To,
The General Manager - Electrical/Patna,
Delhi lVletro Rail Corporation Limited,
DMRC Elect. Project Office,
Gandhi Murti Compound,
Near Energy Park, Patel Nagar,
Patna, Bihar, Pin: 800023.
Name of Work: Contract PE-02: - Design Verification, Detail Engineering, Supply, lnstallation, Testing &
commissioning of Electrical and Mechanical systems, Fire detection, Fire suppression system and DG sets of
Corridor-1 and Corridor-2 of Elevated stations and Depot of Patna Metro Rail Project.
Refe re nce : A) Letter of Accepta n ce : D M RC/20l lll -7 48 / 2020, D ate: 12-70-2021
B) TEL Acceptance of LOA: TELlDMRCIPE-O2127-22/0O89, Dated: l9-7o-202t
C) TE L Letter Referen ce : f ELI HO / P E-02 / DMRC/ 22-23 I 2O3, Da ted : 1.6.03.2023
D) DMRC Letter Reference: DMRC/Elect/Patna Metro/GM/PE-}2|SRT/209/755, Dated: 71-04-2023
E ) TE L Letter Referen ce : T EL/ HO / P E-02 I DMRC/ 23 -24I 248, Date d : 24.05.2023
SUBJECT: Observation compliance of Earth-Mat Design Analysis Report based on -DEGS Software,
supporting drawing of Earth-Mat and Earth-Mat Schematic diagram for Malahi-Pakri Station
(REV-03).
Dear Sir,
With reference to above subject matter & reference letter (H), we are submitting herewith the following
documents as the discussion held in uent meetings:
SL No. Item Description Page No.
7 Earth Mat Report without EEC 1-39
2 Earth Mat Report with EEC 40-80
3 Grid Calculation with EEC 81-86
4 Calculation of EEC(in Earth Pit) 87
5 Meeting Points & Acknowledgement 88
6 Declaration for UL Certificate 89
7 Copy of P.O. to UL lndia Pvt. Ltd 90
8 Calibration Certificate 91
9 Grid Calculation without EEC 92-96
Thanking you and assuring you our best services at all the times.
Yours
For Limited
Mohit
Chief Project Manager
DMRC - Patna Metro Rai! Project
Regd. Office: Fortuna Tower, 8th Floor, 23A, Netaji Subhas Road, Suit. - 16, Kolkata - 700 001
Ph. : 033-2262 8881 ,033-2210 4262,Fax:033-22104262
Corporate Office : 9, Brabourne Road, 1st Floor, Kolkata - 700001
E-mail : tuamanho@tuaman.co.in Website : www.tuaman.co.in
CIN : U45205WB2005P1C10527O
zt' t
EFfr
OETHI
fd ta offitm frffi
TEIRO RIII. CORPOMTIOII tID.
gFC gorldh
^C6*r.
rE
ET
August 2023
Prepared By
surface layer Material Resistivity 10,000 ohm-m (Refer figure 1.1, As per IEEE-8}-
2013, Table 7)
Maximum Grid current, te 13.15 KA at LT and 9.205 KA at HT (lc = Dr x sp x
le) /As per IEEE 80-2073, Clouse-3.19 (Eq.-3) and
Clause-3.27 (Eq.-4))
Maximum Fault Current, Tr 25 KA at LT and 17.5 KA at 1{l (reference from
the colculation provided by AECOM)
Decrement Factor, Ds L.O52 (reference from IEEE-\O-2013, Clouse-15.70
(Table-10))
GPR
Ground Potential Rise, 7466.776 V at LT and5226.743 V at HT
Tolerable Touch Potential zo44.zs2V for 70Kg and 1510.o3 v for 50Kg
Calculated Touch Potential 1398.323 V at LT and 918.926 V at HT
Tolerable Step Potential 77L0.29LV for 70Kg and 5696.775 V for 50Kg
calculated step Potential 322.81:ov at LT and22s967 v at HT K*P,
Page l1
t
I. INTRODUCTION
l.l Purpose
The purpose of this analysis report is to determine the groundrrg system design
parameters to meet design criteria of Malahi Pakri Metro Station, Patna for DMRC.
Page l2
')t
1.4 Software Module Used
i. SESCAD Tool - CDEGS Software
ii. SES Ampacity Tool - CDEGS Software
iii. MILZ module
iv. SES Result Viewer
1
tra
h tol itr {otu E o o.&lJ n) 65ll {10 nhucr rftg {5 (}nr
Irets ICA) ritDfe:t {il.rdnrcd)
No .l ( I -r to2 in) (0 OtS m to
{ o Ot m) rrfihd grJilt. ICAI L5' ld ;64-! r rd 50{tr lrrin wrer, t00fl-fi I
ltu ](2hlo,lhl{0.0568
.f
0.1 rn) w.sld Srrat (CA)
!5e ldol- ld l0 oul(rsr w.trr, lm(I-cl )
Page l3
o
EEeEsmans
IEEE Gd.rc lbr Srl$y h AC $betsdm Grom4q
YES
SIEP 10
92
cogy(ight @ 2015 IEEE All rigttts Gsru.d.
Page l4
/(\
Ot
f_t
Rlting x/R llating X1R
MVA,i I fi \l\'\ 111 15.50
! \.l\',A l til \1 v.A lu 18.60 i
iii. IEEE-81:2012 - IEEE Guide for Measuring Soil Resistivity, Ground Impedance,
Page l5
2. MINIMUM CONDUCTOR SIZING CALCULATION
In an earthing system, the conductor should be able to withstand mechanical damages &
fusing temperafi.rre as per fault current magnitude. In this report, the minimum conductor
sizing calculation has been done using SES Ampacity Tool of CDEGS Software.
considering the RMS fault current, fault duration & decrement factor at 45oC ambient
temperature as per Pafrra location-
At 25 KA al LT and 17.5 KA at HT, RMS fault current, I sec for LT and 3sec for HT
frult duration and considering decrement factor as l, the minimum conductor sizing for
Copper Bonded Tensile Steel Material is as mentioned below-
Proposed Size
Referring table 2.1, considering the conductor size recommended in the tender that is
23 mm Copper Bonded Tensile Steel rods.
The corrosion allowance should be considered as per the soil resistivity value of the
location as mentioned in IS 3043:2018, Table 5. (Refer Figure. 2.1)
Revision No.: 01
Page l6
;,) t
t ;-l
@
Trblc 5 All,omrcca b CFors-i.cdoi.l Ar.. of rlc
Eerthl4 Corductor to tlke ttc Ellesl of
Corrorlot lDto Accou[t
(C/aase 13.6.1)
Hence, the considered sizes are 23mm dia., Copper Bonded Tensile Steel for Horizontal
conductor & Vertical Rod.
