE Self-Reset
LED 34: OPERAND 81U/T Oper On (VO62)
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 12

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

USER PROGRAMMABLE LEDS (continued from last page)


LED 34: TYPE Latched
LED 35: OPERAND 81O/T Oper On (VO63)
LED 35: TYPE Latched
LED 36: OPERAND 21-78 Oper On (VO66)
LED 36: TYPE Latched
LED 37: OPERAND 87S/T Oper On (VO50)
LED 37: TYPE Latched
LED 38: OPERAND 51P/T Oper On (VO51)
LED 38: TYPE Latched
LED 40: OPERAND 64G/T Oper On (VO53)
LED 40: TYPE Latched
LED 41: OPERAND 40/T Oper On (VO56)
LED 41: TYPE Latched
LED 42: OPERAND 46/T Oper On (VO57)
LED 42: TYPE Latched
LED 43: OPERAND 32/T Oper On (VO58)
LED 43: TYPE Latched
LED 44: OPERAND 24/T Oper On (VO59)
LED 44: TYPE Latched
LED 45: OPERAND 27P/T Oper On (VO60)
LED 45: TYPE Latched
LED 46: OPERAND 59P/T Oper On (VO61)
LED 46: TYPE Latched
LED 47: OPERAND 50/27T Oper On (VO54)
LED 47: TYPE Latched

USER-PROGRAMMABLE SELF TESTS


Battery Fail Function Enabled

CONTROL PUSHBUTTONS
CPB 1: Function Enabled
CPB 1: Events Disabled
CPB 3: Function Enabled
CPB 3: Events Disabled

USER-DEFINABLE DISPLAYS
USER DISPLAY 1: Top Line MSila G3 G60
USER DISPLAY 1: Bottom Line Rev 0 13-June 2011
USER DISPLAY 1: Item 1 0
USER DISPLAY 1: Item 2 0
USER DISPLAY 1: Item 3 0
USER DISPLAY 1: Item 4 0
USER DISPLAY 1: Item 5 0
USER DISPLAY 2: Top Line Ia: ~
USER DISPLAY 2: Bottom Line Ib: ~
USER DISPLAY 2: Item 1 6144
USER DISPLAY 2: Item 2 6146
USER DISPLAY 2: Item 3 0
USER DISPLAY 2: Item 4 0
USER DISPLAY 2: Item 5 0
USER DISPLAY 3: Top Line Ic: ~
USER DISPLAY 3: Bottom Line
USER DISPLAY 3: Item 1 6148
USER DISPLAY 3: Item 2 0
USER DISPLAY 3: Item 3 0
USER DISPLAY 3: Item 4 0
USER DISPLAY 3: Item 5 0
USER DISPLAY 4: Top Line Vab: ~
USER DISPLAY 4: Bottom Line Vbc: ~
USER DISPLAY 4: Item 1 6671
USER DISPLAY 4: Item 2 6673
USER DISPLAY 4: Item 3 0
USER DISPLAY 4: Item 4 0
USER DISPLAY 4: Item 5 0
USER DISPLAY 5: Top Line Vca: ~
USER DISPLAY 5: Bottom Line
USER DISPLAY 5: Item 1 6675
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 13

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

USER-DEFINABLE DISPLAYS (continued from last page)


USER DISPLAY 5: Item 2 0
USER DISPLAY 5: Item 3 0
USER DISPLAY 5: Item 4 0
USER DISPLAY 5: Item 5 0
USER DISPLAY 6: Top Line P: ~
USER DISPLAY 6: Bottom Line Q: ~
USER DISPLAY 6: Item 1 7168
USER DISPLAY 6: Item 2 7176
USER DISPLAY 6: Item 3 0
USER DISPLAY 6: Item 4 0
USER DISPLAY 6: Item 5 0
USER DISPLAY 7: Top Line S: ~
USER DISPLAY 7: Bottom Line pf: ~
USER DISPLAY 7: Item 1 7184
USER DISPLAY 7: Item 2 7192
USER DISPLAY 7: Item 3 0
USER DISPLAY 7: Item 4 0
USER DISPLAY 7: Item 5 0
Invoke and Scroll CONTROL PUSHBUTTON 1 ON

INSTALLATION
Relay Name MSila G3 G60

SYSTEM SETUP
AC INPUTS
CURRENT
CT F1: Phase CT Primary 7500 A
CT F1: Phase CT Secondary 1A
CT F1: Ground CT Primary 7500 A
CT F1: Ground CT Secondary 1A
CT M1: Phase CT Primary 7500 A
CT M1: Phase CT Secondary 1A
CT M1: Ground CT Primary 7500 A
CT M1: Ground CT Secondary 1A

VOLTAGE
VT F5: Phase VT Connection Wye
VT F5: Phase VT Secondary 57.7 V
VT F5: Phase VT Ratio 115.00 :1
VT F5: Auxiliary VT Connection Vn
VT F5: Auxiliary VT Secondary 100.0 V
VT F5: Auxiliary VT Ratio 66.40 :1
VT M5: Phase VT Connection Wye
VT M5: Phase VT Secondary 57.7 V
VT M5: Phase VT Ratio 115.00 :1
VT M5: Auxiliary VT Connection Vn
VT M5: Auxiliary VT Secondary 100.0 V
VT M5: Auxiliary VT Ratio 66.40 :1

POWER SYSTEM
Nominal Frequency 50 Hz
Phase Rotation ABC
Reverse Phase Rotation OFF
Frequency And Phase Reference Line (SRC 1)
Frequency Tracking Function Enabled

SIGNAL SOURCES
SOURCE 1: Name Line
SOURCE 1: Phase CT F1
SOURCE 1: Ground CT None
SOURCE 1: Phase VT F5
SOURCE 1: Auxiliary VT None
SOURCE 2: Name Neut
SOURCE 2: Phase CT M1
SOURCE 2: Ground CT None
SOURCE 2: Phase VT None
SOURCE 2: Auxiliary VT None
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 14

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

SIGNAL SOURCES (continued from last page)


SOURCE 3: Name Gnd
SOURCE 3: Phase CT None
SOURCE 3: Ground CT None
SOURCE 3: Phase VT F5
SOURCE 3: Auxiliary VT F5
SOURCE 4: Name Bus V
SOURCE 4: Phase CT None
SOURCE 4: Ground CT None
SOURCE 4: Phase VT M5
SOURCE 4: Auxiliary VT None

BREAKERS
Breaker 1 Function Enabled
Breaker 1 Push Button Control Disabled
Breaker 1 Name CB 52G
Breaker 1 Mode 3-Pole
Breaker 1 Open OFF
Breaker 1 Block Open OFF
Breaker 1 Close OFF
Breaker 1 Block Close OFF
Breaker 1 Phase A/3-Pole Closed 52a CB 52G On(H7a)
Breaker 1 Phase A/3-Pole Opened 52b CB 52G On(H7c)
Breaker 1 Phase B Closed OFF
Breaker 1 Phase B Opened OFF
Breaker 1 Phase C Closed OFF
Breaker 1 Phase C Opened OFF
Breaker 1 Toperate 0.070 s
Breaker 1 External Alarm OFF
Breaker 1 Alarm Delay 0.000 s
Breaker 1 Manual Close Recal Time 0.000 s
Breaker 1 Out Of Service OFF
Breaker 1 Events Enabled

FLEXLOGIC
FLEXLOGIC EQUATION EDITOR
FlexLogic Entry 1 52a CB 52G On(H7a)
FlexLogic Entry 2 52b CB 52G On(H7c)
FlexLogic Entry 3 XOR
FlexLogic Entry 4 = Gen C/B OK (VO13)
FlexLogic Entry 5 Gen C/B OK On (VO13)
FlexLogic Entry 6 NOT
FlexLogic Entry 7 TIMER 11
FlexLogic Entry 8 = Gen C/B Trbl (VO14)
FlexLogic Entry 9 52a CB 52G On(H7a)
FlexLogic Entry 10 Gen C/B OK On (VO13)
FlexLogic Entry 11 AND(2)
FlexLogic Entry 12 = Gen C/B Clos (VO12)
FlexLogic Entry 13 52b CB 52G On(H7c)
FlexLogic Entry 14 Gen C/B OK On (VO13)
FlexLogic Entry 15 AND(2)
FlexLogic Entry 16 = Gen C/B Open (VO11)
FlexLogic Entry 17 RESET OP (PUSHBUTTON)
FlexLogic Entry 18 NOT
FlexLogic Entry 19 = Reset Sealin (VO9)
FlexLogic Entry 20 SRC1 VT FUSE FAIL OP
FlexLogic Entry 21 SRC4 VT FUSE FAIL OP
FlexLogic Entry 22 OR(2)
FlexLogic Entry 23 = VTFF Operate (VO49)
FlexLogic Entry 24 SRC1 VT FUSE FAIL OP
FlexLogic Entry 25 52a CB 52G Off(H7a)
FlexLogic Entry 26 52b CB 52G On(H7c)
FlexLogic Entry 27 AND(2)
FlexLogic Entry 28 OR(2)
FlexLogic Entry 29 = Blk Enable (VO4)
FlexLogic Entry 30 ANY MAJOR ERROR
FlexLogic Entry 31 ANY MINOR ERROR
FlexLogic Entry 32 OR(2)
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 15

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

FLEXLOGIC EQUATION EDITOR (continued from last page)


FlexLogic Entry 33 RESET OP (PUSHBUTTON)
FlexLogic Entry 34 LATCH
FlexLogic Entry 35 = G60 Rly Fail (VO5)
FlexLogic Entry 36 STATOR DIFF OP
FlexLogic Entry 37 = 87S/T Oper (VO50)
FlexLogic Entry 38 LOSS EXCIT STG1 OP
FlexLogic Entry 39 LOSS EXCIT STG2 OP
FlexLogic Entry 40 OR(2)
FlexLogic Entry 41 = 40/T Oper (VO56)
FlexLogic Entry 42 GEN UNBAL STG1 OP
FlexLogic Entry 43 = 46/T Oper (VO57)
FlexLogic Entry 44 GEN UNBAL STG2 OP
FlexLogic Entry 45 = 46/A Oper (VO44)
FlexLogic Entry 46 DIR POWER 1 STG1 OP
FlexLogic Entry 47 = 32/T Oper (VO58)
FlexLogic Entry 48 VOLTS PER HERTZ 1 OP
FlexLogic Entry 49 VOLTS PER HERTZ 2 OP
FlexLogic Entry 50 OR(2)
FlexLogic Entry 51 = 24/T Oper (VO59)
FlexLogic Entry 52 24A (FE 4) OP
FlexLogic Entry 53 = 24/A Oper (VO43)
FlexLogic Entry 54 PHASE TOC1 OP
FlexLogic Entry 55 = 51P/T Oper (VO51)
FlexLogic Entry 56 AUX OV 1 OP
FlexLogic Entry 57 = 64G/T Oper (VO53)
FlexLogic Entry 58 OVERFREQ 2 OP
FlexLogic Entry 59 OVERFREQ 3 OP
FlexLogic Entry 60 OR(2)
FlexLogic Entry 61 = 81O/T Oper (VO63)
FlexLogic Entry 62 UNDERFREQ 1 OP
FlexLogic Entry 63 UNDERFREQ 2 OP
FlexLogic Entry 64 UNDERFREQ 3 OP
FlexLogic Entry 65 UNDERFREQ 4 OP
FlexLogic Entry 66 OR(4)
FlexLogic Entry 67 = 81U/T Oper (VO62)
FlexLogic Entry 68 PHASE UV1 OP
FlexLogic Entry 69 52b CB 52G Off(H7c)
FlexLogic Entry 70 AND(2)
FlexLogic Entry 71 = 27P/T Oper (VO60)
FlexLogic Entry 72 PHASE UV2 OP
FlexLogic Entry 73 52b CB 52G Off(H7c)
FlexLogic Entry 74 AND(2)
FlexLogic Entry 75 = 27P/A Oper (VO41)
FlexLogic Entry 76 PHASE OV1 OP
FlexLogic Entry 77 59P1AB (FE 5) OP
FlexLogic Entry 78 59P1BC (FE 6) OP
FlexLogic Entry 79 59P1CA (FE 7) OP
FlexLogic Entry 80 OR(3)
FlexLogic Entry 81 OR(2)
FlexLogic Entry 82 = 59P/T Oper (VO61)
FlexLogic Entry 83 ACCDNT ENRG OP
FlexLogic Entry 84 = 50/27T Oper (VO54)
FlexLogic Entry 85 Ia Max (FE 1) OP
FlexLogic Entry 86 Ib Max (FE 2) OP
FlexLogic Entry 87 Ic Max (FE 3) OP
FlexLogic Entry 88 OR(3)
FlexLogic Entry 89 = 49/A Oper (VO42)
FlexLogic Entry 90 PH DIST Z2 OP
FlexLogic Entry 91 = 21 Oper (VO64)
FlexLogic Entry 92 POWER SWING TRIP
FlexLogic Entry 93 = 78 Oper (VO65)
FlexLogic Entry 94 21 Oper On (VO64)
FlexLogic Entry 95 78 Oper On (VO65)
FlexLogic Entry 96 OR(2)
FlexLogic Entry 97 = 21-78 Oper (VO66)
FlexLogic Entry 98 21 Oper On (VO64)
FlexLogic Entry 99 27P/T Oper On (VO60)
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 16

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

FLEXLOGIC EQUATION EDITOR (continued from last page)


FlexLogic Entry 100 32/T Oper On (VO58)
FlexLogic Entry 101 40/T Oper On (VO56)
FlexLogic Entry 102 51P/T Oper On (VO51)
FlexLogic Entry 103 59P/T Oper On (VO61)
FlexLogic Entry 104 78 Oper On (VO65)
FlexLogic Entry 105 24/T Oper On (VO59)
FlexLogic Entry 106 64G/T Oper On (VO53)
FlexLogic Entry 107 87S/T Oper On (VO50)
FlexLogic Entry 108 OR(10)
FlexLogic Entry 109 UNDERFREQ 2 OP
FlexLogic Entry 110 UNDERFREQ 3 OP
FlexLogic Entry 111 UNDERFREQ 4 OP
FlexLogic Entry 112 OVERFREQ 2 OP
FlexLogic Entry 113 OVERFREQ 3 OP
FlexLogic Entry 114 OR(5)
FlexLogic Entry 115 Sta Trip 52G On(P1c)
FlexLogic Entry 116 T60-52G Trp1 On(H8a)
FlexLogic Entry 117 T60-52G Trp2 On(H8c)
FlexLogic Entry 118 OR(3)
FlexLogic Entry 119 OR(3)
FlexLogic Entry 120 52a CB 52G On(H7a)
FlexLogic Entry 121 AND(2)
FlexLogic Entry 122 TIMER 20
FlexLogic Entry 123 RESET OP (PUSHBUTTON)
FlexLogic Entry 124 LATCH
FlexLogic Entry 125 = 86BUT Oper (VO67)
FlexLogic Entry 126 87S/T Oper On (VO50)
FlexLogic Entry 127 51P/T Oper On (VO51)
FlexLogic Entry 128 50/27T Oper On (VO54)
FlexLogic Entry 129 59P/T Oper On (VO61)
FlexLogic Entry 130 OR(4)
FlexLogic Entry 131 TIMER 21
FlexLogic Entry 132 = H1 Operate (VO21)
FlexLogic Entry 133 64G/T Oper On (VO53)
FlexLogic Entry 134 40/T Oper On (VO56)
FlexLogic Entry 135 UNDERFREQ 2 OP
FlexLogic Entry 136 OVERFREQ 2 OP
FlexLogic Entry 137 OVERFREQ 3 OP
FlexLogic Entry 138 32/T Oper On (VO58)
FlexLogic Entry 139 78 Oper On (VO65)
FlexLogic Entry 140 T60-52G Trp1 On(H8a)
FlexLogic Entry 141 T60-52G Trp2 On(H8c)
FlexLogic Entry 142 Sta Trip 52G On(P1c)
FlexLogic Entry 143 27P/T Oper On (VO60)
FlexLogic Entry 144 24/T Oper On (VO59)
FlexLogic Entry 145 OR(12)
FlexLogic Entry 146 TIMER 22
FlexLogic Entry 147 = H2 Operate (VO22)
FlexLogic Entry 148 64G/T Oper On (VO53)
FlexLogic Entry 149 40/T Oper On (VO56)
FlexLogic Entry 150 UNDERFREQ 2 OP
FlexLogic Entry 151 OVERFREQ 2 OP
FlexLogic Entry 152 OVERFREQ 3 OP
FlexLogic Entry 153 32/T Oper On (VO58)
FlexLogic Entry 154 78 Oper On (VO65)
FlexLogic Entry 155 T60-52G Trp1 On(H8a)
FlexLogic Entry 156 T60-52G Trp2 On(H8c)
FlexLogic Entry 157 Sta Trip 52G On(P1c)
FlexLogic Entry 158 27P/T Oper On (VO60)
FlexLogic Entry 159 24/T Oper On (VO59)
FlexLogic Entry 160 OR(12)
FlexLogic Entry 161 TIMER 23
FlexLogic Entry 162 = H3 Operate (VO23)
FlexLogic Entry 163 UNDERFREQ 3 OP
FlexLogic Entry 164 UNDERFREQ 4 OP
FlexLogic Entry 165 21 Oper On (VO64)
FlexLogic Entry 166 OR(3)
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 17

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

FLEXLOGIC EQUATION EDITOR (continued from last page)


FlexLogic Entry 167 TIMER 24
FlexLogic Entry 168 = H4 Operate (VO24)
FlexLogic Entry 169 TP3 VT CB4 O On(P1a)
FlexLogic Entry 170 = H5 Operate (VO25)
FlexLogic Entry 171 27P/T Oper On (VO60)
FlexLogic Entry 172 21 Oper On (VO64)
FlexLogic Entry 173 86BUT Oper On (VO67)
FlexLogic Entry 174 OR(3)
FlexLogic Entry 175 TIMER 26
FlexLogic Entry 176 = H6 Operate (VO26)
FlexLogic Entry 177 87S/T Oper On (VO50)
FlexLogic Entry 178 = U1 Operate (VO27)
FlexLogic Entry 179 51P/T Oper On (VO51)
FlexLogic Entry 180 = U3 Operate (VO29)
FlexLogic Entry 181 40/T Oper On (VO56)
FlexLogic Entry 182 = U4 Operate (VO30)
FlexLogic Entry 183 46/T Oper On (VO57)
FlexLogic Entry 184 = U5 Operate (VO31)
FlexLogic Entry 185 32/T Oper On (VO58)
FlexLogic Entry 186 = U6 Operate (VO32)
FlexLogic Entry 187 24/T Oper On (VO59)
FlexLogic Entry 188 = U7 Operate (VO33)
FlexLogic Entry 189 27P/T Oper On (VO60)
FlexLogic Entry 190 = U8 Operate (VO34)
FlexLogic Entry 191 59P/T Oper On (VO61)
FlexLogic Entry 192 = U9 Operate (VO35)
FlexLogic Entry 193 50/27T Oper On (VO54)
FlexLogic Entry 194 = U10 Operate (VO36)
FlexLogic Entry 195 81U/T Oper On (VO62)
FlexLogic Entry 196 81O/T Oper On (VO63)
FlexLogic Entry 197 OR(2)
FlexLogic Entry 198 = U12 Operate (VO38)
FlexLogic Entry 199 64G/T Oper On (VO53)
FlexLogic Entry 200 = U13 Operate (VO39)
FlexLogic Entry 201 21-78 Oper On (VO66)
FlexLogic Entry 202 = U14 Operate (VO40)
FlexLogic Entry 203 87S/T Oper On (VO50)
FlexLogic Entry 204 51P/T Oper On (VO51)
FlexLogic Entry 205 50/27T Oper On (VO54)
FlexLogic Entry 206 46/T Oper On (VO57)
FlexLogic Entry 207 64G/T Oper On (VO53)
FlexLogic Entry 208 27P/T Oper On (VO60)
FlexLogic Entry 209 59P/T Oper On (VO61)
FlexLogic Entry 210 24/T Oper On (VO59)
FlexLogic Entry 211 40/T Oper On (VO56)
FlexLogic Entry 212 81U/T Oper On (VO62)
FlexLogic Entry 213 81O/T Oper On (VO63)
FlexLogic Entry 214 32/T Oper On (VO58)
FlexLogic Entry 215 21 Oper On (VO64)
FlexLogic Entry 216 78 Oper On (VO65)
FlexLogic Entry 217 OR(14)
FlexLogic Entry 218 = W1 Operate (VO81)
FlexLogic Entry 219 46/A Oper On (VO44)
FlexLogic Entry 220 27P/A Oper On (VO41)
FlexLogic Entry 221 24/A Oper On (VO43)
FlexLogic Entry 222 49/A Oper On (VO42)
FlexLogic Entry 223 VTFF Operate On (VO49)
FlexLogic Entry 224 G60 Rly Fail On (VO5)
FlexLogic Entry 225 OR(6)
FlexLogic Entry 226 = W2 Operate (VO82)
FlexLogic Entry 227 UNDERFREQ 2 OP
FlexLogic Entry 228 OVERFREQ 2 OP
FlexLogic Entry 229 OVERFREQ 3 OP
FlexLogic Entry 230 OR(3)
FlexLogic Entry 231 TIMER 27
FlexLogic Entry 232 = W3 Operate (VO83)
FlexLogic Entry 233 86BUT Oper On (VO67)
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 18

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

FLEXLOGIC EQUATION EDITOR (continued from last page)


FlexLogic Entry 234 TIMER 28
FlexLogic Entry 235 = W4 Operate (VO84)
FlexLogic Entry 236 64G/T Oper On (VO53)
FlexLogic Entry 237 24/T Oper On (VO59)
FlexLogic Entry 238 40/T Oper On (VO56)
FlexLogic Entry 239 UNDERFREQ 2 OP
FlexLogic Entry 240 OVERFREQ 2 OP
FlexLogic Entry 241 OVERFREQ 3 OP
FlexLogic Entry 242 78 Oper On (VO65)
FlexLogic Entry 243 86BUT Oper On (VO67)
FlexLogic Entry 244 OR(8)
FlexLogic Entry 245 TIMER 29
FlexLogic Entry 246 = W5 Operate (VO85)
FlexLogic Entry 247 21 Oper On (VO64)
FlexLogic Entry 248 86BUT Oper On (VO67)
FlexLogic Entry 249 OR(2)
FlexLogic Entry 250 TIMER 30
FlexLogic Entry 251 = W6 Operate (VO86)
FlexLogic Entry 252 27P/A Oper On (VO41)
FlexLogic Entry 253 46/T Oper On (VO57)
FlexLogic Entry 254 UNDERFREQ 1 OP
FlexLogic Entry 255 86BUT Oper On (VO67)
FlexLogic Entry 256 OVERFREQ 2 OP
FlexLogic Entry 257 OVERFREQ 3 OP
FlexLogic Entry 258 OR(2)
FlexLogic Entry 259 52LX1 Oper On(P3a)
FlexLogic Entry 260 AND(2)
FlexLogic Entry 261 OR(5)
FlexLogic Entry 262 TIMER 31
FlexLogic Entry 263 = W7 Operate (VO87)
FlexLogic Entry 264 46/T Oper On (VO57)
FlexLogic Entry 265 27P/A Oper On (VO41)
FlexLogic Entry 266 UNDERFREQ 1 OP
FlexLogic Entry 267 86BUT Oper On (VO67)
FlexLogic Entry 268 OVERFREQ 2 OP
FlexLogic Entry 269 OVERFREQ 3 OP
FlexLogic Entry 270 OR(2)
FlexLogic Entry 271 52LX1 Oper On(P3a)
FlexLogic Entry 272 AND(2)
FlexLogic Entry 273 OR(5)
FlexLogic Entry 274 TIMER 32
FlexLogic Entry 275 = W8 Operate (VO88)
FlexLogic Entry 276 87S/T Oper On (VO50)
FlexLogic Entry 277 51P/T Oper On (VO51)
FlexLogic Entry 278 64G/T Oper On (VO53)
FlexLogic Entry 279 50/27T Oper On (VO54)
FlexLogic Entry 280 40/T Oper On (VO56)
FlexLogic Entry 281 46/T Oper On (VO57)
FlexLogic Entry 282 32/T Oper On (VO58)
FlexLogic Entry 283 24/T Oper On (VO59)
FlexLogic Entry 284 27P/T Oper On (VO60)
FlexLogic Entry 285 59P/T Oper On (VO61)
FlexLogic Entry 286 81U/T Oper On (VO62)
FlexLogic Entry 287 81O/T Oper On (VO63)
FlexLogic Entry 288 21 Oper On (VO64)
FlexLogic Entry 289 78 Oper On (VO65)
FlexLogic Entry 290 OR(14)
FlexLogic Entry 291 = Trip LED In (VO7)
FlexLogic Entry 292 87S/T Oper On (VO50)
FlexLogic Entry 293 POSITIVE ONE SHOT
FlexLogic Entry 294 51P/T Oper On (VO51)
FlexLogic Entry 295 POSITIVE ONE SHOT
FlexLogic Entry 296 64G/T Oper On (VO53)
FlexLogic Entry 297 POSITIVE ONE SHOT
FlexLogic Entry 298 50/27T Oper On (VO54)
FlexLogic Entry 299 POSITIVE ONE SHOT
FlexLogic Entry 300 40/T Oper On (VO56)
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 19

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

FLEXLOGIC EQUATION EDITOR (continued from last page)


FlexLogic Entry 301 POSITIVE ONE SHOT
FlexLogic Entry 302 46/T Oper On (VO57)
FlexLogic Entry 303 POSITIVE ONE SHOT
FlexLogic Entry 304 32/T Oper On (VO58)
FlexLogic Entry 305 POSITIVE ONE SHOT
FlexLogic Entry 306 24/T Oper On (VO59)
FlexLogic Entry 307 POSITIVE ONE SHOT
FlexLogic Entry 308 27P/T Oper On (VO60)
FlexLogic Entry 309 POSITIVE ONE SHOT
FlexLogic Entry 310 59P/T Oper On (VO61)
FlexLogic Entry 311 POSITIVE ONE SHOT
FlexLogic Entry 312 81U/T Oper On (VO62)
FlexLogic Entry 313 POSITIVE ONE SHOT
FlexLogic Entry 314 81O/T Oper On (VO63)
FlexLogic Entry 315 POSITIVE ONE SHOT
FlexLogic Entry 316 21 Oper On (VO64)
FlexLogic Entry 317 POSITIVE ONE SHOT
FlexLogic Entry 318 78 Oper On (VO65)
FlexLogic Entry 319 POSITIVE ONE SHOT
FlexLogic Entry 320 OR(14)
FlexLogic Entry 321 = Osc Initiate (VO8)
FlexLogic Entry 322 46/A Oper On (VO44)
FlexLogic Entry 323 27P/A Oper On (VO41)
FlexLogic Entry 324 24/A Oper On (VO43)
FlexLogic Entry 325 49/A Oper On (VO42)
FlexLogic Entry 326 VTFF Operate On (VO49)
FlexLogic Entry 327 G60 Rly Fail On (VO5)
FlexLogic Entry 328 OR(6)
FlexLogic Entry 329 = Alrm LED In (VO6)
FlexLogic Entry 330 END

FLEXLOGIC TIMERS
Timer 11: Type millisecond
Timer 11: Pickup Delay 100
Timer 11: Dropout Delay 0
Timer 20: Type millisecond
Timer 20: Pickup Delay 1000
Timer 20: Dropout Delay 0
Timer 21: Type millisecond
Timer 21: Pickup Delay 0
Timer 21: Dropout Delay 100
Timer 22: Type millisecond
Timer 22: Pickup Delay 0
Timer 22: Dropout Delay 100
Timer 23: Type millisecond
Timer 23: Pickup Delay 0
Timer 23: Dropout Delay 100
Timer 24: Type millisecond
Timer 24: Pickup Delay 0
Timer 24: Dropout Delay 100
Timer 26: Type millisecond
Timer 26: Pickup Delay 0
Timer 26: Dropout Delay 100
Timer 27: Type millisecond
Timer 27: Pickup Delay 0
Timer 27: Dropout Delay 100
Timer 28: Type millisecond
Timer 28: Pickup Delay 0
Timer 28: Dropout Delay 100
Timer 29: Type millisecond
Timer 29: Pickup Delay 0
Timer 29: Dropout Delay 100
Timer 30: Type millisecond
Timer 30: Pickup Delay 0
Timer 30: Dropout Delay 100
Timer 31: Type millisecond
Timer 31: Pickup Delay 0
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 20

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

FLEXLOGIC TIMERS (continued from last page)


Timer 31: Dropout Delay 100
Timer 32: Type millisecond
Timer 32: Pickup Delay 0
Timer 32: Dropout Delay 100

FLEXELEMENTS
FLEXELEMENTS 1: Function Enabled
FLEXELEMENTS 1: Name Ia Max
FLEXELEMENTS 1: InputPlus SRC1 Ia RMS
FLEXELEMENTS 1: InputMinus OFF
FLEXELEMENTS 1: InputMode ABSOLUTE
FLEXELEMENTS 1: Compare Mode LEVEL
FLEXELEMENTS 1: Direction Type OVER
FLEXELEMENTS 1: Pickup 0.977 pu
FLEXELEMENTS 1: Hysteresis 3.0 %
FLEXELEMENTS 1: DeltaTUnits Milliseconds
FLEXELEMENTS 1: DeltaT 20
FLEXELEMENTS 1: Pickup Delay 5.000 s
FLEXELEMENTS 1: Reset Delay 0.100 s
FLEXELEMENTS 1: Block OFF
FLEXELEMENTS 1: Target Self-reset
FLEXELEMENTS 1: Events Enabled
FLEXELEMENTS 2: Function Enabled
FLEXELEMENTS 2: Name Ib Max
FLEXELEMENTS 2: InputPlus SRC1 Ib RMS
FLEXELEMENTS 2: InputMinus OFF
FLEXELEMENTS 2: InputMode ABSOLUTE
FLEXELEMENTS 2: Compare Mode LEVEL
FLEXELEMENTS 2: Direction Type OVER
FLEXELEMENTS 2: Pickup 0.977 pu
FLEXELEMENTS 2: Hysteresis 3.0 %
FLEXELEMENTS 2: DeltaTUnits Milliseconds
FLEXELEMENTS 2: DeltaT 20
FLEXELEMENTS 2: Pickup Delay 5.000 s
FLEXELEMENTS 2: Reset Delay 0.100 s
FLEXELEMENTS 2: Block OFF
FLEXELEMENTS 2: Target Self-reset
FLEXELEMENTS 2: Events Enabled
FLEXELEMENTS 3: Function Enabled
FLEXELEMENTS 3: Name Ic Max
FLEXELEMENTS 3: InputPlus SRC1 Ic RMS
FLEXELEMENTS 3: InputMinus OFF
FLEXELEMENTS 3: InputMode ABSOLUTE
FLEXELEMENTS 3: Compare Mode LEVEL
FLEXELEMENTS 3: Direction Type OVER
FLEXELEMENTS 3: Pickup 0.977 pu
FLEXELEMENTS 3: Hysteresis 3.0 %
FLEXELEMENTS 3: DeltaTUnits Milliseconds
FLEXELEMENTS 3: DeltaT 20
FLEXELEMENTS 3: Pickup Delay 5.000 s
FLEXELEMENTS 3: Reset Delay 0.100 s
FLEXELEMENTS 3: Block OFF
FLEXELEMENTS 3: Target Self-reset
FLEXELEMENTS 3: Events Enabled
FLEXELEMENTS 4: Function Enabled
FLEXELEMENTS 4: Name 24A
FLEXELEMENTS 4: InputPlus Volts Per Hertz 1
FLEXELEMENTS 4: InputMinus OFF
FLEXELEMENTS 4: InputMode ABSOLUTE
FLEXELEMENTS 4: Compare Mode LEVEL
FLEXELEMENTS 4: Direction Type OVER
FLEXELEMENTS 4: Pickup 1.070 pu
FLEXELEMENTS 4: Hysteresis 3.0 %
FLEXELEMENTS 4: DeltaTUnits Milliseconds
FLEXELEMENTS 4: DeltaT 20
FLEXELEMENTS 4: Pickup Delay 10.000 s
FLEXELEMENTS 4: Reset Delay 0.000 s
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 21

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

FLEXELEMENTS (continued from last page)


FLEXELEMENTS 4: Block OFF
FLEXELEMENTS 4: Target Self-reset
FLEXELEMENTS 4: Events Enabled
FLEXELEMENTS 5: Function Enabled
FLEXELEMENTS 5: Name 59P1AB
FLEXELEMENTS 5: InputPlus SRC1 Vab RMS
FLEXELEMENTS 5: InputMinus OFF
FLEXELEMENTS 5: InputMode ABSOLUTE
FLEXELEMENTS 5: Compare Mode LEVEL
FLEXELEMENTS 5: Direction Type OVER
FLEXELEMENTS 5: Pickup 2.078 pu
FLEXELEMENTS 5: Hysteresis 3.0 %
FLEXELEMENTS 5: DeltaTUnits Milliseconds
FLEXELEMENTS 5: DeltaT 20
FLEXELEMENTS 5: Pickup Delay 3.600 s
FLEXELEMENTS 5: Reset Delay 0.100 s
FLEXELEMENTS 5: Block OFF
FLEXELEMENTS 5: Target Latched
FLEXELEMENTS 5: Events Enabled
FLEXELEMENTS 6: Function Enabled
FLEXELEMENTS 6: Name 59P1BC
FLEXELEMENTS 6: InputPlus SRC1 Vbc RMS
FLEXELEMENTS 6: InputMinus OFF
FLEXELEMENTS 6: InputMode ABSOLUTE
FLEXELEMENTS 6: Compare Mode LEVEL
FLEXELEMENTS 6: Direction Type OVER
FLEXELEMENTS 6: Pickup 2.078 pu
FLEXELEMENTS 6: Hysteresis 3.0 %
FLEXELEMENTS 6: DeltaTUnits Milliseconds
FLEXELEMENTS 6: DeltaT 20
FLEXELEMENTS 6: Pickup Delay 3.600 s
FLEXELEMENTS 6: Reset Delay 0.100 s
FLEXELEMENTS 6: Block OFF
FLEXELEMENTS 6: Target Latched
FLEXELEMENTS 6: Events Enabled
FLEXELEMENTS 7: Function Enabled
FLEXELEMENTS 7: Name 59P1CA
FLEXELEMENTS 7: InputPlus SRC1 Vca RMS
FLEXELEMENTS 7: InputMinus OFF
FLEXELEMENTS 7: InputMode ABSOLUTE
FLEXELEMENTS 7: Compare Mode LEVEL
FLEXELEMENTS 7: Direction Type OVER
FLEXELEMENTS 7: Pickup 2.078 pu
FLEXELEMENTS 7: Hysteresis 3.0 %
FLEXELEMENTS 7: DeltaTUnits Milliseconds
FLEXELEMENTS 7: DeltaT 20
FLEXELEMENTS 7: Pickup Delay 3.600 s
FLEXELEMENTS 7: Reset Delay 0.100 s
FLEXELEMENTS 7: Block OFF
FLEXELEMENTS 7: Target Latched
FLEXELEMENTS 7: Events Enabled

GROUPED ELEMENTS
GROUP 1
DISTANCE
DISTANCE [GROUP 1]
Source Line (SRC 1)
Memory Duration 10 cycles
Force Self-Polar OFF
Force Mem-Polar OFF

PHASE DISTANCE [GROUP 1]


PHASE DISTANCE Z2: Function Enabled
PHASE DISTANCE Z2: Direction Forward
PHASE DISTANCE Z2: Shape Mho
PHASE DISTANCE Z2: Xfmr Vol Connection Dy1
PHASE DISTANCE Z2: Xfmr Curr Connection Dy1
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 22

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

PHASE DISTANCE [GROUP 1] (continued from last page)


PHASE DISTANCE Z2: Reach 10.02 ohms
PHASE DISTANCE Z2: RCA 89 deg
PHASE DISTANCE Z2: Rev Reach 10.02 ohms
PHASE DISTANCE Z2: Rev Reach RCA 89 deg
PHASE DISTANCE Z2: Comp Limit 90 deg
PHASE DISTANCE Z2: DIR RCA 89 deg
PHASE DISTANCE Z2: DIR Comp Limit 90 deg
PHASE DISTANCE Z2: Quad Right Blinder 10.00 ohms
PHASE DISTANCE Z2: Quad Right Blinder RCA 85 deg
PHASE DISTANCE Z2: Quad Left Blinder 10.00 ohms
PHASE DISTANCE Z2: Quad Left Blinder RCA 85 deg
PHASE DISTANCE Z2: Supervision 0.849 pu
PHASE DISTANCE Z2: Volt Level 0.000 pu
PHASE DISTANCE Z2: Delay 0.600 s
PHASE DISTANCE Z2: Block SRC1 VT FUSE FAIL OP
PHASE DISTANCE Z2: Target Latched
PHASE DISTANCE Z2: Events Enabled

POWER SWING DETECT [GROUP 1]


Function Enabled
Source Line (SRC 1)
Shape Mho Shape
Mode Two Step
Supv 0.600 pu
Fwd Reach 13.66 ohms
Quad Fwd Mid 13.66 ohms
Quad Fwd Out 13.66 ohms
Fwd Rca 89 deg
Rev Reach 33.04 ohms
Quad Rev Mid 33.04 ohms
Quad Rev Out 33.04 ohms
Rev Rca 89 deg
Outer Limit Angle 120 deg
Middle Limit Angle 90 deg
Inner Limit Angle 60 deg
Outer Rgt Bld 40.08 ohms
Outer Lft Bld 40.80 ohms
Midle Rgt Bld 100.00 ohms
Midle Lft Bld 100.00 ohms
Inner Rgt Bld 13.36 ohms
Inner Lft Bld 13.60 ohms
Delay 1 Pickup 0.030 s
Delay 1 Reset 0.050 s
Delay 2 Pickup 0.017 s
Delay 3 Pickup 0.009 s
Delay 4 Pickup 0.017 s
Seal-In Delay 0.400 s
Trip Mode Delayed
Block SRC1 VT FUSE FAIL OP
Target Latched
Event Enabled

STATOR DIFFERENTIAL [GROUP 1]


Function Enabled
Line End Source Line (SRC 1)
Neutral End Source Neut (SRC 2)
Pickup 0.060 pu
Slope 1 10 %
Break 1 1.15 pu
Slope 2 20 %
Break 2 30.00 pu
Block OFF
Targets Latched
Events Enabled

PHASE CURRENT
PHASE TOC [GROUP 1]
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 23

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

PHASE TOC [GROUP 1] (continued from last page)


PHASE TOC1: Function Enabled
PHASE TOC1: Signal Source Line (SRC 1)
PHASE TOC1: Input RMS
PHASE TOC1: Pickup 1.189 pu
PHASE TOC1: Curve IEEE Mod Inv
PHASE TOC1: TD Multiplier 0.42
PHASE TOC1: Reset Timed
PHASE TOC1: Voltage Restraint Enabled
PHASE TOC1: Block A SRC1 VT FUSE FAIL OP
PHASE TOC1: Block B SRC1 VT FUSE FAIL OP
PHASE TOC1: Block C SRC1 VT FUSE FAIL OP
PHASE TOC1: Target Latched
PHASE TOC1: Events Enabled

GENERATOR UNBALANCE [GROUP 1]


Function Enabled
Source Line (SRC 1)
Inom 0.849 pu
Stage 1 Pickup 6.40 %
Stage 1 K-Value 8.00
Stage 1 Tmin 0.010 s
Stage 1 Tmax 120.0 s
Stage 1 K-Reset 900.0 s
Stage 2 Pickup 4.48 %
Stage 2 Pickup Delay 6.0 s
Block OFF
Target Latched
Events Enabled

