Analysis of Variable Frequency Resonant Withstand


Voltage Test for 220kV Long Cable On Site
Du Sisi, Cai Ye, Wang Wei, Zhang Xuefeng
HIMALAYAL - SHANGHAI - CHINA

Abstract: Newly-completed 220kV cable line in the eastern urban area of Jinan
city is 7.97km and has large capacity. If we want to carry out withstand voltage
test, power source capacity, maximum output total current, weight of needed test
equipment must be minimized and easy to install. This is the first time that such
high-voltage test has been conducted in Jinan. After comparing all available
methods, serial variable frequency resonant withstand voltage test is adopted.
Based on theoretical calculation and analysis, reasonable test scheme is put
forward and implemented smoothly. Finally, we make discussions combing with
test results. Practice has proved that resonant test system is workable and
effective and is of important value for variable frequency resonant withstand
voltage test for long power cable on site.

I. Introduction test.
Conducting effective cable hand-over 3) Variable frequency resonant test
test on site can reduce the probability utilizes the principle of variable
of breakdown to largest extent and frequency resonance to reduce power
ensure reliable and safe cable source capacity to 1/Q of test object
operation. However, the capacity of capacity. Great fall in equipment
cable is great, especially long cable, weight makes it possible to conduct
traditional test methods cannot meet high-voltage and long cable field test.
the requirement of field test. At Meanwhile, test frequency and test
present, There is a lack of long and reactor can be adjusted, adding
high-voltage cable hand-over test in system flexibility.
China.
The test object in this paper is 7.9km
1) Super-low frequency (0.1Hz) cable; test current is high; Q value of
withstand voltage test is mainly test equipment requires to be high.
applicable to medium-low voltage XLP Against the above problems, the paper
insulation cable withstand voltage deeply analyzes some problems,
test. which may occur during the test, and
puts forward test scheme. According
2) Power frequency AC withstand
to test results, test frequency and test
voltage test needs large-capacity test
object length are analyzed, which is of
equipment. The equipment weighs
important reference value. Test object
several tons and huge in size and
is a municipal engineering cable,
difficult to assemble. This type of test
which is located in the eastern urban
cannot meet the requirement of field
T: 86 21 61016212 Himalayal, always by your side. Copy right © HIMALAYAL
info@himalayal.com Page:1 All right reserved.
WWW.HIMALAYAL.COM.CN

o
area of Jinan city. This is the first time
1 L 1 L
that such high-voltage test has been Q = = = =
R R LC R C
conducted in Jinan.
(3)
II. Test Parameter Analysis
The resonant withstand voltage test
1. Principle of variable frequency
makes the circuit in resonant
series resonance
condition via changing inductance of
The voltage of circuit input end U is test system and test frequency. Most
the same phase with current I. capacitive current on test object is
Schematic diagram of series offset by reactive current on the
resonance is shown in Fig.1. reactor in the test circuit. Power
source only provides the energy for
active power consumed in the circuit.
However, both end voltage UCX of test
object CX is Q times of power source
voltage US , UCX = QUS . Q is resonant
Fig.1 Schematic diagram of series
multiple of the system, namely, quality
resonance
factor.
In the Fig.1, R is circuit equivalent
2. Test parameters
resistance (Ω); L is circuit equivalent
inductance (H); C is circuit equivalent According to GB 50150-2006
capacitance (Ω). Standard for Hand-over Test of
Electric Equipment Installation
Under the force of sine wave voltage U
Engineering, 220kV cable field AC
1
C
Z = R + j (ωL - ) = R + j (XL - XC) withstand voltage test requires 1.7
times of rated phase voltage;
=R + jX (1)
frequency ranges from 20Hz to 300Hz;
In the formula: the reactance (X=XL-XC) test time is 60min. Schematic diagram
is the function of anglular frequency of test scheme is shown in Fig.2.
1
C
ω. XL-XC = 0 or XL = XC → ωL = ,

circuit impedance Z (ω0) = R is pure


resistance. The work condition at this
time is called resonant. The resonant
occurring in the series circuit is also
Fig.2 Schematic diagram of test
named resonant test system.
scheme
Resonant angular frequency:
FC: Variable frequency source
1 1 Tr: Exciting transformer
ω0 = →fo = (2)
LC LC L: Reactor
Cx: Test object capacitance
Circuit quality factor:
C1 & C2 : high voltage divider