0
2.1 Ampacity X'unction report for Copper Bonded Tensile Steet Vertical Rod and
Horizontal Conductor
AmpaoU Functinn Report
CDEGS ConduaorAmpacrU Calculation (per IEEE Srandatd 80)
*_*-r-a_*_a t_*-*_l_*_a *_*_ta_r_*a r + a * * * + r rr*, i r * t t t * r * * * + a r * * * +a * * ++ *a it ir* r
^
Date: 71o7t2023
Time: 1l:15:57 pM
AnalysisFilename: 2o23-ot-orf144833
File Path: C:\Users\Public\Documenrs\SES Sofrware\My projects
Sl1storn d Units: Metric
Temperaturc UniS: cetsius
Corduclor Size Units: AWG
Input Data:
Fault Data:
Stage Symmetrical RMS Current (kA) Clearing Time (s) Decrernent Factor
ResistivityofConductoratReferenceTemperature: 10.1pe-cm
Fusing Temperature of Conductor: 1094 "C
Thermal Capacity per Unit Volume: 3.8 J/(cm3..C)
Computation Results:
Overall Asymmetrical RMS Current: 25.00 kA
359.471 MCM
182.103 mm2
0.2823 inz
Page l8
Ampacity Function Report
CDEGS Conductor Ampacity Calq.rlation (per IEEE Standard 80)
*_*_t_*_*_*_*_*_*_1_*_+_r_*-*_*_t_t_t_*_r_*_*_t_*_._r_*_*_r_t_a_*_*_r_*-*_*_+_+_*_*_*_r_a_*_*_* *_*_t_*_*-a_+_r_*_*_*-*_*_t_t_+_+_*_r_+_+_t_r_t_+_
Date: 71o712023
Time: 11:20:30 pM
AnalyeisFilename: 2o2to7-o7r144833
File Path: C:\Users\Public\Docurnents\SES SoftwareWy Projects
S)rst€m d Unils: Metric
Temperatre l,.hriE: cetsius
Con&rcbrSbeUnirs: Awc
* t * * *
* a r r * * r * * a * t a a r * * *r +t * * * *t t* r r * * * *a t a r * aa at r * * t
lnput Dab:
FaultDffi:
Stage Symmetrical RMS Current (kA) Clearing Time (s) Decrernent Factor
1 17.5 1
GompuEton Results:
OverallAsymmerical RMS Current: 17.50 kA
435.835 MCM
22O.788 mm2
0.3422 if
16.767 mm (Dianreter - Solid Conductor)
Page l9
iPA
3. DESIGN SIMULATION
The design &
calculation is based on 25 KA at LT and 17.5 KA at HT fault current at I
second at LT and 3 second at HT of fault duration time along with 50% of split factor. This
Section includes-
/ / / / / /
,/ / / / / / /
,/ ,/ I
'/'/'/'/ /
Page
Document: J MV/EAR/DMRC-MALA
l1O
H tP AKRV22-23/OO2 Revision No.:01
ffi
F.qg
3.3. Chronolory of Modelled Earthing Grid
i. The horizontal earthing grid conductor is made of Copper Bonded Tensile Steel
mderial. The diameter of the conductor is considered as 23 mm as per Section -2
ofthis report.
ii. The vertical earthing rods are of Copper Bonded Tensile Steel material. The
diameter of the vertical rods is considered as 23mm dia.
iii. The depth ofthe Earthing grid is considered as I meter from the road level.
iv. Grid Size is 24 x 9 meter.
v. Total 30 rods are used for earth mat
vi. The diameter of bore for Earth Enhmcement Compound in the pit is of 2COmm
with 3m length, which is 85Kg per pit. (For maintenance fue earthing system)
Page 111
3.5. Touch & Step Potential Criteria as per IS 3043:2018
The safety of a person depends on preventing the critical amount of shock energy from
being absorbed before the fault is cleared and the system de-energized. The maximum
driving voltage of any accidental circuit should not exceed the limits defined as follows
by IS 3043:2018.
g-=1flr+2.Rr)Ie
for body nr(gtrt of 50 kt
E:rlo=000O+6C!'"rff
fan O'"'
= (l Off) + 6C.
" A)
.tr-
Shilrly. de totrch vohege limir i;
Lr - r&+!tt
for body*Gipt of 50 kg
Eq=(l000+r.fc,^,o.19f
Vt'
for body utiglt of 70 kg
aatllrrdlclEhlllqrclflr.lr
fh rrltq ofr lErroo d.F.rdr fll
br&. nr ElL (kdt ilrl Er
Eftril {niae{ Gi.mdtc ltrir &frcd n ffiewr Fc*p rtrp fu kitt
E- =$r+ tl,l,
nn hf,ll.ldrE dfJ6 ft
f*=lrom+6r,, rliry
t,'.
tuMirocttd-otf
ts i R.r
=l lt.+i fl it
tubr-rrErg661qr15
E**=ll0frrrl f,.C)[#
{,
lc bulr rd$r uI Tll tg
rllcrt
f4 Eillg?frJhEv
fH Lllrr$iu:trtEhv
C, tr&mindfimFfm llmFgirr:n
a. n Arri:tivity drhssfucorcil ir0a
,. ir firfii3dlof rb* dEEt h6.ocdr
Document: JMV/EAR/DMRC-MALAH
ffi
lP AKRU2Z-23 lOOz Revision No.: O1
Page 113
QYI
3.8. Plot for Touch Potential at LT for 50Kg
Scak PoldIal6/T@dt
U)
d
IU
F
LU
=
a
=
x Axts (MEIERS)
Touch Voltage Magn. (Volts) [V1,brs]
Page 115
3.9. Plot for Touch Potential at LT for 70Kg
I-reE\D
Ilkimsn Vdrc: 1398.323
Mnim;mThe$old: 2@4252
6
t
I.IJ
F
lU
=
a 3.9
x
-6.2
-15 15
x Axts (METERS)
Touch Voltage Magn. (Volts) [V\brs]
(,
3.10. Ptot for Touch Potential at HT for 50Kg
LrcBD
ItibxirnrnVdue: 97E326
Mrimm Tlrs*pld : 1510.48
6
tr
u.,l
F
ul
=
a2
X
x AXts (METERS)
Touch Voltage Magn. (Volts) [Wors]
Page 117
3.11. Plot for Touch Potential at HT for 70Kg
I,.EED
23.7_
lukinrrn Vdup : 978.86
MrirnmTtre$old: M2Q.
13.7_
6
t
tu
F
lU
=
@ 3.8
x
-6.2
-15 -55 15
x AXrs (METERS)
Touch Voltage Magn. (Volts) [Worsl
Page 118
3.12. Plot for Step Potential at LT for 50Kg
scdsr Pol.ntBrr 6lop v ofl Esee (sptunc.llwoEr Sph.ic.i lD bcmenrl @ H0 @oo Hz l
LEGE\D
i,ibximrmVdrc: 322.E10
lVlninumTHpld: 5ffi.75
6
E
TU
F
ul
=
9 38
$.2
-5
x AXts (METERS)
SIep Vdtage.Worst iragn itude (Volts)
Page 119
3.13. Plot for Step Potential at LT for 70Kg
LfGE\D
lVhimrnValue: 2.810
lVInim,"rn Thm$ol d : Tl1O81
6
tr
UJ
F
UJ
E
o .!a
ee
x
x AXts (METERS)
Step Voltage-Worst Magnitude (Volts)
Page 120
3.14. Plot for Step Potential at HT for 50Kg
scdrPotd{latp vol.e.! 6p[dcll)rrrmt slhdcd 0oitu6dtt ct 50 o00 Rl
LEGA\D
IvhximunValue: 225.967
il[nim.rn Thn$dd : 5@5.75
a
t
ITJ
F
TU
=
u)
x
X AXIS O'iETERS)
Step VoltageWorst ltlagnitude (Volts)
Page 121
@
3.15. Plot for Step Potential at HT for 70Kg
LEiGE\D
G
tr
llJ
F
UJ
E
U)
x
-15
x Axts (METERS)
Step VoftageWorst lMagnitude (Volts)
Page 122 ,
@
3.16. Grid GPR and Grid Resistance
Table 3.3 shows the computed grid GPR and the computed gnd resistance (as
reported by SES Result Viewer). The obtained value of grid resistance is the
combined resistance value of Hoizontal earth mat conductor & Vertical earthing rod
of body pits. The frequency considered is 50 FIz :rs per power supply frequency in
India.
