Water Quality Guidelines:


The following tables indicate PCIPE water quality guidelines for various duties. We
recommend that the customer consult with their local water treatment company for advice
on water treatment and maintaining / cleaning re-circulated cooling water systems

Water chemistry:

WATER QUALITY GUIDE LINES FOR CHARGING AMINES SYSTEMS


Total Dissolved Solids 100 ppm (max)
Total Hardness 51 ppm (max)
Chlorides 2 ppm (max)
Sodium 3 ppm (max)
Potassium 3 ppm (max)
Iron 10 ppm (max)

CIRCULATED COOLING WATER DC COOLER WATER


pH Between 6.50 Iron <1 ppm pH 7.0 to 9.0
to 8.0
Hardness < 50 ppm Manganese <0.1 ppm Hardness as 30 to 500 ppm
as CaCO3 CaCO3
Sulphates < 50 ppm Suspended Solids <50 ppm Alkalinity as 500 ppm (max)
(Non-1brasive) CaCO3
Sulphates < 1 ppm Oil & grease Nil Total 1000 ppm (max)
Dissolved
Solids
Chlorides < 50 ppm Organic Sovents Nil Chlorides 125 ppm (max)
& Organic
Nutrients
Silica < 30 ppm Free Chlorine <1 ppm Sulfates 125 ppm (max)

Note:
High purity water should also be used when charging the plant with MEA. The water should
contain less than 100 ppm total dissolved solids, 51 ppm total hardness, 2 ppm chlorides, 3
ppm sodium, 3 ppm potassium, and 10 ppm iron.
Document No
Manual title: Issue Date
Standard Operating Procedure Revision # 01
Revision Date
Prepared By PATEL USAMA
Document Title Co2 SOP
Approved By

Operational Data: In order to establish routine maintenance schedules and provide rapid
trouble shooting aides, a log sheet of operating conditions should be kept. The following
information should be recorded at least once every 8 hours.