Professional Documents
Culture Documents
Heatless
Parts/Instruction Manual
This manual contains important safety information and should be made available to
all personnel who operate and/or maintain this product. Carefully read this manual
before attempting to operate or perform maintenance on this equipment.
MODEL:
SERIAL NO.:
Maintenance ......................................................................................................................................... 13
QDTH Series Heatless Air Dryer Maintenance ............................................................................... 13
General ...................................................................................................................................... 13
Daily .......................................................................................................................................... 13
Weekly ....................................................................................................................................... 13
Monthly ..................................................................................................................................... 13
Three Months ............................................................................................................................ 13
Twelve Months .......................................................................................................................... 13
Dewpoint Sensor (Optional) ...................................................................................................... 13
Mufflers ..................................................................................................................................... 13
QDTS Mini Series Heatless Air Dryer Maintenance ....................................................................... 14
General ..................................................................................................................................... 14
Daily .......................................................................................................................................... 14
Weekly ...................................................................................................................................... 14
Three Months ............................................................................................................................ 14
Twelve Months .......................................................................................................................... 14
Mufflers ..................................................................................................................................... 14
Desiccant Replacement Procedure ........................................................................................... 14
Desiccant Disposal ................................................................................................................... 15
1
Dewpoint Display Key Functions .......................................................................................................... 16
Setpoint Programming .................................................................................................................... 16
Open Sensor Condition .................................................................................................................. 16
Setpoint Limit Indication ................................................................................................................. 16
Over Range and Under Range Indication ....................................................................................... 16
Peak/Valley Indication .................................................................................................................... 16
Troubleshooting .................................................................................................................................... 19
Parts Lists.............................................................................................................................................. 22
2
GENERAL INFORMATION
The Quincy Drying System is designed to remove moisture SAFETY INSTRUCTIONS
from compressed air.
When using air compressors and compressed air
When properly installed, the unit requires little accessories, basic safety rules and precautions must
maintenance or adjustment. always be followed, including the following:
A list of service parts is provided on the attached parts list. 1. READ ALL INSTRUCTIONS FULLY.
2. WIRING & BREAKERS
Wiring, breakers and other electrical equipment
must conform to local and national electrical codes.
Do not operate this unit with damaged wiring or
DO NOT install, operate, maintain, adjust after the unit or air handling parts have been
or service this unit without thoroughly dropped or damaged in any manner. Notify
reading this manual. authorized service facility for examination, repair
or other adjustments.
March 2004
Back to TOC 3
5. SECURE DRAIN LINES
Fasten drain lines from prefilter/separator to floor or
DISCLAIMER OF WARRANTY
drain. Pressurized air may periodically pass through If this unit is used to produce breathing air, the special
drain lines, which will cause an unsecured line to equipment and precautions expressed in OSHA 29 CFR
whip and may cause bodily injury. 1910.134 for specifications of the necessary equipment
and special precautions to make Breathing Air MUST BE
used or any warranties are VOID and manufacturer
disclaims any liability whatsoever for loss, personal injury
or damage.
March 2004
Back to TOC 5
6
COMPRESSED AIR SYSTEM
RECOMMENDED INSTALLATION
FLOW DIAGRAM
OPTIONAL 3 VALVE INTERMEDIATE
SYSTEM BYPASS CONTROL
RECEIVER (OPTIONAL)
T - TEMPERATURE GAUGE P
DIFFERENTIAL DIFFERENTIAL
P - PRESSURE GAUGE PRESSURE GAUGE PRESSURE GAUGE
R - RELIEF VALVE
RECEIVER REFRIGERATED R
2
P
AIR COOLED (REMOVES 66% T 6
AFTERCOOLER 4
MOISTURE)
P A
INSTALLATION & OPERATION
COALESCING
AFTERFILTER
4
4 DRAIN
AUTO
DRAIN
3
AUTO
Back to TOC
AFTERCOOLER DRAIN
1 3
DIFFERENTIAL DIFFERENTIAL
PRESSURE GAUGE PRESSURE GAUGE
PLANT
AIR
-40°F TO 4477
-100°F PDP AUTO
DRAIN
TO PLANT USE
PARTICULATE 3 ° °F PDP
AFTERFILTER G 37 °F
4 REGENERATIVE PREFILTER °
AIR DRYER
5
March 2004
QDTH SERIES HEATLESS AIR DRYER Start-Up Procedure
1. Leave the power switch in the OFF position.
INSTALLATION & OPERATION
2. Keeping the dryer isolation outlet valve closed,
slowly pressurize both the adsorbent chambers to the
General line pressure.