Page 123
4. CONCLUSION
JMV LPS Limited has done the calculation of Earth Mat at simulation & validation
' for
Malahi Pakri Metro Station, Patna. JMV has assigned to do the earthing design
Substation, Patna.
. The end customer is Dethi Metro Rail Corporation
The design & analysis are based on the total fautt curent of 25 KA at LT
' and 17.5 KA
at HT for 1 second at LT and 3 second at HT in the Matahi pakri Metro station,
Patna.
The maximum step & touch voltages have been calculated as per below mentioned
'
data:
Applicable Code IEEE 90:2013
Body weight 70kg(Reference
from tEEE-80-2o13, Ctause-8.4)
Body resistance 1(80 ohm (Reference from tEEE-8o-7013, Clause_
7.1)
Frequency 50 Hz
X/R Ratio 5.79 (for transformer 37000KVA x/R rotio is 5.79, As
per IEC 60076-5, Clouse_4.2.3.) (refer figure 1.3)
Duration
Fault L sec for LT and 3 sec for HT
Mother soil Resistivity 25.9 ohm-m (Refer appendix D from sRT Repon,
Locotion I D: MT-1989_0j )
surface layer Material Resistivity 1o,ooo ohm-m (Refer flgure 1.1, As per tEEE_80_
2013, Toble 7)
Maximum Grid current, lc 13.15 KA at LT and 9.205 KA at HT (tc = Dr x sr x
lrl (As per 1EEE 80-20L3, Ctouse-i.i.9 (Eq.-3) and
Ctouse-3.27 (Eq.-4))
Maximum Fault Curren! Tr 25 KA at LT and 17.5 KA at HT (reference lrom
the calculation provided by AECOM)
Decrement Factor, Df L.OS2 (reference from tEEE-g0_2013, Ctquse_75.10
(Tobte-70))
o Values Achieved after Simulation are mentioned below:
Earth Grid Resistance, Rg 0.59 ohms
Ground potential Rise,
GpR 7466.776 v at LT and 5226.743 v at HT
Tolerable Touch potentiat 2o44.2szv for 70r(g and 1510.2o3 V for 50Kg
calculated Touch potential 1399.323 v at [T and 97g.g26 v at HT
Tolerable step potentiat 77Lo.zgLV for 70Kg and s696.775 v for 50Kg
calculated step potential Szz.ghov at LT and225.961v at HT
Page 124
Minimum Conductor Size
Calculated as per IEEE 15%
Proposed Size
80:2013 using CDEGS Corrosion
Software Allowance
Sl. No. Conductor Descriotion
' Rod =
Rod = Diameter
(mm) Lross- Lross- Diameter Cross-
strip = yyxl
section' sq section' sq (mm) Section, sq
(mm) mm mm Strip = 1ryx1 mm
(mm)
Earth Mat Horizontal
-r Conductor(Copper
15.27 182.103 209.47845 23 475.265
Bonded Tensile Steel
Rod) at tT
Vertical Rod (Copper
2 Bonded TensileSteel 't5.27 182.103 209.47845 23 475.265
Rod) at LT
Earth Mat Horizontal
Conductor (Copper
^
5 16.767 220.788 253-9062 23 475.265
Bonded TensileSteel
Rod) at HT
Vertical Rod (Copper
4 Bonded TensileSteel 16.767 220.788 253.9062 23 475.265
Rod) at HT
Toble 4.7 Ampocity Colculotion (Refer Section - i'Iot detoiled report)
(E
Appendix A- Grid Impedance Report
AT LT:
DATE OF RUN (Start): DAY 18 / Month I / Yeat 2023
STARTING TIME: 0:09:30:12
Case Nurnber 1
Ereguency for This ;;;;:::: :::::: :::::: :::::; 50-000 Hertz
GPR of Reference Sou.rce Bus (# 1) . . . -Magn. . : '1466 .116 Vo1ts
Angle. : O-16736'12 degrees
Impedance of Grounding System- -Magn..: o.597342L Ohms
Angle.: o- L67361 2 degrees
Revision No.;01
Page 125
@
AT HT:
DATE OE RUN (start): DAY 18 / Month 8 / Year 2023
STARTING TIME: O:2L:O8:.44
Page 127
Appendix B - CDEGS Safety Threshold Report for
Maximum Acceptable Touch and Step Voltages-s0kg
(Reference from IEEE-80)
AT LT:
Report #2:
Site Data
Surface Layer Thickness .. ( m ) 0. 15000
Surface Layer Resistivlty.. - -. ..... (Ohm-m) 10000.
Sub-Surface Layer Resistivity-.... . (Ohm-m) 25.989
Eoot Resistance Calculation Method- IEEE
srd.80-2013
Computed Eoot Resistance- .... ( Ohn per foot ) 24280.
User Defined Footwear Resistance. -....... ( Ohm per foot ) 0.0000
User Defined Glowes Resistance ..... ( ohm per hand ) 0.0000
Human Data
Page l!X)
Computed Decrement Factor. 7 .0092
Site Data
Surface Layer Thlckness .. ( m ) 0.15000
Surface Layer Resistivity.... (Ohm-m) 10000.
Sub-Surface Layer Reslstivity.... . " (Ohm-m) 25.989
Foot Resistance Calcul-ation Method IEEE
srd. B 0-2073
Computed Foot Resistance ..... ( Ohm per foot ) 24280 .
User Defined Footwear Resistance... ( Ohm per foot ) 0.0000
User Defined Gloves Resistance ..... ( Ohm per hand ) 0.0000
Human Data
End of Report #1
AT LT:
Report #3:
Page 132
Main Computation Standard-
srd- 80-2013 : TEEE
Netl^rork Specificatlons
System Frequency.
Shock Duration.. 50-000
X/R Ratio ... (Seconds) : 1.0000
Computed Decrement Eactor. .-....-.-: 5.7900
7.0092
Si-te Data
Surface trayer Thickness
Surface trayer Resistiwity.. -.. .. ( m ): 0.15000
Sub-Surface Layer Resistivlty-.. .. - -. (Ohm_m) : 10000.
-.
Eoot Resistance Cal-cul-ation iethod- . (Ohm_m) : 25 .989
srd.B0-2013 - .-.-.-: rEEE
Computed Foot Resistance. -
User Defined Footurea; ;;;i";;;;;:::::::- 24280 -
User Defined Glowes Resistance - I 3H ff: f::: i ; 0.0000
..... ( Ohm per hand ) : 0.0000
Hr.man Data
Page 133
,(\
!)/
AT HT:
Report #3:
Network Specifications
system Frequency. (Hertz) : 50- oo0
Shock Duration. (Seconds): 1.0000
x/R Ratio- ........: 5.7900
Computed Decrement Eactor. l-0092
Site Data
Surface Layer Thickness .. ( m ): 0.15000
Surface Layer Resistivity- -... -. - - - (Ohm_m) : 10000.