1) Test object parameter


T: 86 21 61016212 Himalayal, always by your side. Copy right © HIMALAYAL
info@himalayal.com Page:2 All right reserved.
WWW.HIMALAYAL.COM.CN
Specification model: Frequency of resonant test system is
ZC-YJLW02-Z127/220kV-1×2500mm2, 30Hz, XL = 0.68 Ω; XC = 2838 Ω; the
7970m; Capacitance per kilometer: ratio of capacitance rise to voltage is
0.2352uF/km about XL / XC = 0.024%.
2) Test voltage Based on theoretical calculation, if AC
U = 1.7 × Ur = 216kV withstand voltage test frequency
ranges from 30Hz to 50Hz, the ratio of
3) Capacitance
capacitance rise to voltage is between
Cx = 1.87uF. Since test object
0.024% and 0.07%, which conforms
capacitance is high, frequency should
to the requirements of GB/T 16927.
be low to make test current within the
Hence, it is not necessary to set
acceptable range: 30Hz.
remote reactor. However, at the
4) maximum total current under moment of voltage up, it is likely that
30Hz test voltage is Ix = ωCx > = transient process causes
76.10a instantaneous over-current. Voltage
divider can be installed at both ends
5) Exciting voltage
to monitor and prevent the voltage
Series resonant condition, Q0 > 40,
from being too high.
Uf >U / Q0 =5.4kV.
III. Field Test Case
6) Power
Q = 15.82Mvar 1. Test scheme
P = Q / Q0 = 395.5kW
Main characteristics of this test are as
Through above calculation, we learn follows: ① maximum total current is
that test object capacitance is great; high and even reaches 76.1A ② test
test frequency should be low; total object capacity is great - 1.87uF.
current should be high; Q value German Hyva RSE 400 on-board
requires to be higher. resonant test system device:
dimension 16m×2.5m×4.1m
3. Capacitance rise of test object
(L×W×H); capacity 21580kV·A;
According to GB/T 16927, capacitance maximum output current 83A;
rise ratio of AC withstand voltage test frequency range 20-300Hz. Device
should not be more than ± 3%. test voltage basically meets the
Hence, it is necessary to reasonably requirement. Picture of real device is
configure test equipment and reduce shown in Fig.3.
capacitance rise of test object.
Schematic diagram of 220kV cable AC
withstand voltage test is shown in
Fig.1. The test object takes on
capacitive condition during the test.
Frequency of resonant test system is
50Hz, XL = 1.14 Ω ; XC = 1703 Ω ; the
ratio of capacitance rise to voltage is
about XL / XC = 0.07%;
T: 86 21 61016212 Himalayal, always by your side. Copy right © HIMALAYAL
info@himalayal.com Page:3 All right reserved.
WWW.HIMALAYAL.COM.CN
Fig.3 Fig.5 Diagram of test vehicle safety
distance
Because of on-board type, test device
is far lighter than assembled device (3) Test Conduction
and its installation is simplified on site.
We should be slow to raise the voltage
Because Q value is high, it can meet
during the test. Otherwise, it will
the requirement of this test under the
affect test equipment. When
available environment condition
breakdown of test object occurs, high
(temperature: 0-7 ℃ ; humidity:
voltage disappears at once because of
30%-50%).
losing resonant condition, which is
According to on-site measurement not helpful for recording test object
results, needed current of input power breakdown voltage. If too slow, it will
source is 400A. The power van in this have effect on test schedule.
test adopts 1000kV·A capacity; Procedures of this scheme are as
current is close to 1100A; there are follows:
also one 5000W generator and one 1) Start power van; open power
1000kV·A generator group, which source switch of test equipment
conform to test requirements. 2) Raise the voltage; speed remains at
10kV/10s; stop for 30s per 10kV
2. Test Site Preparation
voltage rise until 216kV; keep the
1) One end of test wire is connected to voltage stable and test time lasts
transformer or reactor while the other 60min.
is connected to wire clamp on test 3) Inspect the whole device to learn
object cable terminal. Dangling part of operation condition and examine
wire must be higher than 2200mm whether test frequency variation
from the ground. High voltage wiring meets the requirements.
is shown in Fig.4. 4) After completing the test, the
voltage gradually falls to zero and
grounds after discharge.
IV. Analysis of Field Test Results

Data screen-shot during the test is


shown in Fig.6.
Fig.4: High voltage connection
2) Capacity of power van is 1000kV·A.
Objects around the test vehicle is
centered on the vehicle and safety
radius is 5m, which is shown in Fig.5.

