Professional Documents
Culture Documents
MV Switchgear
Distribution Substation
Group: MV Switchgears
Subject: switchgear (11/22)
2 APPLICATION FIELD
This specification refers to the list of equipment mentioned in Table 1 and Table 2 that will be
used for indoor installation only.
4 SERVICE CONDITIONS
The service conditions are specified in TAQA/ADDC/AADC specification S-GEN-SER, in case
something is not or not properly specified regarding the service conditions, the Reference
Standards prescriptions shall be considered.
5.1 General
In these paragraphs the switchgear technical features and the ratings are described.
The supplier shall propose its best solution, considering the characteristics reported in the present
specification and annexes, the best technology available, maintenance, maintenance cost and cost
of switchgear.
5.2 Technical features
The switchgear shall comply with the following technical features:
• switchgear shall be complete in all respects necessary for their effective and trouble-free operation
when connected to the system.
• All components shall be of approved and reliable design. The highest degree of uniformity and
interchangeability shall be attained. The design shall allow easy maintenance, fault diagnosis and repair
of the components.
• switchgear shall be designed to ensure that thermal interaction do not unduly affect the performance of
any of the components.
5.2.1 Type of MV switchboards
The switchgear shall be metal enclosed type, with circuit breaker or fixed or withdrawable.
5.2.2 Type of Insulation
These types of switchgears insulation are acceptable:
• Preferred: AIS – for withdrawable CB solution
• Preferred: AIS or GIS for Fixed CB solution
• Alternative: gas other than SF6 - Fixed CB solution
• Alternative: mixed gas/solid shielded
• Alternative: solid shielded
NOTES:
• solid shielded means conductors are solid insulated (epoxy resin or other) with an external earthed
conductive layer.
• Alternative insulation solutions shall be approved by TAQA/ADDC/AADC. During the evaluation of
the alternative TAQA/ADD/AADC can ask Supplier additional clarification, calculation and testing.
5.2.3 Internal arc classification (IAC)
The enclosure of switchgear shall be AFLR classified according to IEC 62271-200 definitions.
The compliance shall be proved with specific test reports. The switchgear shall be equipped with
all necessary gas exhaust channels/ducts.
5.2.4 Loss of service continuity category
Loss of service continuity, according to IEC 62271-20:
• LSC2A for fixed CB
• LSC2B for withdrawable CB
Partition class shall be PM, in all cases.
Note: LPCT/sensors can be proposed as alternative to the conventional CT, according to the project
requirement and subject to TAQA/ADDC/AADC approval. In case of LPCT/sensors the protection relays
shall be suitable for the use with LPCT/sensors.
10 EXCEPTIONS
Possible exceptions to the present prescriptions, concerning the adoption of technical and/or
manufacturing aspects different from the ones prescribed in the present TS, can be evaluated by
TAQA/ADDC/AADC.
In such a case, TAQA/ADDC/AADC will take into account the opportunity to require additional
tests with regard to the technical/manufacturing proposed solutions.
Such exceptions can be approved by TAQA/ADDC/AADC.
Component Failure Mode Failure Effects Failure Cause Maintenance Task / Actions Frequency
Withdrawable Fixed
Withdrawable Fixed
Withdrawable Fixed