Sub-Surface Laye-r Resistiwity..... .(Ohm_m): 25.9g9
Foot Resistance Calcufation Method. .: IEEE
srd.80-2013
computed Eoot Resistance- .... ( ohm per foot ) : 24280-
user Defined Footwear Resistance.--.--.--( ohmper foot ): 0.0000
user Defined Glowes Resistance - -. - - ( ohm per hand ) : 0-0000
Hlxnan Data
Page l!14
x/R Ratio 5 .7900
Computed Decrement Eactor. 7 -OO92
Site Data
Surface Layer Thickness .-( m ): 0- 15000
Surface Layer Resistiwity..... . .. - - (Ohm_m) : 10000.
Sub-Surface Layer Resistiwj_ty.. ... . (Ohm_m) : 25.989
Eoot Resistance Calculation Method. IEEE
std- 80-2013
Computed Eoot Resistance . -... ( Ohm per foot 24280
): -
User Defined Footwear Resistance...... - - - ( Ohm per foot ): 0.0000
User Defined Gfoves Resistance .... - ( Ohm per hand 0. 0000
):
Human Data
End of Report #3
Page 135
Appendix C- SoiI Resistivity Report
Page f 35
SHREENATH SOIL AND MATERIAL TESTIilG LABORATORY
DESIGN VERIFI
ELECTRICAL AND MECHANICAL SYSTEMS, FIRE DETECTION,
FIRE SUPPRESSION SYSTEM AND DG SETS
R-l AND CORRIDOR-2 ELEVATED STATIONS AND DEPOT PE-02,
PATNA METRO RAIL PROJECT.
50.00
40.00
E
E
h 30.@
d
4
20.00
d
4
o lo.oo
0.00
0
-10.00
SPACIT'IG BETWEEN ELECTRODES
Note: l Division=5O.m
GONTRACT: PE-02
... )r.t"'
I t-
Ilr
,{
i
1,
i!1
x
I
I
!
!:
t
t'
--
-
Earth Mat Report, for Malahi Pakri Metro Station
August 2023
Prepared By
GPR
Ground Potential Rise, 6791.251V at tT and 4758.076 V at HT
Tolerable Touch Potential 2o52.o1-2v for 70Kg and 151G.137 v for 50Kg
Page l1
H
I}
r. INTRODUCTION
1.1 Purpose
The purpose of this analysis report is to determine the grounding system design
parameters to meet design criteria of Malahi Pakri Metro Station, Patna for
DMRC.
i. Ambient Temperature:45oC
ii. Duration of fault current: I sec for LT and 3 sec for HT.
iii. Shock duration: I sec
iv. Uniform Soil Resistivity has been evaluated as per polar curve method in the SRT
report (Refer appendix Dfor details)
Page l2
1.4 Software Module Used
i. SESCAD Tool-CDEGS Softwarc
ii. SES Ampacity Tool -CDEGS Software
iii. MALZ module
iv. SES Result Viewer
I 14 !r) g,lEh.r
i6 (O.Oa ,uq !]uilr
(GA)rtttlhg
1 '/. irr,ol h t0.o2 E b O.0j!5 D) 651! (l0 oratc.dl.r a50,6
trxrE ICA) r|lt tber rd.rdrai.cd)
t{o.4(l Dlo!hf (00!job
{
0lrJ m) nrutcd (GAf 1.5 i ld io4 J, ld 5(xD (rrin ertr" lm O-m )
t'anr
, l,lo, I
(2 5 to 4 tr) l0lN h b
oI rtlf,at dfuE(GA) 2.6
' ldroS' ld li)(ftlfililn !rJlfl lltll!-nr I
Page l3 -,-
EEEST' 8GMI3
IEEE Gdd. br SlHy'hAC $.6ottlion OoundirE
Y€S
\ slEP 10
92
Copynght O 2015 IEEE All nght6 rsorvod
Page l4 is-
Rlling xrR Raling \lil
MV,'\:. I g. MVA -.. l0 15.50
i \l\,\ l | 0 \l \'.\ ltt r8 60
I \t\\ I 4.67 l() \1\;.\ l0
i \1\"{ . I l4t itt \1 \\ ltr
4". MVA 1_i itt \l\\ ltt Ir, {tl
i \1\,,\ . 6 lEi 50 <i MVA 1 t00 14 t0
3.55 100 < MVn: lfi)
f \1".\ li -10{r \l\':\ la)t)()
iii. IEEE-81:2012 - IEEE Guide for Measuring Soil Resistivity, Ground Impedance,
@
2. MINIMUM CONDUCTOR SIZING CALCULATION
In an earthing system, the conductor should be able to withstand mechanical damages &
fusing temperafure as per fault current magnitude. In this report, the minimum conductor
sizing calculation has been done using SES Ampacity Tool of GDEGS Software,
considering the RMS fault curren! fault duration & decrement factor at 45"C ambient
temperature as per Patna location.
At 25 KA at LT and 17.5 KA at HT, RMS fault currenf I sec for LT and 3sec for HT
fault duration and considering decrement factor as l, the minimum conductor sizing for
Copper Bonded Tensile Steel Material is as mentioned below-
Referring table 2.1, considering the conductor size recommended in the tender that is
23 mm Copper Bonded Tensile Steel rods.
The corrosion allowance should be considered as per the soil resistivity value of the
location as mentioned in IS 3043:2018, Table 5. (Refer Figure. 2.1)
@
Ieble S Allortlco h Cnoss!.ctlold Atle of ihc
Errlhllg Cordrctor lo hke the Elfect of
Corrod,or l.to .{ccooDl
((-/orse I3.6.I)
As per CDEGS Calculation soil resistivity considered, lsyo corrosion allowance (reference
from IS 3043:2018, Table 5) has been considered on minimum conductor size achieved by
the calculation through CDEGS software. But as per technical specification the considered
size is 23 mm dia. Copper Bonded Tensile Steel.
Hence, the considered sizes are 23mm dia., Copper Bonded Tensile Steel for Horizontal
conductor & Vertical Rod.