1. Install dryer on a level base, indoors or under a shed. 3. Check for any leaks in the system.
1. During shipment, flange and connecting bolts can 4. When the towers are at line pressure, turn the power
come loose. All bolts should be checked and switch to the ON position.
tightened as needed. 5. One inlet valve will close, and the chamber purge
2. Make sure when the piping is in place that no undue valve will open and depressurize. This may take as
stress is placed on dryer connections. Union joints or long as 3 minutes.
flexible connections are recommended to relieve 6. Adjust the purge pressure to the recommended setting,
stress. Also, properly support the pipes as needed and lock the valve locking mechanism in place.
with hangers or brackets. Air piping must be
7. Slowly open the dryer isolation outlet valve to
installed by an experienced pipe fitter.
pressurize the header system.
3. Equip dryer with inlet and outlet isolation valves and 8. Observe the dryer operation through one or two
a bypass valve for ease of servicing and start-up. complete cycles.
4. Connect electric power to the dryer through a
properly sized fused disconnect switch. Adjustments
5. Reactivation exhaust may be piped away from the 1. Adjust the purge pressure at the recommended level,
dryer, making sure proper pipe size is used. The ____________________PSIG.
pipe size should be increased by one size at the
2. Adjust the time delay relay at____________MIN.
valve, and one additional pipe diameter size for
every ten-foot run to reduce back pressure. 3. Demand Control Setpoint (SP1):_________
High Humidity Alarm Setpoint (SP2):_________
6. Electrical Connections: Follow the recognized
(See dewpoint display settings on Page 16.)
local and municipal electrical codes. All components
must be load rated as approved by NEC, NEMA,
CSA and UL. Microprocessor Control with Sequence Display
7. During shipment, wire connections may become Available on most standard units.
loose. Per U.L. specification, torque screws inside INTRODUCTION
enclosure to 20 in-lbs.
1. GENERAL: The Quincy Microprocessor Control
8. GROUNDING: It is mandatory that the dryer be (MC) is a seven (7) channel sequence timer with LCD
grounded. Use an adequate ground with the and LED display features. The MC consists of a main
conductor sized to NEC. control unit and a remote LCD, LED and I/O module.
9. STORAGE: In case of extended storage period The two units are connected via ribbon cable.
before the installation, follow these simple 2. SEQUENCE OF OPERATION: The sequence of
procedures: operation is based on a five (5) minute or a ten (10)
a. Seal or cover all the parts minute NEMA cycle. For either cycle length, one-half
of the total time is for adsorption of moisture from the
b. Wrap the electrical enclosure process gas and one-half is for desiccant
c. Wrap the mufflers regeneration. Specifics of the timing sequence are
detailed in Figure 2, the Sequence of Operation
d. If the desiccant is shipped loose, store it inside to Diagram (SDG-2). If power is interrupted, the MC
avoid any rain or water damage. electronically stores the point in the timing cycle at
10. LEAK TEST: All the dryers are tested at the factory which power was removed. When power is
for any leaks before shipment. An air leak could reapplied, timing will resume from that point in the
develop during transportation or installation. cycle. At all times during operation, the current status
Pressurize the system and check for any leaks. of the timing cycle is indicated graphically by the
LEDs and textually on the LCD screen.
March 2004
Back to TOC 7
FEATURES 2. MANUAL CYCLE ADVANCE: The backside of the
remote I/O module contains an “ADVANCE” push
• LCD screen indicating right/left tower drying, right/left
button. Each time the “ADVANCE” push button is
tower regenerating, tower switching, actual sequence
pressed, the timing cycle advances by 30 seconds.
time, demand cycle indication (opt.), fail to shift alert
The “ADVANCE” push button is disabled whenever
(opt.)
the timing is stopped by an inhibit switch.
• LED sequence annunciator indicating R/L tower
3. NEMA CYCLE: The Microprocessor Control can be
drying/regenerating, demand cycle indicator (opt.),
set to operate in a 5 minute NEMA Cycle or a 10
high humidity alarm (opt.), fail to shift alarm (opt.)
minute NEMA Cycle. The cycle can be selected via a
• Timer and setting memory slide switch at the back of the remote I/O module.
