You are on page 1of 2

QPIC PV

Fire Water Tank 7/26/2021

1. GENERAL

1.1 Introduction
This standard document is to provide design calculation for the Tank maufactured according to API 650.

1.2 Design Data

1 Design Code API 650 12th Edition Addendum.2


2 Type Supported Cone Roof
3 Nominal(Maximum) Capacity 622 m3
Storage Capacity 553 m3
Net Working Capacity 464 m3
4 Size Inside Diameter 10,500 mm
Shell Height 7,200 mm
Hydrotest Height 7,200 mm
Design Liquid Level 7,200 mm
Shell Course Height 2,438 mm
5 Fluid Service - Gravity Water 1.000
6 Pressure (Design / Operating) 1 ATM kPa
Temperature (Design / Operating) 70 ATM °C
7 Test Pressure 1.30 kPa
8 Test Fluid Gravity Water 1.00
9 Corrosion Shell 1.6 mm
Allowance Bottom 1.6 mm
Roof 1.6 mm
Structure mm
10 Material Design Stress (Sd) Hydro. Test Stress (St)
Shell 1st A283 Gr.C 137 154 MPa
Shell 2nd A283 Gr.C 137 154 MPa
Shell 3rd A283 Gr.C 137 154 MPa

Bottom A283 Gr.C 137 154 MPa


Roof A283 Gr.C 137 154 MPa
11 Wind Velocity 18 km/h
12 Seismic (P.G.A at Bedrock) 0.1 g
13 Roof Live Load 1.2 kPa
14 Minimum Thickness of Shell 5 mm
15 Weight Empty 36 ton
Operating 589 ton
Full Water (Test) 658 ton
(unit : mm)
[Schematic Drawing]

1
Top of Shell Height 16
H = 7,200 Freeboard =
Overflow
Nozzle HHLL = 7,200 ; Design Liquid Level 6,890
Overfill Protection
Level HLL = 6,400 ; Normal fill level 490

Net Working Capacity


464 m3
Maximu Net
m Working
Capacit

D = 10,500

LLL = 1,040 ; Minimum fill level


1
Hb = 44

1
120

You might also like