Page l7 ,
2.1 Ampacity Function report for Copper Bonded Tensile Steel Vertical Rod and
Ilorizontal Conductor
Ampacip Function Report
CDEGS ConductorAmpacity Calq.rlation (per IEEE Standard 80)
t_t_t_t_t_a_a_t_t_t_t_r_t_r_r_r_r_t_r_t_r_r_r_a_r_r-*_r_t-r_t_r_r_r_l_r_t l_r_r_r_t_t_i-*_r_r_t_t_r_a_r_r_ t_*_t_t_t_t_
Date: 7t07t2023
Time: 11:15:57 pM
Analysis Fifename: 2O23-O7-o7r144833
File Path: C:\Users\Public\Documents\SES Sofrware\My Projecrs
System of Units: Metric
Temperature Units: Cetsius
Conductor Size Units: AWG
lnput Data:
Temperature:
Ambient 45.00 'C
Temperature:
Maximum Allowable 1084 "C
ConductorType: Copper-clad steel core tcd(1l%o conductivity)
Fauh Data:
Stage Symmetrical RMS Cunent (kA) Clearing Time (s) Decrement Factor
125 11
Material Constants of Conductor:
Temperature:
Resistivity of Conductor at Reference 10.1 gQ-cm
Computation Resutts:
Overall Asymmetrical RMS Current: 25.00 kA
359.471 MCM
182.103 mrn2
0.2823 in2
@
Ampacity Function Report
CDEGS ConductorAmpacity Calculation (per IEEE Standard 80)
Date: 7t07t2023
Time: 11:20:30 pM
AnalysisFilename: 2023-o74ir144l3s
File Path: C:\Users\Public\Documents\SES Sofrware\My projects
System of Units: Metric
Temperature Units: Cetsius
Conductor Size Units: AWG
lnput Data:
Ambient Temperature: 45.00 "C
Temperature:
Maximum Allowable 10M "C
ConduAor Type: Copper-clad steel core rod (17o/o conductivity)
Fault Data:
Stage Symmetrical RMS Cunent (kA) Clearing Time (s) Decrement Factor
'l 17.5 3 1
Computation Results:
435.835 MCM
22O.788 mmF
0.M22 in"
16.767 mm (Diameter - Solid Conductor)
@
3.3. Chronology of Modelled Earthing Grid
i. The horizontal earthing grid conductor is made of Copper Bonded Tensile Steel
material. The diameter of the conductor is considered as 23 mm as per Section -2
of this report.
ii. The vertical earthing rods are of Copper Bonded Tensile Steel material. The
diameter of the vertical rods is considered as 23mm dia.
iii. The depth of the Earthing grid is considered as I meter from the road level.
iv. Grid Size is 24 x 6 meter.
v. Total l0 rods are used for earth mat.
vi. The diameter of bore for Earth Enhancement Compound in the pit is of 200mm
with 3m length, which is 85Kg per pit. (For maintenance free earthing system)
@
3.5. Touch & Step Potential Criteria as per IS 3043:2018
The safety of a person depends on preventing the critical amount of shock energy from
being absorbed before the fault is cleared and the system de-energized. The maximum
driving voltage of any accidental circuit should not exceed the limits defined as follows
by IS 3043:2018.
Ea=(Rs+2Rt)It
for body {,EilDi of 50 kt
E+to=(10O0+6C',rrff
E* = (.b++)6
for body lreipt of 50 kg
o'J;6
E** = (l 0oo + l.sc, , A)
@
3.6. Touch & Step Potential Criteria as per IEEE 80:2013
The step & touch potential criteria adopted in this report
& for the simulation is as per
internationally adopted code i.e., IEEE 80:20 I 3.
fn Dorfy Et!ts o, q, tf
@
3.7. Maximum Calculated & Tolerable Touch & Step Potential
Since, calculated values of Step & touch potential obtained are within the tolerable
limits. Ifence, the design is safe to install.
Page 114 ./
3.8. Plot for Touch Potential at LT for 50Kg
LEGBD
-10
-15
x Axts (METERS)
Touch Voltage Magn. (Volts) [Wors]
LEGE\D
MaximumValue: 12433f'7
Minimum Thre$dd : 2f,52 O12
10
G
x.
uJ
F
tu
=0
@
x
-10
-15
x AXts (METERS)
Touch Voltage Magn. (Votts) [Wors]
Page 115
3.10. Plot for Touch Potential at HT for 50Kg
ScdrPderiid6,/T@hVdqsfitb6tSptEi€t ltDoocwsil @t{mO &1
LECE\D
l\rhxim.rn\ldr.rc : 870.357
MnimmTlyerhdd :'1516.137
10
6
E.
tU
F
tu
3
9.0
x
-10
-15 -55 15
x AXrs (METERS)
Touch Voltage Magn. (Volts) [Wors]
Page 117
@
3.11. PIot for Touch Potential at HT for 70Kg
Scdar Pddids/Tdrcfi Vd@€/'/Vdst Shgicd [OtbcuMl @ fdo 0O()o tt I
LEGEI\D
-10
-15
x AXts (METERS)
Touch Voltage Magn. (Volts) [Wors]
Page 118
@
3.12. Plot for Step Potential at LT for 50Kg
LrcE\D
f\ibximumValue : 245.781
tVlinimum Thrc$dd: 5719 709
-10
-15
xAxts (METERS)
Step Volhge-Worst tttl4nitude (Volts)
LEGB\D
6
E,
tu
F
UI
=
a
?U
-10
-15
x AXts (METERS)
Step VoltageWorst Magnitude (Volts)
Page 120
3.14. Plot for Step Potential at IIT for 50Kg
LreE\D
wbimum \6lue: 172 047
Minirnum ThE$dd: 57'19 709
-10
-15
x AXts (METERS)
Step VoltageWorst Magnitude (Volts)
Page 121
3.15. PIot for Step Potential at IIT for 70Kg
[.rcIl}\D
lvbximrn Vdue : 172.047
tuinimun Tile$d d : T7 41.332
-10
-15
x AXts (METERS)
Step Vottag+Worst Magnitude (Volts)
Page 122
3.16. Grid GPR and Grid Resistance
Table 3.3 shows the computed grrd GPR and the computed grid r,esistance (as
reported by SES Result Viewer). The obtained value of grid resistance is the
combined resistance value of Horizontal earth mat conductor & Vertical earthing rod
of body pits. The frequency considered is 50 Hz as per power supply frequency in
India.
Page 123
@
4. CONCLUSION
o JMV tPs Umited has done the calculation of Earth Mat at simulation
& validation for
Malahi Pakri Metro station, Patna. JMV has assigned to do the earthing
design
Substation, patna.
o The end customer is Delhi Metro Rail Corporation
The design & analysis are based on the total fault current
' of 25 KA at LT and 17.5 KA
at HT for 1 second at LT and 3 second at HT in the Malahi pakri
Metro Station,
Patna.
