Professional Documents
Culture Documents
SHEET OF
i i
30421007-3CL-00008-
13.8kV BUS DUCT SIZING REPORT OF 4
DESIGN BASIS
FOR
13.8kV BUS DUCT
SIZING
ENGINEERING CONSULTANT
TCE CONSULTING ENGINEERS LIMITED
73/1, ST. MARK’S ROAD
BANGALORE 560 001
INDIA
CONTRACTOR:
AL-TOUKHI COMPANY FOR INDUSTRY & TRADING
P.O. BOX 497, RIYADH 11411, KINGDOM OF SAUDI ARABIA
TEL. 00966-1-4633660 : FAX. 00966–1-4631150
P0B
MP SR
23-03-2005
P0A
DG SR
24-08-2004
30421007-3CL-00008- SHEET: 1 OF 8
13.8kV BUS DUCT SIZING REPORT OF 4
CONTENTS
1.0 INTRODUCTION 2
2.0 OBJECT 3
3.0 REFERENCES 4
6.0 ANNEXURES
ISSUE
P0B
TCE CONSULTING ENGINEERS LIMITED WRITEUP
30421007-3CL-00008- SHEET: 2 OF 8
13.8kV BUS DUCT SIZING REPORT OF 4
1.0 INTRODUCTION:
1.1 Al-Toukhi company for Industry & Trading has been awarded
turnkey contract for Open Cycle Gas Turbine based CPS extension
project at Arar of Saudi Electric Company-Eastern Operation Area
(SEC-EOA), Saudi Arabia.
ISSUE
P0B
TCE CONSULTING ENGINEERS LIMITED WRITEUP
30421007-3CL-00008- SHEET: 3 OF 8
13.8kV BUS DUCT SIZING REPORT OF 4
2.0 OBJECT:
2.1 The object of this report is to determine the ratings of 13.8kV Bus
Duct between Generator Terminals & Generator Circuit breaker
panel and from Generator Circuit breaker panel to 13.8kV side of
Generator Transformer to be installed at Arar Central Power
Station, Saudi Arabia.
2.2 The following parameters are established through this report for
13.8kV Bus Duct:
ISSUE
P0B
TCE CONSULTING ENGINEERS LIMITED WRITEUP
30421007-3CL-00008- SHEET: 4 OF 8
13.8kV BUS DUCT SIZING REPORT OF 4
3.0 REFERENCES:
3.1 Cl.No.3.03 (16), Page 40 of 336 of PTS-1022 which states that “Lot
– 13.8kV, 2500A, 3 phase Segregated Phase Bus Duct with
required Tap Off connections between Generator and Generator
Circuit Breaker Panel and from Generator Circuit Breaker Panel to
Generator Transformer”.
3.3 Cl.No.6.03.G, page 188 of 336 of PTS-1022 which states that “The
HV and LV terminals shall be suitable for XLPE cable connection
and brought out to an air insulated cable end box. At HV side, the
cable end box shall be with Phase Segregated terminal
arrangement”
3.4 Data Schedule for “Metal Enclosed Bus Duct: 4.16kV, 13.8kV or
34.5kV”, Cl.No.4.3, Page 12 of 15 of SEC-EOA’s specification vide
which the material of bus duct enclosure is specified as Steel.
3.5 Data Schedule for “Metal Enclosed Bus Duct: 4.16kV, 13.8kV or
34.5kV”, Cl.No.4.4, Page 13 of 15 of SEC-EOA’s specification vide
which the material of bus duct conductor is specified as Copper.
3.6 SEC-EOA’s Clarification Set No.04 dated 10 th Dec 2003, A.53 vide
which SEC-EOA has informed that Aluminium enclosure also is
acceptable for Bus Duct.
3.7 SEC-EOA’s Clarification Set No.05 dated 28 th Dec 2003, A.119 vide
which SEC-EOA has informed that the gas turbine output
enhancement by intake air cooling will be limited to match the
maximum generator rating at 50 Deg C.
30421007-3CL-00008- SHEET: 5 OF 8
13.8kV BUS DUCT SIZING REPORT OF 4
ISSUE
P0B
TCE CONSULTING ENGINEERS LIMITED WRITEUP
30421007-3CL-00008- SHEET: 6 OF 8
13.8kV BUS DUCT SIZING REPORT OF 4
4.0 ASSUMPTIONS/CONSIDERATIONS:
ISSUE
P0B
TCE CONSULTING ENGINEERS LIMITED WRITEUP
30421007-3CL-00008- SHEET: 7 OF 8
13.8kV BUS DUCT SIZING REPORT OF 4
ISSUE
P0B
TCE CONSULTING ENGINEERS LIMITED WRITEUP
30421007-3CL-00008- SHEET: 8 OF 8
13.8kV BUS DUCT SIZING REPORT OF 4
5.2 Other parameters of the 13.8kV Bus Duct are tabulated below:
As per Cl.No.3.6
6 Enclosure material Aluminium above.
As per Cl.No.4.2
of 24SMSS-1
7 Basic Insulation level kV 95
Rev .2
As per Cl.No.4.2
Power Frequency
8 kV 36 of 24SMSS-1
withstand voltage
Rev .2
(Min 38.70kA as
Short circuit withstand per Cl No.4.9 of
kA
9 (Symmetrical) current for 3 40 System Study
(r.m.s)
sec report for Arar)
ISSUE
P0B