VOLTAGE ELEMENTS
PHASE UV [GROUP 1]
PHASE UV1: Function Enabled
PHASE UV1: Signal Source Line (SRC 1)
PHASE UV1: Mode Phase to Phase
PHASE UV1: Pickup 0.720 pu
PHASE UV1: Curve Definite Time
PHASE UV1: Delay 2.80 s
PHASE UV1: Minimum Voltage 0.000 pu
PHASE UV1: Block Blk Enable On (VO4)
PHASE UV1: Target Latched
PHASE UV1: Events Enabled
PHASE UV2: Function Enabled
PHASE UV2: Signal Source Line (SRC 1)
PHASE UV2: Mode Phase to Phase
PHASE UV2: Pickup 0.720 pu
PHASE UV2: Curve Definite Time
PHASE UV2: Delay 2.50 s
PHASE UV2: Minimum Voltage 0.000 pu
PHASE UV2: Block Blk Enable On (VO4)
PHASE UV2: Target Self-reset
PHASE UV2: Events Enabled

PHASE OV [GROUP 1]
PHASE OV1: Function Enabled
PHASE OV1: Source Line (SRC 1)
PHASE OV1: Pickup 1.300 pu
PHASE OV1: Delay 0.00 s
PHASE OV1: Reset Delay 0.10 s
PHASE OV1: Block OFF
PHASE OV1: Target Latched
PHASE OV1: Events Enabled

AUXILIARY OV [GROUP 1]
AUXILIARY OV 1: Function Enabled
AUXILIARY OV 1: Source Gnd (SRC 3)
AUXILIARY OV 1: Pickup 0.040 pu
AUXILIARY OV 1: Pickup Delay 0.28 s
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 24

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

AUXILIARY OV [GROUP 1] (continued from last page)


AUXILIARY OV 1: Reset Delay 0.10 s
AUXILIARY OV 1: Block OFF
AUXILIARY OV 1: Target Latched
AUXILIARY OV 1: Events Enabled

VOLTS PER HERTZ [GROUP 1]


VOLTS PER HERTZ 1: Function Enabled
VOLTS PER HERTZ 1: Source Line (SRC 1)
VOLTS PER HERTZ 1: Pickup 1.10 pu
VOLTS PER HERTZ 1: Curves Definite Time
VOLTS PER HERTZ 1: TD Multiplier 42.00
VOLTS PER HERTZ 1: T Reset 900.0 s
VOLTS PER HERTZ 1: Block OFF
VOLTS PER HERTZ 1: Target Latched
VOLTS PER HERTZ 1: Events Enabled
VOLTS PER HERTZ 2: Function Enabled
VOLTS PER HERTZ 2: Source Line (SRC 1)
VOLTS PER HERTZ 2: Pickup 1.17 pu
VOLTS PER HERTZ 2: Curves Definite Time
VOLTS PER HERTZ 2: TD Multiplier 1.85
VOLTS PER HERTZ 2: T Reset 10.0 s
VOLTS PER HERTZ 2: Block OFF
VOLTS PER HERTZ 2: Target Latched
VOLTS PER HERTZ 2: Events Enabled

LOSS OF EXCITATION [GROUP 1]


Function Enabled
Source Line (SRC 1)
Center 1 55.32 ohm
Radius 1 47.06 ohm
UV Supervision Enable 1 Disabled
Pickup Delay 1 0.060 s
Center 2 75.49 ohm
Radius 2 67.23 ohm
UV Supervision Enable 2 Disabled
Pickup Delay 2 0.600 s
UV Supervision 1.000 pu
Block SRC1 VT FUSE FAIL OP
Target Latched
Events Enabled

ACCIDENTAL ENERGIZATION [GROUP 1]


Function Enabled
Source Line (SRC 1)
Accidental Energization Arming Mode UV AND OFFLINE
Accidental Energization OC Pickup 0.050
Accidental Energization UV Pickup 0.800
Accidental Energization Offline 52b CB 52G On(H7c)
Block OFF
Target Latched
Events Enabled

STATOR GROUND
STATOR GROUND SOURCE [GROUP 1]
Source Line (SRC 1)

POWER
SENSITIVE DIRECTIONAL POWER
SENSITIVE DIRECTIONAL POWER [GROUP 1]
SENS DIR POWER1: Function Enabled
SENS DIR POWER1: Signal Source Line (SRC 1)
SENS DIR POWER1: Sensitive Directional Power RCA 180 deg
SENS DIR POWER1: Sensitive Directional Power Calibration 0.00 deg
SENS DIR POWER1: Stage 1 SMIN 0.014 pu
SENS DIR POWER1: Stage 1 Delay 2.20 s
SENS DIR POWER1: Stage 2 SMIN 0.014 pu
SENS DIR POWER1: Stage 2 Delay 2.20 s
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 25

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

SENSITIVE DIRECTIONAL POWER [GROUP 1] (continued from last page)


SENS DIR POWER1: Block SRC1 VT FUSE FAIL OP
SENS DIR POWER1: Target Latched
SENS DIR POWER1: Events Enabled

CONTROL ELEMENTS
UNDERFREQUENCY
UNDERFREQUENCY 1: Function Enabled
UNDERFREQUENCY 1: Block 52b CB 52G On(H7c)
UNDERFREQUENCY 1: Source Line (SRC 1)
UNDERFREQUENCY 1: Min Volt/Amp 0.10 pu
UNDERFREQUENCY 1: Pickup 47.80 Hz
UNDERFREQUENCY 1: Pickup Delay 0.300 s
UNDERFREQUENCY 1: Reset Delay 0.100 s
UNDERFREQUENCY 1: Target Latched
UNDERFREQUENCY 1: Events Enabled
UNDERFREQUENCY 2: Function Enabled
UNDERFREQUENCY 2: Block 52b CB 52G On(H7c)
UNDERFREQUENCY 2: Source Line (SRC 1)
UNDERFREQUENCY 2: Min Volt/Amp 0.10 pu
UNDERFREQUENCY 2: Pickup 47.50 Hz
UNDERFREQUENCY 2: Pickup Delay 0.000 s
UNDERFREQUENCY 2: Reset Delay 0.100 s
UNDERFREQUENCY 2: Target Latched
UNDERFREQUENCY 2: Events Enabled
UNDERFREQUENCY 3: Function Enabled
UNDERFREQUENCY 3: Block 52b CB 52G On(H7c)
UNDERFREQUENCY 3: Source Line (SRC 1)
UNDERFREQUENCY 3: Min Volt/Amp 0.10 pu
UNDERFREQUENCY 3: Pickup 47.00 Hz
UNDERFREQUENCY 3: Pickup Delay 20.000 s
UNDERFREQUENCY 3: Reset Delay 0.100 s
UNDERFREQUENCY 3: Target Latched
UNDERFREQUENCY 3: Events Enabled
UNDERFREQUENCY 4: Function Enabled
UNDERFREQUENCY 4: Block 52b CB 52G On(H7c)
UNDERFREQUENCY 4: Source Line (SRC 1)
UNDERFREQUENCY 4: Min Volt/Amp 0.10 pu
UNDERFREQUENCY 4: Pickup 46.00 Hz
UNDERFREQUENCY 4: Pickup Delay 0.000 s
UNDERFREQUENCY 4: Reset Delay 0.100 s
UNDERFREQUENCY 4: Target Latched
UNDERFREQUENCY 4: Events Enabled

OVERFREQUENCY
OVERFREQUENCY 2: Function Enabled
OVERFREQUENCY 2: Block OFF
OVERFREQUENCY 2: Source Line (SRC 1)
OVERFREQUENCY 2: Pickup 51.00 Hz
OVERFREQUENCY 2: Pickup Delay 20.000 s
OVERFREQUENCY 2: Reset Delay 0.100 s
OVERFREQUENCY 2: Target Latched
OVERFREQUENCY 2: Events Enabled
OVERFREQUENCY 3: Function Enabled
OVERFREQUENCY 3: Block OFF
OVERFREQUENCY 3: Source Line (SRC 1)
OVERFREQUENCY 3: Pickup 52.00 Hz
OVERFREQUENCY 3: Pickup Delay 0.300 s
OVERFREQUENCY 3: Reset Delay 0.100 s
OVERFREQUENCY 3: Target Latched
OVERFREQUENCY 3: Events Enabled

MONITORING ELEMENTS
VT FUSE FAILURE
VT FUSE FAILURE 1: Function Enabled
VT FUSE FAILURE 4: Function Enabled

FREQUENCY OOB ACCUMULATION


Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 26

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

FREQUENCY OOB ACCUMULATION (continued from last page)


Freq OOB Accumulator Source Line (SRC 1)
Freq OOB Accumulator Min V A 0.10 pu
Freq OOB Accumulator Block OFF
Freq OOB Accumulator Target Self-reset
Freq OOB Accumulator Events Disabled

INPUTS/OUTPUTS
CONTACT INPUTS
[H7A] Contact Input 1 ID 52a CB 52G
[H7A] Contact Input 1 Debounce Time 4.0 ms
[H7A] Contact Input 1 Events Enabled
[H7C] Contact Input 2 ID 52b CB 52G
[H7C] Contact Input 2 Debounce Time 4.0 ms
[H7C] Contact Input 2 Events Enabled
[H8A] Contact Input 3 ID T60-52G Trp1
[H8A] Contact Input 3 Debounce Time 4.0 ms
[H8A] Contact Input 3 Events Enabled
[H8C] Contact Input 4 ID T60-52G Trp2
[H8C] Contact Input 4 Debounce Time 4.0 ms
[H8C] Contact Input 4 Events Enabled
[P1A] Contact Input 5 ID TP3 VT CB4 O
[P1A] Contact Input 5 Debounce Time 4.0 ms
[P1A] Contact Input 5 Events Enabled
[P1C] Contact Input 6 ID Sta Trip 52G
[P1C] Contact Input 6 Debounce Time 4.0 ms
[P1C] Contact Input 6 Events Enabled
[P2A] Contact Input 7 ID Cont Ip 7
[P2A] Contact Input 7 Debounce Time 4.0 ms
[P2A] Contact Input 7 Events Disabled
[P2C] Contact Input 8 ID Cont Ip 8
[P2C] Contact Input 8 Debounce Time 4.0 ms
[P2C] Contact Input 8 Events Disabled
[P3A] Contact Input 9 ID 52LX1 Oper
[P3A] Contact Input 9 Debounce Time 4.0 ms
[P3A] Contact Input 9 Events Enabled
[P3C] Contact Input 10 ID Cont Ip 10
[P3C] Contact Input 10 Debounce Time 4.0 ms
[P3C] Contact Input 10 Events Disabled
[P4A] Contact Input 11 ID Cont Ip 11
[P4A] Contact Input 11 Debounce Time 4.0 ms
[P4A] Contact Input 11 Events Disabled
[P4C] Contact Input 12 ID Cont Ip 12
[P4C] Contact Input 12 Debounce Time 4.0 ms
[P4C] Contact Input 12 Events Disabled
[P5A] Contact Input 13 ID Cont Ip 13
[P5A] Contact Input 13 Debounce Time 4.0 ms
[P5A] Contact Input 13 Events Disabled
[P5C] Contact Input 14 ID Cont Ip 14
[P5C] Contact Input 14 Debounce Time 4.0 ms
[P5C] Contact Input 14 Events Disabled
[P6A] Contact Input 15 ID Cont Ip 15
[P6A] Contact Input 15 Debounce Time 4.0 ms
[P6A] Contact Input 15 Events Disabled
[P6C] Contact Input 16 ID Cont Ip 16
[P6C] Contact Input 16 Debounce Time 4.0 ms
[P6C] Contact Input 16 Events Disabled
[P7A] Contact Input 17 ID Cont Ip 17
[P7A] Contact Input 17 Debounce Time 4.0 ms
[P7A] Contact Input 17 Events Disabled
[P7C] Contact Input 18 ID Cont Ip 18
[P7C] Contact Input 18 Debounce Time 4.0 ms
[P7C] Contact Input 18 Events Disabled
[P8A] Contact Input 19 ID Cont Ip 19
[P8A] Contact Input 19 Debounce Time 4.0 ms
[P8A] Contact Input 19 Events Disabled
[P8C] Contact Input 20 ID Cont Ip 20
[P8C] Contact Input 20 Debounce Time 4.0 ms
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 27

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

CONTACT INPUTS (continued from last page)


[P8C] Contact Input 20 Events Disabled

CONTACT INPUT THRESHOLDS


52a CB 52G, 52b CB 52G, T60-52G Trp1, T60-52G Trp2(H7A, H7C, H8A, H8C)
33 Vdc
TP3 VT CB4 O, Sta Trip 52G, Cont Ip 7, Cont Ip 8(P1A, P1C, P2A, P2C) 33 Vdc
52LX1 Oper, Cont Ip 10, Cont Ip 11, Cont Ip 12(P3A, P3C, P4A, P4C) 33 Vdc
Cont Ip 13, Cont Ip 14, Cont Ip 15, Cont Ip 16(P5A, P5C, P6A, P6C) 33 Vdc
Cont Ip 17, Cont Ip 18, Cont Ip 19, Cont Ip 20(P7A, P7C, P8A, P8C) 33 Vdc

CONTACT OUTPUTS
[H1] Contact Output 1 ID LO 86G Trip
[H1] Contact Output 1 Operate H1 Operate On (VO21)
[H1] Contact Output 1 Seal-In LO 86G Trip IOn (H1)
[H1] Contact Output 1 Events Enabled
[H2] Contact Output 2 ID CB 52G Trp 1
[H2] Contact Output 2 Operate H2 Operate On (VO22)
[H2] Contact Output 2 Seal-In CB 52G Trp 1 IOn (H2)
[H2] Contact Output 2 Events Enabled
[H3] Contact Output 3 ID CB 52G Trp 2
[H3] Contact Output 3 Operate H3 Operate On (VO23)
[H3] Contact Output 3 Seal-In CB 52G Trp 2 IOn (H3)
[H3] Contact Output 3 Events Enabled
[H4] Contact Output 4 ID LO 86T Trip
[H4] Contact Output 4 Operate H4 Operate On (VO24)
[H4] Contact Output 4 Seal-In LO 86T Trip IOn (H4)
[H4] Contact Output 4 Events Enabled
[H5] Contact Output 5 ID TP3 VT CB4 O
[H5] Contact Output 5 Operate H5 Operate On (VO25)
[H5] Contact Output 5 Seal-In OFF
[H5] Contact Output 5 Events Enabled
[H6] Contact Output 6 ID Chg Src 400V
[H6] Contact Output 6 Operate H6 Operate On (VO26)
[H6] Contact Output 6 Seal-In OFF
[H6] Contact Output 6 Events Enabled
[U1] Contact Output 7 ID 87ST Oper
[U1] Contact Output 7 Operate U1 Operate On (VO27)
[U1] Latching Output 7 Reset RESET OP (PUSHBUTTON)
[U1] Latching Output 7 Type Operate-dominant
[U1] Contact Output 7 Events Enabled
[U2] Contact Output 8 ID 50P Oper
[U2] Contact Output 8 Operate U2 Operate On (VO28)
[U2] Latching Output 8 Reset RESET OP (PUSHBUTTON)
[U2] Latching Output 8 Type Operate-dominant
[U2] Contact Output 8 Events Enabled
[U3] Contact Output 9 ID 51P Oper
[U3] Contact Output 9 Operate U3 Operate On (VO29)
[U3] Latching Output 9 Reset RESET OP (PUSHBUTTON)
[U3] Latching Output 9 Type Operate-dominant
[U3] Contact Output 9 Events Enabled
[U4] Contact Output 10 ID 40 Oper
[U4] Contact Output 10 Operate U4 Operate On (VO30)
[U4] Latching Output 10 Reset RESET OP (PUSHBUTTON)
[U4] Latching Output 10 Type Operate-dominant
[U4] Contact Output 10 Events Enabled
[U5] Contact Output 11 ID 46 Oper
[U5] Contact Output 11 Operate U5 Operate On (VO31)
[U5] Latching Output 11 Reset RESET OP (PUSHBUTTON)
[U5] Latching Output 11 Type Operate-dominant
[U5] Contact Output 11 Events Enabled
[U6] Contact Output 12 ID 32 Oper
[U6] Contact Output 12 Operate U6 Operate On (VO32)
[U6] Latching Output 12 Reset RESET OP (PUSHBUTTON)
[U6] Latching Output 12 Type Operate-dominant
[U6] Contact Output 12 Events Enabled
[U7] Contact Output 13 ID 24 Oper
[U7] Contact Output 13 Operate U7 Operate On (VO33)
[U7] Latching Output 13 Reset RESET OP (PUSHBUTTON)
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 28

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

CONTACT OUTPUTS (continued from last page)


[U7] Latching Output 13 Type Operate-dominant
[U7] Contact Output 13 Events Enabled
[U8] Contact Output 14 ID 27P Oper
[U8] Contact Output 14 Operate U8 Operate On (VO34)
[U8] Latching Output 14 Reset RESET OP (PUSHBUTTON)
[U8] Latching Output 14 Type Operate-dominant
[U8] Contact Output 14 Events Enabled
[U9] Contact Output 15 ID 59P Oper
[U9] Contact Output 15 Operate U9 Operate On (VO35)
[U9] Latching Output 15 Reset RESET OP (PUSHBUTTON)
[U9] Latching Output 15 Type Operate-dominant
[U9] Contact Output 15 Events Enabled
[U10] Contact Output 16 ID 50/27 Oper
[U10] Contact Output 16 Operate U10 Operate On (VO36)
[U10] Latching Output 16 Reset RESET OP (PUSHBUTTON)
[U10] Latching Output 16 Type Operate-dominant
[U10] Contact Output 16 Events Enabled
[U11] Contact Output 17 ID 50/Off Oper
[U11] Contact Output 17 Operate U11 Operate On (VO37)
[U11] Latching Output 17 Reset RESET OP (PUSHBUTTON)
[U11] Latching Output 17 Type Operate-dominant
[U11] Contact Output 17 Events Enabled
[U12] Contact Output 18 ID 81 Oper
[U12] Contact Output 18 Operate U12 Operate On (VO38)
[U12] Latching Output 18 Reset RESET OP (PUSHBUTTON)
[U12] Latching Output 18 Type Operate-dominant
[U12] Contact Output 18 Events Enabled
[U13] Contact Output 19 ID 64G Oper
[U13] Contact Output 19 Operate U13 Operate On (VO39)
[U13] Latching Output 19 Reset RESET OP (PUSHBUTTON)
[U13] Latching Output 19 Type Operate-dominant
[U13] Contact Output 19 Events Enabled
[U14] Contact Output 20 ID 21/78 Oper
[U14] Contact Output 20 Operate U14 Operate On (VO40)
[U14] Latching Output 20 Reset RESET OP (PUSHBUTTON)
[U14] Latching Output 20 Type Operate-dominant
[U14] Contact Output 20 Events Enabled
[W1] Contact Output 21 ID All Trips
[W1] Contact Output 21 Operate W1 Operate On (VO81)
[W1] Contact Output 21 Seal-In OFF
[W1] Contact Output 21 Events Enabled
[W2] Contact Output 22 ID All Alarms
[W2] Contact Output 22 Operate W2 Operate On (VO82)
[W2] Contact Output 22 Seal-In OFF
[W2] Contact Output 22 Events Enabled
[W3] Contact Output 23 ID Turb Norm St
[W3] Contact Output 23 Operate W3 Operate On (VO83)
[W3] Contact Output 23 Seal-In OFF
[W3] Contact Output 23 Events Enabled
[W4] Contact Output 24 ID Turb Trip St
[W4] Contact Output 24 Operate W4 Operate On (VO84)
[W4] Contact Output 24 Seal-In OFF
[W4] Contact Output 24 Events Enabled
[W5] Contact Output 25 ID 41EX Trip
[W5] Contact Output 25 Operate W5 Operate On (VO85)
[W5] Contact Output 25 Seal-In OFF
[W5] Contact Output 25 Events Enabled
[W6] Contact Output 26 ID Chg Src 6 kV
[W6] Contact Output 26 Operate W6 Operate On (VO86)
[W6] Contact Output 26 Seal-In OFF
[W6] Contact Output 26 Events Enabled
[W7] Contact Output 27 ID T60-52L Trp1
[W7] Contact Output 27 Operate W7 Operate On (VO87)
[W7] Contact Output 27 Seal-In OFF
[W7] Contact Output 27 Events Enabled
[W8] Contact Output 28 ID T60-52L Trp2
[W8] Contact Output 28 Operate W8 Operate On (VO88)
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 29

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

CONTACT OUTPUTS (continued from last page)


[W8] Contact Output 28 Seal-In OFF
[W8] Contact Output 28 Events Enabled

VIRTUAL OUTPUTS
Virtual Output 4 ID Blk Enable
Virtual Output 4 Events Enabled
Virtual Output 5 ID G60 Rly Fail
Virtual Output 5 Events Enabled
Virtual Output 6 ID Alrm LED In
Virtual Output 6 Events Disabled
Virtual Output 7 ID Trip LED In
Virtual Output 7 Events Disabled
Virtual Output 8 ID Osc Initiate
Virtual Output 8 Events Disabled
Virtual Output 9 ID Reset Sealin
Virtual Output 9 Events Enabled
Virtual Output 11 ID Gen C/B Open
Virtual Output 11 Events Enabled
Virtual Output 12 ID Gen C/B Clos
Virtual Output 12 Events Enabled
Virtual Output 13 ID Gen C/B OK
Virtual Output 13 Events Enabled
Virtual Output 14 ID Gen C/B Trbl
Virtual Output 14 Events Enabled
Virtual Output 21 ID H1 Operate
Virtual Output 21 Events Enabled
Virtual Output 22 ID H2 Operate
Virtual Output 22 Events Enabled
Virtual Output 23 ID H3 Operate
Virtual Output 23 Events Enabled
Virtual Output 24 ID H4 Operate
Virtual Output 24 Events Enabled
Virtual Output 25 ID H5 Operate
Virtual Output 25 Events Enabled
Virtual Output 26 ID H6 Operate
Virtual Output 26 Events Enabled
Virtual Output 27 ID U1 Operate
Virtual Output 27 Events Enabled
Virtual Output 29 ID U3 Operate
Virtual Output 29 Events Enabled
Virtual Output 30 ID U4 Operate
Virtual Output 30 Events Enabled
Virtual Output 31 ID U5 Operate
Virtual Output 31 Events Enabled
Virtual Output 32 ID U6 Operate
Virtual Output 32 Events Enabled
Virtual Output 33 ID U7 Operate
Virtual Output 33 Events Enabled
Virtual Output 34 ID U8 Operate
Virtual Output 34 Events Enabled
Virtual Output 35 ID U9 Operate
Virtual Output 35 Events Enabled
Virtual Output 36 ID U10 Operate
Virtual Output 36 Events Enabled
Virtual Output 38 ID U12 Operate
Virtual Output 38 Events Enabled
Virtual Output 39 ID U13 Operate
Virtual Output 39 Events Enabled
Virtual Output 40 ID U14 Operate
Virtual Output 40 Events Enabled
Virtual Output 41 ID 27P/A Oper
Virtual Output 41 Events Enabled
Virtual Output 42 ID 49/A Oper
Virtual Output 42 Events Enabled
Virtual Output 43 ID 24/A Oper
Virtual Output 43 Events Enabled
Virtual Output 44 ID 46/A Oper
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 30

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

VIRTUAL OUTPUTS (continued from last page)


Virtual Output 44 Events Enabled
Virtual Output 49 ID VTFF Operate
Virtual Output 49 Events Enabled
Virtual Output 50 ID 87S/T Oper
Virtual Output 50 Events Enabled
Virtual Output 51 ID 51P/T Oper
Virtual Output 51 Events Enabled
Virtual Output 53 ID 64G/T Oper
Virtual Output 53 Events Enabled
Virtual Output 54 ID 50/27T Oper
Virtual Output 54 Events Enabled
Virtual Output 56 ID 40/T Oper
Virtual Output 56 Events Enabled
Virtual Output 57 ID 46/T Oper
Virtual Output 57 Events Enabled
Virtual Output 58 ID 32/T Oper
Virtual Output 58 Events Enabled
Virtual Output 59 ID 24/T Oper
Virtual Output 59 Events Enabled
Virtual Output 60 ID 27P/T Oper
Virtual Output 60 Events Enabled
Virtual Output 61 ID 59P/T Oper
Virtual Output 61 Events Enabled
Virtual Output 62 ID 81U/T Oper
Virtual Output 62 Events Enabled
Virtual Output 63 ID 81O/T Oper
Virtual Output 63 Events Enabled
Virtual Output 64 ID 21 Oper
Virtual Output 64 Events Enabled
Virtual Output 65 ID 78 Oper
Virtual Output 65 Events Enabled
Virtual Output 66 ID 21-78 Oper
Virtual Output 66 Events Enabled
Virtual Output 67 ID 86BUT Oper
Virtual Output 67 Events Enabled
Virtual Output 81 ID W1 Operate
Virtual Output 81 Events Enabled
Virtual Output 82 ID W2 Operate
Virtual Output 82 Events Enabled
Virtual Output 83 ID W3 Operate
Virtual Output 83 Events Enabled
Virtual Output 84 ID W4 Operate
Virtual Output 84 Events Enabled
Virtual Output 85 ID W5 Operate
Virtual Output 85 Events Enabled
Virtual Output 86 ID W6 Operate
Virtual Output 86 Events Enabled
Virtual Output 87 ID W7 Operate
Virtual Output 87 Events Enabled
Virtual Output 88 ID W8 Operate
Virtual Output 88 Events Enabled

REMOTE DEVICES
Remote Device 1 ID Remote Device 1
Remote Device 1 ETYPE APPID 0
Remote Device 1 DATASET Fixed
Remote Device 1 IN PMU SCHEME No
Remote Device 2 ID Remote Device 2
Remote Device 2 ETYPE APPID 0
Remote Device 2 DATASET Fixed
Remote Device 2 IN PMU SCHEME No
Remote Device 3 ID Remote Device 3
Remote Device 3 ETYPE APPID 0
Remote Device 3 DATASET Fixed
Remote Device 3 IN PMU SCHEME No
Remote Device 4 ID Remote Device 4
Remote Device 4 ETYPE APPID 0
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 31

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

REMOTE DEVICES (continued from last page)


Remote Device 4 DATASET Fixed
Remote Device 4 IN PMU SCHEME No
Remote Device 5 ID Remote Device 5
Remote Device 5 ETYPE APPID 0
Remote Device 5 DATASET Fixed
Remote Device 5 IN PMU SCHEME No
Remote Device 6 ID Remote Device 6
Remote Device 6 ETYPE APPID 0
Remote Device 6 DATASET Fixed
Remote Device 6 IN PMU SCHEME No
Remote Device 7 ID Remote Device 7
Remote Device 7 ETYPE APPID 0
Remote Device 7 DATASET Fixed
Remote Device 7 IN PMU SCHEME No
Remote Device 8 ID Remote Device 8
Remote Device 8 ETYPE APPID 0
Remote Device 8 DATASET Fixed
Remote Device 8 IN PMU SCHEME No
Remote Device 9 ID Remote Device 9
Remote Device 9 ETYPE APPID 0
Remote Device 9 DATASET Fixed
Remote Device 9 IN PMU SCHEME No
Remote Device 10 ID Remote Device 10
Remote Device 10 ETYPE APPID 0
Remote Device 10 DATASET Fixed
Remote Device 10 IN PMU SCHEME No
Remote Device 11 ID Remote Device 11
Remote Device 11 ETYPE APPID 0
Remote Device 11 DATASET Fixed
Remote Device 11 IN PMU SCHEME No
Remote Device 12 ID Remote Device 12
Remote Device 12 ETYPE APPID 0
Remote Device 12 DATASET Fixed
Remote Device 12 IN PMU SCHEME No
Remote Device 13 ID Remote Device 13
Remote Device 13 ETYPE APPID 0
Remote Device 13 DATASET Fixed
Remote Device 13 IN PMU SCHEME No
Remote Device 14 ID Remote Device 14
Remote Device 14 ETYPE APPID 0
Remote Device 14 DATASET Fixed
Remote Device 14 IN PMU SCHEME No
Remote Device 15 ID Remote Device 15
Remote Device 15 ETYPE APPID 0
Remote Device 15 DATASET Fixed
Remote Device 15 IN PMU SCHEME No
Remote Device 16 ID Remote Device 16
Remote Device 16 ETYPE APPID 0
Remote Device 16 DATASET Fixed
Remote Device 16 IN PMU SCHEME No

REMOTE DPS INPUTS


Remote DPS Input 1 Name RemDPS Ip 1
Remote DPS Input 1 Device Remote Device 1
Remote DPS Input 1 Item None
Remote DPS Input 1 Events Disabled
Remote DPS Input 2 Name RemDPS Ip 2
Remote DPS Input 2 Device Remote Device 1
Remote DPS Input 2 Item None
Remote DPS Input 2 Events Disabled
Remote DPS Input 3 Name RemDPS Ip 3
Remote DPS Input 3 Device Remote Device 1
Remote DPS Input 3 Item None
Remote DPS Input 3 Events Disabled
Remote DPS Input 4 Name RemDPS Ip 4
Remote DPS Input 4 Device Remote Device 1
Remote DPS Input 4 Item None
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 32

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

REMOTE DPS INPUTS (continued from last page)


Remote DPS Input 4 Events Disabled
Remote DPS Input 5 Name RemDPS Ip 5
Remote DPS Input 5 Device Remote Device 1
Remote DPS Input 5 Item None
Remote DPS Input 5 Events Disabled

IEC 61850 GOOSE ANALOGS INPUTS


IEC61850 GOOSE Analog Input 1 Default Value 1000.000
IEC61850 GOOSE Analog Input 1 Mode Default Value
IEC61850 GOOSE Analog Input 1 Units
IEC61850 GOOSE Analog Input 1 PU Base 1.000
IEC61850 GOOSE Analog Input 2 Default Value 1000.000
IEC61850 GOOSE Analog Input 2 Mode Default Value
IEC61850 GOOSE Analog Input 2 Units
IEC61850 GOOSE Analog Input 2 PU Base 1.000
IEC61850 GOOSE Analog Input 3 Default Value 1000.000
IEC61850 GOOSE Analog Input 3 Mode Default Value
IEC61850 GOOSE Analog Input 3 Units
IEC61850 GOOSE Analog Input 3 PU Base 1.000
IEC61850 GOOSE Analog Input 4 Default Value 1000.000
IEC61850 GOOSE Analog Input 4 Mode Default Value
IEC61850 GOOSE Analog Input 4 Units
IEC61850 GOOSE Analog Input 4 PU Base 1.000
IEC61850 GOOSE Analog Input 5 Default Value 1000.000
IEC61850 GOOSE Analog Input 5 Mode Default Value
IEC61850 GOOSE Analog Input 5 Units
IEC61850 GOOSE Analog Input 5 PU Base 1.000
IEC61850 GOOSE Analog Input 6 Default Value 1000.000
IEC61850 GOOSE Analog Input 6 Mode Default Value
IEC61850 GOOSE Analog Input 6 Units
IEC61850 GOOSE Analog Input 6 PU Base 1.000
IEC61850 GOOSE Analog Input 7 Default Value 1000.000
IEC61850 GOOSE Analog Input 7 Mode Default Value
IEC61850 GOOSE Analog Input 7 Units
IEC61850 GOOSE Analog Input 7 PU Base 1.000
IEC61850 GOOSE Analog Input 8 Default Value 1000.000
IEC61850 GOOSE Analog Input 8 Mode Default Value
IEC61850 GOOSE Analog Input 8 Units
IEC61850 GOOSE Analog Input 8 PU Base 1.000
IEC61850 GOOSE Analog Input 9 Default Value 1000.000
IEC61850 GOOSE Analog Input 9 Mode Default Value
IEC61850 GOOSE Analog Input 9 Units
IEC61850 GOOSE Analog Input 9 PU Base 1.000
IEC61850 GOOSE Analog Input 10 Default Value 1000.000
IEC61850 GOOSE Analog Input 10 Mode Default Value
IEC61850 GOOSE Analog Input 10 Units
IEC61850 GOOSE Analog Input 10 PU Base 1.000
IEC61850 GOOSE Analog Input 11 Default Value 1000.000
IEC61850 GOOSE Analog Input 11 Mode Default Value
IEC61850 GOOSE Analog Input 11 Units
IEC61850 GOOSE Analog Input 11 PU Base 1.000
IEC61850 GOOSE Analog Input 12 Default Value 1000.000
IEC61850 GOOSE Analog Input 12 Mode Default Value
IEC61850 GOOSE Analog Input 12 Units
IEC61850 GOOSE Analog Input 12 PU Base 1.000
IEC61850 GOOSE Analog Input 13 Default Value 1000.000
IEC61850 GOOSE Analog Input 13 Mode Default Value
IEC61850 GOOSE Analog Input 13 Units
IEC61850 GOOSE Analog Input 13 PU Base 1.000
IEC61850 GOOSE Analog Input 14 Default Value 1000.000
IEC61850 GOOSE Analog Input 14 Mode Default Value
IEC61850 GOOSE Analog Input 14 Units
IEC61850 GOOSE Analog Input 14 PU Base 1.000
IEC61850 GOOSE Analog Input 15 Default Value 1000.000
IEC61850 GOOSE Analog Input 15 Mode Default Value
IEC61850 GOOSE Analog Input 15 Units
IEC61850 GOOSE Analog Input 15 PU Base 1.000
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 33

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

IEC 61850 GOOSE ANALOGS INPUTS (continued from last page)


IEC61850 GOOSE Analog Input 16 Default Value 1000.000
IEC61850 GOOSE Analog Input 16 Mode Default Value
IEC61850 GOOSE Analog Input 16 Units
IEC61850 GOOSE Analog Input 16 PU Base 1.000
IEC61850 GOOSE Analog Input 17 Default Value 1000.000
IEC61850 GOOSE Analog Input 17 Mode Default Value
IEC61850 GOOSE Analog Input 17 Units
IEC61850 GOOSE Analog Input 17 PU Base 1.000
IEC61850 GOOSE Analog Input 18 Default Value 1000.000
IEC61850 GOOSE Analog Input 18 Mode Default Value
IEC61850 GOOSE Analog Input 18 Units
IEC61850 GOOSE Analog Input 18 PU Base 1.000
IEC61850 GOOSE Analog Input 19 Default Value 1000.000
IEC61850 GOOSE Analog Input 19 Mode Default Value
IEC61850 GOOSE Analog Input 19 Units
IEC61850 GOOSE Analog Input 19 PU Base 1.000
IEC61850 GOOSE Analog Input 20 Default Value 1000.000
IEC61850 GOOSE Analog Input 20 Mode Default Value
IEC61850 GOOSE Analog Input 20 Units
IEC61850 GOOSE Analog Input 20 PU Base 1.000
IEC61850 GOOSE Analog Input 21 Default Value 1000.000
IEC61850 GOOSE Analog Input 21 Mode Default Value
IEC61850 GOOSE Analog Input 21 Units
IEC61850 GOOSE Analog Input 21 PU Base 1.000
IEC61850 GOOSE Analog Input 22 Default Value 1000.000
IEC61850 GOOSE Analog Input 22 Mode Default Value
IEC61850 GOOSE Analog Input 22 Units
IEC61850 GOOSE Analog Input 22 PU Base 1.000
IEC61850 GOOSE Analog Input 23 Default Value 1000.000
IEC61850 GOOSE Analog Input 23 Mode Default Value
IEC61850 GOOSE Analog Input 23 Units
IEC61850 GOOSE Analog Input 23 PU Base 1.000
IEC61850 GOOSE Analog Input 24 Default Value 1000.000
IEC61850 GOOSE Analog Input 24 Mode Default Value
IEC61850 GOOSE Analog Input 24 Units
IEC61850 GOOSE Analog Input 24 PU Base 1.000
IEC61850 GOOSE Analog Input 25 Default Value 1000.000
IEC61850 GOOSE Analog Input 25 Mode Default Value
IEC61850 GOOSE Analog Input 25 Units
IEC61850 GOOSE Analog Input 25 PU Base 1.000
IEC61850 GOOSE Analog Input 26 Default Value 1000.000
IEC61850 GOOSE Analog Input 26 Mode Default Value
IEC61850 GOOSE Analog Input 26 Units
IEC61850 GOOSE Analog Input 26 PU Base 1.000
IEC61850 GOOSE Analog Input 27 Default Value 1000.000
IEC61850 GOOSE Analog Input 27 Mode Default Value
IEC61850 GOOSE Analog Input 27 Units
IEC61850 GOOSE Analog Input 27 PU Base 1.000
IEC61850 GOOSE Analog Input 28 Default Value 1000.000
IEC61850 GOOSE Analog Input 28 Mode Default Value
IEC61850 GOOSE Analog Input 28 Units
IEC61850 GOOSE Analog Input 28 PU Base 1.000
IEC61850 GOOSE Analog Input 29 Default Value 1000.000
IEC61850 GOOSE Analog Input 29 Mode Default Value
IEC61850 GOOSE Analog Input 29 Units
IEC61850 GOOSE Analog Input 29 PU Base 1.000
IEC61850 GOOSE Analog Input 30 Default Value 1000.000
IEC61850 GOOSE Analog Input 30 Mode Default Value
IEC61850 GOOSE Analog Input 30 Units
IEC61850 GOOSE Analog Input 30 PU Base 1.000
IEC61850 GOOSE Analog Input 31 Default Value 1000.000
IEC61850 GOOSE Analog Input 31 Mode Default Value
IEC61850 GOOSE Analog Input 31 Units
IEC61850 GOOSE Analog Input 31 PU Base 1.000
IEC61850 GOOSE Analog Input 32 Default Value 1000.000
IEC61850 GOOSE Analog Input 32 Mode Default Value
IEC61850 GOOSE Analog Input 32 Units
Fri Jun 10 12:08:29 2011 Version: 5.81 Settings (Enabled Features) PAGE 34

SONELGAZ MSILA G3 G60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: G60-J04-HMH-F8L-H6P-M8L-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONEGAZ MSILA G60 GENERATOR MANAGEMENT RELAY
TEXT COLOR

IEC 61850 GOOSE ANALOGS INPUTS (continued from last page)


IEC61850 GOOSE Analog Input 32 PU Base 1.000

IEC 61850 GOOSE UINTEGERS INPUTS


IEC61850 GOOSE UInteger Input 1 Default Value 1000
IEC61850 GOOSE UInteger Input 1 Mode Default Value
IEC61850 GOOSE UInteger Input 2 Default Value 1000
IEC61850 GOOSE UInteger Input 2 Mode Default Value
IEC61850 GOOSE UInteger Input 3 Default Value 1000
IEC61850 GOOSE UInteger Input 3 Mode Default Value
IEC61850 GOOSE UInteger Input 4 Default Value 1000
IEC61850 GOOSE UInteger Input 4 Mode Default Value
IEC61850 GOOSE UInteger Input 5 Default Value 1000
IEC61850 GOOSE UInteger Input 5 Mode Default Value
IEC61850 GOOSE UInteger Input 6 Default Value 1000
IEC61850 GOOSE UInteger Input 6 Mode Default Value
IEC61850 GOOSE UInteger Input 7 Default Value 1000
IEC61850 GOOSE UInteger Input 7 Mode Default Value
IEC61850 GOOSE UInteger Input 8 Default Value 1000
IEC61850 GOOSE UInteger Input 8 Mode Default Value
IEC61850 GOOSE UInteger Input 9 Default Value 1000
IEC61850 GOOSE UInteger Input 9 Mode Default Value
IEC61850 GOOSE UInteger Input 10 Default Value 1000
IEC61850 GOOSE UInteger Input 10 Mode Default Value
IEC61850 GOOSE UInteger Input 11 Default Value 1000
IEC61850 GOOSE UInteger Input 11 Mode Default Value
IEC61850 GOOSE UInteger Input 12 Default Value 1000
IEC61850 GOOSE UInteger Input 12 Mode Default Value
IEC61850 GOOSE UInteger Input 13 Default Value 1000
IEC61850 GOOSE UInteger Input 13 Mode Default Value
IEC61850 GOOSE UInteger Input 14 Default Value 1000
IEC61850 GOOSE UInteger Input 14 Mode Default Value
IEC61850 GOOSE UInteger Input 15 Default Value 1000
IEC61850 GOOSE UInteger Input 15 Mode Default Value
IEC61850 GOOSE UInteger Input 16 Default Value 1000
IEC61850 GOOSE UInteger Input 16 Mode Default Value
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


Study Appendix

9. Appendix 3 UR T60 Setting File Summary (Step-Up Transformer TP3)

PAGE 117

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
Fri Jun 10 12:09:10 2011 Version: 5.81 Settings (Enabled Features) PAGE 1