o The maximum step & touch voltages have been calculated as per
betow mentioned
data:
Applicable Code IEEE 80:2013
Body weight Okg
7 (R efe re nce fro m t E E E-BO-2 0 7 3, C I o u se-g.4 )
Body resistance 10fi) ohm (Reference from IEEE-80-1013, Clouse_
7.1)
Frequency 50 Hz
X/R Ratio 5.79 (for tronsformer _<7xOOKVA X/R rotio is 5.79, As
per tEC 60076-5, Clouse_4.2.j.) (refer 1.j)
figure
Duration
Fault 1 sec for tT and 3 sec for HT
Mother Soil Resistivity 25.9 ohm-m (Refer oppendix D from SRT Report,
Locoti on
D MT_1999_03 )
I :
Page 124
Minimum Conductor Size
Calculated as per IEEE t5%
80:2013 using CDEGS Corrosion Proposed Size
Software Allowance
Sl. No. Conductor Description
Rod = Diameter Rod =
(mm) Cross- Cross- Diameter Cross_
StriP = 11YrT
Section, sq Section, sq (mm) Section, sq
(mm) mm mm Strip = 17ty*1 mm
(mm)
Earth Mat Horizontal
Conductor (Copper
Bonded Tensile Steel 15.227 182.103 209.41845 23 475.265
Rod) at tT
Vertical Rod (Copper
Bonded Tensile Steel 15.227 182.103 209.47845 23 41,5.26s
Rod) at tT
Earth Mat Horizontal
Conductor (Copper
Bonded Tensile Steel
'16.767
220.7U 253.9062 23 475.265
Rod) at HT
Vertical Rod (Copper
Bonded Tensile Steel 16.767 220.788 253.9062 23 475.265
Rod) at HT
Table 4.7 Ampocity Colculotion (Refer Section _ j for detoited report)
Oogrlment:tnAV/feR@
Page 125
Appendix A- Grid Impedance Report
AT LT:
DATE oE RUN (Start): DAy 19 / uonth 8 / year
STARTING TIME: 8:54:41:69
2023
0.500
Hertz
IIertz
Finite VoLmes: 1O
1 VOIUME: EEC
SOTL PARAMETERS:
Resistivity..... . -..... : 0. 120000
NUMBER OF SPECIETED SUREACE EIEMENTS: ohm-meters
0
2 VOLUME: EEC
SOIL PARAMETERS:
Resistivity. ........... : 0. 120000
NUMBER OF SPECIFIED SUREACE ELEMENTS: ohn-meters
0
3 VOLUME: EEC
SOIL PARAMETERS:
Resistivity............ : 120000
NUMBER OF SPECIETED SURFACE EIEMENTS:
0- ohm-meters
0
4 VOLUME: EEC
SOIL PARAMETERS:
Resistivity. ...........: 0. 120000
NUMBER OF SPECIFIED SURFACE ELEMENTS: ohm-meters
0
5 VOLUME: EEC
SOIL PARAMETERS:
Resistivity .....: 0. 120000
NUMBER OE SPECIFTED SURFACE ELEMENTS: ohm-meters
0
6 VOLUME: EEC
Page 125
@
SOTL PARAMETERS:
Resistivity. ........... : 0.120000
NUMBER OF SPECIFIED SURFACE ELEMENTS: ohm-meters
0
7 VOLUME: EEC
SOII PARAMETERS:
Resistivity......... _.. : 0. l-20000 ohm-meters
NUMBER OF SPECTETED SURFACE EIEMENTS:
0
8 VOLUME: EEC
SOIL PARAMETERS:
Resistivity. ........... : 0. 120000 ohm-meters
NUMBER OF SPECIFIED SUREACE EIEMENTS:
0
9 VOIUME: EEC
SOTI PARAMETERS:
Resistivity ............ : 0.120000 otun-meters
NUMBER OF SPECIETED SUREACE ELEMENTS:
0
10 VOLUME: EEC
SOIL PARAMETERS:
Resistivity. ........... : 0.120000
NUMBER OE SPECIFIED SURFACE EIEMENTS: ohm-met ers
0
Case Number
1
Erequency for rhis C;;;::::. ::::. :::: :.: ::::;
50.000 Hertz
GPR of Reference Source Bus (# 1) ....Maqn. .: 6197.257 VO.ItS
Angle.: 0.7126146 degrees
fmpedance of Grounding System. .Magn..: 0. 5437801 Ohrns
Ang.Ie. : o. L126746 degrees
Page 127
@
AT HT:
0.500
Ilertz
IIertz
1 VOLUME: EEC
SOIL PARAMETERS:
Resistivity -....: 0.120000 olm-meters
NUMBER OE SPECIEIED SUREACE ELEMENTS: O
2 VOLUME: EEc
SOII PARAMETERS:
Resistivity......-.....: 0.120000 ohm-meters
NUMBER OF SPECIEIED SURFACE EIEMENTS:
O
3 VOIUME: EEC
SOIL PARAMETERS:
Resistivity.....-......: 0.120000 ohn-meters
NUMBER OF SPECIFIED SURFACE ELEMENTS:
O
4 VOLUME: EEC
SOIT PARAMETERS:
Resistivity. ........... : 0.120000 ohm-meters
NUMBER OE SPECIETED SURFACE EI,EMENTS:
0
5 VOIUME: EEC
SOIL PARAMETERS:
Resistivity . -...: 0.120000 ohm-meters
NUMBER OF SPECIEIED SURFACE EIEMENTS:
0
5 VOLUI']E: EEC
SOTL PARAMETERS:
Resistivity. ..,........ : 0. 120000 ohm-meters
NUMBER OF SPECIFIED SUREACE EIEMENTS:
0
@
Appendix B - CDBGS Safety Threshold Report for
Maximum Acceptable Touch and Step Voltages-s0kg
(Reference from IEEE-8O)
AT LT:
Report #1:
Page li30
Main Computation Standard. ,.. , .: IEEE
srd. B0-2013
Network Specifications
System Frequency. (Hertz): 50-000
Shock Duratj-on - (Seconds): 1-0000
x/RRatio ...------: 5.Z9OO
Computed Decrement Factor. - - -.......: 1,-0092
Site Data
Surface Layer Thickness .. ( m ): 0.15240
Surface Layer Resistivity.. .. . .. . .. (Ohm-m) : 10000-
Sub-Surface Layer Resistivity..... . (Ohm-n) : 25-989
Foot Resi-stance Calcul-ation Method. .: IEEE
std- 80-2013
Computed Foot Resistance. -... ( Ohm per foot z 2438O.
User Defined Eootwear Resistance-........ ( Ohm per foot : 0.0000
User Defined Gloves Resistance -.... ( Ohm per hand : 0-0000
Human Data
End of Report #1
Page 131
AT HT:
Report *3:
Site Data
Surface Layer Thickness ,. ( n ): 0.15240
Surface Layer Resistivity-... (Ohm-rn): 10000-
Sub-Surface Layer Resistivity,. -. .. (Ohm-m) .- 25.989
Eoot Resistance Calculation Method- .: IEEE
std- 80-2013
Computed Foot Resistance .-..-( Ohmper foot ): 24390.
user Defined Eootwear Resistance.-.--....( ohmper foot ): 0.0000
User Defined Gloves Resistance - -... ( Ohm per hand ): 0-0000
Human Data
Page 132
Computed Decrement pactor .---: 7.OO92
Site Data
Surface Layer Thickness ., ( m ): 0,15240
Surface Layer Resistivity.. - -. .- -.. (Ohm_m) : 10000.
Sub-Surface Layer Resistivity.. -.. . (Ohm_m) : 25.989
Foot Resistance Calculation Method. . . - -.. -: IEEE
srd. B0-2013
Computed Foot Resistance ., . -. ( ohm per foot ) : 24380.
User Defined Footwear Resistance......... ( Ohm per foot ) : 0.0000
User Defi-ned Gloves Resistance -. -. - ( Ohm per hand ) : 0.0000
Human Data
Page 133
Appendix c- CDEGS safety Threshold Report for Maximum
Acceptable Touch and step voltages-T0kg (Reference from
rEEE-80)
AT LT:
Report fl2:
Page l!14
Main Computation Standard ..: IEEE
std- B0-2013
Network Specifications
System Frequency 50.000
Shock Duration .. -. . (Seconds) : 1.0000
x/R Ratio 5.7900
Computed Decrement Factor 1.0092
Site Data
Surface Layer Thickness .-( m ): 0.15240
Surface Layer Resistivity-... . ..... (Ohm_m): 10000.