Fig.6 Test process photo


From Fig.6, high Q value is 144;
resonant frequency keeps at 28.97Hz
T: 86 21 61016212 Himalayal, always by your side. Copy right © HIMALAYAL
info@himalayal.com Page:4 All right reserved.
WWW.HIMALAYAL.COM.CN
at last, which is close to 30Hz; test power frequency test transformer to
current gradually rises to 76.1A, obtain reasonable weight and
which is in line with theoretical frequency range. Based on this test, if
calculation; displayed value of applied the cable is longer and capacitance is
voltage on head end is 224.4kV and greater, needed output current is
error calibration coefficient is -4.3%; higher. Hence, long cable test should
namely, actual voltage of head end is reduce the resonant frequency of test
224.4kV × 0.957 = 214.7kV; tail end equipment in order to reduce test
voltage is 211.2kV; error calibration current.
coefficient is 1.4%; actual voltage of
3) Maximum length of test object.
tail end is 211.2kV × 1.014 = 214.2kV;
Great capacity is one of remarkable
capacitance rise conforms to the range
characteristics for test object cable. In
requirement - ± 3%. The calculation
the test, test object is 7.9km long.
value is close to actual measurement
When the frequency is 30Hz,
value. Test voltage raising curve is
maximum total current has been close
shown in Fig.7.
to upper limit of test equipment. If
frequency and unit capacitance
remain the same, theoretical
maximum length is 8.67m.
Many tests, such as 220kV Xingyao I,
220kV Xingyao II, 220kV Yaowen
cable and 220kV Xingyao test, have
V. Conclusions proved that series resonant withstand
voltage test scheme is workable and
The paper selects suitable test scheme
practical and is of vital significance to
and combines test results to make the
full-scale operation of relevant tests
following conclusions.
all over the nation.
1) Test mode. Practice has proved
that resonant test system is a
workable mode for long and high REFERENCES
voltage cable. The key point lies in
[1] Liu Wei & Xiao Yong. AC withstand
reasonable configuration and
voltage test of 220kV cross-linked
selection of available test equipment if
super-long cable [J]. High Voltage
you want the test to be successful.
Engineering, 2008, 34 (4): 831-832.
According to GB 50150-2006
standards, above cable line test is [2] Wang Wei, Li Yuncai, Ma Wenyue.
conducted and test results indicate Technical foundation for cross-linked
that this line conforms to standard XLPE insulation cable [M]. Xi’an:
requirement. Northwestern Polytechnical
University Press, 2005.
2) Test frequency. Digging through
relevant technical materials at home [3] Zhao Jinming, Duan Xiaohua.
and abroad, it is still an important Application of variable frequency
issue to select suitable test device and series resonant techniques to high
T: 86 21 61016212 Himalayal, always by your side. Copy right © HIMALAYAL
info@himalayal.com Page:5 All right reserved.
WWW.HIMALAYAL.COM.CN
voltage cable hand-over test [J]. Power
System and Clean Energy. 2012, 28(4):
23-25.
[4] GB 50150-2006 Standard for
Hand-over Test of Electric Equipment
Installation Engineering [S]. Beijing:
China Planning Press, 2006.
[5] GB/Z18890-2002 Test method and
requirement for rated voltage 220kV
(Um=252kV) power cables with
cross-linked polyethylene insulation
and accessories [S]. Beijing: China
Standard Press, 2002.
[6] GB/T 16927.2-2013 High Voltage
Test Techniques. Part II: Measuring
System [S]. Beijing: China Standard
Press, 2013.

T: 86 21 61016212 Himalayal, always by your side. Copy right © HIMALAYAL


info@himalayal.com Page:6 All right reserved.

You might also like