Supply, Installation, Testing and Commissioning of a 2 MW Diesel Generator at ERL

We are going to attend the bid by offering DAIHATSU generator. We have to procure the switchgear
associated with the 2MW generator.
Offered by the
SL Item Requirement of the client Manufacturer
1.6 Generator Switchgear:
1-Set of 5.5 kV Generator switchgear panel have to be arranged
for local and remote control. Generator’s 5.5 kV switchgear
shall have to be placed at proposed location or any other
suitable place in ERL existing power house having power
connection to existing 5.5 kV generator bus.
Necessary connection/modification for connecting the
switchgear to ERL’s 5.5 kV bus to be done by the contractor
The switchgear and the associated equipment shall be fully
1.6.1 General metal clad and shall comprise of but limited to the following:
▪ Switchgear bus bar having provision of future extension on
both sides.
▪ Voltage transformers (For Bus & Generator voltage sensing)
▪ Current transformers (For measurement and Protection)
▪ Generator circuit breaker (draw out type VCB)
▪ Generator cable termination facilities
▪ Earthing facilities
▪ Digital Protective Relays: Following protections must be
provided.
i. Earth fault relay
ii. IDMT over-current relay
iii. Percentage differential relay
iv. Reverse power relay
v. Under/Over frequency relay
vi. Under /Over Voltage relay
Earth fault, IDMT over-current, Under/Over frequency and
Under/Over Voltage protection may be ensured by individual
protective relays or all in 1(one) relay. However, Percentage
differential relay and Reverse power relay must be separate
relays. In alarm and tripping system, prior to tripping of circuit
breaker due to over current, earth fault and over/under
voltage, alarm should be provided. All alarms and tripping
indication shall be shown in the multi-windows annunciator &
HMI as well.
Offered by the
SL Item Requirement of the client
Manufacturer
1) The switchgear shall be of the metal clad type and shall
Type and
1.6.2 comply with the standards given below and with the relevant
rating
requirements stated in this specification.
IEC 269 AC metal-enclosed switchgear
IEC 85 insulating materials
IEC 51 Electrical indicating instruments
2) The switchgear, bus-bar and associated connections shall
have the specification as given below:
Rating:
a) Rated voltage : 5.5 KV
b) Rated insulation level : Class F
c) Lighting impulse withstand voltage : 60 KV (peak)
d) Power frequency withstand voltage : 20 KV rms (1
min.)
e) Phase :3
f) Rated frequency : 50 Hz
g) Bus current : 1250 A
h) Rated short circuit current : 31.5 KA
i) Rated short circuit making current : 80 KA
The current rating of main bus shall not be less than the
rated current of the generator & rating of the associated
connections shall be determined by the contractor.
The current rating of main bus shall not be less than the
Construction
1.6.3 rated current of the generator & rating of the associated
and fittings
connections shall be determined by the contractor.
1) The switchgear shall consist of rigid welded steel cubicle &
small house circuit breaker, bus bar, current transformers,
Voltage transformers etc. The circuit breaker shall be of
withdraw able type. All doors shall be pad lockable and
readily removable when necessary.
2) The bus bar and its connections shall be of copper and all
joint surfaces shall be silver plated.
3) All bus bar connections shall be of bolted type. Flexible
joints shall be provided wherever thermal expansion will
occur.
Offered by the
SL Item Requirement of the client
Manufacturer
4) Safety shutters actuated by inserting or withdrawing of the
circuit breaker and voltage transformer shall be provided in the
compartments.
5) Control circuit isolating connector shall also be provided.
Constructi 6) Clearly labeled mechanical interlocks shall be provided in
1.6.3 on and each circuit breaker compartment to prevent.
fittings • A closed circuit breaker from being withdrawn from inserted
into the isolating contacts.
• A circuit breaker from being moved into any location unless it
is fully withdrawn.
• A circuit breaker from being inserted into the fixed position
unless the secondary isolated contacts are fitted.
• A circuit breaker from being closed except when fully inserted
or fully withdrawn.
• A circuit breaker from being inserted against a locked safety
shutter.
7) A common earth bus bar shall be provided in the switchgear.
The bus bar shall consist of one copper bar not less than 200
mm². The earth bar shall be un-insulated.
8) All secondary wiring shall be terminated on terminal blocks
in an enclosure separate from the high voltage compartment.
The circuit breaker shall comply with the requirements of IEC
56 & the requirements of this specification.
a) Type: Withdraw able Vacuum Circuit Breaker (VCB)
b) Closing Operating Mechanism: Motor operated spring
Vacuum charged mechanism
Circuit
1.6.4 c) Rated Current: 630 A
Breaker
(VCB): d) Rated Withstand Voltage: Power Frequency 1 min. = 20kV,
Lightning Impulse = 60kV
e) Rated Short-Circuit Breaking Current: 31.5kA
f) Making Current: 80 kA
g) Rated short-time withstand current and duration: 31.5 kA 3
sec.
h) Tripping System: Shunt Trip
i) Mechanical Switching Life (times): Minimum 10,000
j) Load Switching Life (times): Minimum 10,000
k) Manual ON/OFF: Circuit breaker should have manual
ON/OFF switch/button.
l) Mechanical flags: Circuit breaker must have Open/Closed
and Charged/Discharged indication flag
Only fully type tested circuit breakers complying with IEC 56
will be considered, and a statement as to the availability of
certificates of such type tests including impulse tests on
identical or similar circuit breakers shall be submitted with
tender.
Offered by the
SL Item Requirement of the client
Manufacturer
The current transformers in the generator switchgear
shall be of the epoxy resin insulated and of the bar or
1.6.5 wound primary type. The ratio, rating, polarity, accuracy
Current and classes of current for transformers shall conform to
Transformer: IEC 185.
The voltage transformers shall be of the epoxy resin
1.6.6 Voltage insulated type. The ratio, rating, polarity, accuracy and
Transformer: classes of voltage transformers shall conform to IEC 185

Transducers/ Transducers/Converters of electrical parameters will be


1.6.7 Converters installed in switchgear panel to send the signals to
of Electrical Control & Monitoring system of Generator Control Panel.
Parameters:

Note: We need below documents along with the financial offer of the switchgear

1. Data Sheet/Description/Literature/Catalogue/Brochure of quoted Switchgear, Protective Relays


and VCB. Country of origin: EU/UK/Japan/USA

2. Manufacturer’s Authorization to the bidder.