INTRODUCTION
This paper is a design of shallow foundation for 3B+G+ 13 Building. In
this paper 3types of shallow foundations are used which are
Isolated ,Combined & and MAT/RAFT . As shown in the picture we have
tried to lable the points where the columnS will exert load. And we have
tried to show the minimum AREA if an Isolated foundation were to be
used.
From the Labled Column load Application Points 8 of them are
designed with Isolated footing LABEL(1,2,3,4,14,15,16,17) due their
comparatively low load from superstructure and no possibilty for and
Stress overlap in an effective depth due to the lateral distance among
them.
We have merged 2 of them and made a combined footing with label
(5&6) and label (9&10) due to their proximity and possibility of stress
over lap. And the reamaining points due to their proximity if Isolated
foundation to be used and the wall foundation for the elevator shear
wall, and the huge amount of SUPERSTUCTURE LOAD on this narrow
area we decided to use MAT foundations for this 6 column load transfer
points these are laod from label (7,8,11,12,30,35)
ADDIS ABABA INSTITUTE OF TECHHNOLOGY
ADDIS ABABA INSTITUTE OF TECHHNOLOGY
ADDIS ABABA INSTITUTE OF TECHHNOLOGY
A. Material data(concrete)
Cmin,durability 25mm
Cmin,used 25mm
cover 25+10+25=60mm
B. Reinforcement data
ADDIS ABABA INSTITUTE OF TECHHNOLOGY
Ø – 16mm for F2
ϒconc.=25KN/m3,
Area proportioning
First let us assume that the footing pad is square
Serviceability state(DL+0.3LL)
Ultimate
Limit(1.35DL+1.5LL)
1.374
KNm/1009.5965KN=0.01317982m
474.7236 kpa
422.6955111 kpa
Eccentricity at ultimate
ey=Mx/Fz=1.733/1387.9227 = 0.001248629 m
581.1124889 kpa
ADDIS ABABA INSTITUTE OF TECHHNOLOGY
646.4348 kpa
587.2742667 kpa
652.5965778 kpa
����≤�Ult
qaverage=(581.1124889 +646.4348 +587.2742667 +652.5965778)/4= 616.8545333 kpa
c=0.18/γc=0.18/1.5=0.12
ρmin=min(0.26*fctm/400,0.02) ,0.26*fck²/³*0.3/400=0.002 take ρmin=0.002
K=min((1+√(200/d’)),2)) =1+√ (200/682) =1.542
B, punching shear
1. Punching is critical at 1.5d from the face of the column
Crd, c=0.18/γc=0.18/1.5=0.12
ρmin=min(0.26*fctm/400,0.02) ,0.26*fck²/³*0.3/400=0.002 take ρmin=0.002
K=min((1+√(200/d’),2)) =1+√ (200/682) =1.542 <2……….OK!
Since the critical section lies outside the footing dimension, no verification for punching shear is
required.
ADDIS ABABA INSTITUTE OF TECHHNOLOGY
Reinforcement calculation
Design for Flexure
The maximum moment occurs at the face of the column
X=B/2-b/2=2/2-0.75/2=0.625m Y=L/2-h/2=2/2
0.75/2=0.625m
w = σav*B = 616.8545333 *1.5 = 925.2818 kNm
X-direction moment
65.06 kNm
Msdx=Msdx/B= 43.37
0.007
Using μsd= 0.007 read kz from design table and chart EBCS EN 1992-1-1:2014(for C12/15-
C50/60) kz= 0.993
184.18 mm2
= 242.68
= 121.34
0.0184147
ADDIS ABABA INSTITUTE OF TECHHNOLOGY
Using μsd= 0.0065823 read kz from design table and chart EBCS EN 1992-1-1:2014(for
C12/15-C50/60) kz=0.9927088
184.18187 mm2