SONELGAZ MSILA TP3 T60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: T60-J04-HMH-F8L-H6P-M8N-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONELGAZ MSILA T60 TRANSFORMER MANAGEMENT RELAY
TEXT COLOR

PRODUCT SETUP
SECURITY
Command Password 0
Setting Password 0
Command Password Access Timeout 5 min
Setting Password Access Timeout 30 min
Invalid Password Attempts 3
Password Lockout Duration 5 min
Password Access Events Disabled
Local Setting Authorized ON
Remote Setting Authorized ON
Access Authorized Timeout 30 min

DISPLAY PROPERTIES
Language French
Flash Message Time 4.0 s
Default Message Timeout 24 s
Default Message Intensity (VFD Only) 25 %
Screen Saver Feature (LCD Only) Disabled
Screen Saver Wait Time (LCD Only) 30 min
Current Cutoff Level 0.020 pu
Voltage Cutoff Level 1.0 V

COMMUNICATIONS
SERIAL PORTS
COM2 Selection RS485
RS485 Com2 Baud Rate 115200
RS485 Com2 Parity None
RS485 Com2 Response Min Time 0 ms

NETWORK
IP Address 192.168.101. 85
IP Subnet Mask 255.255.255. 0
Gateway IP Address 192.168.101. 15
Ethernet Operation Mode Half-Duplex
OSI Network Address (NSAP) 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 49 00 00 00

MODBUS PROTOCOL
Modbus Slave Address 254
Modbus TCP Port Number 502

IEC 61850
GSSE / GOOSE CONFIGURATION
TRANSMISSION
GENERAL
Default GSSE/GOOSE Update Time 60 s

GSSE
Function Enabled
ID GSSEOut
Destination MAC 00 00 00 00 00 00

TX CONFIGURABLE GOOSE
GOOSEOut 1 Function Enabled
GOOSEOut 1 ID GOOSEOut_1
GOOSEOut 1 Destination MAC 00 00 00 00 00 00
GOOSEOut 1 VLAN Priority 4
GOOSEOut 1 VLAN ID 0
GOOSEOut 1 ETYPE APPID 0
GOOSEOut 1 ConfRev 1
GOOSEOut 1 Retransmission Curve Relaxed
GOOSEOut 2 Function Enabled
GOOSEOut 2 ID GOOSEOut_2
GOOSEOut 2 Destination MAC 00 00 00 00 00 00
GOOSEOut 2 VLAN Priority 4
GOOSEOut 2 VLAN ID 0
GOOSEOut 2 ETYPE APPID 0
GOOSEOut 2 ConfRev 1
Fri Jun 10 12:09:10 2011 Version: 5.81 Settings (Enabled Features) PAGE 2

SONELGAZ MSILA TP3 T60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: T60-J04-HMH-F8L-H6P-M8N-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONELGAZ MSILA T60 TRANSFORMER MANAGEMENT RELAY
TEXT COLOR

TX CONFIGURABLE GOOSE (continued from last page)


GOOSEOut 2 Retransmission Curve Relaxed
GOOSEOut 3 Function Enabled
GOOSEOut 3 ID GOOSEOut_3
GOOSEOut 3 Destination MAC 00 00 00 00 00 00
GOOSEOut 3 VLAN Priority 4
GOOSEOut 3 VLAN ID 0
GOOSEOut 3 ETYPE APPID 0
GOOSEOut 3 ConfRev 1
GOOSEOut 3 Retransmission Curve Relaxed
GOOSEOut 4 Function Enabled
GOOSEOut 4 ID GOOSEOut_4
GOOSEOut 4 Destination MAC 00 00 00 00 00 00
GOOSEOut 4 VLAN Priority 4
GOOSEOut 4 VLAN ID 0
GOOSEOut 4 ETYPE APPID 0
GOOSEOut 4 ConfRev 1
GOOSEOut 4 Retransmission Curve Relaxed
GOOSEOut 5 Function Enabled
GOOSEOut 5 ID GOOSEOut_5
GOOSEOut 5 Destination MAC 00 00 00 00 00 00
GOOSEOut 5 VLAN Priority 4
GOOSEOut 5 VLAN ID 0
GOOSEOut 5 ETYPE APPID 0
GOOSEOut 5 ConfRev 1
GOOSEOut 5 Retransmission Curve Relaxed
GOOSEOut 6 Function Enabled
GOOSEOut 6 ID GOOSEOut_6
GOOSEOut 6 Destination MAC 00 00 00 00 00 00
GOOSEOut 6 VLAN Priority 4
GOOSEOut 6 VLAN ID 0
GOOSEOut 6 ETYPE APPID 0
GOOSEOut 6 ConfRev 1
GOOSEOut 6 Retransmission Curve Relaxed
GOOSEOut 7 Function Enabled
GOOSEOut 7 ID GOOSEOut_7
GOOSEOut 7 Destination MAC 00 00 00 00 00 00
GOOSEOut 7 VLAN Priority 4
GOOSEOut 7 VLAN ID 0
GOOSEOut 7 ETYPE APPID 0
GOOSEOut 7 ConfRev 1
GOOSEOut 7 Retransmission Curve Relaxed
GOOSEOut 8 Function Enabled
GOOSEOut 8 ID GOOSEOut_8
GOOSEOut 8 Destination MAC 00 00 00 00 00 00
GOOSEOut 8 VLAN Priority 4
GOOSEOut 8 VLAN ID 0
GOOSEOut 8 ETYPE APPID 0
GOOSEOut 8 ConfRev 1
GOOSEOut 8 Retransmission Curve Relaxed

SERVER CONFIGURATION
IEDName IEDName
Logical Device Instance LDInst
LPHD DC PhyNam location Location
MMS TCP Port Number 102

MMXU DEADBANDS
MMXU1: TotW Deadband 10.000 %
MMXU1: TotVAr Deadband 10.000 %
MMXU1: TotVA Deadband 10.000 %
MMXU1: TotPF Deadband 10.000 %
MMXU1: Hz Deadband 10.000 %
MMXU1: PPV phsAB Deadband 10.000 %
MMXU1: PPV phsBC Deadband 10.000 %
MMXU1: PPV phsCA Deadband 10.000 %
MMXU1: PhV phsA Deadband 10.000 %
MMXU1: PhV phsB Deadband 10.000 %
Fri Jun 10 12:09:10 2011 Version: 5.81 Settings (Enabled Features) PAGE 3

SONELGAZ MSILA TP3 T60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: T60-J04-HMH-F8L-H6P-M8N-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONELGAZ MSILA T60 TRANSFORMER MANAGEMENT RELAY
TEXT COLOR

MMXU DEADBANDS (continued from last page)


MMXU1: PhV phsC Deadband 10.000 %
MMXU1: A phsA Deadband 10.000 %
MMXU1: A phsB Deadband 10.000 %
MMXU1: A phsC Deadband 10.000 %
MMXU1: A neut Deadband 10.000 %
MMXU1: W phsA Deadband 10.000 %
MMXU1: W phsB Deadband 10.000 %
MMXU1: W phsC Deadband 10.000 %
MMXU1: VAr phsA Deadband 10.000 %
MMXU1: VAr phsB Deadband 10.000 %
MMXU1: VAr phsC Deadband 10.000 %
MMXU1: VA phsA Deadband 10.000 %
MMXU1: VA phsB Deadband 10.000 %
MMXU1: VA phsC Deadband 10.000 %
MMXU1: PF phsA Deadband 10.000 %
MMXU1: PF phsB Deadband 10.000 %
MMXU1: PF phsC Deadband 10.000 %
MMXU2: TotW Deadband 10.000 %
MMXU2: TotVAr Deadband 10.000 %
MMXU2: TotVA Deadband 10.000 %
MMXU2: TotPF Deadband 10.000 %
MMXU2: Hz Deadband 10.000 %
MMXU2: PPV phsAB Deadband 10.000 %
MMXU2: PPV phsBC Deadband 10.000 %
MMXU2: PPV phsCA Deadband 10.000 %
MMXU2: PhV phsA Deadband 10.000 %
MMXU2: PhV phsB Deadband 10.000 %
MMXU2: PhV phsC Deadband 10.000 %
MMXU2: A phsA Deadband 10.000 %
MMXU2: A phsB Deadband 10.000 %
MMXU2: A phsC Deadband 10.000 %
MMXU2: A neut Deadband 10.000 %
MMXU2: W phsA Deadband 10.000 %
MMXU2: W phsB Deadband 10.000 %
MMXU2: W phsC Deadband 10.000 %
MMXU2: VAr phsA Deadband 10.000 %
MMXU2: VAr phsB Deadband 10.000 %
MMXU2: VAr phsC Deadband 10.000 %
MMXU2: VA phsA Deadband 10.000 %
MMXU2: VA phsB Deadband 10.000 %
MMXU2: VA phsC Deadband 10.000 %
MMXU2: PF phsA Deadband 10.000 %
MMXU2: PF phsB Deadband 10.000 %
MMXU2: PF phsC Deadband 10.000 %
MMXU3: TotW Deadband 10.000 %
MMXU3: TotVAr Deadband 10.000 %
MMXU3: TotVA Deadband 10.000 %
MMXU3: TotPF Deadband 10.000 %
MMXU3: Hz Deadband 10.000 %
MMXU3: PPV phsAB Deadband 10.000 %
MMXU3: PPV phsBC Deadband 10.000 %
MMXU3: PPV phsCA Deadband 10.000 %
MMXU3: PhV phsA Deadband 10.000 %
MMXU3: PhV phsB Deadband 10.000 %
MMXU3: PhV phsC Deadband 10.000 %
MMXU3: A phsA Deadband 10.000 %
MMXU3: A phsB Deadband 10.000 %
MMXU3: A phsC Deadband 10.000 %
MMXU3: A neut Deadband 10.000 %
MMXU3: W phsA Deadband 10.000 %
MMXU3: W phsB Deadband 10.000 %
MMXU3: W phsC Deadband 10.000 %
MMXU3: VAr phsA Deadband 10.000 %
MMXU3: VAr phsB Deadband 10.000 %
MMXU3: VAr phsC Deadband 10.000 %
MMXU3: VA phsA Deadband 10.000 %
MMXU3: VA phsB Deadband 10.000 %
Fri Jun 10 12:09:10 2011 Version: 5.81 Settings (Enabled Features) PAGE 4

SONELGAZ MSILA TP3 T60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: T60-J04-HMH-F8L-H6P-M8N-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONELGAZ MSILA T60 TRANSFORMER MANAGEMENT RELAY
TEXT COLOR

MMXU DEADBANDS (continued from last page)


MMXU3: VA phsC Deadband 10.000 %
MMXU3: PF phsA Deadband 10.000 %
MMXU3: PF phsB Deadband 10.000 %
MMXU3: PF phsC Deadband 10.000 %
MMXU4: TotW Deadband 10.000 %
MMXU4: TotVAr Deadband 10.000 %
MMXU4: TotVA Deadband 10.000 %
MMXU4: TotPF Deadband 10.000 %
MMXU4: Hz Deadband 10.000 %
MMXU4: PPV phsAB Deadband 10.000 %
MMXU4: PPV phsBC Deadband 10.000 %
MMXU4: PPV phsCA Deadband 10.000 %
MMXU4: PhV phsA Deadband 10.000 %
MMXU4: PhV phsB Deadband 10.000 %
MMXU4: PhV phsC Deadband 10.000 %
MMXU4: A phsA Deadband 10.000 %
MMXU4: A phsB Deadband 10.000 %
MMXU4: A phsC Deadband 10.000 %
MMXU4: A neut Deadband 10.000 %
MMXU4: W phsA Deadband 10.000 %
MMXU4: W phsB Deadband 10.000 %
MMXU4: W phsC Deadband 10.000 %
MMXU4: VAr phsA Deadband 10.000 %
MMXU4: VAr phsB Deadband 10.000 %
MMXU4: VAr phsC Deadband 10.000 %
MMXU4: VA phsA Deadband 10.000 %
MMXU4: VA phsB Deadband 10.000 %
MMXU4: VA phsC Deadband 10.000 %
MMXU4: PF phsA Deadband 10.000 %
MMXU4: PF phsB Deadband 10.000 %
MMXU4: PF phsC Deadband 10.000 %

GGIO1 STATUS CONFIGURATION


Number of Status Points 8

GGIO2 CONTROL CONFIGURATION


SPCSO 1 ctlModel 1
SPCSO 2 ctlModel 1
SPCSO 3 ctlModel 1
SPCSO 4 ctlModel 1
SPCSO 5 ctlModel 1
SPCSO 6 ctlModel 1
SPCSO 7 ctlModel 1
SPCSO 8 ctlModel 1
SPCSO 9 ctlModel 1
SPCSO 10 ctlModel 1
SPCSO 11 ctlModel 1
SPCSO 12 ctlModel 1
SPCSO 13 ctlModel 1
SPCSO 14 ctlModel 1
SPCSO 15 ctlModel 1
SPCSO 16 ctlModel 1
SPCSO 17 ctlModel 1
SPCSO 18 ctlModel 1
SPCSO 19 ctlModel 1
SPCSO 20 ctlModel 1
SPCSO 21 ctlModel 1
SPCSO 22 ctlModel 1
SPCSO 23 ctlModel 1
SPCSO 24 ctlModel 1
SPCSO 25 ctlModel 1
SPCSO 26 ctlModel 1
SPCSO 27 ctlModel 1
SPCSO 28 ctlModel 1
SPCSO 29 ctlModel 1
SPCSO 30 ctlModel 1
SPCSO 31 ctlModel 1
Fri Jun 10 12:09:10 2011 Version: 5.81 Settings (Enabled Features) PAGE 5

SONELGAZ MSILA TP3 T60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: T60-J04-HMH-F8L-H6P-M8N-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONELGAZ MSILA T60 TRANSFORMER MANAGEMENT RELAY
TEXT COLOR

GGIO2 CONTROL CONFIGURATION (continued from last page)


SPCSO 32 ctlModel 1
SPCSO 33 ctlModel 1
SPCSO 34 ctlModel 1
SPCSO 35 ctlModel 1
SPCSO 36 ctlModel 1
SPCSO 37 ctlModel 1
SPCSO 38 ctlModel 1
SPCSO 39 ctlModel 1
SPCSO 40 ctlModel 1
SPCSO 41 ctlModel 1
SPCSO 42 ctlModel 1
SPCSO 43 ctlModel 1
SPCSO 44 ctlModel 1
SPCSO 45 ctlModel 1
SPCSO 46 ctlModel 1
SPCSO 47 ctlModel 1
SPCSO 48 ctlModel 1
SPCSO 49 ctlModel 1
SPCSO 50 ctlModel 1
SPCSO 51 ctlModel 1
SPCSO 52 ctlModel 1
SPCSO 53 ctlModel 1
SPCSO 54 ctlModel 1
SPCSO 55 ctlModel 1
SPCSO 56 ctlModel 1
SPCSO 57 ctlModel 1
SPCSO 58 ctlModel 1
SPCSO 59 ctlModel 1
SPCSO 60 ctlModel 1
SPCSO 61 ctlModel 1
SPCSO 62 ctlModel 1
SPCSO 63 ctlModel 1
SPCSO 64 ctlModel 1

GGIO4 ANALOG CONFIGURATION


IEC61850 GGIO4 Analogs 4
IEC61850 GGIO4 Analog 1 Value OFF
IEC61850 GGIO4 Analog 1 db 100.000 %
IEC61850 GGIO4 Analog 1 min 0.000
IEC61850 GGIO4 Analog 1 max 1000000.000
IEC61850 GGIO4 Analog 2 Value OFF
IEC61850 GGIO4 Analog 2 db 100.000 %
IEC61850 GGIO4 Analog 2 min 0.000
IEC61850 GGIO4 Analog 2 max 1000000.000
IEC61850 GGIO4 Analog 3 Value OFF
IEC61850 GGIO4 Analog 3 db 100.000 %
IEC61850 GGIO4 Analog 3 min 0.000
IEC61850 GGIO4 Analog 3 max 1000000.000
IEC61850 GGIO4 Analog 4 Value OFF
IEC61850 GGIO4 Analog 4 db 100.000 %
IEC61850 GGIO4 Analog 4 min 0.000
IEC61850 GGIO4 Analog 4 max 1000000.000
IEC61850 GGIO4 Analog 5 Value OFF
IEC61850 GGIO4 Analog 5 db 100.000 %
IEC61850 GGIO4 Analog 5 min 0.000
IEC61850 GGIO4 Analog 5 max 1000000.000
IEC61850 GGIO4 Analog 6 Value OFF
IEC61850 GGIO4 Analog 6 db 100.000 %
IEC61850 GGIO4 Analog 6 min 0.000
IEC61850 GGIO4 Analog 6 max 1000000.000
IEC61850 GGIO4 Analog 7 Value OFF
IEC61850 GGIO4 Analog 7 db 100.000 %
IEC61850 GGIO4 Analog 7 min 0.000
IEC61850 GGIO4 Analog 7 max 1000000.000
IEC61850 GGIO4 Analog 8 Value OFF
IEC61850 GGIO4 Analog 8 db 100.000 %
IEC61850 GGIO4 Analog 8 min 0.000
Fri Jun 10 12:09:10 2011 Version: 5.81 Settings (Enabled Features) PAGE 6

SONELGAZ MSILA TP3 T60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: T60-J04-HMH-F8L-H6P-M8N-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONELGAZ MSILA T60 TRANSFORMER MANAGEMENT RELAY
TEXT COLOR

GGIO4 ANALOG CONFIGURATION (continued from last page)


IEC61850 GGIO4 Analog 8 max 1000000.000
IEC61850 GGIO4 Analog 9 Value OFF
IEC61850 GGIO4 Analog 9 db 100.000 %
IEC61850 GGIO4 Analog 9 min 0.000
IEC61850 GGIO4 Analog 9 max 1000000.000
IEC61850 GGIO4 Analog 10 Value OFF
IEC61850 GGIO4 Analog 10 db 100.000 %
IEC61850 GGIO4 Analog 10 min 0.000
IEC61850 GGIO4 Analog 10 max 1000000.000
IEC61850 GGIO4 Analog 11 Value OFF
IEC61850 GGIO4 Analog 11 db 100.000 %
IEC61850 GGIO4 Analog 11 min 0.000
IEC61850 GGIO4 Analog 11 max 1000000.000
IEC61850 GGIO4 Analog 12 Value OFF
IEC61850 GGIO4 Analog 12 db 100.000 %
IEC61850 GGIO4 Analog 12 min 0.000
IEC61850 GGIO4 Analog 12 max 1000000.000
IEC61850 GGIO4 Analog 13 Value OFF
IEC61850 GGIO4 Analog 13 db 100.000 %
IEC61850 GGIO4 Analog 13 min 0.000
IEC61850 GGIO4 Analog 13 max 1000000.000
IEC61850 GGIO4 Analog 14 Value OFF
IEC61850 GGIO4 Analog 14 db 100.000 %
IEC61850 GGIO4 Analog 14 min 0.000
IEC61850 GGIO4 Analog 14 max 1000000.000
IEC61850 GGIO4 Analog 15 Value OFF
IEC61850 GGIO4 Analog 15 db 100.000 %
IEC61850 GGIO4 Analog 15 min 0.000
IEC61850 GGIO4 Analog 15 max 1000000.000
IEC61850 GGIO4 Analog 16 Value OFF
IEC61850 GGIO4 Analog 16 db 100.000 %
IEC61850 GGIO4 Analog 16 min 0.000
IEC61850 GGIO4 Analog 16 max 1000000.000
IEC61850 GGIO4 Analog 17 Value OFF
IEC61850 GGIO4 Analog 17 db 100.000 %
IEC61850 GGIO4 Analog 17 min 0.000
IEC61850 GGIO4 Analog 17 max 1000000.000
IEC61850 GGIO4 Analog 18 Value OFF
IEC61850 GGIO4 Analog 18 db 100.000 %
IEC61850 GGIO4 Analog 18 min 0.000
IEC61850 GGIO4 Analog 18 max 1000000.000
IEC61850 GGIO4 Analog 19 Value OFF
IEC61850 GGIO4 Analog 19 db 100.000 %
IEC61850 GGIO4 Analog 19 min 0.000
IEC61850 GGIO4 Analog 19 max 1000000.000
IEC61850 GGIO4 Analog 20 Value OFF
IEC61850 GGIO4 Analog 20 db 100.000 %
IEC61850 GGIO4 Analog 20 min 0.000
IEC61850 GGIO4 Analog 20 max 1000000.000
IEC61850 GGIO4 Analog 21 Value OFF
IEC61850 GGIO4 Analog 21 db 100.000 %
IEC61850 GGIO4 Analog 21 min 0.000
IEC61850 GGIO4 Analog 21 max 1000000.000
IEC61850 GGIO4 Analog 22 Value OFF
IEC61850 GGIO4 Analog 22 db 100.000 %
IEC61850 GGIO4 Analog 22 min 0.000
IEC61850 GGIO4 Analog 22 max 1000000.000
IEC61850 GGIO4 Analog 23 Value OFF
IEC61850 GGIO4 Analog 23 db 100.000 %
IEC61850 GGIO4 Analog 23 min 0.000
IEC61850 GGIO4 Analog 23 max 1000000.000
IEC61850 GGIO4 Analog 24 Value OFF
IEC61850 GGIO4 Analog 24 db 100.000 %
IEC61850 GGIO4 Analog 24 min 0.000
IEC61850 GGIO4 Analog 24 max 1000000.000
IEC61850 GGIO4 Analog 25 Value OFF
IEC61850 GGIO4 Analog 25 db 100.000 %
Fri Jun 10 12:09:10 2011 Version: 5.81 Settings (Enabled Features) PAGE 7

SONELGAZ MSILA TP3 T60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: T60-J04-HMH-F8L-H6P-M8N-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONELGAZ MSILA T60 TRANSFORMER MANAGEMENT RELAY
TEXT COLOR

GGIO4 ANALOG CONFIGURATION (continued from last page)


IEC61850 GGIO4 Analog 25 min 0.000
IEC61850 GGIO4 Analog 25 max 1000000.000
IEC61850 GGIO4 Analog 26 Value OFF
IEC61850 GGIO4 Analog 26 db 100.000 %
IEC61850 GGIO4 Analog 26 min 0.000
IEC61850 GGIO4 Analog 26 max 1000000.000
IEC61850 GGIO4 Analog 27 Value OFF
IEC61850 GGIO4 Analog 27 db 100.000 %
IEC61850 GGIO4 Analog 27 min 0.000
IEC61850 GGIO4 Analog 27 max 1000000.000
IEC61850 GGIO4 Analog 28 Value OFF
IEC61850 GGIO4 Analog 28 db 100.000 %
IEC61850 GGIO4 Analog 28 min 0.000
IEC61850 GGIO4 Analog 28 max 1000000.000
IEC61850 GGIO4 Analog 29 Value OFF
IEC61850 GGIO4 Analog 29 db 100.000 %
IEC61850 GGIO4 Analog 29 min 0.000
IEC61850 GGIO4 Analog 29 max 1000000.000
IEC61850 GGIO4 Analog 30 Value OFF
IEC61850 GGIO4 Analog 30 db 100.000 %
IEC61850 GGIO4 Analog 30 min 0.000
IEC61850 GGIO4 Analog 30 max 1000000.000
IEC61850 GGIO4 Analog 31 Value OFF
IEC61850 GGIO4 Analog 31 db 100.000 %
IEC61850 GGIO4 Analog 31 min 0.000
IEC61850 GGIO4 Analog 31 max 1000000.000
IEC61850 GGIO4 Analog 32 Value OFF
IEC61850 GGIO4 Analog 32 db 100.000 %
IEC61850 GGIO4 Analog 32 min 0.000
IEC61850 GGIO4 Analog 32 max 1000000.000

REPORT CONTROL CONFIGURATION


REPORT 1 (GGIO1.BR): RptID
REPORT 1 (GGIO1.BR): OptFlds 0
REPORT 1 (GGIO1.BR): BufTm 0
REPORT 1 (GGIO1.BR): TrgOps 0
REPORT 1 (GGIO1.BR): IntgPd 0
REPORT 2 (GGIO1.BR01): RptID
REPORT 2 (GGIO1.BR01): OptFlds 0
REPORT 2 (GGIO1.BR01): BufTm 0
REPORT 2 (GGIO1.BR01): TrgOps 0
REPORT 2 (GGIO1.BR01): IntgPd 0
REPORT 3 (GGIO1.RP): RptID
REPORT 3 (GGIO1.RP): OptFlds 0
REPORT 3 (GGIO1.RP): BufTm 0
REPORT 3 (GGIO1.RP): TrgOps 0
REPORT 3 (GGIO1.RP): IntgPd 0
REPORT 4 (GGIO4.RP): RptID
REPORT 4 (GGIO4.RP): OptFlds 0
REPORT 4 (GGIO4.RP): BufTm 0
REPORT 4 (GGIO4.RP): TrgOps 0
REPORT 4 (GGIO4.RP): IntgPd 0
REPORT 5 (MMXU1.BR): RptID
REPORT 5 (MMXU1.BR): OptFlds 0
REPORT 5 (MMXU1.BR): BufTm 0
REPORT 5 (MMXU1.BR): TrgOps 0
REPORT 5 (MMXU1.BR): IntgPd 0
REPORT 6 (MMXU1.RP): RptID
REPORT 6 (MMXU1.RP): OptFlds 0
REPORT 6 (MMXU1.RP): BufTm 0
REPORT 6 (MMXU1.RP): TrgOps 0
REPORT 6 (MMXU1.RP): IntgPd 0
REPORT 7 (MMXU2.BR): RptID
REPORT 7 (MMXU2.BR): OptFlds 0
REPORT 7 (MMXU2.BR): BufTm 0
REPORT 7 (MMXU2.BR): TrgOps 0
REPORT 7 (MMXU2.BR): IntgPd 0
Fri Jun 10 12:09:10 2011 Version: 5.81 Settings (Enabled Features) PAGE 8

SONELGAZ MSILA TP3 T60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: T60-J04-HMH-F8L-H6P-M8N-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONELGAZ MSILA T60 TRANSFORMER MANAGEMENT RELAY
TEXT COLOR

REPORT CONTROL CONFIGURATION (continued from last page)


REPORT 8 (MMXU2.RP): RptID
REPORT 8 (MMXU2.RP): OptFlds 0
REPORT 8 (MMXU2.RP): BufTm 0
REPORT 8 (MMXU2.RP): TrgOps 0
REPORT 8 (MMXU2.RP): IntgPd 0
REPORT 9 (MMXU3.BR): RptID
REPORT 9 (MMXU3.BR): OptFlds 0
REPORT 9 (MMXU3.BR): BufTm 0
REPORT 9 (MMXU3.BR): TrgOps 0
REPORT 9 (MMXU3.BR): IntgPd 0
REPORT 10 (MMXU3.RP): RptID
REPORT 10 (MMXU3.RP): OptFlds 0
REPORT 10 (MMXU3.RP): BufTm 0
REPORT 10 (MMXU3.RP): TrgOps 0
REPORT 10 (MMXU3.RP): IntgPd 0
REPORT 11 (MMXU4.BR): RptID
REPORT 11 (MMXU4.BR): OptFlds 0
REPORT 11 (MMXU4.BR): BufTm 0
REPORT 11 (MMXU4.BR): TrgOps 0
REPORT 11 (MMXU4.BR): IntgPd 0
REPORT 12 (MMXU4.RP): RptID
REPORT 12 (MMXU4.RP): OptFlds 0
REPORT 12 (MMXU4.RP): BufTm 0
REPORT 12 (MMXU4.RP): TrgOps 0
REPORT 12 (MMXU4.RP): IntgPd 0

XCBR CONFIGURATION
XCBR1 ST.Loc Operand OFF
XCBR2 ST.Loc Operand OFF
XCBR3 ST.Loc Operand OFF
XCBR4 ST.Loc Operand OFF
Clear XCBR1 OpCnt No
Clear XCBR2 OpCnt No
Clear XCBR3 OpCnt No
Clear XCBR4 OpCnt No

XSWI CONFIGURATION
XSWI1 ST.Loc Operand OFF
XSWI2 ST.Loc Operand OFF
XSWI3 ST.Loc Operand OFF
XSWI4 ST.Loc Operand OFF
XSWI5 ST.Loc Operand OFF
XSWI6 ST.Loc Operand OFF
XSWI7 ST.Loc Operand OFF
XSWI8 ST.Loc Operand OFF
XSWI9 ST.Loc Operand OFF
XSWI10 ST.Loc Operand OFF
XSWI11 ST.Loc Operand OFF
XSWI12 ST.Loc Operand OFF
XSWI13 ST.Loc Operand OFF
XSWI14 ST.Loc Operand OFF
XSWI15 ST.Loc Operand OFF
XSWI16 ST.Loc Operand OFF
Clear XSWI1 OpCnt No
Clear XSWI2 OpCnt No
Clear XSWI3 OpCnt No
Clear XSWI4 OpCnt No
Clear XSWI5 OpCnt No
Clear XSWI6 OpCnt No
Clear XSWI7 OpCnt No
Clear XSWI8 OpCnt No
Clear XSWI9 OpCnt No
Clear XSWI10 OpCnt No
Clear XSWI11 OpCnt No
Clear XSWI12 OpCnt No
Clear XSWI13 OpCnt No
Clear XSWI14 OpCnt No
Fri Jun 10 12:09:10 2011 Version: 5.81 Settings (Enabled Features) PAGE 9

SONELGAZ MSILA TP3 T60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: T60-J04-HMH-F8L-H6P-M8N-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONELGAZ MSILA T60 TRANSFORMER MANAGEMENT RELAY
TEXT COLOR

XSWI CONFIGURATION (continued from last page)


Clear XSWI15 OpCnt No
Clear XSWI16 OpCnt No

HTTP
HTTP TCP Port Number 80

TFTP
TFTP Main UDP Port Number 69
TFTP Data UDP Port Number 1 0
TFTP Data UDP Port Number 2 0

EGD PROTOCOL
FAST PRODUCER EXCHANGE
Function Enabled
Destination 192.168.101.255
Data Rate 50 ms
Data Item 1 5416
Data Item 2 5417
Data Item 3 5418
Data Item 4 5419
Data Item 5 5420
Data Item 6 5421
Data Item 7 0
Data Item 8 0
Data Item 9 0
Data Item 10 0
Data Item 11 0
Data Item 12 0
Data Item 13 0
Data Item 14 0
Data Item 15 0
Data Item 16 0
Data Item 17 0
Data Item 18 0
Data Item 19 0
Data Item 20 0

REAL TIME CLOCK


IRIG-B Signal Type DC Shift
Real Time Clock Events Enabled
Time Zone Offset 0.0 hr
DST Function Enabled
DST Start Month January
DST Start Day Sunday
DST Start Day Instance First
DST Start Hour 2
DST Stop Month January
DST Stop Day Sunday
DST Stop Day Instance First
DST Stop Hour 2

OSCILLOGRAPHY
Number Of Records 15
Trigger Mode Automatic Overwrite
Trigger Position 25 %
Trigger Source Osc Initiate On (VO8)
AC Input Waveforms 32 samples/cycle
Digital Channel 1 VOLTS PER HERTZ 1 OP
Digital Channel 2 VOLTS PER HERTZ 2 OP
Digital Channel 3 XFMR INST DIFF OP
Digital Channel 4 XFMR PCNT DIFF OP
Digital Channel 5 XFMR INST DIFF OP A
Digital Channel 6 XFMR INST DIFF OP B
Digital Channel 7 XFMR INST DIFF OP C
Digital Channel 8 XFMR PCNT DIFF 2ND A
Digital Channel 9 XFMR PCNT DIFF 2ND B
Digital Channel 10 XFMR PCNT DIFF 2ND C
Fri Jun 10 12:09:10 2011 Version: 5.81 Settings (Enabled Features) PAGE 10

SONELGAZ MSILA TP3 T60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: T60-J04-HMH-F8L-H6P-M8N-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONELGAZ MSILA T60 TRANSFORMER MANAGEMENT RELAY
TEXT COLOR

OSCILLOGRAPHY (continued from last page)


Digital Channel 11 XFMR PCNT DIFF OP A
Digital Channel 12 XFMR PCNT DIFF OP B
Digital Channel 13 XFMR PCNT DIFF OP C
Digital Channel 14 PHASE TOC1 OP
Digital Channel 15 PHASE IOC1 OP
Digital Channel 16 PHASE IOC2 OP
Digital Channel 17 PHASE TOC3 OP
Digital Channel 18 PHASE IOC3 OP
Digital Channel 19 PHASE TOC5 OP
Digital Channel 20 PHASE IOC5 OP
Digital Channel 21 PHASE TOC1 OP A
Digital Channel 22 PHASE TOC1 OP B
Digital Channel 23 PHASE TOC1 OP C
Digital Channel 24 PHASE IOC1 OP A
Digital Channel 25 PHASE IOC1 OP B
Digital Channel 26 PHASE IOC1 OP C
Digital Channel 27 PHASE IOC2 OP A
Digital Channel 28 PHASE IOC2 OP B
Digital Channel 29 PHASE IOC2 OP C
Digital Channel 30 PHASE TOC3 OP A
Digital Channel 31 PHASE TOC3 OP B
Digital Channel 32 PHASE TOC3 OP C
Digital Channel 33 PHASE IOC3 OP A
Digital Channel 34 PHASE IOC3 OP B
Digital Channel 35 PHASE IOC3 OP C
Digital Channel 36 PHASE TOC5 OP A
Digital Channel 37 PHASE TOC5 OP B
Digital Channel 38 PHASE TOC5 OP C
Digital Channel 39 PHASE IOC5 OP A
Digital Channel 40 PHASE IOC5 OP B
Digital Channel 41 PHASE IOC5 OP C
Digital Channel 42 PHASE IOC6 OP A
Digital Channel 43 PHASE IOC6 OP B
Digital Channel 44 PHASE IOC6 OP C
Digital Channel 45 GROUND TOC1 OP
Digital Channel 46 GROUND IOC1 OP
Digital Channel 47 Pri CB 52a On(H7a)
Digital Channel 48 Pri CB 52b On(H7c)
Digital Channel 49 CB 52G 52a On(P1a)
Digital Channel 50 CB 52G 52b On(P1c)
Digital Channel 51 TL Sec 52a On(P2a)
Digital Channel 52 TL Sec 52b On(P2c)
Digital Channel 53 87T Oper On (VO51)
Digital Channel 54 50/51P Oper On (VO52)
Digital Channel 55 51P Gen Oper On (VO53)
Digital Channel 56 51P Aux Oper On (VO54)
Digital Channel 57 51NP Oper On (VO55)
Digital Channel 58 24T Oper On (VO56)
Digital Channel 59 H1 Out Oper On (VO21)
Digital Channel 60 H2 Out Oper On (VO22)
Digital Channel 61 H3 Out Oper On (VO23)
Digital Channel 62 H4 Out Oper On (VO24)
Digital Channel 63 VTFF Oper On (VO49)
Analog Channel 1 SRC1 Ia Mag
Analog Channel 2 SRC1 Ib Mag
Analog Channel 3 SRC1 Ic Mag
Analog Channel 4 SRC2 Ia Mag
Analog Channel 5 SRC2 Ib Mag
Analog Channel 6 SRC2 Ic Mag
Analog Channel 8 SRC4 Vx Mag
Analog Channel 9 Volts Per Hertz 1
Analog Channel 10 Xfmr Iad Mag
Analog Channel 11 Xfmr Iar Mag
Analog Channel 12 Xfmr Ibd Mag
Analog Channel 13 Xfmr Ibr Mag
Analog Channel 14 Xfmr Icd Mag
Analog Channel 15 Xfmr Icr Mag
Fri Jun 10 12:09:10 2011 Version: 5.81 Settings (Enabled Features) PAGE 11

SONELGAZ MSILA TP3 T60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: T60-J04-HMH-F8L-H6P-M8N-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONELGAZ MSILA T60 TRANSFORMER MANAGEMENT RELAY
TEXT COLOR

OSCILLOGRAPHY (continued from last page)


Analog Channel 16 Tracking Frequency

DATA LOGGER
Data Logger Mode Continuous
Data Logger Trigger OFF
Rate 60000 msec
Channel 1 SRC1 Ia RMS
Channel 2 SRC1 Ib RMS
Channel 3 SRC1 Ic RMS
Channel 4 SRC2 Ia RMS
Channel 5 SRC2 Ib RMS
Channel 6 SRC2 Ic RMS
Channel 7 SRC1 I_1 Mag
Channel 8 SRC1 I_2 Mag
Channel 9 SRC1 I_0 Mag
Channel 10 SRC4 Vx Mag
Channel 11 SRC2 Vab RMS
Channel 12 SRC2 Vbc RMS
Channel 13 SRC2 Vca RMS
Channel 14 SRC1 Ig Mag
Channel 15 Volts Per Hertz 1
Channel 16 Tracking Frequency

DEMAND
Current Method Thermal Exponential
Power Method Thermal Exponential
Interval 15 MIN
Trigger OFF

USER-PROGRAMMABLE LEDS
LED TEST
Function Enabled
Control CONTROL PUSHBUTTON 3 ON

TRIP AND ALARMS LEDS


Trip LED Input Trip LED In On (VO7)
Alarm LED Input Alrm LED In On (VO6)

USER PROGRAMMABLE LEDS


LED 1: OPERAND BREAKER 1 OPEN
LED 1: TYPE Self-Reset
LED 2: OPERAND BREAKER 1 CLOSED
LED 2: TYPE Self-Reset
LED 3: OPERAND BREAKER 1 BAD STATUS
LED 3: TYPE Self-Reset
LED 5: OPERAND BREAKER 2 OPEN
LED 5: TYPE Self-Reset
LED 6: OPERAND BREAKER 2 CLOSED
LED 6: TYPE Self-Reset
LED 7: OPERAND BREAKER 2 BAD STATUS
LED 7: TYPE Self-Reset
LED 9: OPERAND BREAKER 3 OPEN
LED 9: TYPE Self-Reset
LED 10: OPERAND BREAKER 3 CLOSED
LED 10: TYPE Self-Reset
LED 11: OPERAND BREAKER 3 BAD STATUS
LED 11: TYPE Self-Reset
LED 12: OPERAND SETTING GROUP ACT 1
LED 12: TYPE Self-Reset
LED 13: OPERAND H1 Out Oper On (VO21)
LED 13: TYPE Latched
LED 14: OPERAND H2 Out Oper On (VO22)
LED 14: TYPE Latched
LED 15: OPERAND H3 Out Oper On (VO23)
LED 15: TYPE Latched
LED 16: OPERAND H4 Out Oper On (VO24)
LED 16: TYPE Latched
Fri Jun 10 12:09:10 2011 Version: 5.81 Settings (Enabled Features) PAGE 12

SONELGAZ MSILA TP3 T60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: T60-J04-HMH-F8L-H6P-M8N-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONELGAZ MSILA T60 TRANSFORMER MANAGEMENT RELAY
TEXT COLOR

USER PROGRAMMABLE LEDS (continued from last page)


LED 23: OPERAND W1 Out Oper On (VO81)
LED 23: TYPE Latched
LED 24: OPERAND W2 Out Oper On (VO82)
LED 24: TYPE Self-Reset
LED 25: OPERAND XFMR PCNT DIFF 2ND A
LED 25: TYPE Self-Reset
LED 26: OPERAND XFMR PCNT DIFF 2ND B
LED 26: TYPE Self-Reset
LED 27: OPERAND XFMR PCNT DIFF 2ND C
LED 27: TYPE Self-Reset
LED 36: OPERAND VTFF Oper On (VO49)
LED 36: TYPE Self-Reset
LED 37: OPERAND 87T Oper On (VO51)
LED 37: TYPE Latched
LED 38: OPERAND 50/51P Oper On (VO52)
LED 38: TYPE Latched
LED 39: OPERAND 51P Gen Oper On (VO53)
LED 39: TYPE Latched
LED 40: OPERAND 51P Aux Oper On (VO54)
LED 40: TYPE Latched
LED 41: OPERAND 51NP Oper On (VO55)
LED 41: TYPE Latched
LED 42: OPERAND 24T Oper On (VO56)
LED 42: TYPE Latched
LED 43: OPERAND 64B Oper On (VO58)
LED 43: TYPE Latched