• Time cycle advance button RELAY OUTPUTS (DRY CONTACTS): There are two
relay outputs for remote annunciation. The output is
• 5 or 10 minute NEMA cycle selector
normally open and rated for 10 AMPS resistive at
• Open thermocouple protection 125VAC, 5 AMPS resistive at 30VDC. The outputs are for
the failure to switch and high humidity alarms. If one or
MODE OF OPERATION:
both inhibits are made, the relays will be energized and
1. START UP: The Microprocessor Control will start to the LED on the remote I/O will light up.
operate as soon as power is supplied and the unit is
turned on. The load outputs will recycle on and off
based on a 5 minute or a 10 minute NEMA cycle.
The sequence will proceed according to the
Sequence of Operation Diagram SDG-2. The point
of the sequence at which the timing starts depends This unit may be damaged by electrostatic
on where the cycle stopped when power was last discharge. Follow procedures for static
turned off. sensitive parts when handling, shipping or
installing this unit.
1 LEFT TOWER ON
SWITCHING OFF
2 RIGHT TOWER ON
SWITCHING OFF
3 LEFT TOWER ON
REGENERATING OFF
4 RIGHT TOWER ON
REGENERATING OFF
5 DEMAND ON
CYCLE OFF
6 REPRESSURIZING ON
OFF
7 LEFT TOWER ON
DEPRESSURIZING (OPT.) OFF
8 RIGHT TOWER ON
DEPRESSURIZING (OPT.) OFF
March 2004
Back to TOC 9
At time equal to 5.1 minutes, the left tower purge 1. If the compressed air system has been
valve opens to commence the regeneration cycle and the piped with a bypass around the dryer then
above process is then repeated on the opposite towers. the following should be completed:
NOTE: During the regeneration air flow through the a. Open the bypass valve to allow process flow to
desiccant bed, the tower pressure gauge should read 0 continue downstream. Then close the outlet
PSIG. Any higher pressure is an indication of a plugged isolation valve on the dryer bypass piping.
muffler, which will retard the regeneration of desiccant. b. Turn the power switch to the OFF position.
c. Close the inlet isolation valve on the dryer bypass
Shutdown Procedure piping. At this time the dryer is isolated and can
Heatless type dryers operate on a standard timer cycle of be depressurized, for servicing.
10 minutes, 5 minutes drying and 5 minutes regenerating. 2. If the compressed air system has not been
This cycle should not be interrupted (except for servicing). piped with a bypass then the following
If the dryer needs to be shut down for a certain shift or should be completed:
weekend, it should be turned off at the end of the 5 minute
regenerating cycle with both towers at line pressure. If a. Turn the power switch to the OFF position.
servicing is required, advance the time sequence so the b. The tower switching valves are normally open
purge valves close and both towers pressurize. At this time valves; therefore, with the power OFF the inlet
the dryer can be turned off. valves to the towers will be open, and the purge
For normal dryer shutdown, wait until both towers are at valves will close. This will give you extended
line pressure. At this time the purge valves will close. drying time until desiccant chambers are
saturated.
AIR OUTLET
16 17 18
EX (SLIGHT BLEED)
3 3
CLOSED OPEN
7 14 7
9 9
10 13 15 S ES 10
CLOSED
11 11
12
OPEN CLOSED
9 9
REGEN 4 4 DRYING
FLOW FLOW
1 1
9 9
8 8
CLOSED OPEN
2 2
OPEN CLOSED
5 5
6
EX EX EX
AIR
INLET
21 19 20 22
ES S ES S ES S ES S
EX - EXHAUST
ES - ELECTRICAL SIGNAL
March 2004
Back to TOC 11
QDTS MINI SERIES HEATLESS AIR DRYER Theory of Operation
The Quincy QDTS Mini Series Heatless Regenerative Air
INSTALLATION & OPERATION Dryer features “State of the Art” design. The 4-Way Inlet
valve & outlet shuttle valve make these dryers trouble-free
General in operation and require very little maintenance. Standard
Heatless Regenerative Air Dryers operate on a 10 minute
1. If base mounted, secure base plat to hard surface, or
NEMA cycle.
hang securely on a wall.