Sub-Surface Layer Resistivity. -.. ,. (Ohm_rn) : 25.989
Foot Resistance Ca]culation Method. . .. ... -: rEEE
srd.80-2013
Computed Foot Resistance .. ... ( Ohm per foot 24380.
):
User Defined Footwear Resistance-..... . - - ( Ohm per foot ): 0.0000
User Defined Gl-oves Resistance .... - ( Ohm per hand ): 0.0000
Hrman Data
Page 135
AT HT:
Report *1:
Page 136
x/R Ratio ...... -, -: 5-7900
Computed Decrement Factor. -..... --- -: \.0092
Site Data
Page !37
Appendix C- SoiI Resistivity Report
Page l!18
i'
@
SHREE]IAIH SOII A]ID ITATERIAL TESTIIIG LABORATORY
Locatim lD xT-t9t9_3 Te*hg lhilr 210tm23
Pdect llarn€ DESIGN I/ER]FICATION, DETAIT ENGINEMIilG, S'PPLY, INSTAI-LATION, IESTIilG & COMMISSIOilII{G OI
ELECTRICAL AND MECHAMCAL SYSTEUS, FIRE I}ETECNON, FIRE SI'PPRESS$N SYSTEI1 AND DG SETS OT
CORRIDOR.I AND CORfilDOR.2 ELEVAIED STATIO}IS AND DEPOT PE{T2, PATM METRO RAIL PROJECT,
I 1
1.5 6.35 39.90 8.34 Ea f,n 6.38 44.05 5.16 32.42
2 2 3.0 't 42 17.U 2.27 28.53 1.48 18.60 2.02 2s 38
3 4.5 4.12 2.26 'l.M 1 9.60
4 5 7.5
lrear Resistiyily
28.87 40.{6 20.32 25.80
P (o'm)
l{ote: UQL = Upper Qualifying Umit
l&fllihbd +sstil€ac
-so{|tswe.i
=
?
F
z
Note: l Division=5O-m
@
fl 4 EL
GRID CAI.CUIATK'H
TAOTEOf CqWUr
S.ia Dsi]tim
I Ctrsideratifl
2 Eathint Grid Ctlculirtion
3 Result
cm*larin taErrl[atc:bfri(n
5,llo
A ob*EdE
1 To detemire the no. of Rod ftr €.thirg sfstem.
2 To detemiE the size of main €rth glid orductor.
I To @kuhte arth mat ara.
.l To d6Gn cEll EBtire of ttE earthiig sl5tem-
8. Fadil.qdDetaih
f fhe follouitrgfauh leels atl3 kv is @Eidercdfor@kulatio:-
voltagel-qd(l(vl radtCutut(XA) rmFl
& lc oducfor sizirg o.415 E I
C naftrtlr!
I rEEE'
2 E:at*l
D. BIntDat
f Pffediltrdl Ebttrdty SdfEt{,rryfirrr{)
@nirdgdfErErH rE&matd jtep& !o$dt pdentidl_ 259{!t
s.f,c TFUTPAAAflEIES
t-r{
dirnD
*L-=rr-
Total peripheEl lflgth of grid cooductor
Material onstant (Table2 tEEE-t(}.2Ol:tl
A
l!-
where
I is the nns cumt in kA
Arrm2 is the @rductr oo$ sedio in mm2
Tm isth€ mimum alloraue t€mpeEturc in rc
Ta is the ambitrt tmperature in t
IT istfE dsmloeffiderrt of si*ryity at r*rgE tril?Enm Tr in lrl:C
9r b dre Eisfn ity of dE grolltd @ndEtDr at reierere tenpratrre Tr in UO-o[
Xo lolrc or ({o} - Tr in rC
tc is t E duratim of unmt itr s
TCAP is the themal oprity ps unit rclure frcm TaHe ! in /(cm3':Cl
-_ 5,,rz2lB v
Gemetric factor
n": 2-L-
-;
na = 3anflE2
trb:f4 -
^J4 J4
nb = ,-Gffi7
rc = 1 FrsqErc&lwErEle8id
nd = 1 FcsSJarE&EGErElegrU
n = ie 'l\'lls. Ei
n = Lo4,fr.
= OsffiZ
= O769532
= 74{E-!Il2 v
PEmtsabae tMh vdr{E ir itXE body rdght Ea...n= r lfiD+ I 5C,p,{ li, at,
= 1963'21a v
= l.212El
Totd lgBth oftrcuod .Dds li = nRIl, m
=3Om
= A{5.56,r V
carcrtra'ridortorelidEdt'try *, = ***ftr-o-s"-.1]
*[+
= O.IEDI
s.rpvotae. ,, = OrI##
= 5:D.5961 V
n0
RESUTT
I <1 o
2 hlorlated R€sistsE of Grid 0.434581017 o
I Ground Potential Rise
1 <25 xA
akdarEd symmfri(d er*, farrt drrrent t25 rA
2 <m Rv
5 4322527L5 xv
(n E
rn (n (n E o
d.
E E E o0 o0
o
z rn rn
o rn
f o)
N
rn
@
Io o
G =C E E
rn
sf
6l
st
ot
sf
rn o (\
CN
E N rl @
-o =
E E rl
o e cn Cfi
(\t CN oo
q o e
a tft
a7
8o o
rJ o o +
6
OL
ok F-
zl'J
oo zEI
LJ
jo Irl +
oo
9d
fto-
e=
{r (n (n o
o
E
C
L
o
.lt
(U
Y= N f
3,5 !r- N
o E =f
oo ZE,
ur< o- C o
Or-
zz E f
IJI o o -C
E
ITU - (J o 3
t8 D,Z C E
o E
z i-
ltl
(l)
E
o
L)
E
c
:,
o
-z u- (J o o-
UJ
-F
o E .=
o o- -c
L
(o E
(l)
E
o
z v,
L
(l, G, r+ c
trl
(J
c U
E.
[U
o (u
tts
o o s
o L
(D
-c
C
C
o
E
kJ (o
L
(o : E E
CJ
E
f lrl
(U IJ
.C
+,
E
(u
(J
f(J o- E =
o o I g g
E o E (o (o
J
o
OE
E, o IJ.J
c
o E= IJ
L' o L
.(o
o _9 E,
-c o)
.= iE rts L
(o
a0 (u o- E o rrl
c E o-
o v_
J .(o
o o v,
C
o
E
f
oo) .P
.F
o c(U
f
d
o
lU
=F
@=
q?J
1u)
q?tL
SJ
-
!,
o
c
.9
c
o
.9
E s
C o-
'=
i: (
\ & h
.9
v(l, 0 lq V
L
(l,
-D
(U
o-
E o CL
E'
o, o
o
E
o E E
=3 E oo
co oo
c
ro
* .;c
E o o
sf
(E
o (o
E
L
EO
ll E' E'
o c(!bb (,
-g t(J
3 0,c E
o
C
P
l!
(5
'a=
O- .-
C1
J E ooL
C' E
o o et, ol
=l
o -c
L)
-.c
ql I
lt (o
ES .loJl
!