USER-PROGRAMMABLE SELF TESTS


Battery Fail Function Enabled

CONTROL PUSHBUTTONS
CPB 1: Function Enabled
CPB 1: Events Disabled
CPB 3: Function Enabled
CPB 3: Events Disabled

USER-DEFINABLE DISPLAYS
USER DISPLAY 1: Top Line MSila TP3 T60
USER DISPLAY 1: Bottom Line Rev 0 13-June 2011
USER DISPLAY 1: Item 1 0
USER DISPLAY 1: Item 2 0
USER DISPLAY 1: Item 3 0
USER DISPLAY 1: Item 4 0
USER DISPLAY 1: Item 5 0
USER DISPLAY 2: Top Line Ia-pri: ~
USER DISPLAY 2: Bottom Line Ib-pri: ~
USER DISPLAY 2: Item 1 6144
USER DISPLAY 2: Item 2 6146
USER DISPLAY 2: Item 3 0
USER DISPLAY 2: Item 4 0
USER DISPLAY 2: Item 5 0
USER DISPLAY 3: Top Line Ic-pri: ~
USER DISPLAY 3: Bottom Line
USER DISPLAY 3: Item 1 6148
USER DISPLAY 3: Item 2 0
USER DISPLAY 3: Item 3 0
USER DISPLAY 3: Item 4 0
USER DISPLAY 3: Item 5 0
USER DISPLAY 4: Top Line Ia-Gen: ~
USER DISPLAY 4: Bottom Line Ib-Gen: ~
USER DISPLAY 4: Item 1 6208
USER DISPLAY 4: Item 2 6210
USER DISPLAY 4: Item 3 0
USER DISPLAY 4: Item 4 0
USER DISPLAY 4: Item 5 0
USER DISPLAY 5: Top Line Ic-Gen: ~
USER DISPLAY 5: Bottom Line
Fri Jun 10 12:09:10 2011 Version: 5.81 Settings (Enabled Features) PAGE 13

SONELGAZ MSILA TP3 T60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: T60-J04-HMH-F8L-H6P-M8N-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONELGAZ MSILA T60 TRANSFORMER MANAGEMENT RELAY
TEXT COLOR

USER-DEFINABLE DISPLAYS (continued from last page)


USER DISPLAY 5: Item 1 6212
USER DISPLAY 5: Item 2 0
USER DISPLAY 5: Item 3 0
USER DISPLAY 5: Item 4 0
USER DISPLAY 5: Item 5 0
USER DISPLAY 6: Top Line Ia-Aux: ~
USER DISPLAY 6: Bottom Line Ib-Aux: ~
USER DISPLAY 6: Item 1 6272
USER DISPLAY 6: Item 2 6274
USER DISPLAY 6: Item 3 0
USER DISPLAY 6: Item 4 0
USER DISPLAY 6: Item 5 0
USER DISPLAY 7: Top Line Ic-Aux: ~
USER DISPLAY 7: Bottom Line
USER DISPLAY 7: Item 1 6276
USER DISPLAY 7: Item 2 0
USER DISPLAY 7: Item 3 0
USER DISPLAY 7: Item 4 0
USER DISPLAY 7: Item 5 0
Invoke and Scroll CONTROL PUSHBUTTON 1 ON

INSTALLATION
Relay Name MSila TP3 T60

SYSTEM SETUP
AC INPUTS
CURRENT
CT F1: Phase CT Primary 400 A
CT F1: Phase CT Secondary 1A
CT F1: Ground CT Primary 400 A
CT F1: Ground CT Secondary 1A
CT M1: Phase CT Primary 7500 A
CT M1: Phase CT Secondary 1A
CT M1: Ground CT Primary 7500 A
CT M1: Ground CT Secondary 1A
CT M5: Phase CT Primary 300 A
CT M5: Phase CT Secondary 1A
CT M5: Ground CT Primary 300 A
CT M5: Ground CT Secondary 1A

VOLTAGE
VT F5: Phase VT Connection Wye
VT F5: Phase VT Secondary 57.7 V
VT F5: Phase VT Ratio 115.00 :1
VT F5: Auxiliary VT Connection Vn
VT F5: Auxiliary VT Secondary 173.2 V
VT F5: Auxiliary VT Ratio 115.00 :1

POWER SYSTEM
Nominal Frequency 50 Hz
Phase Rotation ABC
Frequency And Phase Reference S-Gen (SRC 2)
Frequency Tracking Function Enabled

SIGNAL SOURCES
SOURCE 1: Name Xf Pri
SOURCE 1: Phase CT F1
SOURCE 1: Ground CT F1
SOURCE 1: Phase VT None
SOURCE 1: Auxiliary VT None
SOURCE 2: Name S-Gen
SOURCE 2: Phase CT M1
SOURCE 2: Ground CT None
SOURCE 2: Phase VT F5
SOURCE 2: Auxiliary VT None
SOURCE 3: Name S-Aux
SOURCE 3: Phase CT M5
Fri Jun 10 12:09:10 2011 Version: 5.81 Settings (Enabled Features) PAGE 14

SONELGAZ MSILA TP3 T60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: T60-J04-HMH-F8L-H6P-M8N-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONELGAZ MSILA T60 TRANSFORMER MANAGEMENT RELAY
TEXT COLOR

SIGNAL SOURCES (continued from last page)


SOURCE 3: Ground CT None
SOURCE 3: Phase VT F5
SOURCE 3: Auxiliary VT None
SOURCE 4: Name Bus Gr
SOURCE 4: Phase CT None
SOURCE 4: Ground CT None
SOURCE 4: Phase VT F5
SOURCE 4: Auxiliary VT F5

TRANSFORMER
GENERAL
Number Of Windings 3
Reference Winding Selection Automatic Selection
Phase Compensation Internal (software)
Load Loss At Rated Load 100 kW
Rated Winding Temperature Rise 65°C (oil)
No Load Loss 10 kW
Type Of Cooling OA
Top-oil Rise Over Ambient 35 °C
Thermal Capacity 100.00 kWh/°C
Winding Thermal Time Constant 2.00 min

WINDINGS
WINDING 1: Source Xf Pri (SRC 1)
WINDING 1: Rated MVA 125.000 MVA
WINDING 1: Nominal Phs-phs Voltage 240.750 kV
WINDING 1: Connection Wye
WINDING 1: Grounding Within zone
WINDING 1: Angle Wrt Winding 1 0.0 deg
WINDING 1: Resistance 10.0000 ohms
WINDING 2: Source S-Gen (SRC 2)
WINDING 2: Rated MVA 125.000 MVA
WINDING 2: Nominal Phs-phs Voltage 11.500 kV
WINDING 2: Connection Delta
WINDING 2: Grounding Not within zone
WINDING 2: Angle Wrt Winding 1 -330.0 deg
WINDING 2: Resistance 10.0000 ohms
WINDING 3: Source S-Aux (SRC 3)
WINDING 3: Rated MVA 3.000 MVA
WINDING 3: Nominal Phs-phs Voltage 11.500 kV
WINDING 3: Connection Delta
WINDING 3: Grounding Not within zone
WINDING 3: Angle Wrt Winding 1 -330.0 deg
WINDING 3: Resistance 10.0000 ohms

THERMAL INPUTS
Winding Currents Xf Pri (SRC 1)
Ambient Temperature Sensor RRTD Input 1
Ambient Temperature January Average -20 °C
Ambient Temperature February Average -30 °C
Ambient Temperature March Average -10 °C
Ambient Temperature April Average 10 °C
Ambient Temperature May Average 20 °C
Ambient Temperature June Average 30 °C
Ambient Temperature July Average 30 °C
Ambient Temperature August Average 30 °C
Ambient Temperature September Average 20 °C
Ambient Temperature October Average 10 °C
Ambient Temperature November Average 10 °C
Ambient Temperature December Average -10 °C
Top Oil Temperature Sensor RRTD Input 1

BREAKERS
Breaker 1 Function Enabled
Breaker 1 Push Button Control Disabled
Breaker 1 Name CB 52L
Breaker 1 Mode 3-Pole
Fri Jun 10 12:09:10 2011 Version: 5.81 Settings (Enabled Features) PAGE 15

SONELGAZ MSILA TP3 T60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: T60-J04-HMH-F8L-H6P-M8N-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONELGAZ MSILA T60 TRANSFORMER MANAGEMENT RELAY
TEXT COLOR

BREAKERS (continued from last page)


Breaker 1 Open OFF
Breaker 1 Block Open OFF
Breaker 1 Close OFF
Breaker 1 Block Close OFF
Breaker 1 Phase A/3-Pole Closed Pri CB 52a On(H7a)
Breaker 1 Phase A/3-Pole Opened Pri CB 52b On(H7c)
Breaker 1 Phase B Closed OFF
Breaker 1 Phase B Opened OFF
Breaker 1 Phase C Closed OFF
Breaker 1 Phase C Opened OFF
Breaker 1 Toperate 0.070 s
Breaker 1 External Alarm OFF
Breaker 1 Alarm Delay 0.000 s
Breaker 1 Manual Close Recal Time 0.000 s
Breaker 1 Out Of Service OFF
Breaker 1 Events Enabled
Breaker 2 Function Enabled
Breaker 2 Push Button Control Disabled
Breaker 2 Name CB 52G
Breaker 2 Mode 3-Pole
Breaker 2 Open OFF
Breaker 2 Block Open OFF
Breaker 2 Close OFF
Breaker 2 Block Close OFF
Breaker 2 Phase A/3-Pole Closed CB 52G 52a On(P1a)
Breaker 2 Phase A/3-Pole Opened CB 52G 52b On(P1c)
Breaker 2 Phase B Closed OFF
Breaker 2 Phase B Opened OFF
Breaker 2 Phase C Closed OFF
Breaker 2 Phase C Opened OFF
Breaker 2 Toperate 0.070 s
Breaker 2 External Alarm OFF
Breaker 2 Alarm Delay 0.000 s
Breaker 2 Manual Close Recal Time 0.000 s
Breaker 2 Out Of Service OFF
Breaker 2 Events Disabled
Breaker 3 Function Enabled
Breaker 3 Push Button Control Disabled
Breaker 3 Name TL Sec
Breaker 3 Mode 3-Pole
Breaker 3 Open OFF
Breaker 3 Block Open OFF
Breaker 3 Close OFF
Breaker 3 Block Close OFF
Breaker 3 Phase A/3-Pole Closed TL Sec 52a On(P2a)
Breaker 3 Phase A/3-Pole Opened TL Sec 52b On(P2c)
Breaker 3 Phase B Closed OFF
Breaker 3 Phase B Opened OFF
Breaker 3 Phase C Closed OFF
Breaker 3 Phase C Opened OFF
Breaker 3 Toperate 0.070 s
Breaker 3 External Alarm OFF
Breaker 3 Alarm Delay 0.000 s
Breaker 3 Manual Close Recal Time 0.000 s
Breaker 3 Out Of Service OFF
Breaker 3 Events Disabled

FLEXLOGIC
FLEXLOGIC EQUATION EDITOR
FlexLogic Entry 1 RESET OP (PUSHBUTTON)
FlexLogic Entry 2 NOT
FlexLogic Entry 3 = Reset Sealin (VO9)
FlexLogic Entry 4 SRC2 VT FUSE FAIL OP
FlexLogic Entry 5 SRC3 VT FUSE FAIL OP
FlexLogic Entry 6 OR(2)
FlexLogic Entry 7 = VTFF Oper (VO49)
FlexLogic Entry 8 ANY MAJOR ERROR
Fri Jun 10 12:09:10 2011 Version: 5.81 Settings (Enabled Features) PAGE 16

SONELGAZ MSILA TP3 T60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: T60-J04-HMH-F8L-H6P-M8N-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONELGAZ MSILA T60 TRANSFORMER MANAGEMENT RELAY
TEXT COLOR

FLEXLOGIC EQUATION EDITOR (continued from last page)


FlexLogic Entry 9 ANY MINOR ERROR
FlexLogic Entry 10 OR(2)
FlexLogic Entry 11 RESET OP (PUSHBUTTON)
FlexLogic Entry 12 LATCH
FlexLogic Entry 13 = T60 Rly Fail (VO10)
FlexLogic Entry 14 XFMR PCNT DIFF OP
FlexLogic Entry 15 XFMR INST DIFF OP
FlexLogic Entry 16 OR(2)
FlexLogic Entry 17 = 87T Oper (VO51)
FlexLogic Entry 18 PHASE TOC1 OP
FlexLogic Entry 19 PHASE IOC1 OP
FlexLogic Entry 20 PHASE IOC2 OP
FlexLogic Entry 21 OR(3)
FlexLogic Entry 22 = 50/51P Oper (VO52)
FlexLogic Entry 23 PHASE TOC3 OP
FlexLogic Entry 24 PHASE IOC3 OP
FlexLogic Entry 25 OR(2)
FlexLogic Entry 26 = 51P Gen Oper (VO53)
FlexLogic Entry 27 PHASE TOC5 OP
FlexLogic Entry 28 PHASE IOC5 OP
FlexLogic Entry 29 PHASE IOC6 OP
FlexLogic Entry 30 OR(3)
FlexLogic Entry 31 = 51P Aux Oper (VO54)
FlexLogic Entry 32 VOLTS PER HERTZ 1 OP
FlexLogic Entry 33 VOLTS PER HERTZ 2 OP
FlexLogic Entry 34 OR(2)
FlexLogic Entry 35 = 24T Oper (VO56)
FlexLogic Entry 36 GROUND TOC1 OP
FlexLogic Entry 37 GROUND IOC1 OP
FlexLogic Entry 38 OR(2)
FlexLogic Entry 39 = 51NP Oper (VO55)
FlexLogic Entry 40 AUX OV 1 OP
FlexLogic Entry 41 = 64B Oper (VO58)
FlexLogic Entry 42 87T Oper On (VO51)
FlexLogic Entry 43 50/51P Oper On (VO52)
FlexLogic Entry 44 51P Gen Oper On (VO53)
FlexLogic Entry 45 51P Aux Oper On (VO54)
FlexLogic Entry 46 51NP Oper On (VO55)
FlexLogic Entry 47 24T Oper On (VO56)
FlexLogic Entry 48 64B Oper On (VO58)
FlexLogic Entry 49 63TP Stg2 Op On(P7c)
FlexLogic Entry 50 45FTP Oper On(P8c)
FlexLogic Entry 51 OR(9)
FlexLogic Entry 52 TIMER 21
FlexLogic Entry 53 = H1 Out Oper (VO21)
FlexLogic Entry 54 G60-52L Trp1 On(H8a)
FlexLogic Entry 55 G60-52L Trp2 On(H8c)
FlexLogic Entry 56 DL91 Pr Trip On(P3c)
FlexLogic Entry 57 OR(3)
FlexLogic Entry 58 TIMER 22
FlexLogic Entry 59 = H3 Out Oper (VO23)
FlexLogic Entry 60 G60-52L Trp1 On(H8a)
FlexLogic Entry 61 G60-52L Trp2 On(H8c)
FlexLogic Entry 62 DL91 Pr Trip On(P3c)
FlexLogic Entry 63 OR(3)
FlexLogic Entry 64 TIMER 23
FlexLogic Entry 65 = H4 Out Oper (VO24)
FlexLogic Entry 66 87T Oper On (VO51)
FlexLogic Entry 67 50/51P Oper On (VO52)
FlexLogic Entry 68 51P Gen Oper On (VO53)
FlexLogic Entry 69 51P Aux Oper On (VO54)
FlexLogic Entry 70 51NP Oper On (VO55)
FlexLogic Entry 71 24T Oper On (VO56)
FlexLogic Entry 72 64B Oper On (VO58)
FlexLogic Entry 73 49TP Stg2 Op On(P6c)
FlexLogic Entry 74 63TP Stg2 Op On(P7c)
FlexLogic Entry 75 45FTP Oper On(P8c)
Fri Jun 10 12:09:10 2011 Version: 5.81 Settings (Enabled Features) PAGE 17

SONELGAZ MSILA TP3 T60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: T60-J04-HMH-F8L-H6P-M8N-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONELGAZ MSILA T60 TRANSFORMER MANAGEMENT RELAY
TEXT COLOR

FLEXLOGIC EQUATION EDITOR (continued from last page)


FlexLogic Entry 76 DL91 Pr Trip On(P3c)
FlexLogic Entry 77 OR(11)
FlexLogic Entry 78 TIMER 24
FlexLogic Entry 79 = H6 Out Oper (VO26)
FlexLogic Entry 80 87T Oper On (VO51)
FlexLogic Entry 81 = U1 Out Oper (VO27)
FlexLogic Entry 82 50/51P Oper On (VO52)
FlexLogic Entry 83 = U2 Out Oper (VO28)
FlexLogic Entry 84 51NP Oper On (VO55)
FlexLogic Entry 85 = U3 Out Oper (VO29)
FlexLogic Entry 86 51P Gen Oper On (VO53)
FlexLogic Entry 87 = U4 Out Oper (VO30)
FlexLogic Entry 88 51P Aux Oper On (VO54)
FlexLogic Entry 89 = U5 Out Oper (VO31)
FlexLogic Entry 90 24T Oper On (VO56)
FlexLogic Entry 91 = U6 Out Oper (VO32)
FlexLogic Entry 92 26TP Stg2 Op On(P5c)
FlexLogic Entry 93 = U7 Out Oper (VO33)
FlexLogic Entry 94 49TP Stg2 Op On(P6c)
FlexLogic Entry 95 = U8 Out Oper (VO34)
FlexLogic Entry 96 63TP Stg2 Op On(P7c)
FlexLogic Entry 97 = U9 Out Oper (VO35)
FlexLogic Entry 98 45FTP Oper On(P8c)
FlexLogic Entry 99 = U10 Out Oper (VO36)
FlexLogic Entry 100 64B Oper On (VO58)
FlexLogic Entry 101 = U12 Out Oper (VO38)
FlexLogic Entry 102 DL91 Pr Trip On(P3c)
FlexLogic Entry 103 = U13 Out Oper (VO39)
FlexLogic Entry 104 87T Oper On (VO51)
FlexLogic Entry 105 50/51P Oper On (VO52)
FlexLogic Entry 106 51P Gen Oper On (VO53)
FlexLogic Entry 107 51P Aux Oper On (VO54)
FlexLogic Entry 108 51NP Oper On (VO55)
FlexLogic Entry 109 24T Oper On (VO56)
FlexLogic Entry 110 64B Oper On (VO58)
FlexLogic Entry 111 OR(7)
FlexLogic Entry 112 = W1 Out Oper (VO81)
FlexLogic Entry 113 T60 Rly Fail On (VO10)
FlexLogic Entry 114 VTFF Oper On (VO49)
FlexLogic Entry 115 TP4 VT CB5 O On(P4a)
FlexLogic Entry 116 TP Ref Fault On(P4c)
FlexLogic Entry 117 26TP Stg1 Op On(P5a)
FlexLogic Entry 118 26TP Stg2 Op On(P5c)
FlexLogic Entry 119 49TP Stg1 Op On(P6a)
FlexLogic Entry 120 49TP Stg2 Op On(P6c)
FlexLogic Entry 121 63TP Stg1 Op On(P7a)
FlexLogic Entry 122 63TP Stg2 Op On(P7c)
FlexLogic Entry 123 71TP Operate On(P8a)
FlexLogic Entry 124 45FTP Oper On(P8c)
FlexLogic Entry 125 OR(12)
FlexLogic Entry 126 = W2 Out Oper (VO82)
FlexLogic Entry 127 26TP Stg2 Op On(P5c)
FlexLogic Entry 128 49TP Stg2 Op On(P6c)
FlexLogic Entry 129 OR(2)
FlexLogic Entry 130 = W3 Out Oper (VO83)
FlexLogic Entry 131 87T Oper On (VO51)
FlexLogic Entry 132 50/51P Oper On (VO52)
FlexLogic Entry 133 51P Gen Oper On (VO53)
FlexLogic Entry 134 51P Aux Oper On (VO54)
FlexLogic Entry 135 51NP Oper On (VO55)
FlexLogic Entry 136 24T Oper On (VO56)
FlexLogic Entry 137 64B Oper On (VO58)
FlexLogic Entry 138 49TP Stg2 Op On(P6c)
FlexLogic Entry 139 63TP Stg2 Op On(P7c)
FlexLogic Entry 140 45FTP Oper On(P8c)
FlexLogic Entry 141 DL91 Pr Trip On(P3c)
FlexLogic Entry 142 OR(11)
Fri Jun 10 12:09:10 2011 Version: 5.81 Settings (Enabled Features) PAGE 18

SONELGAZ MSILA TP3 T60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: T60-J04-HMH-F8L-H6P-M8N-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONELGAZ MSILA T60 TRANSFORMER MANAGEMENT RELAY
TEXT COLOR

FLEXLOGIC EQUATION EDITOR (continued from last page)


FlexLogic Entry 143 TIMER 25
FlexLogic Entry 144 = W4 Out Oper (VO84)
FlexLogic Entry 145 49TP Stg2 Op On(P6c)
FlexLogic Entry 146 TIMER 26
FlexLogic Entry 147 = W5 Out Oper (VO85)
FlexLogic Entry 148 49TP Stg2 Op On(P6c)
FlexLogic Entry 149 26TP Stg2 Op On(P5c)
FlexLogic Entry 150 DL91 Pr Trip On(P3c)
FlexLogic Entry 151 OR(3)
FlexLogic Entry 152 = W6 Out Oper (VO86)
FlexLogic Entry 153 49TP Stg2 Op On(P6c)
FlexLogic Entry 154 26TP Stg2 Op On(P5c)
FlexLogic Entry 155 DL91 Pr Trip On(P3c)
FlexLogic Entry 156 OR(3)
FlexLogic Entry 157 = W7 Out Oper (VO87)
FlexLogic Entry 158 G60-52L Trp1 On(H8a)
FlexLogic Entry 159 G60-52L Trp2 On(H8c)
FlexLogic Entry 160 OR(2)
FlexLogic Entry 161 = W8 Out Oper (VO88)
FlexLogic Entry 162 87T Oper On (VO51)
FlexLogic Entry 163 50/51P Oper On (VO52)
FlexLogic Entry 164 51P Gen Oper On (VO53)
FlexLogic Entry 165 51P Aux Oper On (VO54)
FlexLogic Entry 166 51NP Oper On (VO55)
FlexLogic Entry 167 24T Oper On (VO56)
FlexLogic Entry 168 64B Oper On (VO58)
FlexLogic Entry 169 OR(7)
FlexLogic Entry 170 = Trip LED In (VO7)
FlexLogic Entry 171 87T Oper On (VO51)
FlexLogic Entry 172 POSITIVE ONE SHOT
FlexLogic Entry 173 50/51P Oper On (VO52)
FlexLogic Entry 174 POSITIVE ONE SHOT
FlexLogic Entry 175 51P Gen Oper On (VO53)
FlexLogic Entry 176 POSITIVE ONE SHOT
FlexLogic Entry 177 51P Aux Oper On (VO54)
FlexLogic Entry 178 POSITIVE ONE SHOT
FlexLogic Entry 179 51NP Oper On (VO55)
FlexLogic Entry 180 POSITIVE ONE SHOT
FlexLogic Entry 181 24T Oper On (VO56)
FlexLogic Entry 182 POSITIVE ONE SHOT
FlexLogic Entry 183 64B Oper On (VO58)
FlexLogic Entry 184 POSITIVE ONE SHOT
FlexLogic Entry 185 63TP Stg2 Op On(P7c)
FlexLogic Entry 186 POSITIVE ONE SHOT
FlexLogic Entry 187 45FTP Oper On(P8c)
FlexLogic Entry 188 POSITIVE ONE SHOT
FlexLogic Entry 189 OR(9)
FlexLogic Entry 190 = Osc Initiate (VO8)
FlexLogic Entry 191 T60 Rly Fail On (VO10)
FlexLogic Entry 192 VTFF Oper On (VO49)
FlexLogic Entry 193 TP4 VT CB5 O On(P4a)
FlexLogic Entry 194 TP Ref Fault On(P4c)
FlexLogic Entry 195 26TP Stg1 Op On(P5a)
FlexLogic Entry 196 26TP Stg2 Op On(P5c)
FlexLogic Entry 197 49TP Stg1 Op On(P6a)
FlexLogic Entry 198 49TP Stg2 Op On(P6c)
FlexLogic Entry 199 63TP Stg1 Op On(P7a)
FlexLogic Entry 200 63TP Stg2 Op On(P7c)
FlexLogic Entry 201 71TP Operate On(P8a)
FlexLogic Entry 202 45FTP Oper On(P8c)
FlexLogic Entry 203 OR(12)
FlexLogic Entry 204 = Alrm LED In (VO6)
FlexLogic Entry 205 TP4 VT CB5 O On(P4a)
FlexLogic Entry 206 = TP 4 VT CB5 (VO92)
FlexLogic Entry 207 TP Ref Fault On(P4c)
FlexLogic Entry 208 = TP REFRIG FL (VO93)
FlexLogic Entry 209 26TP Stg1 Op On(P5a)
Fri Jun 10 12:09:10 2011 Version: 5.81 Settings (Enabled Features) PAGE 19

SONELGAZ MSILA TP3 T60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: T60-J04-HMH-F8L-H6P-M8N-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONELGAZ MSILA T60 TRANSFORMER MANAGEMENT RELAY
TEXT COLOR

FLEXLOGIC EQUATION EDITOR (continued from last page)


FlexLogic Entry 210 = STAGE 1 TEMP (VO94)
FlexLogic Entry 211 49TP Stg1 Op On(P6a)
FlexLogic Entry 212 = STAGE 1 IMAG (VO95)
FlexLogic Entry 213 71TP Operate On(P8a)
FlexLogic Entry 214 = TP 71 (VO96)
FlexLogic Entry 215 63TP Stg1 Op On(P7a)
FlexLogic Entry 216 = 53 stage 1 (VO91)
FlexLogic Entry 217 END

FLEXLOGIC TIMERS
Timer 21: Type millisecond
Timer 21: Pickup Delay 0
Timer 21: Dropout Delay 100
Timer 22: Type millisecond
Timer 22: Pickup Delay 0
Timer 22: Dropout Delay 100
Timer 23: Type millisecond
Timer 23: Pickup Delay 0
Timer 23: Dropout Delay 100
Timer 24: Type millisecond
Timer 24: Pickup Delay 0
Timer 24: Dropout Delay 100
Timer 25: Type millisecond
Timer 25: Pickup Delay 0
Timer 25: Dropout Delay 100
Timer 26: Type millisecond
Timer 26: Pickup Delay 0
Timer 26: Dropout Delay 100

GROUPED ELEMENTS
GROUP 1
TRANSFORMER
PERCENT DIFFERENTIAL [GROUP 1]
Function Enabled
Pickup 0.100 pu
Slope 1 20 %
Break 1 2.000 pu
Break 2 30.000 pu
Slope 2 50 %
Inrush Inhibit Function Trad. 2nd
Inrush Inhibit Mode Per phase
Inrush Inhibit Level 20.0 % fo
Overexcitation Inhibit Function Disabled
Overexcitation Inhibit Level 10.0 % fo
Block OFF
Target Latched
Events Enabled

INSTANTANEOUS DIFFERENTIAL [GROUP 1]


Function Enabled
Pickup 4.000 pu
Block OFF
Target Latched
Events Enabled

PHASE CURRENT
PHASE TOC [GROUP 1]
PHASE TOC1: Function Enabled
PHASE TOC1: Signal Source Xf Pri (SRC 1)
PHASE TOC1: Input RMS
PHASE TOC1: Pickup 0.910 pu
PHASE TOC1: Curve IEEE Mod Inv
PHASE TOC1: TD Multiplier 0.88
PHASE TOC1: Reset Timed
PHASE TOC1: Voltage Restraint Disabled
PHASE TOC1: Block A OFF
PHASE TOC1: Block B OFF
Fri Jun 10 12:09:10 2011 Version: 5.81 Settings (Enabled Features) PAGE 20

SONELGAZ MSILA TP3 T60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: T60-J04-HMH-F8L-H6P-M8N-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONELGAZ MSILA T60 TRANSFORMER MANAGEMENT RELAY
TEXT COLOR

PHASE TOC [GROUP 1] (continued from last page)


PHASE TOC1: Block C OFF
PHASE TOC1: Target Latched
PHASE TOC1: Events Enabled
PHASE TOC3: Function Enabled
PHASE TOC3: Signal Source S-Gen (SRC 2)
PHASE TOC3: Input RMS
PHASE TOC3: Pickup 1.020 pu
PHASE TOC3: Curve IEEE Mod Inv
PHASE TOC3: TD Multiplier 0.86
PHASE TOC3: Reset Timed
PHASE TOC3: Voltage Restraint Disabled
PHASE TOC3: Block A OFF
PHASE TOC3: Block B OFF
PHASE TOC3: Block C OFF
PHASE TOC3: Target Latched
PHASE TOC3: Events Enabled
PHASE TOC5: Function Enabled
PHASE TOC5: Signal Source S-Aux (SRC 3)
PHASE TOC5: Input RMS
PHASE TOC5: Pickup 0.600 pu
PHASE TOC5: Curve IEEE Ext Inv
PHASE TOC5: TD Multiplier 3.60
PHASE TOC5: Reset Timed
PHASE TOC5: Voltage Restraint Disabled
PHASE TOC5: Block A OFF
PHASE TOC5: Block B OFF
PHASE TOC5: Block C OFF
PHASE TOC5: Target Latched
PHASE TOC5: Events Enabled

PHASE IOC [GROUP 1]


PHASE IOC1: Function Enabled
PHASE IOC1: Source Xf Pri (SRC 1)
PHASE IOC1: Pickup 1.900 pu
PHASE IOC1: Delay 0.60 s
PHASE IOC1: Reset Delay 0.10 s
PHASE IOC1: Block A OFF
PHASE IOC1: Block B OFF
PHASE IOC1: Block C OFF
PHASE IOC1: Target Latched
PHASE IOC1: Events Enabled
PHASE IOC2: Function Enabled
PHASE IOC2: Source Xf Pri (SRC 1)
PHASE IOC2: Pickup 9.250 pu
PHASE IOC2: Delay 0.00 s
PHASE IOC2: Reset Delay 0.10 s
PHASE IOC2: Block A OFF
PHASE IOC2: Block B OFF
PHASE IOC2: Block C OFF
PHASE IOC2: Target Latched
PHASE IOC2: Events Enabled
PHASE IOC3: Function Enabled
PHASE IOC3: Source S-Gen (SRC 2)
PHASE IOC3: Pickup 2.120 pu
PHASE IOC3: Delay 0.60 s
PHASE IOC3: Reset Delay 0.10 s
PHASE IOC3: Block A OFF
PHASE IOC3: Block B OFF
PHASE IOC3: Block C OFF
PHASE IOC3: Target Latched
PHASE IOC3: Events Enabled
PHASE IOC5: Function Enabled
PHASE IOC5: Source S-Aux (SRC 3)
PHASE IOC5: Pickup 1.500 pu
PHASE IOC5: Delay 0.60 s
PHASE IOC5: Reset Delay 0.10 s
PHASE IOC5: Block A OFF
Fri Jun 10 12:09:10 2011 Version: 5.81 Settings (Enabled Features) PAGE 21

SONELGAZ MSILA TP3 T60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: T60-J04-HMH-F8L-H6P-M8N-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONELGAZ MSILA T60 TRANSFORMER MANAGEMENT RELAY
TEXT COLOR

PHASE IOC [GROUP 1] (continued from last page)


PHASE IOC5: Block B OFF
PHASE IOC5: Block C OFF
PHASE IOC5: Target Latched
PHASE IOC5: Events Enabled
PHASE IOC6: Function Enabled
PHASE IOC6: Source S-Aux (SRC 3)
PHASE IOC6: Pickup 9.000 pu
PHASE IOC6: Delay 0.00 s
PHASE IOC6: Reset Delay 0.10 s
PHASE IOC6: Block A OFF
PHASE IOC6: Block B OFF
PHASE IOC6: Block C OFF
PHASE IOC6: Target Latched
PHASE IOC6: Events Enabled

GROUND CURRENT
GROUND TOC [GROUP 1]
GROUND TOC1: Function Enabled
GROUND TOC1: Source Xf Pri (SRC 1)
GROUND TOC1: Input Phasor
GROUND TOC1: Pickup 0.125 pu
GROUND TOC1: Curve IEEE Mod Inv
GROUND TOC1: TD Multiplier 1.00
GROUND TOC1: Reset Instantaneous
GROUND TOC1: Block OFF
GROUND TOC1: Target Latched
GROUND TOC1: Events Enabled

GROUND IOC [GROUP 1]


GROUND IOC1: Function Enabled
GROUND IOC1: Source Xf Pri (SRC 1)
GROUND IOC1: Pickup 0.375 pu
GROUND IOC1: Delay 0.60 s
GROUND IOC1: Reset Delay 0.10 s
GROUND IOC1: Block OFF
GROUND IOC1: Target Latched
GROUND IOC1: Events Enabled

VOLTAGE ELEMENTS
AUXILIARY OV [GROUP 1]
AUXILIARY OV 1: Function Enabled
AUXILIARY OV 1: Source Bus Gr (SRC 4)
AUXILIARY OV 1: Pickup 0.070 pu
AUXILIARY OV 1: Pickup Delay 0.50 s
AUXILIARY OV 1: Reset Delay 0.10 s
AUXILIARY OV 1: Block OFF
AUXILIARY OV 1: Target Latched
AUXILIARY OV 1: Events Enabled

VOLTS PER HERTZ [GROUP 1]


VOLTS PER HERTZ 1: Function Enabled
VOLTS PER HERTZ 1: Source S-Gen (SRC 2)
VOLTS PER HERTZ 1: Pickup 1.10 pu
VOLTS PER HERTZ 1: Curves Definite Time
VOLTS PER HERTZ 1: TD Multiplier 42.00
VOLTS PER HERTZ 1: T Reset 900.0 s
VOLTS PER HERTZ 1: Block OFF
VOLTS PER HERTZ 1: Target Latched
VOLTS PER HERTZ 1: Events Enabled
VOLTS PER HERTZ 2: Function Enabled
VOLTS PER HERTZ 2: Source S-Gen (SRC 2)
VOLTS PER HERTZ 2: Pickup 1.17 pu
VOLTS PER HERTZ 2: Curves Definite Time
VOLTS PER HERTZ 2: TD Multiplier 1.85
VOLTS PER HERTZ 2: T Reset 10.0 s
VOLTS PER HERTZ 2: Block OFF
VOLTS PER HERTZ 2: Target Latched
Fri Jun 10 12:09:10 2011 Version: 5.81 Settings (Enabled Features) PAGE 22

SONELGAZ MSILA TP3 T60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: T60-J04-HMH-F8L-H6P-M8N-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONELGAZ MSILA T60 TRANSFORMER MANAGEMENT RELAY
TEXT COLOR

VOLTS PER HERTZ [GROUP 1] (continued from last page)


VOLTS PER HERTZ 2: Events Enabled

CONTROL ELEMENTS
MONITORING ELEMENTS
VT FUSE FAILURE
VT FUSE FAILURE 2: Function Enabled
VT FUSE FAILURE 3: Function Enabled

INPUTS/OUTPUTS
CONTACT INPUTS
[H7A] Contact Input 1 ID Pri CB 52a
[H7A] Contact Input 1 Debounce Time 4.0 ms
[H7A] Contact Input 1 Events Enabled
[H7C] Contact Input 2 ID Pri CB 52b
[H7C] Contact Input 2 Debounce Time 4.0 ms
[H7C] Contact Input 2 Events Enabled
[H8A] Contact Input 3 ID G60-52L Trp1
[H8A] Contact Input 3 Debounce Time 4.0 ms
[H8A] Contact Input 3 Events Enabled
[H8C] Contact Input 4 ID G60-52L Trp2
[H8C] Contact Input 4 Debounce Time 4.0 ms
[H8C] Contact Input 4 Events Enabled
[P1A] Contact Input 5 ID CB 52G 52a
[P1A] Contact Input 5 Debounce Time 4.0 ms
[P1A] Contact Input 5 Events Enabled
[P1C] Contact Input 6 ID CB 52G 52b
[P1C] Contact Input 6 Debounce Time 4.0 ms
[P1C] Contact Input 6 Events Enabled
[P2A] Contact Input 7 ID TL Sec 52a
[P2A] Contact Input 7 Debounce Time 4.0 ms
[P2A] Contact Input 7 Events Enabled
[P2C] Contact Input 8 ID TL Sec 52b
[P2C] Contact Input 8 Debounce Time 4.0 ms
[P2C] Contact Input 8 Events Enabled
[P3A] Contact Input 9 ID Cont Ip 9
[P3A] Contact Input 9 Debounce Time 4.0 ms
[P3A] Contact Input 9 Events Disabled
[P3C] Contact Input 10 ID DL91 Pr Trip
[P3C] Contact Input 10 Debounce Time 4.0 ms
[P3C] Contact Input 10 Events Enabled
[P4A] Contact Input 11 ID TP4 VT CB5 O
[P4A] Contact Input 11 Debounce Time 4.0 ms
[P4A] Contact Input 11 Events Enabled
[P4C] Contact Input 12 ID TP Ref Fault
[P4C] Contact Input 12 Debounce Time 4.0 ms
[P4C] Contact Input 12 Events Enabled
[P5A] Contact Input 13 ID 26TP Stg1 Op
[P5A] Contact Input 13 Debounce Time 4.0 ms
[P5A] Contact Input 13 Events Enabled
[P5C] Contact Input 14 ID 26TP Stg2 Op
[P5C] Contact Input 14 Debounce Time 4.0 ms
[P5C] Contact Input 14 Events Enabled
[P6A] Contact Input 15 ID 49TP Stg1 Op
[P6A] Contact Input 15 Debounce Time 4.0 ms
[P6A] Contact Input 15 Events Enabled
[P6C] Contact Input 16 ID 49TP Stg2 Op
[P6C] Contact Input 16 Debounce Time 4.0 ms
[P6C] Contact Input 16 Events Enabled
[P7A] Contact Input 17 ID 63TP Stg1 Op
[P7A] Contact Input 17 Debounce Time 4.0 ms
[P7A] Contact Input 17 Events Enabled
[P7C] Contact Input 18 ID 63TP Stg2 Op
[P7C] Contact Input 18 Debounce Time 4.0 ms
[P7C] Contact Input 18 Events Enabled
[P8A] Contact Input 19 ID 71TP Operate
[P8A] Contact Input 19 Debounce Time 4.0 ms
[P8A] Contact Input 19 Events Enabled
Fri Jun 10 12:09:10 2011 Version: 5.81 Settings (Enabled Features) PAGE 23

SONELGAZ MSILA TP3 T60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: T60-J04-HMH-F8L-H6P-M8N-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONELGAZ MSILA T60 TRANSFORMER MANAGEMENT RELAY
TEXT COLOR

CONTACT INPUTS (continued from last page)


[P8C] Contact Input 20 ID 45FTP Oper
[P8C] Contact Input 20 Debounce Time 4.0 ms
[P8C] Contact Input 20 Events Enabled

CONTACT INPUT THRESHOLDS


Pri CB 52a, Pri CB 52b, G60-52L Trp1, G60-52L Trp2(H7A, H7C, H8A, H8C) 33 Vdc
CB 52G 52a, CB 52G 52b, TL Sec 52a, TL Sec 52b(P1A, P1C, P2A, P2C) 33 Vdc
Cont Ip 9, DL91 Pr Trip, TP4 VT CB5 O, TP Ref Fault(P3A, P3C, P4A, P4C) 33 Vdc
26TP Stg1 Op, 26TP Stg2 Op, 49TP Stg1 Op, 49TP Stg2 Op(P5A, P5C, P6A, P6C)
33 Vdc
63TP Stg1 Op, 63TP Stg2 Op, 71TP Operate, 45FTP Oper(P7A, P7C, P8A, P8C)33 Vdc

CONTACT OUTPUTS
[H1] Contact Output 1 ID LO 86T Trip
[H1] Contact Output 1 Operate H1 Out Oper On (VO21)
[H1] Contact Output 1 Seal-In LO 86T Trip IOn (H1)
[H1] Contact Output 1 Events Enabled
[H2] Contact Output 2 ID LO 86G Trip
[H2] Contact Output 2 Operate H2 Out Oper On (VO22)
[H2] Contact Output 2 Seal-In LO 86G Trip IOn (H2)
[H2] Contact Output 2 Events Enabled
[H3] Contact Output 3 ID Pri CB Trp 1
[H3] Contact Output 3 Operate H3 Out Oper On (VO23)
[H3] Contact Output 3 Seal-In Pri CB Trp 1 IOn (H3)
[H3] Contact Output 3 Events Enabled
[H4] Contact Output 4 ID Pri CB Trp 2
[H4] Contact Output 4 Operate H4 Out Oper On (VO24)
[H4] Contact Output 4 Seal-In Pri CB Trp 2 IOn (H4)
[H4] Contact Output 4 Events Enabled
[H5] Contact Output 5 ID Cont Op 5
[H5] Contact Output 5 Operate H5 Out Oper On (VO25)
[H5] Contact Output 5 Seal-In OFF
[H5] Contact Output 5 Events Enabled
[H6] Contact Output 6 ID Chg Src 400V
[H6] Contact Output 6 Operate H6 Out Oper On (VO26)
[H6] Contact Output 6 Seal-In OFF
[H6] Contact Output 6 Events Enabled
[U1] Contact Output 7 ID 87T Oper
[U1] Contact Output 7 Operate U1 Out Oper On (VO27)
[U1] Latching Output 7 Reset RESET OP (PUSHBUTTON)
[U1] Latching Output 7 Type Operate-dominant
[U1] Contact Output 7 Events Enabled
[U2] Contact Output 8 ID 50/51P Oper
[U2] Contact Output 8 Operate U2 Out Oper On (VO28)
[U2] Latching Output 8 Reset RESET OP (PUSHBUTTON)
[U2] Latching Output 8 Type Operate-dominant
[U2] Contact Output 8 Events Enabled
[U3] Contact Output 9 ID 51NP Oper
[U3] Contact Output 9 Operate U3 Out Oper On (VO29)
[U3] Latching Output 9 Reset RESET OP (PUSHBUTTON)
[U3] Latching Output 9 Type Operate-dominant
[U3] Contact Output 9 Events Enabled
[U4] Contact Output 10 ID 51P Gen Oper
[U4] Contact Output 10 Operate U4 Out Oper On (VO30)
[U4] Latching Output 10 Reset RESET OP (PUSHBUTTON)
[U4] Latching Output 10 Type Operate-dominant
[U4] Contact Output 10 Events Enabled
[U5] Contact Output 11 ID 51P Aux Oper
[U5] Contact Output 11 Operate U5 Out Oper On (VO31)
[U5] Latching Output 11 Reset RESET OP (PUSHBUTTON)
[U5] Latching Output 11 Type Operate-dominant
[U5] Contact Output 11 Events Enabled
[U6] Contact Output 12 ID 24 Trip Oper
[U6] Contact Output 12 Operate U6 Out Oper On (VO32)
[U6] Latching Output 12 Reset RESET OP (PUSHBUTTON)
[U6] Latching Output 12 Type Operate-dominant
[U6] Contact Output 12 Events Enabled
[U7] Contact Output 13 ID 26TP Stg2 Op
Fri Jun 10 12:09:10 2011 Version: 5.81 Settings (Enabled Features) PAGE 24

SONELGAZ MSILA TP3 T60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: T60-J04-HMH-F8L-H6P-M8N-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONELGAZ MSILA T60 TRANSFORMER MANAGEMENT RELAY
TEXT COLOR

CONTACT OUTPUTS (continued from last page)


[U7] Contact Output 13 Operate U7 Out Oper On (VO33)
[U7] Latching Output 13 Reset RESET OP (PUSHBUTTON)
[U7] Latching Output 13 Type Operate-dominant
[U7] Contact Output 13 Events Enabled
[U8] Contact Output 14 ID 49TP Stg2 Op
[U8] Contact Output 14 Operate U8 Out Oper On (VO34)
[U8] Latching Output 14 Reset RESET OP (PUSHBUTTON)
[U8] Latching Output 14 Type Operate-dominant
[U8] Contact Output 14 Events Enabled
[U9] Contact Output 15 ID 63TP Stg2 Op
[U9] Contact Output 15 Operate U9 Out Oper On (VO35)
[U9] Latching Output 15 Reset RESET OP (PUSHBUTTON)
[U9] Latching Output 15 Type Operate-dominant
[U9] Contact Output 15 Events Enabled
[U10] Contact Output 16 ID 45F Trip Op
[U10] Contact Output 16 Operate U10 Out Oper On (VO36)
[U10] Latching Output 16 Reset RESET OP (PUSHBUTTON)
[U10] Latching Output 16 Type Operate-dominant
[U10] Contact Output 16 Events Enabled
[U11] Contact Output 17 ID 21P Trip Op
[U11] Contact Output 17 Operate U11 Out Oper On (VO37)
[U11] Latching Output 17 Reset RESET OP (PUSHBUTTON)
[U11] Latching Output 17 Type Operate-dominant
[U11] Contact Output 17 Events Enabled
[U12] Contact Output 18 ID 64B Back Op
[U12] Contact Output 18 Operate U12 Out Oper On (VO38)
[U12] Latching Output 18 Reset RESET OP (PUSHBUTTON)
[U12] Latching Output 18 Type Operate-dominant
[U12] Contact Output 18 Events Enabled
[U13] Contact Output 19 ID DL91 Trip Op
[U13] Contact Output 19 Operate U13 Out Oper On (VO39)
[U13] Latching Output 19 Reset RESET OP (PUSHBUTTON)
[U13] Latching Output 19 Type Operate-dominant
[U13] Contact Output 19 Events Enabled
[U14] Contact Output 20 ID Cont Op 20
[U14] Contact Output 20 Operate U14 Out Oper On (VO40)
[U14] Latching Output 20 Reset RESET OP (PUSHBUTTON)
[U14] Latching Output 20 Type Operate-dominant
[U14] Contact Output 20 Events Enabled
[W1] Contact Output 21 ID All Trips
[W1] Contact Output 21 Operate W1 Out Oper On (VO81)
[W1] Contact Output 21 Seal-In OFF
[W1] Contact Output 21 Events Enabled
[W2] Contact Output 22 ID All Alarms
[W2] Contact Output 22 Operate W2 Out Oper On (VO82)
[W2] Contact Output 22 Seal-In OFF
[W2] Contact Output 22 Events Enabled
[W3] Contact Output 23 ID Turb Norm St
[W3] Contact Output 23 Operate W3 Out Oper On (VO83)
[W3] Contact Output 23 Seal-In OFF
[W3] Contact Output 23 Events Enabled
[W4] Contact Output 24 ID Chg Src 6kV
[W4] Contact Output 24 Operate W4 Out Oper On (VO84)
[W4] Contact Output 24 Seal-In OFF
[W4] Contact Output 24 Events Enabled
[W5] Contact Output 25 ID 41EX Trip
[W5] Contact Output 25 Operate W5 Out Oper On (VO85)
[W5] Contact Output 25 Seal-In OFF
[W5] Contact Output 25 Events Enabled
[W6] Contact Output 26 ID G60-52G Trp1
[W6] Contact Output 26 Operate W6 Out Oper On (VO86)
[W6] Contact Output 26 Seal-In OFF
[W6] Contact Output 26 Events Enabled
[W7] Contact Output 27 ID G60-52G Trp2
[W7] Contact Output 27 Operate W7 Out Oper On (VO87)
[W7] Contact Output 27 Seal-In OFF
[W7] Contact Output 27 Events Enabled
Fri Jun 10 12:09:10 2011 Version: 5.81 Settings (Enabled Features) PAGE 25

SONELGAZ MSILA TP3 T60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: T60-J04-HMH-F8L-H6P-M8N-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONELGAZ MSILA T60 TRANSFORMER MANAGEMENT RELAY
TEXT COLOR

CONTACT OUTPUTS (continued from last page)


[W8] Contact Output 28 ID Pr CB Cl Per
[W8] Contact Output 28 Operate W8 Out Oper On (VO88)
[W8] Contact Output 28 Seal-In Reset Sealin On (VO9)
[W8] Contact Output 28 Events Enabled

VIRTUAL OUTPUTS
Virtual Output 6 ID Alrm LED In
Virtual Output 6 Events Disabled
Virtual Output 7 ID Trip LED In
Virtual Output 7 Events Enabled
Virtual Output 8 ID Osc Initiate
Virtual Output 8 Events Enabled
Virtual Output 9 ID Reset Sealin
Virtual Output 9 Events Enabled
Virtual Output 10 ID T60 Rly Fail
Virtual Output 10 Events Enabled
Virtual Output 21 ID H1 Out Oper
Virtual Output 21 Events Enabled
Virtual Output 23 ID H3 Out Oper
Virtual Output 23 Events Enabled
Virtual Output 24 ID H4 Out Oper
Virtual Output 24 Events Enabled
Virtual Output 26 ID H6 Out Oper
Virtual Output 26 Events Enabled
Virtual Output 27 ID U1 Out Oper
Virtual Output 27 Events Enabled
Virtual Output 28 ID U2 Out Oper
Virtual Output 28 Events Enabled
Virtual Output 29 ID U3 Out Oper
Virtual Output 29 Events Enabled
Virtual Output 30 ID U4 Out Oper
Virtual Output 30 Events Enabled
Virtual Output 31 ID U5 Out Oper
Virtual Output 31 Events Enabled
Virtual Output 32 ID U6 Out Oper
Virtual Output 32 Events Enabled
Virtual Output 33 ID U7 Out Oper
Virtual Output 33 Events Enabled
Virtual Output 34 ID U8 Out Oper
Virtual Output 34 Events Enabled
Virtual Output 35 ID U9 Out Oper
Virtual Output 35 Events Enabled
Virtual Output 36 ID U10 Out Oper
Virtual Output 36 Events Enabled
Virtual Output 38 ID U12 Out Oper
Virtual Output 38 Events Enabled
Virtual Output 39 ID U13 Out Oper
Virtual Output 39 Events Enabled
Virtual Output 49 ID VTFF Oper
Virtual Output 49 Events Enabled
Virtual Output 51 ID 87T Oper
Virtual Output 51 Events Enabled
Virtual Output 52 ID 50/51P Oper
Virtual Output 52 Events Enabled
Virtual Output 53 ID 51P Gen Oper
Virtual Output 53 Events Enabled
Virtual Output 54 ID 51P Aux Oper
Virtual Output 54 Events Enabled
Virtual Output 55 ID 51NP Oper
Virtual Output 55 Events Enabled
Virtual Output 56 ID 24T Oper
Virtual Output 56 Events Enabled
Virtual Output 58 ID 64B Oper
Virtual Output 58 Events Enabled
Virtual Output 81 ID W1 Out Oper
Virtual Output 81 Events Enabled
Virtual Output 82 ID W2 Out Oper
Fri Jun 10 12:09:10 2011 Version: 5.81 Settings (Enabled Features) PAGE 26

SONELGAZ MSILA TP3 T60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: T60-J04-HMH-F8L-H6P-M8N-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONELGAZ MSILA T60 TRANSFORMER MANAGEMENT RELAY
TEXT COLOR

VIRTUAL OUTPUTS (continued from last page)


Virtual Output 82 Events Enabled
Virtual Output 83 ID W3 Out Oper
Virtual Output 83 Events Enabled
Virtual Output 84 ID W4 Out Oper
Virtual Output 84 Events Enabled
Virtual Output 85 ID W5 Out Oper
Virtual Output 85 Events Enabled
Virtual Output 86 ID W6 Out Oper
Virtual Output 86 Events Enabled
Virtual Output 87 ID W7 Out Oper
Virtual Output 87 Events Enabled
Virtual Output 88 ID W8 Out Oper
Virtual Output 88 Events Enabled
Virtual Output 91 ID 53 stage 1
Virtual Output 91 Events Enabled
Virtual Output 92 ID TP 4 VT CB5
Virtual Output 92 Events Enabled
Virtual Output 93 ID TP REFRIG FL
Virtual Output 93 Events Enabled
Virtual Output 94 ID STAGE 1 TEMP
Virtual Output 94 Events Enabled
Virtual Output 95 ID STAGE 1 IMAG
Virtual Output 95 Events Enabled
Virtual Output 96 ID TP 71
Virtual Output 96 Events Enabled

REMOTE DEVICES
Remote Device 1 ID Remote Device 1
Remote Device 1 ETYPE APPID 0
Remote Device 1 DATASET Fixed
Remote Device 1 IN PMU SCHEME No
Remote Device 2 ID Remote Device 2
Remote Device 2 ETYPE APPID 0
Remote Device 2 DATASET Fixed
Remote Device 2 IN PMU SCHEME No
Remote Device 3 ID Remote Device 3
Remote Device 3 ETYPE APPID 0
Remote Device 3 DATASET Fixed
Remote Device 3 IN PMU SCHEME No
Remote Device 4 ID Remote Device 4
Remote Device 4 ETYPE APPID 0
Remote Device 4 DATASET Fixed
Remote Device 4 IN PMU SCHEME No
Remote Device 5 ID Remote Device 5
Remote Device 5 ETYPE APPID 0
Remote Device 5 DATASET Fixed
Remote Device 5 IN PMU SCHEME No
Remote Device 6 ID Remote Device 6
Remote Device 6 ETYPE APPID 0
Remote Device 6 DATASET Fixed
Remote Device 6 IN PMU SCHEME No
Remote Device 7 ID Remote Device 7
Remote Device 7 ETYPE APPID 0
Remote Device 7 DATASET Fixed
Remote Device 7 IN PMU SCHEME No
Remote Device 8 ID Remote Device 8
Remote Device 8 ETYPE APPID 0
Remote Device 8 DATASET Fixed
Remote Device 8 IN PMU SCHEME No
Remote Device 9 ID Remote Device 9
Remote Device 9 ETYPE APPID 0
Remote Device 9 DATASET Fixed
Remote Device 9 IN PMU SCHEME No
Remote Device 10 ID Remote Device 10
Remote Device 10 ETYPE APPID 0
Remote Device 10 DATASET Fixed
Remote Device 10 IN PMU SCHEME No
Fri Jun 10 12:09:10 2011 Version: 5.81 Settings (Enabled Features) PAGE 27

SONELGAZ MSILA TP3 T60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: T60-J04-HMH-F8L-H6P-M8N-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONELGAZ MSILA T60 TRANSFORMER MANAGEMENT RELAY
TEXT COLOR

REMOTE DEVICES (continued from last page)


Remote Device 11 ID Remote Device 11
Remote Device 11 ETYPE APPID 0
Remote Device 11 DATASET Fixed
Remote Device 11 IN PMU SCHEME No
Remote Device 12 ID Remote Device 12
Remote Device 12 ETYPE APPID 0
Remote Device 12 DATASET Fixed
Remote Device 12 IN PMU SCHEME No
Remote Device 13 ID Remote Device 13
Remote Device 13 ETYPE APPID 0
Remote Device 13 DATASET Fixed
Remote Device 13 IN PMU SCHEME No
Remote Device 14 ID Remote Device 14
Remote Device 14 ETYPE APPID 0
Remote Device 14 DATASET Fixed
Remote Device 14 IN PMU SCHEME No
Remote Device 15 ID Remote Device 15
Remote Device 15 ETYPE APPID 0
Remote Device 15 DATASET Fixed
Remote Device 15 IN PMU SCHEME No
Remote Device 16 ID Remote Device 16
Remote Device 16 ETYPE APPID 0
Remote Device 16 DATASET Fixed
Remote Device 16 IN PMU SCHEME No

REMOTE DPS INPUTS


Remote DPS Input 1 Name RemDPS Ip 1
Remote DPS Input 1 Device Remote Device 1
Remote DPS Input 1 Item None
Remote DPS Input 1 Events Disabled
Remote DPS Input 2 Name RemDPS Ip 2
Remote DPS Input 2 Device Remote Device 1
Remote DPS Input 2 Item None
Remote DPS Input 2 Events Disabled
Remote DPS Input 3 Name RemDPS Ip 3
Remote DPS Input 3 Device Remote Device 1
Remote DPS Input 3 Item None
Remote DPS Input 3 Events Disabled
Remote DPS Input 4 Name RemDPS Ip 4
Remote DPS Input 4 Device Remote Device 1
Remote DPS Input 4 Item None
Remote DPS Input 4 Events Disabled
Remote DPS Input 5 Name RemDPS Ip 5
Remote DPS Input 5 Device Remote Device 1
Remote DPS Input 5 Item None
Remote DPS Input 5 Events Disabled

IEC 61850 GOOSE ANALOGS INPUTS


IEC61850 GOOSE Analog Input 1 Default Value 1000.000
IEC61850 GOOSE Analog Input 1 Mode Default Value
IEC61850 GOOSE Analog Input 1 Units
IEC61850 GOOSE Analog Input 1 PU Base 1.000
IEC61850 GOOSE Analog Input 2 Default Value 1000.000
IEC61850 GOOSE Analog Input 2 Mode Default Value
IEC61850 GOOSE Analog Input 2 Units
IEC61850 GOOSE Analog Input 2 PU Base 1.000
IEC61850 GOOSE Analog Input 3 Default Value 1000.000
IEC61850 GOOSE Analog Input 3 Mode Default Value
IEC61850 GOOSE Analog Input 3 Units
IEC61850 GOOSE Analog Input 3 PU Base 1.000
IEC61850 GOOSE Analog Input 4 Default Value 1000.000
IEC61850 GOOSE Analog Input 4 Mode Default Value
IEC61850 GOOSE Analog Input 4 Units
IEC61850 GOOSE Analog Input 4 PU Base 1.000
IEC61850 GOOSE Analog Input 5 Default Value 1000.000
IEC61850 GOOSE Analog Input 5 Mode Default Value
IEC61850 GOOSE Analog Input 5 Units
Fri Jun 10 12:09:10 2011 Version: 5.81 Settings (Enabled Features) PAGE 28

SONELGAZ MSILA TP3 T60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: T60-J04-HMH-F8L-H6P-M8N-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONELGAZ MSILA T60 TRANSFORMER MANAGEMENT RELAY
TEXT COLOR

IEC 61850 GOOSE ANALOGS INPUTS (continued from last page)


IEC61850 GOOSE Analog Input 5 PU Base 1.000
IEC61850 GOOSE Analog Input 6 Default Value 1000.000
IEC61850 GOOSE Analog Input 6 Mode Default Value
IEC61850 GOOSE Analog Input 6 Units
IEC61850 GOOSE Analog Input 6 PU Base 1.000
IEC61850 GOOSE Analog Input 7 Default Value 1000.000
IEC61850 GOOSE Analog Input 7 Mode Default Value
IEC61850 GOOSE Analog Input 7 Units
IEC61850 GOOSE Analog Input 7 PU Base 1.000
IEC61850 GOOSE Analog Input 8 Default Value 1000.000
IEC61850 GOOSE Analog Input 8 Mode Default Value
IEC61850 GOOSE Analog Input 8 Units
IEC61850 GOOSE Analog Input 8 PU Base 1.000
IEC61850 GOOSE Analog Input 9 Default Value 1000.000
IEC61850 GOOSE Analog Input 9 Mode Default Value
IEC61850 GOOSE Analog Input 9 Units
IEC61850 GOOSE Analog Input 9 PU Base 1.000
IEC61850 GOOSE Analog Input 10 Default Value 1000.000
IEC61850 GOOSE Analog Input 10 Mode Default Value
IEC61850 GOOSE Analog Input 10 Units
IEC61850 GOOSE Analog Input 10 PU Base 1.000
IEC61850 GOOSE Analog Input 11 Default Value 1000.000
IEC61850 GOOSE Analog Input 11 Mode Default Value
IEC61850 GOOSE Analog Input 11 Units
IEC61850 GOOSE Analog Input 11 PU Base 1.000
IEC61850 GOOSE Analog Input 12 Default Value 1000.000
IEC61850 GOOSE Analog Input 12 Mode Default Value
IEC61850 GOOSE Analog Input 12 Units
IEC61850 GOOSE Analog Input 12 PU Base 1.000
IEC61850 GOOSE Analog Input 13 Default Value 1000.000
IEC61850 GOOSE Analog Input 13 Mode Default Value
IEC61850 GOOSE Analog Input 13 Units
IEC61850 GOOSE Analog Input 13 PU Base 1.000
IEC61850 GOOSE Analog Input 14 Default Value 1000.000
IEC61850 GOOSE Analog Input 14 Mode Default Value
IEC61850 GOOSE Analog Input 14 Units
IEC61850 GOOSE Analog Input 14 PU Base 1.000
IEC61850 GOOSE Analog Input 15 Default Value 1000.000
IEC61850 GOOSE Analog Input 15 Mode Default Value
IEC61850 GOOSE Analog Input 15 Units
IEC61850 GOOSE Analog Input 15 PU Base 1.000
IEC61850 GOOSE Analog Input 16 Default Value 1000.000
IEC61850 GOOSE Analog Input 16 Mode Default Value
IEC61850 GOOSE Analog Input 16 Units
IEC61850 GOOSE Analog Input 16 PU Base 1.000
IEC61850 GOOSE Analog Input 17 Default Value 1000.000
IEC61850 GOOSE Analog Input 17 Mode Default Value
IEC61850 GOOSE Analog Input 17 Units
IEC61850 GOOSE Analog Input 17 PU Base 1.000
IEC61850 GOOSE Analog Input 18 Default Value 1000.000
IEC61850 GOOSE Analog Input 18 Mode Default Value
IEC61850 GOOSE Analog Input 18 Units
IEC61850 GOOSE Analog Input 18 PU Base 1.000
IEC61850 GOOSE Analog Input 19 Default Value 1000.000
IEC61850 GOOSE Analog Input 19 Mode Default Value
IEC61850 GOOSE Analog Input 19 Units
IEC61850 GOOSE Analog Input 19 PU Base 1.000
IEC61850 GOOSE Analog Input 20 Default Value 1000.000
IEC61850 GOOSE Analog Input 20 Mode Default Value
IEC61850 GOOSE Analog Input 20 Units
IEC61850 GOOSE Analog Input 20 PU Base 1.000
IEC61850 GOOSE Analog Input 21 Default Value 1000.000
IEC61850 GOOSE Analog Input 21 Mode Default Value
IEC61850 GOOSE Analog Input 21 Units
IEC61850 GOOSE Analog Input 21 PU Base 1.000
IEC61850 GOOSE Analog Input 22 Default Value 1000.000
IEC61850 GOOSE Analog Input 22 Mode Default Value
Fri Jun 10 12:09:10 2011 Version: 5.81 Settings (Enabled Features) PAGE 29

SONELGAZ MSILA TP3 T60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: T60-J04-HMH-F8L-H6P-M8N-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONELGAZ MSILA T60 TRANSFORMER MANAGEMENT RELAY
TEXT COLOR

IEC 61850 GOOSE ANALOGS INPUTS (continued from last page)


IEC61850 GOOSE Analog Input 22 Units
IEC61850 GOOSE Analog Input 22 PU Base 1.000
IEC61850 GOOSE Analog Input 23 Default Value 1000.000
IEC61850 GOOSE Analog Input 23 Mode Default Value
IEC61850 GOOSE Analog Input 23 Units
IEC61850 GOOSE Analog Input 23 PU Base 1.000
IEC61850 GOOSE Analog Input 24 Default Value 1000.000
IEC61850 GOOSE Analog Input 24 Mode Default Value
IEC61850 GOOSE Analog Input 24 Units
IEC61850 GOOSE Analog Input 24 PU Base 1.000
IEC61850 GOOSE Analog Input 25 Default Value 1000.000
IEC61850 GOOSE Analog Input 25 Mode Default Value
IEC61850 GOOSE Analog Input 25 Units
IEC61850 GOOSE Analog Input 25 PU Base 1.000
IEC61850 GOOSE Analog Input 26 Default Value 1000.000
IEC61850 GOOSE Analog Input 26 Mode Default Value
IEC61850 GOOSE Analog Input 26 Units
IEC61850 GOOSE Analog Input 26 PU Base 1.000
IEC61850 GOOSE Analog Input 27 Default Value 1000.000
IEC61850 GOOSE Analog Input 27 Mode Default Value
IEC61850 GOOSE Analog Input 27 Units
IEC61850 GOOSE Analog Input 27 PU Base 1.000
IEC61850 GOOSE Analog Input 28 Default Value 1000.000
IEC61850 GOOSE Analog Input 28 Mode Default Value
IEC61850 GOOSE Analog Input 28 Units
IEC61850 GOOSE Analog Input 28 PU Base 1.000
IEC61850 GOOSE Analog Input 29 Default Value 1000.000
IEC61850 GOOSE Analog Input 29 Mode Default Value
IEC61850 GOOSE Analog Input 29 Units
IEC61850 GOOSE Analog Input 29 PU Base 1.000
IEC61850 GOOSE Analog Input 30 Default Value 1000.000
IEC61850 GOOSE Analog Input 30 Mode Default Value
IEC61850 GOOSE Analog Input 30 Units
IEC61850 GOOSE Analog Input 30 PU Base 1.000
IEC61850 GOOSE Analog Input 31 Default Value 1000.000
IEC61850 GOOSE Analog Input 31 Mode Default Value
IEC61850 GOOSE Analog Input 31 Units
IEC61850 GOOSE Analog Input 31 PU Base 1.000
IEC61850 GOOSE Analog Input 32 Default Value 1000.000
IEC61850 GOOSE Analog Input 32 Mode Default Value
IEC61850 GOOSE Analog Input 32 Units
IEC61850 GOOSE Analog Input 32 PU Base 1.000

IEC 61850 GOOSE UINTEGERS INPUTS


IEC61850 GOOSE UInteger Input 1 Default Value 1000
IEC61850 GOOSE UInteger Input 1 Mode Default Value
IEC61850 GOOSE UInteger Input 2 Default Value 1000
IEC61850 GOOSE UInteger Input 2 Mode Default Value
IEC61850 GOOSE UInteger Input 3 Default Value 1000
IEC61850 GOOSE UInteger Input 3 Mode Default Value
IEC61850 GOOSE UInteger Input 4 Default Value 1000
IEC61850 GOOSE UInteger Input 4 Mode Default Value
IEC61850 GOOSE UInteger Input 5 Default Value 1000
IEC61850 GOOSE UInteger Input 5 Mode Default Value
IEC61850 GOOSE UInteger Input 6 Default Value 1000
IEC61850 GOOSE UInteger Input 6 Mode Default Value
IEC61850 GOOSE UInteger Input 7 Default Value 1000
IEC61850 GOOSE UInteger Input 7 Mode Default Value
IEC61850 GOOSE UInteger Input 8 Default Value 1000
IEC61850 GOOSE UInteger Input 8 Mode Default Value
IEC61850 GOOSE UInteger Input 9 Default Value 1000
IEC61850 GOOSE UInteger Input 9 Mode Default Value
IEC61850 GOOSE UInteger Input 10 Default Value 1000
IEC61850 GOOSE UInteger Input 10 Mode Default Value
IEC61850 GOOSE UInteger Input 11 Default Value 1000
IEC61850 GOOSE UInteger Input 11 Mode Default Value
IEC61850 GOOSE UInteger Input 12 Default Value 1000
Fri Jun 10 12:09:10 2011 Version: 5.81 Settings (Enabled Features) PAGE 30

SONELGAZ MSILA TP3 T60 REV 0.URS


D:\DOCUMENTS AND SETTINGS\CABLEBE\MY DOCUMENTS\URPC SETTING FILES\SONELGAZ ARCHIVE\
DEVICE DEFINITION
FILES
ORDER CODE: T60-J04-HMH-F8L-H6P-M8N-P6D-U4L-W6C
VERSION: 5.7X
DESCRIPTION: SONELGAZ MSILA T60 TRANSFORMER MANAGEMENT RELAY
TEXT COLOR

IEC 61850 GOOSE UINTEGERS INPUTS (continued from last page)


IEC61850 GOOSE UInteger Input 12 Mode Default Value
IEC61850 GOOSE UInteger Input 13 Default Value 1000
IEC61850 GOOSE UInteger Input 13 Mode Default Value
IEC61850 GOOSE UInteger Input 14 Default Value 1000
IEC61850 GOOSE UInteger Input 14 Mode Default Value
IEC61850 GOOSE UInteger Input 15 Default Value 1000
IEC61850 GOOSE UInteger Input 15 Mode Default Value
IEC61850 GOOSE UInteger Input 16 Default Value 1000
IEC61850 GOOSE UInteger Input 16 Mode Default Value
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


Study Appendix

10. Appendix 4: F650 Setting File Summary (Station Auxiliary Transformer TL2)

PAGE 118

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

File Name: Sonelgaz MSila TL2-650 rev 0 v5_40.650


Comment: Sonelgaz Tiaret TL F650
Model: F650***F2G1***6
Version: 5.40
Part: 21.12.9.0

SETPOINTS

SERIAL PORTS

NAME VALUE UNIT


COM1 Baud Rate 19200
COM2 Baud Rate 19200
COM1 Parity NONE
COM2 Parity NONE

NETWORK(ETHERNET) 1

NAME VALUE UNIT


IP Address Oct1 192 [0 : 255]
IP Address Oct2 168 [0 : 255]
IP Address Oct3 101 [0 : 255]
IP Address Oct4 2 [0 : 255]
Netmask Oct1 255 [0 : 255]
Netmask Oct2 255 [0 : 255]
Netmask Oct3 255 [0 : 255]
Netmask Oct4 0 [0 : 255]
Gateway IP Oct1 0 [0 : 255]
Gateway IP Oct2 0 [0 : 255]
Gateway IP Oct3 0 [0 : 255]
Gateway IP Oct4 0 [0 : 255]

NETWORK(ETHERNET) 2

NAME VALUE UNIT


IP Address Oct1 0 [0 : 255]
IP Address Oct2 0 [0 : 255]
IP Address Oct3 0 [0 : 255]
IP Address Oct4 0 [0 : 255]
Netmask Oct1 0 [0 : 255]
Netmask Oct2 0 [0 : 255]
Netmask Oct3 0 [0 : 255]
Netmask Oct4 0 [0 : 255]
Gateway IP Oct1 0 [0 : 255]
Gateway IP Oct2 0 [0 : 255]
Gateway IP Oct3 0 [0 : 255]
Gateway IP Oct4 0 [0 : 255]

MODBUS PROTOCOL

NAME VALUE UNIT


Modbus Address COM1 254 [1 : 255]
Modbus Address COM2 254 [1 : 255]
Modbus Port Number 502 [0 : 65535]

DNP3 SLAVE 1

1
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Physical Port NONE
Address 0 [0 : 65534]
IP Addr Client1 Oct1 0 [0 : 255]
IP Addr Client1 Oct2 0 [0 : 255]
IP Addr Client1 Oct3 0 [0 : 255]
IP Addr Client1 Oct4 0 [0 : 255]
IP Addr Client2 Oct1 0 [0 : 255]
IP Addr Client2 Oct2 0 [0 : 255]
IP Addr Client2 Oct3 0 [0 : 255]
IP Addr Client2 Oct4 0 [0 : 255]
IP Addr Client3 Oct1 0 [0 : 255]
IP Addr Client3 Oct2 0 [0 : 255]
IP Addr Client3 Oct3 0 [0 : 255]
IP Addr Client3 Oct4 0 [0 : 255]
IP Addr Client4 Oct1 0 [0 : 255]
IP Addr Client4 Oct2 0 [0 : 255]
IP Addr Client4 Oct3 0 [0 : 255]
IP Addr Client4 Oct4 0 [0 : 255]
IP Addr Client5 Oct1 0 [0 : 255]
IP Addr Client5 Oct2 0 [0 : 255]
IP Addr Client5 Oct3 0 [0 : 255]
IP Addr Client5 Oct4 0 [0 : 255]
TCP/UDP Port 0 [0 : 65535]
Unsol Resp Function DISABLED
Unsol Resp TimeOut 0 [0 : 60] s
Unsol Resp Max Ret 0 [0 : 255]
Unsol Resp Dest Adr 0 [0 : 65519]
Current Scale Factor 0.00001
Voltage Scale Factor 0.00001
Power Scale Factor 0.00001
Energy Scale Factor 0.00001
Other Scale Factor 0.00001
Current Deadband 0 [0 : 65535]
Voltage Deadband 0 [0 : 65535]
Power Deadband 0 [0 : 65535]
Energy Deadband 0 [0 : 65535]
Other Deadband 0 [0 : 65535]
Msg Fragment Size 30 [30 : 2048]
Binary Input Block 1 NOT USED
Binary Input Block 2 NOT USED
Binary Input Block 3 NOT USED
Binary Input Block 4 NOT USED
Binary Input Block 5 NOT USED
Binary Input Block 6 NOT USED
Binary Input Block 7 NOT USED
Binary Input Block 8 NOT USED
Binary Input Block 9 NOT USED
Binary Input Block 10 NOT USED

DNP3 SLAVE 2

NAME VALUE UNIT


Physical Port NONE
Address 0 [0 : 65534]
IP Addr Client1 Oct1 0 [0 : 255]
IP Addr Client1 Oct2 0 [0 : 255]
IP Addr Client1 Oct3 0 [0 : 255]
IP Addr Client1 Oct4 0 [0 : 255]
IP Addr Client2 Oct1 0 [0 : 255]
IP Addr Client2 Oct2 0 [0 : 255]
IP Addr Client2 Oct3 0 [0 : 255]
IP Addr Client2 Oct4 0 [0 : 255]
IP Addr Client3 Oct1 0 [0 : 255]
IP Addr Client3 Oct2 0 [0 : 255]

2
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


IP Addr Client3 Oct3 0 [0 : 255]
IP Addr Client3 Oct4 0 [0 : 255]
IP Addr Client4 Oct1 0 [0 : 255]
IP Addr Client4 Oct2 0 [0 : 255]
IP Addr Client4 Oct3 0 [0 : 255]
IP Addr Client4 Oct4 0 [0 : 255]
IP Addr Client5 Oct1 0 [0 : 255]
IP Addr Client5 Oct2 0 [0 : 255]
IP Addr Client5 Oct3 0 [0 : 255]
IP Addr Client5 Oct4 0 [0 : 255]
TCP/UDP Port 0 [0 : 65535]
Unsol Resp Function DISABLED
Unsol Resp TimeOut 0 [0 : 60] s
Unsol Resp Max Ret 0 [0 : 255]
Unsol Resp Dest Adr 0 [0 : 65519]
Current Scale Factor 0.00001
Voltage Scale Factor 0.00001
Power Scale Factor 0.00001
Energy Scale Factor 0.00001
Other Scale Factor 0.00001
Current Deadband 0 [0 : 65535]
Voltage Deadband 0 [0 : 65535]
Power Deadband 0 [0 : 65535]
Energy Deadband 0 [0 : 65535]
Other Deadband 0 [0 : 65535]
Msg Fragment Size 30 [30 : 2048]
Binary Input Block 1 NOT USED
Binary Input Block 2 NOT USED
Binary Input Block 3 NOT USED
Binary Input Block 4 NOT USED
Binary Input Block 5 NOT USED
Binary Input Block 6 NOT USED
Binary Input Block 7 NOT USED
Binary Input Block 8 NOT USED
Binary Input Block 9 NOT USED
Binary Input Block 10 NOT USED

DNP3 SLAVE 3

NAME VALUE UNIT


Physical Port NONE
Address 0 [0 : 65534]
IP Addr Client1 Oct1 0 [0 : 255]
IP Addr Client1 Oct2 0 [0 : 255]
IP Addr Client1 Oct3 0 [0 : 255]
IP Addr Client1 Oct4 0 [0 : 255]
IP Addr Client2 Oct1 0 [0 : 255]
IP Addr Client2 Oct2 0 [0 : 255]
IP Addr Client2 Oct3 0 [0 : 255]
IP Addr Client2 Oct4 0 [0 : 255]
IP Addr Client3 Oct1 0 [0 : 255]
IP Addr Client3 Oct2 0 [0 : 255]
IP Addr Client3 Oct3 0 [0 : 255]
IP Addr Client3 Oct4 0 [0 : 255]
IP Addr Client4 Oct1 0 [0 : 255]
IP Addr Client4 Oct2 0 [0 : 255]
IP Addr Client4 Oct3 0 [0 : 255]
IP Addr Client4 Oct4 0 [0 : 255]
IP Addr Client5 Oct1 0 [0 : 255]
IP Addr Client5 Oct2 0 [0 : 255]
IP Addr Client5 Oct3 0 [0 : 255]
IP Addr Client5 Oct4 0 [0 : 255]
TCP/UDP Port 0 [0 : 65535]
Unsol Resp Function DISABLED

3
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Unsol Resp TimeOut 0 [0 : 60] s
Unsol Resp Max Ret 0 [0 : 255]
Unsol Resp Dest Adr 0 [0 : 65519]
Current Scale Factor 0.00001
Voltage Scale Factor 0.00001
Power Scale Factor 0.00001
Energy Scale Factor 0.00001
Other Scale Factor 0.00001
Current Deadband 0 [0 : 65535]
Voltage Deadband 0 [0 : 65535]
Power Deadband 0 [0 : 65535]
Energy Deadband 0 [0 : 65535]
Other Deadband 0 [0 : 65535]
Msg Fragment Size 30 [30 : 2048]
Binary Input Block 1 NOT USED
Binary Input Block 2 NOT USED
Binary Input Block 3 NOT USED
Binary Input Block 4 NOT USED
Binary Input Block 5 NOT USED
Binary Input Block 6 NOT USED
Binary Input Block 7 NOT USED
Binary Input Block 8 NOT USED
Binary Input Block 9 NOT USED
Binary Input Block 10 NOT USED

SNTP

NAME VALUE UNIT


Function DISABLED
UDP Port 123 [1 : 65535]
Server IP Oct1 0 [0 : 255]
Server IP Oct2 0 [0 : 255]
Server IP Oct3 0 [0 : 255]
Server IP Oct4 0 [0 : 255]

MODBUS USER MAP

NAME VALUE UNIT


Address 00 0000 [0000 : FFFF]
Address 01 0000 [0000 : FFFF]
Address 02 0000 [0000 : FFFF]
Address 03 0000 [0000 : FFFF]
Address 04 0000 [0000 : FFFF]
Address 05 0000 [0000 : FFFF]
Address 06 0000 [0000 : FFFF]
Address 07 0000 [0000 : FFFF]
Address 08 0000 [0000 : FFFF]
Address 09 0000 [0000 : FFFF]
Address 10 0000 [0000 : FFFF]
Address 11 0000 [0000 : FFFF]
Address 12 0000 [0000 : FFFF]
Address 13 0000 [0000 : FFFF]
Address 14 0000 [0000 : FFFF]
Address 15 0000 [0000 : FFFF]
Address 16 0000 [0000 : FFFF]
Address 17 0000 [0000 : FFFF]
Address 18 0000 [0000 : FFFF]
Address 19 0000 [0000 : FFFF]
Address 20 0000 [0000 : FFFF]
Address 21 0000 [0000 : FFFF]
Address 22 0000 [0000 : FFFF]
Address 23 0000 [0000 : FFFF]
Address 24 0000 [0000 : FFFF]
Address 25 0000 [0000 : FFFF]
Address 26 0000 [0000 : FFFF]