6
(g
P
E
9: .I,
aJl
rtl
o
CL
o
o tu@
o-
9u E
-l
(ol
-cl
_t E
EI E
E(l) o t o ot cl
o 0) -9 al (l)
5la (J
!
C)
CL
(o
E- ol ! (J
o sl5
(l,
P
CL (E
o =El
EEI E o-l
ol P(E
c,
F <lu o
lJ-
= o-l
z ln .=l o
(J il
IJJ '(o
@ T' o
c, (U
= tjc,
o -9 lg
o-
zF l
(!
q
I
o
F
6
o o
(J
(lJ
l
o- CL -o
dl E o
L o E
o
(J
o-
L o! o-
ol
=l -,c
o =
'6 '=
P
=B d0) E'
to C
3l s.= =
o
= s
=
o L
(u
E
o 6
o o
)
sl
*l 3
.9
C
CL
CL
o- o.
o
o E
ol
=l !
c
.=
o
.o u =q
6 L
CL o
o <lr IJ C)
lto Pc
(o I
c .=l'tr .9
o,
o.
o ..!
'6 3l o!
!
! E
c E o c,
.c .9
o-
o0
C
Elt
olo E= .C
L
o L
o
q
c
o
E
E
(6
.=
E
o
(J
o =lo
'=l€
9lL .=
0.,
xoo
I
-o
(E .E Rd E (o
o ! c
E
Fo o
(t)
.-l L (u E -:
'1 o
Ll9 -o o c(! N6 L s
c v
fls o
-o
o
=
.9 E
o 'a
CL
o N=
EU
a t(E
o o
EIE o
(E
o L r(l,
6lL d3 c o
o E c
.C:
o)
P
(,
b0
zo (,
cl .oc
El# 6
(E
(l,
() (l,oh(J dro ot
-lc
olo E JE
I (E
6 ru (O Orl bol
9lo o E o @cn cl .E
We JMV LPS Limited registered office at W-50, Sector-ll, Noida-201301, U.P. do hereby
declare that in the project "Elevated Stations of Corridor-l and Corridor-2 andDepot of Patna
Metro Rail Project" the UL testing is under process for the exothermic joint and the UL
certificate will be submitted by October month.
@
)MVl23-24luLoot
23/Os/2023
PUBCHASE ORDER
Email: Raza.Ahmad@ul.com
quote Number: 1102378566
Subject: Offer for CUt US of Solid Cu rods wlth Erothermic weld Joints: 4 Models, Cu Bonded rods with exo
Joints: 3 models and Solid Cu Rods: 6 Models
Dear Sir,
We thank you very much for showing your interest in our products. As per your requirement following is our
Purchase order :
Commercial Offer:
5.No. Product/Services Quoted Unit Unit Price (in Rs)
Account No.:1683043
File no: E359515
Hope you find the above in order. Should you desire any further information / Clarification please feel
free to contact.
Thanking you and looking forward for your valuable orders'
CALIBRATION CERTIFICATE
Detail of Force Measurng lnstruments Serial No r1201711 & Capacrty - 1000 kN & 20(D kN
Master lnst Used: Load Cell & Proving 2U)0KN.NECS.004 Ref Std Valid Upto:-]0/09/2021 &LAlOLl2024
certificate No. " FRli07l2li 13458 & 211@853/D1 05/C-316
Dv Div
14 1410.00 1410.0
50 5009.00 s009,0 I s020.0
10006.00 10006.0 I 1oo2s.0 10060 0 0.r9
200 20003.00
-TrouilT |
20082.0
I
Eq--J
Z ovtt"fj
GRID CALCULATION
TA'TEOF COT{IETTT
Dcrittbn
1 CoEideEtl0
2 Eathing Grid Calculatio
3 Reuh
S.No,
A. Obtsctic
1 To dEteminethe no. of Rod fsenhingsystem-
2 To deteminethe size of main earth gril coductq.
3 Toalculate€rthmatarea
4 To dsign orerall r66tarce of the qrthing system.
C, RGfgrcme
1 IEEE 80
2 lS:3043
D. ERT Report
I Effective soil resistivity Soil R€slrtivity (Otrm_ml
coisdered for grid resistance and step & toEh potential. 25 9a9
S.No. INPUTPARIIMETERS
1 System Vohate
2 System Frequency
v 0.415 KV
f 50 Hz
3 Symmetntal fauh curent in suktation
4 tl 25 XA
Current division factor
sf 0.5
5 Soil resistivity
P 25.989 O-m
6 Tire of current flw (for qductq sizing)
tC 1 s
7 Duration of sh@k (fortorch & Step rcltage)
t5 1
8 Surface layer rsistiuly frableT tEEE-SG2mO)
5
@
n?
SIZING OF EARTHING CONDUCTOR
ccs CBR
L The maximum allowable temperature 'C Tm 7084 1084
2 The ambient temperature 'C Ta 40 40
3 The thermal coefficient of resistivity at reference tempeEture Tr 7fC ar o.oo378 o.@378
4 The resistivity of the ground conductor at reference temperature Tr BO-cm pr 70.L 10.1
5 Tlao or (7/arl -Tr 'C Ko 245 245
6 The themal capacity per unit volume /(cm3iC) TCAP 3.8 3.8
erf .=I
It(,.rqr
h(
where
I is the ms current in kA
Amm2 is the conductor cross section in mm2
Tm is the maximum allo$rable temperafure in "C
Ta is tl'le ambient temperature in'C
(Ir is the thermal cefficient of resistivity at reference temperature Tr in 1f C
pf is the resistivity of the ground cmductd at reference temperature Tr in pe+m
Ko 7/aoor. lTlwl -rr in'C
tc is the duration ofcurent in s
TCAP is the thermal capacity per unit vdume from Table 1, in J/(cm3.'Cl
Tm Ta CT 9f Ko tc TCAP Amm2 D
KA 'c 7rc uorm s J/(cm3'( mm2 mm
25 1064 40 0.00378 to.1 245 I 3.8 201.9472 76.03924957
*- = of+*frir=;#;,1
hP
Calculation of Ground Potenthl Ris (cPR)
= 125@
= 9948.852
1
weighting factor that adjusts for the effects of inner cmductors on the ffi, = l
mesh.
{l'nl'
1 Forgrid with Srdnd rod.
Geometric factor
1.L^
fra : -Z;
na = 5.363636
,rL :
TL-"
I
" ^14-JA
nb = 1.059567
= 5.683134
o.och - P\
? -t \
RedEtbn frtor
'' -'-lal]o.FPy'
= o-7698:t1
Premi.sibh Step whaSe for 70kg bodv reiSht E r.7g = (lOm +6Crpr10.157 t rt
= 7uO8.&)3 V
= 159.951 V
RcdEtbn factor
o.oc/r -r\
\py'
' 2[, + 0.09
= 0.769831
= 5474.02
= !15s5)5
= fu85104
Td.ll-.ntthdg.qid.ods [-R = nR x L, m
=9Ofr
M€hwkatE.ttheertqdtlEc@rrch
- +*lr.,s*r. (ffi1"
E.- -
P'fa'Er'Kt
= 726s.87 v
= 776A743
1 Symmetrical grid fault current Required <25 KA SYMMETRICAI GRID FALILT CURREN]
Glculated Symmetrical grid fault current 12.5 KA CRI ITRIA 15 PA55
PrP