4
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Address 27 0000 [0000 : FFFF]
Address 28 0000 [0000 : FFFF]
Address 29 0000 [0000 : FFFF]
Address 30 0000 [0000 : FFFF]
Address 31 0000 [0000 : FFFF]
Address 32 0000 [0000 : FFFF]
Address 33 0000 [0000 : FFFF]
Address 34 0000 [0000 : FFFF]
Address 35 0000 [0000 : FFFF]
Address 36 0000 [0000 : FFFF]
Address 37 0000 [0000 : FFFF]
Address 38 0000 [0000 : FFFF]
Address 39 0000 [0000 : FFFF]
Address 40 0000 [0000 : FFFF]
Address 41 0000 [0000 : FFFF]
Address 42 0000 [0000 : FFFF]
Address 43 0000 [0000 : FFFF]
Address 44 0000 [0000 : FFFF]
Address 45 0000 [0000 : FFFF]
Address 46 0000 [0000 : FFFF]
Address 47 0000 [0000 : FFFF]
Address 48 0000 [0000 : FFFF]
Address 49 0000 [0000 : FFFF]
Address 50 0000 [0000 : FFFF]
Address 51 0000 [0000 : FFFF]
Address 52 0000 [0000 : FFFF]
Address 53 0000 [0000 : FFFF]
Address 54 0000 [0000 : FFFF]
Address 55 0000 [0000 : FFFF]
Address 56 0000 [0000 : FFFF]
Address 57 0000 [0000 : FFFF]
Address 58 0000 [0000 : FFFF]
Address 59 0000 [0000 : FFFF]
Address 60 0000 [0000 : FFFF]
Address 61 0000 [0000 : FFFF]
Address 62 0000 [0000 : FFFF]
Address 63 0000 [0000 : FFFF]
Address 64 0000 [0000 : FFFF]
Address 65 0000 [0000 : FFFF]
Address 66 0000 [0000 : FFFF]
Address 67 0000 [0000 : FFFF]
Address 68 0000 [0000 : FFFF]
Address 69 0000 [0000 : FFFF]
Address 70 0000 [0000 : FFFF]
Address 71 0000 [0000 : FFFF]
Address 72 0000 [0000 : FFFF]
Address 73 0000 [0000 : FFFF]
Address 74 0000 [0000 : FFFF]
Address 75 0000 [0000 : FFFF]
Address 76 0000 [0000 : FFFF]
Address 77 0000 [0000 : FFFF]
Address 78 0000 [0000 : FFFF]
Address 79 0000 [0000 : FFFF]
Address 80 0000 [0000 : FFFF]
Address 81 0000 [0000 : FFFF]
Address 82 0000 [0000 : FFFF]
Address 83 0000 [0000 : FFFF]
Address 84 0000 [0000 : FFFF]
Address 85 0000 [0000 : FFFF]
Address 86 0000 [0000 : FFFF]
Address 87 0000 [0000 : FFFF]
Address 88 0000 [0000 : FFFF]
Address 89 0000 [0000 : FFFF]
Address 90 0000 [0000 : FFFF]
Address 91 0000 [0000 : FFFF]
Address 92 0000 [0000 : FFFF]

5
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Address 93 0000 [0000 : FFFF]
Address 94 0000 [0000 : FFFF]
Address 95 0000 [0000 : FFFF]
Address 96 0000 [0000 : FFFF]
Address 97 0000 [0000 : FFFF]
Address 98 0000 [0000 : FFFF]
Address 99 0000 [0000 : FFFF]
Address 100 0000 [0000 : FFFF]
Address 101 0000 [0000 : FFFF]
Address 102 0000 [0000 : FFFF]
Address 103 0000 [0000 : FFFF]
Address 104 0000 [0000 : FFFF]
Address 105 0000 [0000 : FFFF]
Address 106 0000 [0000 : FFFF]
Address 107 0000 [0000 : FFFF]
Address 108 0000 [0000 : FFFF]
Address 109 0000 [0000 : FFFF]
Address 110 0000 [0000 : FFFF]
Address 111 0000 [0000 : FFFF]
Address 112 0000 [0000 : FFFF]
Address 113 0000 [0000 : FFFF]
Address 114 0000 [0000 : FFFF]
Address 115 0000 [0000 : FFFF]
Address 116 0000 [0000 : FFFF]
Address 117 0000 [0000 : FFFF]
Address 118 0000 [0000 : FFFF]
Address 119 0000 [0000 : FFFF]
Address 120 0000 [0000 : FFFF]
Address 121 0000 [0000 : FFFF]
Address 122 0000 [0000 : FFFF]
Address 123 0000 [0000 : FFFF]
Address 124 0000 [0000 : FFFF]
Address 125 0000 [0000 : FFFF]
Address 126 0000 [0000 : FFFF]
Address 127 0000 [0000 : FFFF]
Address 128 0000 [0000 : FFFF]
Address 129 0000 [0000 : FFFF]
Address 130 0000 [0000 : FFFF]
Address 131 0000 [0000 : FFFF]
Address 132 0000 [0000 : FFFF]
Address 133 0000 [0000 : FFFF]
Address 134 0000 [0000 : FFFF]
Address 135 0000 [0000 : FFFF]
Address 136 0000 [0000 : FFFF]
Address 137 0000 [0000 : FFFF]
Address 138 0000 [0000 : FFFF]
Address 139 0000 [0000 : FFFF]
Address 140 0000 [0000 : FFFF]
Address 141 0000 [0000 : FFFF]
Address 142 0000 [0000 : FFFF]
Address 143 0000 [0000 : FFFF]
Address 144 0000 [0000 : FFFF]
Address 145 0000 [0000 : FFFF]
Address 146 0000 [0000 : FFFF]
Address 147 0000 [0000 : FFFF]
Address 148 0000 [0000 : FFFF]
Address 149 0000 [0000 : FFFF]
Address 150 0000 [0000 : FFFF]
Address 151 0000 [0000 : FFFF]
Address 152 0000 [0000 : FFFF]
Address 153 0000 [0000 : FFFF]
Address 154 0000 [0000 : FFFF]
Address 155 0000 [0000 : FFFF]
Address 156 0000 [0000 : FFFF]
Address 157 0000 [0000 : FFFF]
Address 158 0000 [0000 : FFFF]

6
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Address 159 0000 [0000 : FFFF]
Address 160 0000 [0000 : FFFF]
Address 161 0000 [0000 : FFFF]
Address 162 0000 [0000 : FFFF]
Address 163 0000 [0000 : FFFF]
Address 164 0000 [0000 : FFFF]
Address 165 0000 [0000 : FFFF]
Address 166 0000 [0000 : FFFF]
Address 167 0000 [0000 : FFFF]
Address 168 0000 [0000 : FFFF]
Address 169 0000 [0000 : FFFF]
Address 170 0000 [0000 : FFFF]
Address 171 0000 [0000 : FFFF]
Address 172 0000 [0000 : FFFF]
Address 173 0000 [0000 : FFFF]
Address 174 0000 [0000 : FFFF]
Address 175 0000 [0000 : FFFF]
Address 176 0000 [0000 : FFFF]
Address 177 0000 [0000 : FFFF]
Address 178 0000 [0000 : FFFF]
Address 179 0000 [0000 : FFFF]
Address 180 0000 [0000 : FFFF]
Address 181 0000 [0000 : FFFF]
Address 182 0000 [0000 : FFFF]
Address 183 0000 [0000 : FFFF]
Address 184 0000 [0000 : FFFF]
Address 185 0000 [0000 : FFFF]
Address 186 0000 [0000 : FFFF]
Address 187 0000 [0000 : FFFF]
Address 188 0000 [0000 : FFFF]
Address 189 0000 [0000 : FFFF]
Address 190 0000 [0000 : FFFF]
Address 191 0000 [0000 : FFFF]
Address 192 0000 [0000 : FFFF]
Address 193 0000 [0000 : FFFF]
Address 194 0000 [0000 : FFFF]
Address 195 0000 [0000 : FFFF]
Address 196 0000 [0000 : FFFF]
Address 197 0000 [0000 : FFFF]
Address 198 0000 [0000 : FFFF]
Address 199 0000 [0000 : FFFF]
Address 200 0000 [0000 : FFFF]
Address 201 0000 [0000 : FFFF]
Address 202 0000 [0000 : FFFF]
Address 203 0000 [0000 : FFFF]
Address 204 0000 [0000 : FFFF]
Address 205 0000 [0000 : FFFF]
Address 206 0000 [0000 : FFFF]
Address 207 0000 [0000 : FFFF]
Address 208 0000 [0000 : FFFF]
Address 209 0000 [0000 : FFFF]
Address 210 0000 [0000 : FFFF]
Address 211 0000 [0000 : FFFF]
Address 212 0000 [0000 : FFFF]
Address 213 0000 [0000 : FFFF]
Address 214 0000 [0000 : FFFF]
Address 215 0000 [0000 : FFFF]
Address 216 0000 [0000 : FFFF]
Address 217 0000 [0000 : FFFF]
Address 218 0000 [0000 : FFFF]
Address 219 0000 [0000 : FFFF]
Address 220 0000 [0000 : FFFF]
Address 221 0000 [0000 : FFFF]
Address 222 0000 [0000 : FFFF]
Address 223 0000 [0000 : FFFF]
Address 224 0000 [0000 : FFFF]

7
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Address 225 0000 [0000 : FFFF]
Address 226 0000 [0000 : FFFF]
Address 227 0000 [0000 : FFFF]
Address 228 0000 [0000 : FFFF]
Address 229 0000 [0000 : FFFF]
Address 230 0000 [0000 : FFFF]
Address 231 0000 [0000 : FFFF]
Address 232 0000 [0000 : FFFF]
Address 233 0000 [0000 : FFFF]
Address 234 0000 [0000 : FFFF]
Address 235 0000 [0000 : FFFF]
Address 236 0000 [0000 : FFFF]
Address 237 0000 [0000 : FFFF]
Address 238 0000 [0000 : FFFF]
Address 239 0000 [0000 : FFFF]
Address 240 0000 [0000 : FFFF]
Address 241 0000 [0000 : FFFF]
Address 242 0000 [0000 : FFFF]
Address 243 0000 [0000 : FFFF]
Address 244 0000 [0000 : FFFF]
Address 245 0000 [0000 : FFFF]
Address 246 0000 [0000 : FFFF]
Address 247 0000 [0000 : FFFF]
Address 248 0000 [0000 : FFFF]
Address 249 0000 [0000 : FFFF]
Address 250 0000 [0000 : FFFF]
Address 251 0000 [0000 : FFFF]
Address 252 0000 [0000 : FFFF]
Address 253 0000 [0000 : FFFF]
Address 254 0000 [0000 : FFFF]
Address 255 0000 [0000 : FFFF]

OSCILLOGRAPHY

NAME VALUE UNIT


Function ENABLED
Trigger Position 25 [5 : 95] %
Samples/Cycle 32
Max. Number Osc. 16 [1 : 20]
Automatic Overwrite ENABLED
Snapshot Events ENABLED

DATA LOGGER

NAME VALUE UNIT


Function ENABLED
Data Logger Rate 5 Minutes
Data Logger Chnl 1 RMS Ia Primary
Data Logger Chnl 2 RMS Ib Primary
Data Logger Chnl 3 RMS Ic Primary
Data Logger Chnl 4 Vab Primary
Data Logger Chnl 5 Vbc Primary
Data Logger Chnl 6 Vca Primary
Data Logger Chnl 7 3 Phase Real Pwr
Data Logger Chnl 8 3 Phase Reactive Pwr
Data Logger Chnl 9 3 Phase Apparent Pwr
Data Logger Chnl 10 I0 Primary
Data Logger Chnl 11 I1 Primary
Data Logger Chnl 12 I2 Primary
Data Logger Chnl 13 V0 Primary
Data Logger Chnl 14 V1 Primary
Data Logger Chnl 15 V2 Primary
Data Logger Chnl 16 Bus Frequency

TIME SETTINGS

8
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


LOC. TIME OFFS. UTC 0.0 [-24.0 : 24.0]
DAYLIG. SAVINGS TIME DISABLED
DST START MONTH MAR
DST START WEEKDAY SUNDAY
DST START DAY INST LAST
DST START HOUR 2 [0 : 23]
DST STOP MONTH OCT
DST STOP WEEKDAY SUNDAY
DST STOP DAY INST LAST
DST STOP HOUR 2 [0 : 23]
IRIG-B LOCAL TIME OFF

GENERAL SETTINGS

NAME VALUE UNIT


Phase CT Ratio 300.0 [1.0 : 6000.0]
Ground CT Ratio 300.0 [1.0 : 6000.0]
Stv Ground CT Ratio 300.0 [1.0 : 6000.0]
Phase VT Ratio 115.0 [1.0 : 6000.0]
Phase VT Connection WYE
Nominal Voltage 100.0 [1.0 : 250.0] V
Nominal Frequency 50 Hz
Phase Rotation ABC
Frequency Reference VI
Auxiliary Voltage VX
Snapshot Events DISABLED
Relay Out Of Service ENABLED

FLEX CURVES A

NAME VALUE UNIT


Time 0.00xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.05xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.10xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.15xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.20xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.25xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.30xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.35xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.40xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.45xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.48xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.50xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.52xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.54xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.56xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.58xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.60xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.62xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.64xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.66xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.68xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.70xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.72xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.74xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.76xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.78xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.80xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.82xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.84xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.86xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.88xPKP [RST] 0.000 [0.000 : 65.535] s

9
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Time 0.90xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.91xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.92xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.93xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.94xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.95xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.96xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.97xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.98xPKP [RST] 0.000 [0.000 : 65.535] s
Time 1.03xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.05xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 6.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 6.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 7.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 7.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 8.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 8.50xPKP [OP] 0.000 [0.000 : 65.535] s

10
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Time 9.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 9.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 10.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 10.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 11.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 11.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 12.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 12.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 13.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 13.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 14.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 14.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 15.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 15.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 16.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 16.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 17.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 17.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 18.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 18.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 19.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 19.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 20.00xPKP [OP] 0.000 [0.000 : 65.535] s

FLEX CURVES B

NAME VALUE UNIT


Time 0.00xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.05xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.10xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.15xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.20xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.25xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.30xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.35xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.40xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.45xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.48xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.50xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.52xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.54xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.56xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.58xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.60xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.62xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.64xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.66xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.68xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.70xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.72xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.74xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.76xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.78xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.80xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.82xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.84xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.86xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.88xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.90xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.91xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.92xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.93xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.94xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.95xPKP [RST] 0.000 [0.000 : 65.535] s

11
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Time 0.96xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.97xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.98xPKP [RST] 0.000 [0.000 : 65.535] s
Time 1.03xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.05xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 6.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 6.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 7.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 7.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 8.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 8.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 9.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 9.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 10.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 10.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 11.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 11.50xPKP [OP] 0.000 [0.000 : 65.535] s

12
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Time 12.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 12.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 13.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 13.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 14.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 14.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 15.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 15.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 16.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 16.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 17.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 17.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 18.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 18.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 19.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 19.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 20.00xPKP [OP] 0.000 [0.000 : 65.535] s

FLEX CURVES C

NAME VALUE UNIT


Time 0.00xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.05xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.10xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.15xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.20xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.25xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.30xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.35xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.40xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.45xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.48xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.50xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.52xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.54xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.56xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.58xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.60xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.62xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.64xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.66xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.68xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.70xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.72xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.74xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.76xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.78xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.80xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.82xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.84xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.86xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.88xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.90xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.91xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.92xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.93xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.94xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.95xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.96xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.97xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.98xPKP [RST] 0.000 [0.000 : 65.535] s
Time 1.03xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.05xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.10xPKP [OP] 0.000 [0.000 : 65.535] s

13
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Time 1.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 6.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 6.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 7.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 7.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 8.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 8.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 9.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 9.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 10.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 10.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 11.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 11.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 12.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 12.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 13.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 13.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 14.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 14.50xPKP [OP] 0.000 [0.000 : 65.535] s

14
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Time 15.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 15.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 16.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 16.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 17.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 17.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 18.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 18.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 19.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 19.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 20.00xPKP [OP] 0.000 [0.000 : 65.535] s

FLEX CURVES D

NAME VALUE UNIT


Time 0.00xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.05xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.10xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.15xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.20xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.25xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.30xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.35xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.40xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.45xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.48xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.50xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.52xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.54xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.56xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.58xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.60xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.62xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.64xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.66xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.68xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.70xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.72xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.74xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.76xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.78xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.80xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.82xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.84xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.86xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.88xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.90xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.91xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.92xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.93xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.94xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.95xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.96xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.97xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.98xPKP [RST] 0.000 [0.000 : 65.535] s
Time 1.03xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.05xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.70xPKP [OP] 0.000 [0.000 : 65.535] s

15
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Time 1.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 6.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 6.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 7.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 7.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 8.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 8.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 9.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 9.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 10.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 10.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 11.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 11.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 12.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 12.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 13.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 13.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 14.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 14.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 15.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 15.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 16.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 16.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 17.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 17.50xPKP [OP] 0.000 [0.000 : 65.535] s

16
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Time 18.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 18.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 19.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 19.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 20.00xPKP [OP] 0.000 [0.000 : 65.535] s

BREAKER SETTINGS

NAME VALUE UNIT


Number of Switchgear 1 [1 : 16]
Maximum KI2t 9999.99 [0.00 : 9999.99] (KA)2 s
KI2t Integ. Time 0.03 [0.03 : 0.25] s
Maximum Openings 0 [0 : 9999]
Max.Openings 1 hour 1 [1 : 60]
Snapshot Events DISABLED

BREAKER MAINTENANCE

NAME VALUE UNIT


KI2t BKR Ph A Cnt 0.00 [0.00 : 9999.99] (KA)2 s
KI2t BKR Ph B Cnt 0.00 [0.00 : 9999.99] (KA)2 s
KI2t BKR Ph C Cnt 0.00 [0.00 : 9999.99] (KA)2 s
BKR Openings Cnt 0 [0 : 9999]
BKR Closings Cnt 0 [0 : 9999]

SWITCHGEAR

NAME VALUE UNIT


Snapshot Events SWGR 1 DISABLED
Snapshot Events SWGR 2 DISABLED
Snapshot Events SWGR 3 DISABLED
Snapshot Events SWGR 4 DISABLED
Snapshot Events SWGR 5 DISABLED
Snapshot Events SWGR 6 DISABLED
Snapshot Events SWGR 7 DISABLED
Snapshot Events SWGR 8 DISABLED
Snapshot Events SWGR 9 DISABLED
Snapshot Events SWGR 10 DISABLED
Snapshot Events SWGR 11 DISABLED
Snapshot Events SWGR 12 DISABLED
Snapshot Events SWGR 13 DISABLED
Snapshot Events SWGR 14 DISABLED
Snapshot Events SWGR 15 DISABLED
Snapshot Events SWGR 16 DISABLED

PHASE TOC HIGH 1

NAME VALUE UNIT


Function ENABLED
Input RMS
Pickup Level 0.60 [0.05 : 160.00] A
Curve IEEE Ext Inv
TD Multiplier 3.50 [0.00 : 900.00] s
Reset INSTANTANEOUS
Voltage Restraint DISABLED
Snapshot Events ENABLED

PHASE IOC HIGH 1

17
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Function ENABLED
Input PHASOR(DFT)
Pickup Level 9.00 [0.05 : 160.00] A
Trip Delay 0.00 [0.00 : 900.00] s
Reset Delay 0.00 [0.00 : 900.00] s
Snapshot Events ENABLED

PHASE IOC LOW 1

NAME VALUE UNIT


Function ENABLED
Input PHASOR(DFT)
Pickup Level 1.50 [0.05 : 160.00] A
Trip Delay 0.60 [0.00 : 900.00] s
Reset Delay 0.00 [0.00 : 900.00] s
Snapshot Events ENABLED

SETTING GROUP

NAME VALUE UNIT


Function DISABLED
Active Group GROUP 1
Snapshot Events DISABLED

VT FUSE FAILURE

NAME VALUE UNIT


Function ENABLED
Snapshot Events ENABLED

PULSE COUNTERS

NAME VALUE UNIT


PulseCntr Enabled 1 DISABLED
PulseCntr Name 1 Pulse Counter 1
PulseCntr Factor 1 1.000 [0.000 : 65000.000]
PulseCntr Overflow 1 65535 [0 : 1000000]
PulseCntr Board Origin 1 F
PulseCntr Input Origin 1 1 [1 : 32]
PulseCntr Enabled 2 DISABLED
PulseCntr Name 2 Pulse Counter 2
PulseCntr Factor 2 1.000 [0.000 : 65000.000]
PulseCntr Overflow 2 65535 [0 : 1000000]
PulseCntr Board Origin 2 F
PulseCntr Input Origin 2 1 [1 : 32]
PulseCntr Enabled 3 DISABLED
PulseCntr Name 3 Pulse Counter 3
PulseCntr Factor 3 1.000 [0.000 : 65000.000]
PulseCntr Overflow 3 65535 [0 : 1000000]
PulseCntr Board Origin 3 F
PulseCntr Input Origin 3 1 [1 : 32]
PulseCntr Enabled 4 DISABLED
PulseCntr Name 4 Pulse Counter 4
PulseCntr Factor 4 1.000 [0.000 : 65000.000]
PulseCntr Overflow 4 65535 [0 : 1000000]
PulseCntr Board Origin 4 F
PulseCntr Input Origin 4 1 [1 : 32]
PulseCntr Enabled 5 DISABLED
PulseCntr Name 5 Pulse Counter 5
PulseCntr Factor 5 1.000 [0.000 : 65000.000]
PulseCntr Overflow 5 65535 [0 : 1000000]
PulseCntr Board Origin 5 F
PulseCntr Input Origin 5 1 [1 : 32]

18
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


PulseCntr Enabled 6 DISABLED
PulseCntr Name 6 Pulse Counter 6
PulseCntr Factor 6 1.000 [0.000 : 65000.000]
PulseCntr Overflow 6 65535 [0 : 1000000]
PulseCntr Board Origin 6 F
PulseCntr Input Origin 6 1 [1 : 32]
PulseCntr Enabled 7 DISABLED
PulseCntr Name 7 Pulse Counter 7
PulseCntr Factor 7 1.000 [0.000 : 65000.000]
PulseCntr Overflow 7 65535 [0 : 1000000]
PulseCntr Board Origin 7 F
PulseCntr Input Origin 7 1 [1 : 32]
PulseCntr Enabled 8 DISABLED
PulseCntr Name 8 Pulse Counter 8
PulseCntr Factor 8 1.000 [0.000 : 65000.000]
PulseCntr Overflow 8 65535 [0 : 1000000]
PulseCntr Board Origin 8 F
PulseCntr Input Origin 8 1 [1 : 32]

ANALOG COMPARATORS

NAME VALUE UNIT


Analog Function DISABLED
Snapshot Events DISABLED
Analog Input 01 None
Analog Maximum 1 1.000 [-100000.000 : 100000.000]
Analog Minimum 1 1.000 [-100000.000 : 100000.000]
Analog Delay 01 1.00 [0.00 : 900.00] s
Analog Hysteresis 1 1.0 [0.0 : 50.0]
Analog Direction 1 OUT
Analog Input 2 None
Analog Maximum 2 1.000 [-100000.000 : 100000.000]
Analog Minimum 2 1.000 [-100000.000 : 100000.000]
Analog Delay 2 1.00 [0.00 : 900.00] s
Analog Hysteresis 2 1.0 [0.0 : 50.0]
Analog Direction 2 OUT
Analog Input 3 None
Analog Maximum 3 1.000 [-100000.000 : 100000.000]
Analog Minimum 3 1.000 [-100000.000 : 100000.000]
Analog Delay 3 1.00 [0.00 : 900.00] s
Analog Hysteresis 3 1.0 [0.0 : 50.0]
Analog Direction 3 OUT
Analog Input 4 None
Analog Maximum 4 1.000 [-100000.000 : 100000.000]
Analog Minimum 4 1.000 [-100000.000 : 100000.000]
Analog Delay 4 1.00 [0.00 : 900.00] s
Analog Hysteresis 4 1.0 [0.0 : 50.0]
Analog Direction 4 OUT
Analog Input 5 None
Analog Maximum 5 1.000 [-100000.000 : 100000.000]
Analog Minimum 5 1.000 [-100000.000 : 100000.000]
Analog Delay 5 1.00 [0.00 : 900.00] s
Analog Hysteresis 5 1.0 [0.0 : 50.0]
Analog Direction 5 OUT
Analog Input 6 None
Analog Maximum 6 1.000 [-100000.000 : 100000.000]
Analog Minimum 6 1.000 [-100000.000 : 100000.000]
Analog Delay 6 1.00 [0.00 : 900.00] s
Analog Hysteresis 6 1.0 [0.0 : 50.0]
Analog Direction 6 OUT
Analog Input 7 None
Analog Maximum 7 1.000 [-100000.000 : 100000.000]
Analog Minimum 7 1.000 [-100000.000 : 100000.000]
Analog Delay 7 1.00 [0.00 : 900.00] s
Analog Hysteresis 7 1.0 [0.0 : 50.0]
Analog Direction 7 OUT

19
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Analog Input 8 None
Analog Maximum 8 1.000 [-100000.000 : 100000.000]
Analog Minimum 8 1.000 [-100000.000 : 100000.000]
Analog Delay 8 1.00 [0.00 : 900.00] s
Analog Hysteresis 8 1.0 [0.0 : 50.0]
Analog Direction 8 OUT
Analog Input 9 None
Analog Maximum 9 1.000 [-100000.000 : 100000.000]
Analog Minimum 9 1.000 [-100000.000 : 100000.000]
Analog Delay 9 1.00 [0.00 : 900.00] s
Analog Hysteresis 9 1.0 [0.0 : 50.0]
Analog Direction 9 OUT
Analog Input 10 None
Analog Maximum 10 1.000 [-100000.000 : 100000.000]
Analog Minimum 10 1.000 [-100000.000 : 100000.000]
Analog Delay 10 1.00 [0.00 : 900.00] s
Analog Hysteresis 10 1.0 [0.0 : 50.0]
Analog Direction 10 OUT
Analog Input 11 None
Analog Maximum 11 1.000 [-100000.000 : 100000.000]
Analog Minimum 11 1.000 [-100000.000 : 100000.000]
Analog Delay 11 1.00 [0.00 : 900.00] s
Analog Hysteresis 11 1.0 [0.0 : 50.0]
Analog Direction 11 OUT
Analog Input 12 None
Analog Maximum 12 1.000 [-100000.000 : 100000.000]
Analog Minimum 12 1.000 [-100000.000 : 100000.000]
Analog Delay 12 1.00 [0.00 : 900.00] s
Analog Hysteresis 12 1.0 [0.0 : 50.0]
Analog Direction 12 OUT
Analog Input 13 None
Analog Maximum 13 1.000 [-100000.000 : 100000.000]
Analog Minimum 13 1.000 [-100000.000 : 100000.000]
Analog Delay 13 1.00 [0.00 : 900.00] s
Analog Hysteresis 13 1.0 [0.0 : 50.0]
Analog Direction 13 OUT
Analog Input 14 None
Analog Maximum 14 1.000 [-100000.000 : 100000.000]
Analog Minimum 14 1.000 [-100000.000 : 100000.000]
Analog Delay 14 1.00 [0.00 : 900.00] s
Analog Hysteresis 14 1.0 [0.0 : 50.0]
Analog Direction 14 OUT
Analog Input 15 None
Analog Maximum 15 1.000 [-100000.000 : 100000.000]
Analog Minimum 15 1.000 [-100000.000 : 100000.000]
Analog Delay 15 1.00 [0.00 : 900.00] s
Analog Hysteresis 15 1.0 [0.0 : 50.0]
Analog Direction 15 OUT
Analog Input 16 None
Analog Maximum 16 1.000 [-100000.000 : 100000.000]
Analog Minimum 16 1.000 [-100000.000 : 100000.000]
Analog Delay 16 1.00 [0.00 : 900.00] s
Analog Hysteresis 16 1.0 [0.0 : 50.0]
Analog Direction 16 OUT
Analog Input 17 None
Analog Maximum 17 1.000 [-100000.000 : 100000.000]
Analog Minimum 17 1.000 [-100000.000 : 100000.000]
Analog Delay 17 1.00 [0.00 : 900.00] s
Analog Hysteresis 17 1.0 [0.0 : 50.0]
Analog Direction 17 OUT
Analog Input 18 None
Analog Maximum 18 1.000 [-100000.000 : 100000.000]
Analog Minimum 18 1.000 [-100000.000 : 100000.000]
Analog Delay 18 1.00 [0.00 : 900.00] s
Analog Hysteresis 18 1.0 [0.0 : 50.0]
Analog Direction 18 OUT

20
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Analog Input 19 None
Analog Maximum 19 1.000 [-100000.000 : 100000.000]
Analog Minimum 19 1.000 [-100000.000 : 100000.000]
Analog Delay 19 1.00 [0.00 : 900.00] s
Analog Hysteresis 19 1.0 [0.0 : 50.0]
Analog Direction 19 OUT
Analog Input 20 None
Analog Maximum 20 1.000 [-100000.000 : 100000.000]
Analog Minimum 20 1.000 [-100000.000 : 100000.000]
Analog Delay 20 1.00 [0.00 : 900.00] s
Analog Hysteresis 20 1.0 [0.0 : 50.0]
Analog Direction 20 OUT

BOARD F

NAME VALUE UNIT


Voltage Threshold A_F 30 [10 : 230] V
Voltage Threshold B_F 30 [10 : 230] V
Debounce Time A_F 3 [1 : 50] ms
Debounce Time B_F 3 [1 : 50] ms
Input Type_F_CC1 (CC1) POSITIVE
Input Type_F_CC2 (CC2) POSITIVE
Input Type_F_CC3 (CC3) POSITIVE
Input Type_F_CC4 (CC4) POSITIVE
Input Type_F_CC5 (CC5) POSITIVE
Input Type_F_CC6 (CC6) POSITIVE
Input Type_F_CC7 (CC7) POSITIVE
Input Type_F_CC8 (CC8) POSITIVE
Input Type_F_CC9 (Va_COIL1) POSITIVE-EDGE
Input Type_F_CC10 (Vb_COIL1) POSITIVE-EDGE
Input Type_F_CC11 (Va_COIL2) POSITIVE-EDGE
Input Type_F_CC12 (Vb_COIL2) POSITIVE-EDGE
Input Type_F_CC13 (O7_SEAL) POSITIVE-EDGE
Input Type_F_CC14 (O8_SEAL) POSITIVE-EDGE
Input Type_F_CC15 (SUP_COIL1) POSITIVE-EDGE
Input Type_F_CC16 (SUP_COIL2) POSITIVE-EDGE
Delay Input Time_F_CC1 (CC1) 0 [0 : 60000] ms
Delay Input Time_F_CC2 (CC2) 0 [0 : 60000] ms
Delay Input Time_F_CC3 (CC3) 0 [0 : 60000] ms
Delay Input Time_F_CC4 (CC4) 0 [0 : 60000] ms
Delay Input Time_F_CC5 (CC5) 0 [0 : 60000] ms
Delay Input Time_F_CC6 (CC6) 0 [0 : 60000] ms
Delay Input Time_F_CC7 (CC7) 0 [0 : 60000] ms
Delay Input Time_F_CC8 (CC8) 0 [0 : 60000] ms
Delay Input Time_F_CC9 (Va_COIL1) 0 [0 : 60000] ms
Delay Input Time_F_CC10 (Vb_COIL1) 0 [0 : 60000] ms
Delay Input Time_F_CC11 (Va_COIL2) 0 [0 : 60000] ms
Delay Input Time_F_CC12 (Vb_COIL2) 0 [0 : 60000] ms
Delay Input Time_F_CC13 (O7_SEAL) 0 [0 : 60000] ms
Delay Input Time_F_CC14 (O8_SEAL) 0 [0 : 60000] ms
Delay Input Time_F_CC15 (SUP_COIL1) 0 [0 : 60000] ms
Delay Input Time_F_CC16 (SUP_COIL2) 0 [0 : 60000] ms
Output Logic_F_01 POSITIVE
Output Logic_F_02 POSITIVE
Output Logic_F_03 POSITIVE
Output Logic_F_04 POSITIVE
Output Logic_F_05 POSITIVE
Output Logic_F_06 POSITIVE
Output Logic_F_07 POSITIVE
Output Logic_F_08 POSITIVE
Output Type_F_01 NORMAL
Output Type_F_02 NORMAL
Output Type_F_03 NORMAL
Output Type_F_04 NORMAL
Output Type_F_05 NORMAL
Output Type_F_06 NORMAL

21
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Output Type_F_07 PULSE
Output Type_F_08 PULSE
Pulse Output Time_F_01 0 [0 : 60000] ms
Pulse Output Time_F_02 0 [0 : 60000] ms
Pulse Output Time_F_03 0 [0 : 60000] ms
Pulse Output Time_F_04 0 [0 : 60000] ms
Pulse Output Time_F_05 0 [0 : 60000] ms
Pulse Output Time_F_06 200 [0 : 60000] ms
Pulse Output Time_F_07 200 [0 : 60000] ms
Pulse Output Time_F_08 200 [0 : 60000] ms
Snapshot Events ENABLED

BOARD G

NAME VALUE UNIT


Voltage Threshold A_G 30 [10 : 230] V
Voltage Threshold B_G 30 [10 : 230] V
Debounce Time A_G 3 [1 : 50] ms
Debounce Time B_G 3 [1 : 50] ms
Input Type_G_CC1 (CC1) POSITIVE
Input Type_G_CC2 (CC2) POSITIVE
Input Type_G_CC3 (CC3) POSITIVE
Input Type_G_CC4 (CC4) POSITIVE
Input Type_G_CC5 (CC5) POSITIVE
Input Type_G_CC6 (CC6) POSITIVE
Input Type_G_CC7 (CC7) POSITIVE
Input Type_G_CC8 (CC8) POSITIVE
Input Type_G_CC9 (CC9) POSITIVE
Input Type_G_CC10 (CC10) POSITIVE
Input Type_G_CC11 (CC11) POSITIVE
Input Type_G_CC12 (CC12) POSITIVE
Input Type_G_CC13 (CC13) POSITIVE
Input Type_G_CC14 (CC14) POSITIVE
Input Type_G_CC15 (CC15) POSITIVE
Input Type_G_CC16 (CC16) POSITIVE
Delay Input Time_G_CC1 (CC1) 0 [0 : 60000] ms
Delay Input Time_G_CC2 (CC2) 0 [0 : 60000] ms
Delay Input Time_G_CC3 (CC3) 0 [0 : 60000] ms
Delay Input Time_G_CC4 (CC4) 0 [0 : 60000] ms
Delay Input Time_G_CC5 (CC5) 0 [0 : 60000] ms
Delay Input Time_G_CC6 (CC6) 0 [0 : 60000] ms
Delay Input Time_G_CC7 (CC7) 0 [0 : 60000] ms
Delay Input Time_G_CC8 (CC8) 0 [0 : 60000] ms
Delay Input Time_G_CC9 (CC9) 0 [0 : 60000] ms
Delay Input Time_G_CC10 (CC10) 0 [0 : 60000] ms
Delay Input Time_G_CC11 (CC11) 0 [0 : 60000] ms
Delay Input Time_G_CC12 (CC12) 0 [0 : 60000] ms
Delay Input Time_G_CC13 (CC13) 0 [0 : 60000] ms
Delay Input Time_G_CC14 (CC14) 0 [0 : 60000] ms
Delay Input Time_G_CC15 (CC15) 0 [0 : 60000] ms
Delay Input Time_G_CC16 (CC16) 0 [0 : 60000] ms
Output Logic_G_01 POSITIVE
Output Logic_G_02 POSITIVE
Output Logic_G_03 POSITIVE
Output Logic_G_04 POSITIVE
Output Logic_G_05 POSITIVE
Output Logic_G_06 POSITIVE
Output Logic_G_07 POSITIVE
Output Logic_G_08 POSITIVE
Output Type_G_01 PULSE
Output Type_G_02 PULSE
Output Type_G_03 NORMAL
Output Type_G_04 NORMAL
Output Type_G_05 PULSE
Output Type_G_06 PULSE
Output Type_G_07 PULSE

22
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Output Type_G_08 PULSE
Pulse Output Time_G_01 200 [0 : 60000] ms
Pulse Output Time_G_02 200 [0 : 60000] ms
Pulse Output Time_G_03 0 [0 : 60000] ms
Pulse Output Time_G_04 0 [0 : 60000] ms
Pulse Output Time_G_05 200 [0 : 60000] ms
Pulse Output Time_G_06 200 [0 : 60000] ms
Pulse Output Time_G_07 200 [0 : 60000] ms
Pulse Output Time_G_08 200 [0 : 60000] ms
Snapshot Events ENABLED

REMOTE COMMS

NAME VALUE UNIT


Remote Comms NONE
650 ID F650
Hold Time 10000 [1000 : 60000] ms
Snapshot Events Remote Out DISABLED
Remote Device 1 Remote Device 1
Bit Pair 1 None
Default Value 1 OFF
Remote Device 2 Remote Device 2
Bit Pair 2 None
Default Value 2 OFF
Remote Device 3 Remote Device 3
Bit Pair 3 None
Default Value 3 OFF
Remote Device 4 Remote Device 4
Bit Pair 4 None
Default Value 4 OFF
Remote Device 5 Remote Device 5
Bit Pair 5 None
Default Value 5 OFF
Remote Device 6 Remote Device 6
Bit Pair 6 None
Default Value 6 OFF
Remote Device 7 Remote Device 7
Bit Pair 7 None
Default Value 7 OFF
Remote Device 8 Remote Device 8
Bit Pair 8 None
Default Value 8 OFF
Remote Device 9 Remote Device 9
Bit Pair 9 None
Default Value 9 OFF
Remote Device 10 Remote Device 10
Bit Pair 10 None
Default Value 10 OFF
Remote Device 11 Remote Device 11
Bit Pair 11 None
Default Value 11 OFF
Remote Device 12 Remote Device 12
Bit Pair 12 None
Default Value 12 OFF
Remote Device 13 Remote Device 13
Bit Pair 13 None
Default Value 13 OFF
Remote Device 14 Remote Device 14
Bit Pair 14 None
Default Value 14 OFF
Remote Device 15 Remote Device 15
Bit Pair 15 None
Default Value 15 OFF
Remote Device 16 Remote Device 16
Bit Pair 16 None
Default Value 16 OFF

23
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Remote Device 17 Remote Device 17
Bit Pair 17 None
Default Value 17 OFF
Remote Device 18 Remote Device 18
Bit Pair 18 None
Default Value 18 OFF
Remote Device 19 Remote Device 19
Bit Pair 19 None
Default Value 19 OFF
Remote Device 20 Remote Device 20
Bit Pair 20 None
Default Value 20 OFF
Remote Device 21 Remote Device 21
Bit Pair 21 None
Default Value 21 OFF
Remote Device 22 Remote Device 22
Bit Pair 22 None
Default Value 22 OFF
Remote Device 23 Remote Device 23
Bit Pair 23 None
Default Value 23 OFF
Remote Device 24 Remote Device 24
Bit Pair 24 None
Default Value 24 OFF
Remote Device 25 Remote Device 25
Bit Pair 25 None
Default Value 25 OFF
Remote Device 26 Remote Device 26
Bit Pair 26 None
Default Value 26 OFF
Remote Device 27 Remote Device 27
Bit Pair 27 None
Default Value 27 OFF
Remote Device 28 Remote Device 28
Bit Pair 28 None
Default Value 28 OFF
Remote Device 29 Remote Device 29
Bit Pair 29 None
Default Value 29 OFF
Remote Device 30 Remote Device 30
Bit Pair 30 None
Default Value 30 OFF
Remote Device 31 Remote Device 31
Bit Pair 31 None
Default Value 31 OFF
Remote Device 32 Remote Device 32
Bit Pair 32 None
Default Value 32 OFF
Snapshot Events Remote Inp DISABLED

RELAY CONFIGURATION

OUTPUTS

OUTPUT SOURCE SOURCE LOGIC LOGIC


26TL STAGE 1 -
26TL STAGE 1 OP(CC1) -
63TL STAGE 1 -
63TL STAGE 1 OP(CC3) -
63TL STAGE 2 -
63TL STAGE 2 OP(CC4) -
71TL -
71TL OPERATE(CC5) -
45FTL -

24
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

OUTPUT SOURCE SOURCE LOGIC LOGIC


45FTL OPERATE(CC6) -
TRIP 41EX NOT
45FTL OPERATE(CC6) -
PH IOC1 LOW OP -
PH TOC1 HIGH OP -
PH IOC1 HIGH OP -
TRIP LO 86/T1 -
PH TOC1 HIGH OP -
PH IOC1 LOW OP -
PH IOC1 HIGH OP -
C/B 52L TRIP -
PH IOC1 LOW OP -
PH IOC1 HIGH OP -
PH TOC1 HIGH OP -
45FTL OPERATE(CC6) -
63TL STAGE 2 OP(CC4) -
C/B 52G TRIP -
PH IOC1 LOW OP -
PH TOC1 HIGH OP -
PH IOC1 HIGH OP -
45FTL OPERATE(CC6) -
63TL STAGE 2 OP(CC4) -
MK VI 50P/51P ALARM -
PH IOC1 LOW OP -
PH IOC1 HIGH OP -
PH TOC1 HIGH OP -
MK VI ALARM -
45FTL OPERATE(CC6) -
VT FUSE FAILURE -
READY LED NOT
26TL STAGE 1 OP(CC1) -
26TL STAGE 2 OP(CC2) -
63TL STAGE 1 OP(CC3) -
63TL STAGE 2 OP(CC4) -
71TL OPERATE(CC5) -
CHANGE SOURCE 400 V -
PH IOC1 HIGH OP -
PH IOC1 LOW OP -
PH TOC1 HIGH OP -
45FTL OPERATE(CC6) -
TRIP LO 86/T2 -
PH TOC1 HIGH OP -
PH IOC1 LOW OP -
PH IOC1 HIGH OP -
TURBINE NORMAL STOP -
PH IOC1 LOW OP -
PH IOC1 HIGH OP -
PH TOC1 HIGH OP -
45FTL OPERATE(CC6) -
63TL STAGE 2 OP(CC4) -
CHANGE SOURCE 6 kV
-
NO
PH TOC1 HIGH OP -
PH IOC1 HIGH OP -
PH IOC1 LOW OP -
26TL STAGE 2 OP(CC2) -
63TL STAGE 2 OP(CC4) -
45FTL OPERATE(CC6) -

LEDS

LED SOURCE SOURCE LOGIC LOGIC TEXT


LED01 - Trip
PH TOC1 HIGH OP -
PH IOC1 LOW OP -
PH IOC1 HIGH OP -

25
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

LED SOURCE SOURCE LOGIC LOGIC TEXT


LED02 - 50/51P Trip
PH TOC1 HIGH OP -
PH IOC1 LOW OP -
PH IOC1 HIGH OP -
LED06 - Pickup
PH TOC1 HIGH PKP -
50/51P
LED07 -
Pickup
PH TOC1 HIGH PKP -
LED15 - LOCAL
LOCAL OPERATION MODE -

PROTECTION ELEMENTS

PROTECTION ELEMENT SOURCE SOURCE LOGIC LOGIC


PH IOC1 HIGH A BLK -
GROUP 1 BLOCKED -
PH IOC1 HIGH B BLK -
GROUP 1 BLOCKED -
PH IOC1 HIGH C BLK -
GROUP 1 BLOCKED -
PH IOC2 HIGH A BLK -
GROUP 2 BLOCKED -
PH IOC2 HIGH B BLK -
GROUP 2 BLOCKED -
PH IOC2 HIGH C BLK -
GROUP 2 BLOCKED -
PH IOC3 HIGH A BLK -
GROUP 3 BLOCKED -
PH IOC3 HIGH B BLK -
GROUP 3 BLOCKED -
PH IOC3 HIGH C BLK -
GROUP 3 BLOCKED -
PH IOC1 LOW A BLK -
GROUP 1 BLOCKED -
PH IOC1 LOW B BLK -
GROUP 1 BLOCKED -
PH IOC1 LOW C BLK -
GROUP 1 BLOCKED -
PH IOC2 LOW A BLK -
GROUP 2 BLOCKED -
PH IOC2 LOW B BLK -
GROUP 2 BLOCKED -
PH IOC2 LOW C BLK -
GROUP 2 BLOCKED -
PH IOC3 LOW A BLK -
GROUP 3 BLOCKED -
PH IOC3 LOW B BLK -
GROUP 3 BLOCKED -
PH IOC3 LOW C BLK -
GROUP 3 BLOCKED -
NEUTRAL IOC1 BLOCK -
GROUP 1 BLOCKED -
NEUTRAL IOC2 BLOCK -
GROUP 2 BLOCKED -
NEUTRAL IOC3 BLOCK -
GROUP 3 BLOCKED -
GROUND IOC1 BLOCK -
GROUP 1 BLOCKED -
GROUND IOC2 BLOCK -
GROUP 2 BLOCKED -
GROUND IOC3 BLOCK -
GROUP 3 BLOCKED -
SENS GND IOC1 BLK -
GROUP 1 BLOCKED -
SENS GND IOC2 BLK -

26
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

PROTECTION ELEMENT SOURCE SOURCE LOGIC LOGIC


GROUP 2 BLOCKED -
SENS GND IOC3 BLK -
GROUP 3 BLOCKED -
PH TOC1 HIGH A BLK -
GROUP 1 BLOCKED -
PH TOC1 HIGH B BLK -
GROUP 1 BLOCKED -
PH TOC1 HIGH C BLK -
GROUP 1 BLOCKED -
PH TOC2 HIGH A BLK -
GROUP 2 BLOCKED -
PH TOC2 HIGH B BLK -
GROUP 2 BLOCKED -
PH TOC2 HIGH C BLK -
GROUP 2 BLOCKED -
PH TOC3 HIGH A BLK -
GROUP 3 BLOCKED -
PH TOC3 HIGH B BLK -
GROUP 3 BLOCKED -
PH TOC3 HIGH C BLK -
GROUP 3 BLOCKED -
NEUTRAL TOC1 BLOCK -
GROUP 1 BLOCKED -
NEUTRAL TOC2 BLOCK -
GROUP 2 BLOCKED -
NEUTRAL TOC3 BLOCK -
GROUP 3 BLOCKED -
GROUND TOC1 BLOCK -
GROUP 1 BLOCKED -
GROUND TOC2 BLOCK -
GROUP 2 BLOCKED -
GROUND TOC3 BLOCK -
GROUP 3 BLOCKED -
SENS GND TOC1 BLOCK -
GROUP 1 BLOCKED -
SENS GND TOC2 BLOCK -
GROUP 2 BLOCKED -
SENS GND TOC3 BLOCK -
GROUP 3 BLOCKED -
PHASE UV1 BLOCK -
GROUP 1 BLOCKED -
PHASE UV2 BLOCK -
GROUP 2 BLOCKED -
PHASE UV3 BLOCK -
GROUP 3 BLOCKED -
NEG SEQ OV1 BLOCK -
GROUP 1 BLOCKED -
NEG SEQ OV2 BLOCK -
GROUP 2 BLOCKED -
NEG SEQ OV3 BLOCK -
GROUP 3 BLOCKED -
THERMAL1 BLOCK -
GROUP 1 BLOCKED -
THERMAL2 BLOCK -
GROUP 2 BLOCKED -
THERMAL3 BLOCK -
GROUP 3 BLOCKED -
PHASE DIR1 BLK INP -
GROUP 1 BLOCKED -
PHASE DIR2 BLK INP -
GROUP 2 BLOCKED -
PHASE DIR3 BLK INP -
GROUP 3 BLOCKED -
NEUTRAL DIR1 BLK INP -
GROUP 1 BLOCKED -
NEUTRAL DIR2 BLK INP -

27
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

PROTECTION ELEMENT SOURCE SOURCE LOGIC LOGIC


GROUP 2 BLOCKED -
NEUTRAL DIR3 BLK INP -
GROUP 3 BLOCKED -
GROUND DIR1 BLK INP -
GROUP 1 BLOCKED -
GROUND DIR2 BLK INP -
GROUP 2 BLOCKED -
GROUND DIR3 BLK INP -
GROUP 3 BLOCKED -
NEUTRAL OV1 HIGH BLK -
GROUP 1 BLOCKED -
NEUTRAL OV2 HIGH BLK -
GROUP 2 BLOCKED -
NEUTRAL OV3 HIGH BLK -
GROUP 3 BLOCKED -
NEUTRAL OV1 LOW BLK -
GROUP 1 BLOCKED -
NEUTRAL OV2 LOW BLK -
GROUP 2 BLOCKED -
NEUTRAL OV3 LOW BLK -
GROUP 3 BLOCKED -
AUXILIARY UV1 BLOCK -
GROUP 1 BLOCKED -
AUXILIARY UV2 BLOCK -
GROUP 2 BLOCKED -
AUXILIARY UV3 BLOCK -
GROUP 3 BLOCKED -
PHASE OV1 BLOCK -
GROUP 1 BLOCKED -
PHASE OV2 BLOCK -
GROUP 2 BLOCKED -
PHASE OV3 BLOCK -
GROUP 3 BLOCKED -
AUXILIARY OV1 BLOCK -
GROUP 1 BLOCKED -
AUXILIARY OV2 BLOCK -
GROUP 2 BLOCKED -
AUXILIARY OV3 BLOCK -
GROUP 3 BLOCKED -
NEG SEQ TOC1 BLOCK -
GROUP 1 BLOCKED -
NEG SEQ TOC2 BLOCK -
GROUP 2 BLOCKED -
NEG SEQ TOC3 BLOCK -
GROUP 3 BLOCKED -
OVERFREQ1 BLOCK -
GROUP 1 BLOCKED -
OVERFREQ2 BLOCK -
GROUP 2 BLOCKED -
OVERFREQ3 BLOCK -
GROUP 3 BLOCKED -
UNDERFREQ1 BLOCK -
GROUP 1 BLOCKED -
UNDERFREQ2 BLOCK -
GROUP 2 BLOCKED -
UNDERFREQ3 BLOCK -
GROUP 3 BLOCKED -
BROKEN CONDUCT1 BLK -
GROUP 1 BLOCKED -
BROKEN CONDUCT2 BLK -
GROUP 2 BLOCKED -
BROKEN CONDUCT3 BLK -
GROUP 3 BLOCKED -
ISOLATED GND1 BLK -
GROUP 1 BLOCKED -
ISOLATED GND2 BLK -

28
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

PROTECTION ELEMENT SOURCE SOURCE LOGIC LOGIC


GROUP 2 BLOCKED -
ISOLATED GND3 BLK -
GROUP 3 BLOCKED -
SENS GND DIR1 BLK IP -
GROUP 1 BLOCKED -
SENS GND DIR2 BLK IP -
GROUP 2 BLOCKED -
SENS GND DIR3 BLK IP -
GROUP 3 BLOCKED -
FWD PWR1 BLOCK -
GROUP 1 BLOCKED -
FWD PWR2 BLOCK -
GROUP 2 BLOCKED -
FWD PWR3 BLOCK -
GROUP 3 BLOCKED -
PH TOC1 LOW A BLK -
GROUP 1 BLOCKED -
PH TOC1 LOW B BLK -
GROUP 1 BLOCKED -
PH TOC1 LOW C BLK -
GROUP 1 BLOCKED -
PH TOC2 LOW A BLK -
GROUP 2 BLOCKED -
PH TOC2 LOW B BLK -
GROUP 2 BLOCKED -
PH TOC2 LOW C BLK -
GROUP 2 BLOCKED -
PH TOC3 LOW A BLK -
GROUP 3 BLOCKED -
PH TOC3 LOW B BLK -
GROUP 3 BLOCKED -
PH TOC3 LOW C BLK -
GROUP 3 BLOCKED -
DIR PWR1 BLOCK -
GROUP 1 BLOCKED -
DIR PWR2 BLOCK -
GROUP 2 BLOCKED -
DIR PWR3 BLOCK -
GROUP 3 BLOCKED -
LOCKED ROTOR1 BLK -
GROUP 1 BLOCKED -
LOCKED ROTOR2 BLK -
GROUP 2 BLOCKED -
LOCKED ROTOR3 BLK -
GROUP 3 BLOCKED -
FREQ RATE1 BLOCK -
GROUP 1 BLOCKED -
FREQ RATE2 BLOCK -
GROUP 2 BLOCKED -
FREQ RATE3 BLOCK -
GROUP 3 BLOCKED -
LOAD ENCR1 BLOCK -
GROUP 1 BLOCKED -
LOAD ENCR2 BLOCK -
GROUP 2 BLOCKED -
LOAD ENCR3 BLOCK -
GROUP 3 BLOCKED -
32N1 HIGH BLOCK -
GROUP 1 BLOCKED -
32N2 HIGH BLOCK -
GROUP 2 BLOCKED -
32N3 HIGH BLOCK -
GROUP 3 BLOCKED -
32N1 LOW BLOCK -
GROUP 1 BLOCKED -
32N2 LOW BLOCK -

29
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

PROTECTION ELEMENT SOURCE SOURCE LOGIC LOGIC


GROUP 2 BLOCKED -
32N3 LOW BLOCK -
GROUP 3 BLOCKED -

OSCILLOGRAPHY

SOURCE
OSCILLOGRAPHY SOURCE LOGIC TEXT
LOGIC
OSC DIG CHANNEL 1 - 52b LO 86T1/2
52/b LO 86T1*86T2(CC1) -
OSC DIG CHANNEL 2 - 52a LO 86T1
52/a LO 86T1(CC2) -
OSC DIG CHANNEL 3 - 52a LO 86T2
52/a LO 86T2(CC3) -
OSC DIG CHANNEL 4 - 51P
PH TOC1 HIGH OP -
OSC DIG CHANNEL 5 - 50PH
PH IOC1 HIGH OP -
OSC DIG CHANNEL 6 - 50PL
PH IOC1 LOW OP -
OSCILLO TRIGGER - OSCILLO TRIGGER
PH TOC1 HIGH OP -
PH IOC1 HIGH OP -
PH IOC1 LOW OP -

SWITCHGEARS

ID OPENING TIME (ms) CLOSING TIME (ms)


1 100 150

CONTACT
CONTACT
ID CONTACT A SOURCE A SOURCE
A LOGIC
LOGIC
1 -
52/a LO 86T2(CC3) -
52/a LO 86T1(CC2) -

CONTACT
CONTACT
ID CONTACT B SOURCE B SOURCE
B LOGIC
LOGIC
1 -
52/b LO 86T1*86T2(CC1) -

CLOSED ERROR 00 ERROR 11


ID OPEN TXT ALARM ALARM ALARM ALARM
TXT TXT TXT
LO 86T1/2 LO 86T1/2 LO 86T1/2 LO 86T1/2
1 NO NO YES YES
Reset Operate Disc Disc

OPENING CLOSING
ID
INIT INIT
1

30
GE Energy
________________________________________________________________________

GE Energy for Sonelgaz M’Sila Unit 25


Study Appendix

11. Appendix 5: F650 Setting File Summary (Gen Auxiliary Transformer TAM3)

PAGE 119

GE ENERGY FOR SONELGAZ M’SILA LAST SAVED: 6/10/2011 10:57:00 AM


GE ENERGY (ANDRZEJ SWARCEWICZ 8)(SONELGAZ MSILA UNIT 25 RELAY SETTINGS DOCUMENTATION)(REV 0).DOC
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

File Name: Sonelgaz MSila TAM3-650 rev 0 v5_40.650


Comment: Sonelgaz Tiaret TAM F650
Model: F650***F2G1***6
Version: 5.40
Part: 21.12.9.0

SETPOINTS

SERIAL PORTS

NAME VALUE UNIT


COM1 Baud Rate 19200
COM2 Baud Rate 19200
COM1 Parity NONE
COM2 Parity NONE

NETWORK(ETHERNET) 1

NAME VALUE UNIT


IP Address Oct1 192 [0 : 255]
IP Address Oct2 168 [0 : 255]
IP Address Oct3 101 [0 : 255]
IP Address Oct4 2 [0 : 255]
Netmask Oct1 255 [0 : 255]
Netmask Oct2 255 [0 : 255]
Netmask Oct3 255 [0 : 255]
Netmask Oct4 0 [0 : 255]
Gateway IP Oct1 0 [0 : 255]
Gateway IP Oct2 0 [0 : 255]
Gateway IP Oct3 0 [0 : 255]
Gateway IP Oct4 0 [0 : 255]

NETWORK(ETHERNET) 2

NAME VALUE UNIT


IP Address Oct1 0 [0 : 255]
IP Address Oct2 0 [0 : 255]
IP Address Oct3 0 [0 : 255]
IP Address Oct4 0 [0 : 255]
Netmask Oct1 0 [0 : 255]
Netmask Oct2 0 [0 : 255]
Netmask Oct3 0 [0 : 255]
Netmask Oct4 0 [0 : 255]
Gateway IP Oct1 0 [0 : 255]
Gateway IP Oct2 0 [0 : 255]
Gateway IP Oct3 0 [0 : 255]
Gateway IP Oct4 0 [0 : 255]

MODBUS PROTOCOL

NAME VALUE UNIT


Modbus Address COM1 254 [1 : 255]
Modbus Address COM2 254 [1 : 255]
Modbus Port Number 502 [0 : 65535]

DNP3 SLAVE 1

1
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Physical Port NONE
Address 0 [0 : 65534]
IP Addr Client1 Oct1 0 [0 : 255]
IP Addr Client1 Oct2 0 [0 : 255]
IP Addr Client1 Oct3 0 [0 : 255]
IP Addr Client1 Oct4 0 [0 : 255]
IP Addr Client2 Oct1 0 [0 : 255]
IP Addr Client2 Oct2 0 [0 : 255]
IP Addr Client2 Oct3 0 [0 : 255]
IP Addr Client2 Oct4 0 [0 : 255]
IP Addr Client3 Oct1 0 [0 : 255]
IP Addr Client3 Oct2 0 [0 : 255]
IP Addr Client3 Oct3 0 [0 : 255]
IP Addr Client3 Oct4 0 [0 : 255]
IP Addr Client4 Oct1 0 [0 : 255]
IP Addr Client4 Oct2 0 [0 : 255]
IP Addr Client4 Oct3 0 [0 : 255]
IP Addr Client4 Oct4 0 [0 : 255]
IP Addr Client5 Oct1 0 [0 : 255]
IP Addr Client5 Oct2 0 [0 : 255]
IP Addr Client5 Oct3 0 [0 : 255]
IP Addr Client5 Oct4 0 [0 : 255]
TCP/UDP Port 0 [0 : 65535]
Unsol Resp Function DISABLED
Unsol Resp TimeOut 0 [0 : 60] s
Unsol Resp Max Ret 0 [0 : 255]
Unsol Resp Dest Adr 0 [0 : 65519]
Current Scale Factor 0.00001
Voltage Scale Factor 0.00001
Power Scale Factor 0.00001
Energy Scale Factor 0.00001
Other Scale Factor 0.00001
Current Deadband 0 [0 : 65535]
Voltage Deadband 0 [0 : 65535]
Power Deadband 0 [0 : 65535]
Energy Deadband 0 [0 : 65535]
Other Deadband 0 [0 : 65535]
Msg Fragment Size 30 [30 : 2048]
Binary Input Block 1 NOT USED
Binary Input Block 2 NOT USED
Binary Input Block 3 NOT USED
Binary Input Block 4 NOT USED
Binary Input Block 5 NOT USED
Binary Input Block 6 NOT USED
Binary Input Block 7 NOT USED
Binary Input Block 8 NOT USED
Binary Input Block 9 NOT USED
Binary Input Block 10 NOT USED

DNP3 SLAVE 2

NAME VALUE UNIT


Physical Port NONE
Address 0 [0 : 65534]
IP Addr Client1 Oct1 0 [0 : 255]
IP Addr Client1 Oct2 0 [0 : 255]
IP Addr Client1 Oct3 0 [0 : 255]
IP Addr Client1 Oct4 0 [0 : 255]
IP Addr Client2 Oct1 0 [0 : 255]
IP Addr Client2 Oct2 0 [0 : 255]
IP Addr Client2 Oct3 0 [0 : 255]
IP Addr Client2 Oct4 0 [0 : 255]
IP Addr Client3 Oct1 0 [0 : 255]

2
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


IP Addr Client3 Oct2 0 [0 : 255]
IP Addr Client3 Oct3 0 [0 : 255]
IP Addr Client3 Oct4 0 [0 : 255]
IP Addr Client4 Oct1 0 [0 : 255]
IP Addr Client4 Oct2 0 [0 : 255]
IP Addr Client4 Oct3 0 [0 : 255]
IP Addr Client4 Oct4 0 [0 : 255]
IP Addr Client5 Oct1 0 [0 : 255]
IP Addr Client5 Oct2 0 [0 : 255]
IP Addr Client5 Oct3 0 [0 : 255]
IP Addr Client5 Oct4 0 [0 : 255]
TCP/UDP Port 0 [0 : 65535]
Unsol Resp Function DISABLED
Unsol Resp TimeOut 0 [0 : 60] s
Unsol Resp Max Ret 0 [0 : 255]
Unsol Resp Dest Adr 0 [0 : 65519]
Current Scale Factor 0.00001
Voltage Scale Factor 0.00001
Power Scale Factor 0.00001
Energy Scale Factor 0.00001
Other Scale Factor 0.00001
Current Deadband 0 [0 : 65535]
Voltage Deadband 0 [0 : 65535]
Power Deadband 0 [0 : 65535]
Energy Deadband 0 [0 : 65535]
Other Deadband 0 [0 : 65535]
Msg Fragment Size 30 [30 : 2048]
Binary Input Block 1 NOT USED
Binary Input Block 2 NOT USED
Binary Input Block 3 NOT USED
Binary Input Block 4 NOT USED
Binary Input Block 5 NOT USED
Binary Input Block 6 NOT USED
Binary Input Block 7 NOT USED
Binary Input Block 8 NOT USED
Binary Input Block 9 NOT USED
Binary Input Block 10 NOT USED

DNP3 SLAVE 3

NAME VALUE UNIT


Physical Port NONE
Address 0 [0 : 65534]
IP Addr Client1 Oct1 0 [0 : 255]
IP Addr Client1 Oct2 0 [0 : 255]
IP Addr Client1 Oct3 0 [0 : 255]
IP Addr Client1 Oct4 0 [0 : 255]
IP Addr Client2 Oct1 0 [0 : 255]
IP Addr Client2 Oct2 0 [0 : 255]
IP Addr Client2 Oct3 0 [0 : 255]
IP Addr Client2 Oct4 0 [0 : 255]
IP Addr Client3 Oct1 0 [0 : 255]
IP Addr Client3 Oct2 0 [0 : 255]
IP Addr Client3 Oct3 0 [0 : 255]
IP Addr Client3 Oct4 0 [0 : 255]
IP Addr Client4 Oct1 0 [0 : 255]
IP Addr Client4 Oct2 0 [0 : 255]
IP Addr Client4 Oct3 0 [0 : 255]
IP Addr Client4 Oct4 0 [0 : 255]
IP Addr Client5 Oct1 0 [0 : 255]
IP Addr Client5 Oct2 0 [0 : 255]
IP Addr Client5 Oct3 0 [0 : 255]
IP Addr Client5 Oct4 0 [0 : 255]
TCP/UDP Port 0 [0 : 65535]

3
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Unsol Resp Function DISABLED
Unsol Resp TimeOut 0 [0 : 60] s
Unsol Resp Max Ret 0 [0 : 255]
Unsol Resp Dest Adr 0 [0 : 65519]
Current Scale Factor 0.00001
Voltage Scale Factor 0.00001
Power Scale Factor 0.00001
Energy Scale Factor 0.00001
Other Scale Factor 0.00001
Current Deadband 0 [0 : 65535]
Voltage Deadband 0 [0 : 65535]
Power Deadband 0 [0 : 65535]
Energy Deadband 0 [0 : 65535]
Other Deadband 0 [0 : 65535]
Msg Fragment Size 30 [30 : 2048]
Binary Input Block 1 NOT USED
Binary Input Block 2 NOT USED
Binary Input Block 3 NOT USED
Binary Input Block 4 NOT USED
Binary Input Block 5 NOT USED
Binary Input Block 6 NOT USED
Binary Input Block 7 NOT USED
Binary Input Block 8 NOT USED
Binary Input Block 9 NOT USED
Binary Input Block 10 NOT USED

SNTP

NAME VALUE UNIT


Function DISABLED
UDP Port 123 [1 : 65535]
Server IP Oct1 0 [0 : 255]
Server IP Oct2 0 [0 : 255]
Server IP Oct3 0 [0 : 255]
Server IP Oct4 0 [0 : 255]

MODBUS USER MAP

NAME VALUE UNIT


Address 00 0000 [0000 : FFFF]
Address 01 0000 [0000 : FFFF]
Address 02 0000 [0000 : FFFF]
Address 03 0000 [0000 : FFFF]
Address 04 0000 [0000 : FFFF]
Address 05 0000 [0000 : FFFF]
Address 06 0000 [0000 : FFFF]
Address 07 0000 [0000 : FFFF]
Address 08 0000 [0000 : FFFF]
Address 09 0000 [0000 : FFFF]
Address 10 0000 [0000 : FFFF]
Address 11 0000 [0000 : FFFF]
Address 12 0000 [0000 : FFFF]
Address 13 0000 [0000 : FFFF]
Address 14 0000 [0000 : FFFF]
Address 15 0000 [0000 : FFFF]
Address 16 0000 [0000 : FFFF]
Address 17 0000 [0000 : FFFF]
Address 18 0000 [0000 : FFFF]
Address 19 0000 [0000 : FFFF]
Address 20 0000 [0000 : FFFF]
Address 21 0000 [0000 : FFFF]
Address 22 0000 [0000 : FFFF]
Address 23 0000 [0000 : FFFF]
Address 24 0000 [0000 : FFFF]
Address 25 0000 [0000 : FFFF]

4
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Address 26 0000 [0000 : FFFF]
Address 27 0000 [0000 : FFFF]
Address 28 0000 [0000 : FFFF]
Address 29 0000 [0000 : FFFF]
Address 30 0000 [0000 : FFFF]
Address 31 0000 [0000 : FFFF]
Address 32 0000 [0000 : FFFF]
Address 33 0000 [0000 : FFFF]
Address 34 0000 [0000 : FFFF]
Address 35 0000 [0000 : FFFF]
Address 36 0000 [0000 : FFFF]
Address 37 0000 [0000 : FFFF]
Address 38 0000 [0000 : FFFF]
Address 39 0000 [0000 : FFFF]
Address 40 0000 [0000 : FFFF]
Address 41 0000 [0000 : FFFF]
Address 42 0000 [0000 : FFFF]
Address 43 0000 [0000 : FFFF]
Address 44 0000 [0000 : FFFF]
Address 45 0000 [0000 : FFFF]
Address 46 0000 [0000 : FFFF]
Address 47 0000 [0000 : FFFF]
Address 48 0000 [0000 : FFFF]
Address 49 0000 [0000 : FFFF]
Address 50 0000 [0000 : FFFF]
Address 51 0000 [0000 : FFFF]
Address 52 0000 [0000 : FFFF]
Address 53 0000 [0000 : FFFF]
Address 54 0000 [0000 : FFFF]
Address 55 0000 [0000 : FFFF]
Address 56 0000 [0000 : FFFF]
Address 57 0000 [0000 : FFFF]
Address 58 0000 [0000 : FFFF]
Address 59 0000 [0000 : FFFF]
Address 60 0000 [0000 : FFFF]
Address 61 0000 [0000 : FFFF]
Address 62 0000 [0000 : FFFF]
Address 63 0000 [0000 : FFFF]
Address 64 0000 [0000 : FFFF]
Address 65 0000 [0000 : FFFF]
Address 66 0000 [0000 : FFFF]
Address 67 0000 [0000 : FFFF]
Address 68 0000 [0000 : FFFF]
Address 69 0000 [0000 : FFFF]
Address 70 0000 [0000 : FFFF]
Address 71 0000 [0000 : FFFF]
Address 72 0000 [0000 : FFFF]
Address 73 0000 [0000 : FFFF]
Address 74 0000 [0000 : FFFF]
Address 75 0000 [0000 : FFFF]
Address 76 0000 [0000 : FFFF]
Address 77 0000 [0000 : FFFF]
Address 78 0000 [0000 : FFFF]
Address 79 0000 [0000 : FFFF]
Address 80 0000 [0000 : FFFF]
Address 81 0000 [0000 : FFFF]
Address 82 0000 [0000 : FFFF]
Address 83 0000 [0000 : FFFF]
Address 84 0000 [0000 : FFFF]
Address 85 0000 [0000 : FFFF]
Address 86 0000 [0000 : FFFF]
Address 87 0000 [0000 : FFFF]
Address 88 0000 [0000 : FFFF]
Address 89 0000 [0000 : FFFF]
Address 90 0000 [0000 : FFFF]
Address 91 0000 [0000 : FFFF]

5
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Address 92 0000 [0000 : FFFF]
Address 93 0000 [0000 : FFFF]
Address 94 0000 [0000 : FFFF]
Address 95 0000 [0000 : FFFF]
Address 96 0000 [0000 : FFFF]
Address 97 0000 [0000 : FFFF]
Address 98 0000 [0000 : FFFF]
Address 99 0000 [0000 : FFFF]
Address 100 0000 [0000 : FFFF]
Address 101 0000 [0000 : FFFF]
Address 102 0000 [0000 : FFFF]
Address 103 0000 [0000 : FFFF]
Address 104 0000 [0000 : FFFF]
Address 105 0000 [0000 : FFFF]
Address 106 0000 [0000 : FFFF]
Address 107 0000 [0000 : FFFF]
Address 108 0000 [0000 : FFFF]
Address 109 0000 [0000 : FFFF]
Address 110 0000 [0000 : FFFF]
Address 111 0000 [0000 : FFFF]
Address 112 0000 [0000 : FFFF]
Address 113 0000 [0000 : FFFF]
Address 114 0000 [0000 : FFFF]
Address 115 0000 [0000 : FFFF]
Address 116 0000 [0000 : FFFF]
Address 117 0000 [0000 : FFFF]
Address 118 0000 [0000 : FFFF]
Address 119 0000 [0000 : FFFF]
Address 120 0000 [0000 : FFFF]
Address 121 0000 [0000 : FFFF]
Address 122 0000 [0000 : FFFF]
Address 123 0000 [0000 : FFFF]
Address 124 0000 [0000 : FFFF]
Address 125 0000 [0000 : FFFF]
Address 126 0000 [0000 : FFFF]
Address 127 0000 [0000 : FFFF]
Address 128 0000 [0000 : FFFF]
Address 129 0000 [0000 : FFFF]
Address 130 0000 [0000 : FFFF]
Address 131 0000 [0000 : FFFF]
Address 132 0000 [0000 : FFFF]
Address 133 0000 [0000 : FFFF]
Address 134 0000 [0000 : FFFF]
Address 135 0000 [0000 : FFFF]
Address 136 0000 [0000 : FFFF]
Address 137 0000 [0000 : FFFF]
Address 138 0000 [0000 : FFFF]
Address 139 0000 [0000 : FFFF]
Address 140 0000 [0000 : FFFF]
Address 141 0000 [0000 : FFFF]
Address 142 0000 [0000 : FFFF]
Address 143 0000 [0000 : FFFF]
Address 144 0000 [0000 : FFFF]
Address 145 0000 [0000 : FFFF]
Address 146 0000 [0000 : FFFF]
Address 147 0000 [0000 : FFFF]
Address 148 0000 [0000 : FFFF]
Address 149 0000 [0000 : FFFF]
Address 150 0000 [0000 : FFFF]
Address 151 0000 [0000 : FFFF]
Address 152 0000 [0000 : FFFF]
Address 153 0000 [0000 : FFFF]
Address 154 0000 [0000 : FFFF]
Address 155 0000 [0000 : FFFF]
Address 156 0000 [0000 : FFFF]
Address 157 0000 [0000 : FFFF]

6
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Address 158 0000 [0000 : FFFF]
Address 159 0000 [0000 : FFFF]
Address 160 0000 [0000 : FFFF]
Address 161 0000 [0000 : FFFF]
Address 162 0000 [0000 : FFFF]
Address 163 0000 [0000 : FFFF]
Address 164 0000 [0000 : FFFF]
Address 165 0000 [0000 : FFFF]
Address 166 0000 [0000 : FFFF]
Address 167 0000 [0000 : FFFF]
Address 168 0000 [0000 : FFFF]
Address 169 0000 [0000 : FFFF]
Address 170 0000 [0000 : FFFF]
Address 171 0000 [0000 : FFFF]
Address 172 0000 [0000 : FFFF]
Address 173 0000 [0000 : FFFF]
Address 174 0000 [0000 : FFFF]
Address 175 0000 [0000 : FFFF]
Address 176 0000 [0000 : FFFF]
Address 177 0000 [0000 : FFFF]
Address 178 0000 [0000 : FFFF]
Address 179 0000 [0000 : FFFF]
Address 180 0000 [0000 : FFFF]
Address 181 0000 [0000 : FFFF]
Address 182 0000 [0000 : FFFF]
Address 183 0000 [0000 : FFFF]
Address 184 0000 [0000 : FFFF]
Address 185 0000 [0000 : FFFF]
Address 186 0000 [0000 : FFFF]
Address 187 0000 [0000 : FFFF]
Address 188 0000 [0000 : FFFF]
Address 189 0000 [0000 : FFFF]
Address 190 0000 [0000 : FFFF]
Address 191 0000 [0000 : FFFF]
Address 192 0000 [0000 : FFFF]
Address 193 0000 [0000 : FFFF]
Address 194 0000 [0000 : FFFF]
Address 195 0000 [0000 : FFFF]
Address 196 0000 [0000 : FFFF]
Address 197 0000 [0000 : FFFF]
Address 198 0000 [0000 : FFFF]
Address 199 0000 [0000 : FFFF]
Address 200 0000 [0000 : FFFF]
Address 201 0000 [0000 : FFFF]
Address 202 0000 [0000 : FFFF]
Address 203 0000 [0000 : FFFF]
Address 204 0000 [0000 : FFFF]
Address 205 0000 [0000 : FFFF]
Address 206 0000 [0000 : FFFF]
Address 207 0000 [0000 : FFFF]
Address 208 0000 [0000 : FFFF]
Address 209 0000 [0000 : FFFF]
Address 210 0000 [0000 : FFFF]
Address 211 0000 [0000 : FFFF]
Address 212 0000 [0000 : FFFF]
Address 213 0000 [0000 : FFFF]
Address 214 0000 [0000 : FFFF]
Address 215 0000 [0000 : FFFF]
Address 216 0000 [0000 : FFFF]
Address 217 0000 [0000 : FFFF]
Address 218 0000 [0000 : FFFF]
Address 219 0000 [0000 : FFFF]
Address 220 0000 [0000 : FFFF]
Address 221 0000 [0000 : FFFF]
Address 222 0000 [0000 : FFFF]
Address 223 0000 [0000 : FFFF]

7
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Address 224 0000 [0000 : FFFF]
Address 225 0000 [0000 : FFFF]
Address 226 0000 [0000 : FFFF]
Address 227 0000 [0000 : FFFF]
Address 228 0000 [0000 : FFFF]
Address 229 0000 [0000 : FFFF]
Address 230 0000 [0000 : FFFF]
Address 231 0000 [0000 : FFFF]
Address 232 0000 [0000 : FFFF]
Address 233 0000 [0000 : FFFF]
Address 234 0000 [0000 : FFFF]
Address 235 0000 [0000 : FFFF]
Address 236 0000 [0000 : FFFF]
Address 237 0000 [0000 : FFFF]
Address 238 0000 [0000 : FFFF]
Address 239 0000 [0000 : FFFF]
Address 240 0000 [0000 : FFFF]
Address 241 0000 [0000 : FFFF]
Address 242 0000 [0000 : FFFF]
Address 243 0000 [0000 : FFFF]
Address 244 0000 [0000 : FFFF]
Address 245 0000 [0000 : FFFF]
Address 246 0000 [0000 : FFFF]
Address 247 0000 [0000 : FFFF]
Address 248 0000 [0000 : FFFF]
Address 249 0000 [0000 : FFFF]
Address 250 0000 [0000 : FFFF]
Address 251 0000 [0000 : FFFF]
Address 252 0000 [0000 : FFFF]
Address 253 0000 [0000 : FFFF]
Address 254 0000 [0000 : FFFF]
Address 255 0000 [0000 : FFFF]

OSCILLOGRAPHY

NAME VALUE UNIT


Function ENABLED
Trigger Position 25 [5 : 95] %
Samples/Cycle 32
Max. Number Osc. 16 [1 : 20]
Automatic Overwrite ENABLED
Snapshot Events ENABLED

DATA LOGGER

NAME VALUE UNIT


Function ENABLED
Data Logger Rate 5 Minutes
Data Logger Chnl 1 RMS Ia Primary
Data Logger Chnl 2 RMS Ib Primary
Data Logger Chnl 3 RMS Ic Primary
Data Logger Chnl 4 Vab Primary
Data Logger Chnl 5 Vbc Primary
Data Logger Chnl 6 Vca Primary
Data Logger Chnl 7 3 Phase Real Pwr
Data Logger Chnl 8 3 Phase Reactive Pwr
Data Logger Chnl 9 3 Phase Apparent Pwr
Data Logger Chnl 10 I0 Primary
Data Logger Chnl 11 I1 Primary
Data Logger Chnl 12 I2 Primary
Data Logger Chnl 13 V0 Primary
Data Logger Chnl 14 V1 Primary
Data Logger Chnl 15 V2 Primary
Data Logger Chnl 16 Bus Frequency

TIME SETTINGS
8
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


LOC. TIME OFFS. UTC 0.0 [-24.0 : 24.0]
DAYLIG. SAVINGS TIME DISABLED
DST START MONTH MAR
DST START WEEKDAY SUNDAY
DST START DAY INST LAST
DST START HOUR 2 [0 : 23]
DST STOP MONTH OCT
DST STOP WEEKDAY SUNDAY
DST STOP DAY INST LAST
DST STOP HOUR 2 [0 : 23]
IRIG-B LOCAL TIME OFF

GENERAL SETTINGS

NAME VALUE UNIT


Phase CT Ratio 100.0 [1.0 : 6000.0]
Ground CT Ratio 100.0 [1.0 : 6000.0]
Stv Ground CT Ratio 100.0 [1.0 : 6000.0]
Phase VT Ratio 115.0 [1.0 : 6000.0]
Phase VT Connection WYE
Nominal Voltage 100.0 [1.0 : 250.0] V
Nominal Frequency 50 Hz
Phase Rotation ABC
Frequency Reference VI
Auxiliary Voltage VX
Snapshot Events DISABLED
Relay Out Of Service ENABLED

FLEX CURVES A

NAME VALUE UNIT


Time 0.00xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.05xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.10xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.15xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.20xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.25xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.30xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.35xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.40xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.45xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.48xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.50xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.52xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.54xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.56xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.58xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.60xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.62xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.64xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.66xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.68xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.70xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.72xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.74xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.76xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.78xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.80xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.82xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.84xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.86xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.88xPKP [RST] 0.000 [0.000 : 65.535] s

9
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Time 0.90xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.91xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.92xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.93xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.94xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.95xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.96xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.97xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.98xPKP [RST] 0.000 [0.000 : 65.535] s
Time 1.03xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.05xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 6.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 6.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 7.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 7.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 8.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 8.50xPKP [OP] 0.000 [0.000 : 65.535] s

10
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Time 9.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 9.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 10.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 10.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 11.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 11.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 12.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 12.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 13.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 13.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 14.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 14.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 15.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 15.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 16.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 16.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 17.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 17.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 18.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 18.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 19.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 19.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 20.00xPKP [OP] 0.000 [0.000 : 65.535] s

FLEX CURVES B

NAME VALUE UNIT


Time 0.00xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.05xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.10xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.15xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.20xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.25xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.30xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.35xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.40xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.45xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.48xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.50xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.52xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.54xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.56xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.58xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.60xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.62xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.64xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.66xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.68xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.70xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.72xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.74xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.76xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.78xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.80xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.82xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.84xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.86xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.88xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.90xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.91xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.92xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.93xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.94xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.95xPKP [RST] 0.000 [0.000 : 65.535] s

11
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Time 0.96xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.97xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.98xPKP [RST] 0.000 [0.000 : 65.535] s
Time 1.03xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.05xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 6.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 6.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 7.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 7.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 8.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 8.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 9.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 9.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 10.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 10.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 11.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 11.50xPKP [OP] 0.000 [0.000 : 65.535] s

12
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Time 12.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 12.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 13.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 13.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 14.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 14.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 15.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 15.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 16.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 16.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 17.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 17.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 18.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 18.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 19.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 19.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 20.00xPKP [OP] 0.000 [0.000 : 65.535] s

FLEX CURVES C

NAME VALUE UNIT


Time 0.00xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.05xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.10xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.15xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.20xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.25xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.30xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.35xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.40xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.45xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.48xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.50xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.52xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.54xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.56xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.58xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.60xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.62xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.64xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.66xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.68xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.70xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.72xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.74xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.76xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.78xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.80xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.82xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.84xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.86xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.88xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.90xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.91xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.92xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.93xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.94xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.95xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.96xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.97xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.98xPKP [RST] 0.000 [0.000 : 65.535] s
Time 1.03xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.05xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.10xPKP [OP] 0.000 [0.000 : 65.535] s

13
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Time 1.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 6.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 6.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 7.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 7.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 8.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 8.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 9.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 9.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 10.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 10.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 11.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 11.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 12.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 12.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 13.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 13.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 14.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 14.50xPKP [OP] 0.000 [0.000 : 65.535] s

14
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Time 15.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 15.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 16.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 16.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 17.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 17.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 18.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 18.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 19.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 19.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 20.00xPKP [OP] 0.000 [0.000 : 65.535] s

FLEX CURVES D

NAME VALUE UNIT


Time 0.00xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.05xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.10xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.15xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.20xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.25xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.30xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.35xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.40xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.45xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.48xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.50xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.52xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.54xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.56xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.58xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.60xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.62xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.64xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.66xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.68xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.70xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.72xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.74xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.76xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.78xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.80xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.82xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.84xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.86xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.88xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.90xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.91xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.92xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.93xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.94xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.95xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.96xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.97xPKP [RST] 0.000 [0.000 : 65.535] s
Time 0.98xPKP [RST] 0.000 [0.000 : 65.535] s
Time 1.03xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.05xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.70xPKP [OP] 0.000 [0.000 : 65.535] s

15
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Time 1.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 1.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 2.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 3.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 4.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.10xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.20xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.30xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.40xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.60xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.70xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.80xPKP [OP] 0.000 [0.000 : 65.535] s
Time 5.90xPKP [OP] 0.000 [0.000 : 65.535] s
Time 6.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 6.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 7.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 7.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 8.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 8.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 9.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 9.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 10.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 10.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 11.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 11.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 12.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 12.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 13.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 13.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 14.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 14.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 15.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 15.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 16.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 16.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 17.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 17.50xPKP [OP] 0.000 [0.000 : 65.535] s

16
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Time 18.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 18.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 19.00xPKP [OP] 0.000 [0.000 : 65.535] s
Time 19.50xPKP [OP] 0.000 [0.000 : 65.535] s
Time 20.00xPKP [OP] 0.000 [0.000 : 65.535] s

BREAKER SETTINGS

NAME VALUE UNIT


Number of Switchgear 1 [1 : 16]
Maximum KI2t 9999.99 [0.00 : 9999.99] (KA)2 s
KI2t Integ. Time 0.03 [0.03 : 0.25] s
Maximum Openings 0 [0 : 9999]
Max.Openings 1 hour 1 [1 : 60]
Snapshot Events DISABLED

BREAKER MAINTENANCE

NAME VALUE UNIT


KI2t BKR Ph A Cnt 0.00 [0.00 : 9999.99] (KA)2 s
KI2t BKR Ph B Cnt 0.00 [0.00 : 9999.99] (KA)2 s
KI2t BKR Ph C Cnt 0.00 [0.00 : 9999.99] (KA)2 s
BKR Openings Cnt 0 [0 : 9999]
BKR Closings Cnt 0 [0 : 9999]

SWITCHGEAR

NAME VALUE UNIT


Snapshot Events SWGR 1 DISABLED
Snapshot Events SWGR 2 DISABLED
Snapshot Events SWGR 3 DISABLED
Snapshot Events SWGR 4 DISABLED
Snapshot Events SWGR 5 DISABLED
Snapshot Events SWGR 6 DISABLED
Snapshot Events SWGR 7 DISABLED
Snapshot Events SWGR 8 DISABLED
Snapshot Events SWGR 9 DISABLED
Snapshot Events SWGR 10 DISABLED
Snapshot Events SWGR 11 DISABLED
Snapshot Events SWGR 12 DISABLED
Snapshot Events SWGR 13 DISABLED
Snapshot Events SWGR 14 DISABLED
Snapshot Events SWGR 15 DISABLED
Snapshot Events SWGR 16 DISABLED

PHASE TOC HIGH 1

NAME VALUE UNIT


Function ENABLED
Input RMS
Pickup Level 0.50 [0.05 : 160.00] A
Curve IEEE Ext Inv
TD Multiplier 3.20 [0.00 : 900.00] s
Reset INSTANTANEOUS
Voltage Restraint DISABLED
Snapshot Events ENABLED

PHASE IOC HIGH 1

17
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Function ENABLED
Input PHASOR(DFT)
Pickup Level 9.80 [0.05 : 160.00] A
Trip Delay 0.00 [0.00 : 900.00] s
Reset Delay 0.00 [0.00 : 900.00] s
Snapshot Events ENABLED

PHASE IOC LOW 1

NAME VALUE UNIT


Function ENABLED
Input PHASOR(DFT)
Pickup Level 1.20 [0.05 : 160.00] A
Trip Delay 0.60 [0.00 : 900.00] s
Reset Delay 0.00 [0.00 : 900.00] s
Snapshot Events ENABLED

SETTING GROUP

NAME VALUE UNIT


Function DISABLED
Active Group GROUP 1
Snapshot Events DISABLED

VT FUSE FAILURE

NAME VALUE UNIT


Function ENABLED
Snapshot Events ENABLED

PULSE COUNTERS

NAME VALUE UNIT


PulseCntr Enabled 1 DISABLED
PulseCntr Name 1 Pulse Counter 1
PulseCntr Factor 1 1.000 [0.000 : 65000.000]
PulseCntr Overflow 1 65535 [0 : 1000000]
PulseCntr Board Origin 1 F
PulseCntr Input Origin 1 1 [1 : 32]
PulseCntr Enabled 2 DISABLED
PulseCntr Name 2 Pulse Counter 2
PulseCntr Factor 2 1.000 [0.000 : 65000.000]
PulseCntr Overflow 2 65535 [0 : 1000000]
PulseCntr Board Origin 2 F
PulseCntr Input Origin 2 1 [1 : 32]
PulseCntr Enabled 3 DISABLED
PulseCntr Name 3 Pulse Counter 3
PulseCntr Factor 3 1.000 [0.000 : 65000.000]
PulseCntr Overflow 3 65535 [0 : 1000000]
PulseCntr Board Origin 3 F
PulseCntr Input Origin 3 1 [1 : 32]
PulseCntr Enabled 4 DISABLED
PulseCntr Name 4 Pulse Counter 4
PulseCntr Factor 4 1.000 [0.000 : 65000.000]
PulseCntr Overflow 4 65535 [0 : 1000000]
PulseCntr Board Origin 4 F
PulseCntr Input Origin 4 1 [1 : 32]
PulseCntr Enabled 5 DISABLED
PulseCntr Name 5 Pulse Counter 5
PulseCntr Factor 5 1.000 [0.000 : 65000.000]
PulseCntr Overflow 5 65535 [0 : 1000000]
PulseCntr Board Origin 5 F
PulseCntr Input Origin 5 1 [1 : 32]

18
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


PulseCntr Enabled 6 DISABLED
PulseCntr Name 6 Pulse Counter 6
PulseCntr Factor 6 1.000 [0.000 : 65000.000]
PulseCntr Overflow 6 65535 [0 : 1000000]
PulseCntr Board Origin 6 F
PulseCntr Input Origin 6 1 [1 : 32]
PulseCntr Enabled 7 DISABLED
PulseCntr Name 7 Pulse Counter 7
PulseCntr Factor 7 1.000 [0.000 : 65000.000]
PulseCntr Overflow 7 65535 [0 : 1000000]
PulseCntr Board Origin 7 F
PulseCntr Input Origin 7 1 [1 : 32]
PulseCntr Enabled 8 DISABLED
PulseCntr Name 8 Pulse Counter 8
PulseCntr Factor 8 1.000 [0.000 : 65000.000]
PulseCntr Overflow 8 65535 [0 : 1000000]
PulseCntr Board Origin 8 F
PulseCntr Input Origin 8 1 [1 : 32]

ANALOG COMPARATORS

NAME VALUE UNIT


Analog Function DISABLED
Snapshot Events DISABLED
Analog Input 01 None
Analog Maximum 1 1.000 [-100000.000 : 100000.000]
Analog Minimum 1 1.000 [-100000.000 : 100000.000]
Analog Delay 01 1.00 [0.00 : 900.00] s
Analog Hysteresis 1 1.0 [0.0 : 50.0]
Analog Direction 1 OUT
Analog Input 2 None
Analog Maximum 2 1.000 [-100000.000 : 100000.000]
Analog Minimum 2 1.000 [-100000.000 : 100000.000]
Analog Delay 2 1.00 [0.00 : 900.00] s
Analog Hysteresis 2 1.0 [0.0 : 50.0]
Analog Direction 2 OUT
Analog Input 3 None
Analog Maximum 3 1.000 [-100000.000 : 100000.000]
Analog Minimum 3 1.000 [-100000.000 : 100000.000]
Analog Delay 3 1.00 [0.00 : 900.00] s
Analog Hysteresis 3 1.0 [0.0 : 50.0]
Analog Direction 3 OUT
Analog Input 4 None
Analog Maximum 4 1.000 [-100000.000 : 100000.000]
Analog Minimum 4 1.000 [-100000.000 : 100000.000]
Analog Delay 4 1.00 [0.00 : 900.00] s
Analog Hysteresis 4 1.0 [0.0 : 50.0]
Analog Direction 4 OUT
Analog Input 5 None
Analog Maximum 5 1.000 [-100000.000 : 100000.000]
Analog Minimum 5 1.000 [-100000.000 : 100000.000]
Analog Delay 5 1.00 [0.00 : 900.00] s
Analog Hysteresis 5 1.0 [0.0 : 50.0]
Analog Direction 5 OUT
Analog Input 6 None
Analog Maximum 6 1.000 [-100000.000 : 100000.000]
Analog Minimum 6 1.000 [-100000.000 : 100000.000]
Analog Delay 6 1.00 [0.00 : 900.00] s
Analog Hysteresis 6 1.0 [0.0 : 50.0]
Analog Direction 6 OUT
Analog Input 7 None
Analog Maximum 7 1.000 [-100000.000 : 100000.000]
Analog Minimum 7 1.000 [-100000.000 : 100000.000]
Analog Delay 7 1.00 [0.00 : 900.00] s
Analog Hysteresis 7 1.0 [0.0 : 50.0]
Analog Direction 7 OUT

19
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Analog Input 8 None
Analog Maximum 8 1.000 [-100000.000 : 100000.000]
Analog Minimum 8 1.000 [-100000.000 : 100000.000]
Analog Delay 8 1.00 [0.00 : 900.00] s
Analog Hysteresis 8 1.0 [0.0 : 50.0]
Analog Direction 8 OUT
Analog Input 9 None
Analog Maximum 9 1.000 [-100000.000 : 100000.000]
Analog Minimum 9 1.000 [-100000.000 : 100000.000]
Analog Delay 9 1.00 [0.00 : 900.00] s
Analog Hysteresis 9 1.0 [0.0 : 50.0]
Analog Direction 9 OUT
Analog Input 10 None
Analog Maximum 10 1.000 [-100000.000 : 100000.000]
Analog Minimum 10 1.000 [-100000.000 : 100000.000]
Analog Delay 10 1.00 [0.00 : 900.00] s
Analog Hysteresis 10 1.0 [0.0 : 50.0]
Analog Direction 10 OUT
Analog Input 11 None
Analog Maximum 11 1.000 [-100000.000 : 100000.000]
Analog Minimum 11 1.000 [-100000.000 : 100000.000]
Analog Delay 11 1.00 [0.00 : 900.00] s
Analog Hysteresis 11 1.0 [0.0 : 50.0]
Analog Direction 11 OUT
Analog Input 12 None
Analog Maximum 12 1.000 [-100000.000 : 100000.000]
Analog Minimum 12 1.000 [-100000.000 : 100000.000]
Analog Delay 12 1.00 [0.00 : 900.00] s
Analog Hysteresis 12 1.0 [0.0 : 50.0]
Analog Direction 12 OUT
Analog Input 13 None
Analog Maximum 13 1.000 [-100000.000 : 100000.000]
Analog Minimum 13 1.000 [-100000.000 : 100000.000]
Analog Delay 13 1.00 [0.00 : 900.00] s
Analog Hysteresis 13 1.0 [0.0 : 50.0]
Analog Direction 13 OUT
Analog Input 14 None
Analog Maximum 14 1.000 [-100000.000 : 100000.000]
Analog Minimum 14 1.000 [-100000.000 : 100000.000]
Analog Delay 14 1.00 [0.00 : 900.00] s
Analog Hysteresis 14 1.0 [0.0 : 50.0]
Analog Direction 14 OUT
Analog Input 15 None
Analog Maximum 15 1.000 [-100000.000 : 100000.000]
Analog Minimum 15 1.000 [-100000.000 : 100000.000]
Analog Delay 15 1.00 [0.00 : 900.00] s
Analog Hysteresis 15 1.0 [0.0 : 50.0]
Analog Direction 15 OUT
Analog Input 16 None
Analog Maximum 16 1.000 [-100000.000 : 100000.000]
Analog Minimum 16 1.000 [-100000.000 : 100000.000]
Analog Delay 16 1.00 [0.00 : 900.00] s
Analog Hysteresis 16 1.0 [0.0 : 50.0]
Analog Direction 16 OUT
Analog Input 17 None
Analog Maximum 17 1.000 [-100000.000 : 100000.000]
Analog Minimum 17 1.000 [-100000.000 : 100000.000]
Analog Delay 17 1.00 [0.00 : 900.00] s
Analog Hysteresis 17 1.0 [0.0 : 50.0]
Analog Direction 17 OUT
Analog Input 18 None
Analog Maximum 18 1.000 [-100000.000 : 100000.000]
Analog Minimum 18 1.000 [-100000.000 : 100000.000]
Analog Delay 18 1.00 [0.00 : 900.00] s
Analog Hysteresis 18 1.0 [0.0 : 50.0]
Analog Direction 18 OUT

20
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Analog Input 19 None
Analog Maximum 19 1.000 [-100000.000 : 100000.000]
Analog Minimum 19 1.000 [-100000.000 : 100000.000]
Analog Delay 19 1.00 [0.00 : 900.00] s
Analog Hysteresis 19 1.0 [0.0 : 50.0]
Analog Direction 19 OUT
Analog Input 20 None
Analog Maximum 20 1.000 [-100000.000 : 100000.000]
Analog Minimum 20 1.000 [-100000.000 : 100000.000]
Analog Delay 20 1.00 [0.00 : 900.00] s
Analog Hysteresis 20 1.0 [0.0 : 50.0]
Analog Direction 20 OUT

BOARD F

NAME VALUE UNIT


Voltage Threshold A_F 30 [10 : 230] V
Voltage Threshold B_F 30 [10 : 230] V
Debounce Time A_F 3 [1 : 50] ms
Debounce Time B_F 3 [1 : 50] ms
Input Type_F_CC1 (CC1) POSITIVE
Input Type_F_CC2 (CC2) POSITIVE
Input Type_F_CC3 (CC3) POSITIVE
Input Type_F_CC4 (CC4) POSITIVE
Input Type_F_CC5 (CC5) POSITIVE
Input Type_F_CC6 (CC6) POSITIVE
Input Type_F_CC7 (CC7) POSITIVE
Input Type_F_CC8 (CC8) POSITIVE
Input Type_F_CC9 (Va_COIL1) POSITIVE-EDGE
Input Type_F_CC10 (Vb_COIL1) POSITIVE-EDGE
Input Type_F_CC11 (Va_COIL2) POSITIVE-EDGE
Input Type_F_CC12 (Vb_COIL2) POSITIVE-EDGE
Input Type_F_CC13 (O7_SEAL) POSITIVE-EDGE
Input Type_F_CC14 (O8_SEAL) POSITIVE-EDGE
Input Type_F_CC15 (SUP_COIL1) POSITIVE-EDGE
Input Type_F_CC16 (SUP_COIL2) POSITIVE-EDGE
Delay Input Time_F_CC1 (CC1) 0 [0 : 60000] ms
Delay Input Time_F_CC2 (CC2) 0 [0 : 60000] ms
Delay Input Time_F_CC3 (CC3) 0 [0 : 60000] ms
Delay Input Time_F_CC4 (CC4) 0 [0 : 60000] ms
Delay Input Time_F_CC5 (CC5) 0 [0 : 60000] ms
Delay Input Time_F_CC6 (CC6) 0 [0 : 60000] ms
Delay Input Time_F_CC7 (CC7) 0 [0 : 60000] ms
Delay Input Time_F_CC8 (CC8) 0 [0 : 60000] ms
Delay Input Time_F_CC9 (Va_COIL1) 0 [0 : 60000] ms
Delay Input Time_F_CC10 (Vb_COIL1) 0 [0 : 60000] ms
Delay Input Time_F_CC11 (Va_COIL2) 0 [0 : 60000] ms
Delay Input Time_F_CC12 (Vb_COIL2) 0 [0 : 60000] ms
Delay Input Time_F_CC13 (O7_SEAL) 0 [0 : 60000] ms
Delay Input Time_F_CC14 (O8_SEAL) 0 [0 : 60000] ms
Delay Input Time_F_CC15 (SUP_COIL1) 0 [0 : 60000] ms
Delay Input Time_F_CC16 (SUP_COIL2) 0 [0 : 60000] ms
Output Logic_F_01 POSITIVE
Output Logic_F_02 POSITIVE
Output Logic_F_03 POSITIVE
Output Logic_F_04 POSITIVE
Output Logic_F_05 POSITIVE
Output Logic_F_06 POSITIVE
Output Logic_F_07 POSITIVE
Output Logic_F_08 POSITIVE
Output Type_F_01 NORMAL
Output Type_F_02 NORMAL
Output Type_F_03 NORMAL
Output Type_F_04 NORMAL
Output Type_F_05 NORMAL
Output Type_F_06 NORMAL

21
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Output Type_F_07 PULSE
Output Type_F_08 PULSE
Pulse Output Time_F_01 0 [0 : 60000] ms
Pulse Output Time_F_02 0 [0 : 60000] ms
Pulse Output Time_F_03 0 [0 : 60000] ms
Pulse Output Time_F_04 0 [0 : 60000] ms
Pulse Output Time_F_05 0 [0 : 60000] ms
Pulse Output Time_F_06 200 [0 : 60000] ms
Pulse Output Time_F_07 200 [0 : 60000] ms
Pulse Output Time_F_08 200 [0 : 60000] ms
Snapshot Events ENABLED

BOARD G

NAME VALUE UNIT


Voltage Threshold A_G 30 [10 : 230] V
Voltage Threshold B_G 30 [10 : 230] V
Debounce Time A_G 3 [1 : 50] ms
Debounce Time B_G 3 [1 : 50] ms
Input Type_G_CC1 (CC1) POSITIVE
Input Type_G_CC2 (CC2) POSITIVE
Input Type_G_CC3 (CC3) POSITIVE
Input Type_G_CC4 (CC4) POSITIVE
Input Type_G_CC5 (CC5) POSITIVE
Input Type_G_CC6 (CC6) POSITIVE
Input Type_G_CC7 (CC7) POSITIVE
Input Type_G_CC8 (CC8) POSITIVE
Input Type_G_CC9 (CC9) POSITIVE
Input Type_G_CC10 (CC10) POSITIVE
Input Type_G_CC11 (CC11) POSITIVE
Input Type_G_CC12 (CC12) POSITIVE
Input Type_G_CC13 (CC13) POSITIVE
Input Type_G_CC14 (CC14) POSITIVE
Input Type_G_CC15 (CC15) POSITIVE
Input Type_G_CC16 (CC16) POSITIVE
Delay Input Time_G_CC1 (CC1) 0 [0 : 60000] ms
Delay Input Time_G_CC2 (CC2) 0 [0 : 60000] ms
Delay Input Time_G_CC3 (CC3) 0 [0 : 60000] ms
Delay Input Time_G_CC4 (CC4) 0 [0 : 60000] ms
Delay Input Time_G_CC5 (CC5) 0 [0 : 60000] ms
Delay Input Time_G_CC6 (CC6) 0 [0 : 60000] ms
Delay Input Time_G_CC7 (CC7) 0 [0 : 60000] ms
Delay Input Time_G_CC8 (CC8) 0 [0 : 60000] ms
Delay Input Time_G_CC9 (CC9) 0 [0 : 60000] ms
Delay Input Time_G_CC10 (CC10) 0 [0 : 60000] ms
Delay Input Time_G_CC11 (CC11) 0 [0 : 60000] ms
Delay Input Time_G_CC12 (CC12) 0 [0 : 60000] ms
Delay Input Time_G_CC13 (CC13) 0 [0 : 60000] ms
Delay Input Time_G_CC14 (CC14) 0 [0 : 60000] ms
Delay Input Time_G_CC15 (CC15) 0 [0 : 60000] ms
Delay Input Time_G_CC16 (CC16) 0 [0 : 60000] ms
Output Logic_G_01 POSITIVE
Output Logic_G_02 POSITIVE
Output Logic_G_03 POSITIVE
Output Logic_G_04 POSITIVE
Output Logic_G_05 POSITIVE
Output Logic_G_06 POSITIVE
Output Logic_G_07 POSITIVE
Output Logic_G_08 POSITIVE
Output Type_G_01 PULSE
Output Type_G_02 PULSE
Output Type_G_03 NORMAL
Output Type_G_04 NORMAL
Output Type_G_05 PULSE
Output Type_G_06 PULSE
Output Type_G_07 PULSE

22
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Output Type_G_08 PULSE
Pulse Output Time_G_01 200 [0 : 60000] ms
Pulse Output Time_G_02 200 [0 : 60000] ms
Pulse Output Time_G_03 0 [0 : 60000] ms
Pulse Output Time_G_04 0 [0 : 60000] ms
Pulse Output Time_G_05 200 [0 : 60000] ms
Pulse Output Time_G_06 200 [0 : 60000] ms
Pulse Output Time_G_07 200 [0 : 60000] ms
Pulse Output Time_G_08 200 [0 : 60000] ms
Snapshot Events ENABLED

REMOTE COMMS

NAME VALUE UNIT


Remote Comms NONE
650 ID F650
Hold Time 10000 [1000 : 60000] ms
Snapshot Events Remote Out DISABLED
Remote Device 1 Remote Device 1
Bit Pair 1 None
Default Value 1 OFF
Remote Device 2 Remote Device 2
Bit Pair 2 None
Default Value 2 OFF
Remote Device 3 Remote Device 3
Bit Pair 3 None
Default Value 3 OFF
Remote Device 4 Remote Device 4
Bit Pair 4 None
Default Value 4 OFF
Remote Device 5 Remote Device 5
Bit Pair 5 None
Default Value 5 OFF
Remote Device 6 Remote Device 6
Bit Pair 6 None
Default Value 6 OFF
Remote Device 7 Remote Device 7
Bit Pair 7 None
Default Value 7 OFF
Remote Device 8 Remote Device 8
Bit Pair 8 None
Default Value 8 OFF
Remote Device 9 Remote Device 9
Bit Pair 9 None
Default Value 9 OFF
Remote Device 10 Remote Device 10
Bit Pair 10 None
Default Value 10 OFF
Remote Device 11 Remote Device 11
Bit Pair 11 None
Default Value 11 OFF
Remote Device 12 Remote Device 12
Bit Pair 12 None
Default Value 12 OFF
Remote Device 13 Remote Device 13
Bit Pair 13 None
Default Value 13 OFF
Remote Device 14 Remote Device 14
Bit Pair 14 None
Default Value 14 OFF
Remote Device 15 Remote Device 15
Bit Pair 15 None
Default Value 15 OFF
Remote Device 16 Remote Device 16
Bit Pair 16 None
Default Value 16 OFF

23
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

NAME VALUE UNIT


Remote Device 17 Remote Device 17
Bit Pair 17 None
Default Value 17 OFF
Remote Device 18 Remote Device 18
Bit Pair 18 None
Default Value 18 OFF
Remote Device 19 Remote Device 19
Bit Pair 19 None
Default Value 19 OFF
Remote Device 20 Remote Device 20
Bit Pair 20 None
Default Value 20 OFF
Remote Device 21 Remote Device 21
Bit Pair 21 None
Default Value 21 OFF
Remote Device 22 Remote Device 22
Bit Pair 22 None
Default Value 22 OFF
Remote Device 23 Remote Device 23
Bit Pair 23 None
Default Value 23 OFF
Remote Device 24 Remote Device 24
Bit Pair 24 None
Default Value 24 OFF
Remote Device 25 Remote Device 25
Bit Pair 25 None
Default Value 25 OFF
Remote Device 26 Remote Device 26
Bit Pair 26 None
Default Value 26 OFF
Remote Device 27 Remote Device 27
Bit Pair 27 None
Default Value 27 OFF
Remote Device 28 Remote Device 28
Bit Pair 28 None
Default Value 28 OFF
Remote Device 29 Remote Device 29
Bit Pair 29 None
Default Value 29 OFF
Remote Device 30 Remote Device 30
Bit Pair 30 None
Default Value 30 OFF
Remote Device 31 Remote Device 31
Bit Pair 31 None
Default Value 31 OFF
Remote Device 32 Remote Device 32
Bit Pair 32 None
Default Value 32 OFF
Snapshot Events Remote Inp DISABLED

RELAY CONFIGURATION

OUTPUTS

OUTPUT SOURCE SOURCE LOGIC LOGIC


26TAM STAGE 1 -
26TAM STAGE 1 OP(CC1) -
26TAM STAGE 2 -
26TAM STAGE 2 OP(CC2) -
63TAM STAGE 2 -
63TAM STAGE 2 OP(CC3) -
71TAM -
71TAM OPERATE(CC4) -
45FTAM -

24
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

OUTPUT SOURCE SOURCE LOGIC LOGIC


45FTAM OPERATE(CC5) -
TRIP 41EX NOT
PH IOC1 HIGH OP -
PH TOC1 HIGH OP -
PH IOC1 LOW OP -
63TAM STAGE 2 OP(CC3) -
45FTAM OPERATE(CC5) -
TRIP LO 86/T1 -
PH TOC1 HIGH OP -
PH IOC1 LOW OP -
PH IOC1 HIGH OP -
C/B 52L TRIP -
PH IOC1 HIGH OP -
PH IOC1 LOW OP -
PH TOC1 HIGH OP -
63TAM STAGE 2 OP(CC3) -
45FTAM OPERATE(CC5) -
CHANGE SOURCE 6 kV
-
NC
CHANGE SOURCE 6 KV(CC7) -
PH TOC1 HIGH OP -
PH IOC1 HIGH OP -
PH IOC1 LOW OP -
45FTAM OPERATE(CC5) -
C/B 52G TRIP -
PH IOC1 HIGH OP -
PH IOC1 LOW OP -
PH TOC1 HIGH OP -
63TAM STAGE 2 OP(CC3) -
45FTAM OPERATE(CC5) -
MK VI 50P/51P ALARM -
PH IOC1 LOW OP -
PH IOC1 HIGH OP -
PH TOC1 HIGH OP -
MK VI ALARM -
45FTAM OPERATE(CC5) -
71TAM OPERATE(CC4) -
63TAM STAGE 2 OP(CC3) -
26TAM STAGE 2 OP(CC2) -
26TAM STAGE 1 OP(CC1) -
READY LED NOT
VT FUSE FAILURE -
CHANGE SOURCE 400 V -
26TAM STAGE 2 OP(CC2) -
PH TOC1 HIGH OP -
PH IOC1 LOW OP -
PH IOC1 HIGH OP -
63TAM STAGE 2 OP(CC3) -
45FTAM OPERATE(CC5) -
TRIP LO 86/T2 -
PH TOC1 HIGH OP -
PH IOC1 LOW OP -
PH IOC1 HIGH OP -
TURBINE NORMAL STOP -
PH TOC1 HIGH OP -
PH IOC1 LOW OP -
PH IOC1 HIGH OP -
63TAM STAGE 2 OP(CC3) -
45FTAM OPERATE(CC5) -
CHANGE SOURCE 6 kV
-
NO
CHANGE SOURCE 6 KV(CC7) -
45FTAM OPERATE(CC5) -
PH IOC1 HIGH OP -
PH IOC1 LOW OP -
PH TOC1 HIGH OP -

25
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

LEDS

LED SOURCE SOURCE LOGIC LOGIC TEXT


LED01 - Trip
PH TOC1 HIGH OP -
PH IOC1 LOW OP -
PH IOC1 HIGH OP -
LED02 - 50/51P Trip
PH TOC1 HIGH OP -
PH IOC1 LOW OP -
PH IOC1 HIGH OP -
LED06 - Pickup
PH TOC1 HIGH PKP -
50/51P
LED07 -
Pickup
PH TOC1 HIGH PKP -
LED15 - LOCAL
LOCAL OPERATION MODE -

PROTECTION ELEMENTS

PROTECTION ELEMENT SOURCE SOURCE LOGIC LOGIC


PH IOC1 HIGH A BLK -
GROUP 1 BLOCKED -
PH IOC1 HIGH B BLK -
GROUP 1 BLOCKED -
PH IOC1 HIGH C BLK -
GROUP 1 BLOCKED -
PH IOC2 HIGH A BLK -
GROUP 2 BLOCKED -
PH IOC2 HIGH B BLK -
GROUP 2 BLOCKED -
PH IOC2 HIGH C BLK -
GROUP 2 BLOCKED -
PH IOC3 HIGH A BLK -
GROUP 3 BLOCKED -
PH IOC3 HIGH B BLK -
GROUP 3 BLOCKED -
PH IOC3 HIGH C BLK -
GROUP 3 BLOCKED -
PH IOC1 LOW A BLK -
GROUP 1 BLOCKED -
PH IOC1 LOW B BLK -
GROUP 1 BLOCKED -
PH IOC1 LOW C BLK -
GROUP 1 BLOCKED -
PH IOC2 LOW A BLK -
GROUP 2 BLOCKED -
PH IOC2 LOW B BLK -
GROUP 2 BLOCKED -
PH IOC2 LOW C BLK -
GROUP 2 BLOCKED -
PH IOC3 LOW A BLK -
GROUP 3 BLOCKED -
PH IOC3 LOW B BLK -
GROUP 3 BLOCKED -
PH IOC3 LOW C BLK -
GROUP 3 BLOCKED -
NEUTRAL IOC1 BLOCK -
GROUP 1 BLOCKED -
NEUTRAL IOC2 BLOCK -
GROUP 2 BLOCKED -
NEUTRAL IOC3 BLOCK -
GROUP 3 BLOCKED -
GROUND IOC1 BLOCK -

26
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

PROTECTION ELEMENT SOURCE SOURCE LOGIC LOGIC


GROUP 1 BLOCKED -
GROUND IOC2 BLOCK -
GROUP 2 BLOCKED -
GROUND IOC3 BLOCK -
GROUP 3 BLOCKED -
SENS GND IOC1 BLK -
GROUP 1 BLOCKED -
SENS GND IOC2 BLK -
GROUP 2 BLOCKED -
SENS GND IOC3 BLK -
GROUP 3 BLOCKED -
PH TOC1 HIGH A BLK -
GROUP 1 BLOCKED -
PH TOC1 HIGH B BLK -
GROUP 1 BLOCKED -
PH TOC1 HIGH C BLK -
GROUP 1 BLOCKED -
PH TOC2 HIGH A BLK -
GROUP 2 BLOCKED -
PH TOC2 HIGH B BLK -
GROUP 2 BLOCKED -
PH TOC2 HIGH C BLK -
GROUP 2 BLOCKED -
PH TOC3 HIGH A BLK -
GROUP 3 BLOCKED -
PH TOC3 HIGH B BLK -
GROUP 3 BLOCKED -
PH TOC3 HIGH C BLK -
GROUP 3 BLOCKED -
NEUTRAL TOC1 BLOCK -
GROUP 1 BLOCKED -
NEUTRAL TOC2 BLOCK -
GROUP 2 BLOCKED -
NEUTRAL TOC3 BLOCK -
GROUP 3 BLOCKED -
GROUND TOC1 BLOCK -
GROUP 1 BLOCKED -
GROUND TOC2 BLOCK -
GROUP 2 BLOCKED -
GROUND TOC3 BLOCK -
GROUP 3 BLOCKED -
SENS GND TOC1 BLOCK -
GROUP 1 BLOCKED -
SENS GND TOC2 BLOCK -
GROUP 2 BLOCKED -
SENS GND TOC3 BLOCK -
GROUP 3 BLOCKED -
PHASE UV1 BLOCK -
GROUP 1 BLOCKED -
PHASE UV2 BLOCK -
GROUP 2 BLOCKED -
PHASE UV3 BLOCK -
GROUP 3 BLOCKED -
NEG SEQ OV1 BLOCK -
GROUP 1 BLOCKED -
NEG SEQ OV2 BLOCK -
GROUP 2 BLOCKED -
NEG SEQ OV3 BLOCK -
GROUP 3 BLOCKED -
THERMAL1 BLOCK -
GROUP 1 BLOCKED -
THERMAL2 BLOCK -
GROUP 2 BLOCKED -
THERMAL3 BLOCK -
GROUP 3 BLOCKED -
PHASE DIR1 BLK INP -

27
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

PROTECTION ELEMENT SOURCE SOURCE LOGIC LOGIC


GROUP 1 BLOCKED -
PHASE DIR2 BLK INP -
GROUP 2 BLOCKED -
PHASE DIR3 BLK INP -
GROUP 3 BLOCKED -
NEUTRAL DIR1 BLK INP -
GROUP 1 BLOCKED -
NEUTRAL DIR2 BLK INP -
GROUP 2 BLOCKED -
NEUTRAL DIR3 BLK INP -
GROUP 3 BLOCKED -
GROUND DIR1 BLK INP -
GROUP 1 BLOCKED -
GROUND DIR2 BLK INP -
GROUP 2 BLOCKED -
GROUND DIR3 BLK INP -
GROUP 3 BLOCKED -
NEUTRAL OV1 HIGH BLK -
GROUP 1 BLOCKED -
NEUTRAL OV2 HIGH BLK -
GROUP 2 BLOCKED -
NEUTRAL OV3 HIGH BLK -
GROUP 3 BLOCKED -
NEUTRAL OV1 LOW BLK -
GROUP 1 BLOCKED -
NEUTRAL OV2 LOW BLK -
GROUP 2 BLOCKED -
NEUTRAL OV3 LOW BLK -
GROUP 3 BLOCKED -
AUXILIARY UV1 BLOCK -
GROUP 1 BLOCKED -
AUXILIARY UV2 BLOCK -
GROUP 2 BLOCKED -
AUXILIARY UV3 BLOCK -
GROUP 3 BLOCKED -
PHASE OV1 BLOCK -
GROUP 1 BLOCKED -
PHASE OV2 BLOCK -
GROUP 2 BLOCKED -
PHASE OV3 BLOCK -
GROUP 3 BLOCKED -
AUXILIARY OV1 BLOCK -
GROUP 1 BLOCKED -
AUXILIARY OV2 BLOCK -
GROUP 2 BLOCKED -
AUXILIARY OV3 BLOCK -
GROUP 3 BLOCKED -
NEG SEQ TOC1 BLOCK -
GROUP 1 BLOCKED -
NEG SEQ TOC2 BLOCK -
GROUP 2 BLOCKED -
NEG SEQ TOC3 BLOCK -
GROUP 3 BLOCKED -
OVERFREQ1 BLOCK -
GROUP 1 BLOCKED -
OVERFREQ2 BLOCK -
GROUP 2 BLOCKED -
OVERFREQ3 BLOCK -
GROUP 3 BLOCKED -
UNDERFREQ1 BLOCK -
GROUP 1 BLOCKED -
UNDERFREQ2 BLOCK -
GROUP 2 BLOCKED -
UNDERFREQ3 BLOCK -
GROUP 3 BLOCKED -
BROKEN CONDUCT1 BLK -

28
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

PROTECTION ELEMENT SOURCE SOURCE LOGIC LOGIC


GROUP 1 BLOCKED -
BROKEN CONDUCT2 BLK -
GROUP 2 BLOCKED -
BROKEN CONDUCT3 BLK -
GROUP 3 BLOCKED -
ISOLATED GND1 BLK -
GROUP 1 BLOCKED -
ISOLATED GND2 BLK -
GROUP 2 BLOCKED -
ISOLATED GND3 BLK -
GROUP 3 BLOCKED -
SENS GND DIR1 BLK IP -
GROUP 1 BLOCKED -
SENS GND DIR2 BLK IP -
GROUP 2 BLOCKED -
SENS GND DIR3 BLK IP -
GROUP 3 BLOCKED -
FWD PWR1 BLOCK -
GROUP 1 BLOCKED -
FWD PWR2 BLOCK -
GROUP 2 BLOCKED -
FWD PWR3 BLOCK -
GROUP 3 BLOCKED -
PH TOC1 LOW A BLK -
GROUP 1 BLOCKED -
PH TOC1 LOW B BLK -
GROUP 1 BLOCKED -
PH TOC1 LOW C BLK -
GROUP 1 BLOCKED -
PH TOC2 LOW A BLK -
GROUP 2 BLOCKED -
PH TOC2 LOW B BLK -
GROUP 2 BLOCKED -
PH TOC2 LOW C BLK -
GROUP 2 BLOCKED -
PH TOC3 LOW A BLK -
GROUP 3 BLOCKED -
PH TOC3 LOW B BLK -
GROUP 3 BLOCKED -
PH TOC3 LOW C BLK -
GROUP 3 BLOCKED -
DIR PWR1 BLOCK -
GROUP 1 BLOCKED -
DIR PWR2 BLOCK -
GROUP 2 BLOCKED -
DIR PWR3 BLOCK -
GROUP 3 BLOCKED -
LOCKED ROTOR1 BLK -
GROUP 1 BLOCKED -
LOCKED ROTOR2 BLK -
GROUP 2 BLOCKED -
LOCKED ROTOR3 BLK -
GROUP 3 BLOCKED -
FREQ RATE1 BLOCK -
GROUP 1 BLOCKED -
FREQ RATE2 BLOCK -
GROUP 2 BLOCKED -
FREQ RATE3 BLOCK -
GROUP 3 BLOCKED -
LOAD ENCR1 BLOCK -
GROUP 1 BLOCKED -
LOAD ENCR2 BLOCK -
GROUP 2 BLOCKED -
LOAD ENCR3 BLOCK -
GROUP 3 BLOCKED -
32N1 HIGH BLOCK -

29
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup

PROTECTION ELEMENT SOURCE SOURCE LOGIC LOGIC


GROUP 1 BLOCKED -
32N2 HIGH BLOCK -
GROUP 2 BLOCKED -
32N3 HIGH BLOCK -
GROUP 3 BLOCKED -
32N1 LOW BLOCK -
GROUP 1 BLOCKED -
32N2 LOW BLOCK -
GROUP 2 BLOCKED -
32N3 LOW BLOCK -
GROUP 3 BLOCKED -

OSCILLOGRAPHY

SOURCE
OSCILLOGRAPHY SOURCE LOGIC TEXT
LOGIC
OSC DIG CHANNEL 1 - 52b LO 86T1/2
52/b LO 86T1*86T2(CC1) -
OSC DIG CHANNEL 2 - 52a LO 86T1
52/a LO 86T1(CC2) -
OSC DIG CHANNEL 3 - 52a LO 86T2
52/a LO 86T2(CC3) -
OSC DIG CHANNEL 4 - 51P
PH TOC1 HIGH OP -
OSC DIG CHANNEL 5 - 50PH
PH IOC1 HIGH OP -
OSC DIG CHANNEL 6 - 50PL
PH IOC1 LOW OP -
OSCILLO TRIGGER - OSCILLO TRIGGER
PH TOC1 HIGH OP -
PH IOC1 HIGH OP -
PH IOC1 LOW OP -

SWITCHGEARS

ID OPENING TIME (ms) CLOSING TIME (ms)


1 100 150

CONTACT
CONTACT
ID CONTACT A SOURCE A SOURCE
A LOGIC
LOGIC
1 -
52/a LO 86T2(CC3) -
52/a LO 86T1(CC2) -

CONTACT
CONTACT
ID CONTACT B SOURCE B SOURCE
B LOGIC
LOGIC
1 -
52/b LO 86T1*86T2(CC1) -

CLOSED ERROR 00 ERROR 11


ID OPEN TXT ALARM ALARM ALARM ALARM
TXT TXT TXT
LO 86T1/2 LO 86T1/2 LO 86T1/2 LO 86T1/2
1 NO NO YES YES
Reset Operate Disc Disc

OPENING CLOSING
ID
INIT INIT
1

30

You might also like