• Drying: 5 minutes
2. Dryer should be installed indoors, or under a shed.
• Regeneration: 4 minutes, 20 seconds
3. Equip the dryer with inlet and outlet isolation valves
(continuous flow)
and a bypass valve for ease of servicing and
start-up. • Repressurizing: 40 seconds
4. Connect electric power to the dryer through a While one absorbent filled tower is drying the inlet flow at
properly sized fused disconnect switch. the line pressure, in the upward direction for 5 minutes,
the other tower goes through a mode of desiccant
5. Reactivation exhaust may be piped away from the
regeneration in counter flow for 4 minutes, 20 seconds.
dryer, making sure proper pipe size is used. For
every ten foot run, increase the pipe diameter by one
size to reduce back pressure. Start-Up Procedure
6. Electrical Connections: Follow the recognized 1. Leave the dryer power supply disconnected.
electrical codes with local and municipal codes for 2. Keeping the dryer isolation outlet valve closed,
electrical connection. All components must be load slowly pressurize both the desiccant chambers to line
rated as approved by NEC, NEMA, CSA and UL. pressure.
7. During shipment wire connection may become loose. 3. Check for any leaks in the system.
Per U.L. specification, torque screws inside enclosure
to 20 in-lbs. 4. Purge valve should be closed at this time (N.C.
Valve).
8. GROUNDING: It is mandatory that the dryer be
grounded. Use an adequate ground with the 5. Connect the dryer power supply.
conductor sized to NEC. 6. The purge valve should open and depressurize one
9. STORAGE: In case of extended storage period desiccant chamber.
before the installation, follow these simple 7. Run the dryer through one or two cycles before
procedures: slowly opening the dryer isolation outlet valve.
a. Seal or cover all the parts
b. Wrap the electrical enclosure Operational Observation
c. Wrap the mufflers 1. The drying chamber should be at the line pressure
indicated on the drying chamber pressure gauge.
d. If the desiccant is shipped loose, store it inside to
avoid any rain or water damage. 2. The reactivation chamber should be at 0 PSIG. (Any
higher pressure is an indication of some malfunction,
10. LEAK TEST: All the dryers are tested at the factory refer to Troubleshooting Guide on Page 21.)
for any leaks before shipment. An air leak could
develop during transportation or installation. 3. The standard time cycle is 10 minutes. While one
Pressurize the system and check for any leaks. chamber is drying for 5 minutes the other chamber
goes through a mode of desiccant reactivation and
purge for about 4.3 minutes. The purge exhaust
valve then closes to allow the chamber to
repressurize to line pressure before switch-over
occurs at the end of 5 minutes.
2. Check the purge control setting. 5. Check pilot air solenoid valves for possible defects.
3. Check the operating conditions; inlet pressure, inlet 6. Replace diaphragms in valves. See parts list for
temperature and the flow rate. sizing. For premium switching valves, clean or
replace worn out seats and seals as necessary.
4. Check the moisture indicator. BLUE color indicates
DRY conditions. If the color is PINK, refer to the
moisture indicator chart on alarm conditions for Dewpoint Sensor (Optional)
probable cause. (Optional equipment.) It is recommended to recalibrate the sensor probe
annually to maintain accuracy. Contact your local
5. Check the purge mufflers for blockage. Possible distributor or factory for exchange policy.
indication is back pressure on tower under
regeneration. Replace if necessary. Calibration: To maintain accuracy, replace the probe
every two years.
6. Check the pressure drop across prefilter and after-
filter. Replace the elements when the differential Probe Replacement: Turn the normal/demand selector
reaches 5-10 PSID. switch to the normal position. This will disable the contacts
for Demand Control. Isolate and depressurize the probe
chamber. Remove, and replace the probe. Pressurize the
Monthly probe chamber and connect the sensor cable. A small
Check the pilot air filter element. Replace if necessary. amount of sample air (approximately 2-10 SCFH) should
expel out the chamber needle valve.
March 2004
Back to TOC 13
Mufflers Three Months
Purge mufflers are installed to reduce the noise level. The 1. Check the prefilter and afterfilter elements for
mufflers tend to plug up and increase back pressure over excessive clogging or possible damage. Replace as
time due to oil carryover and contaminants from necessary.
compressor, or due to desiccant dust at the initial start-up.
2. Check outlet dewpoint conditions.
To eliminate back pressure, replace muffler after three
months, or when the back pressure increases in the
regenerating tower. Twelve Months
1. Close the inlet and outlet valves on the dryer or
bypass the dryer and completely depressurize the
QDTS MINI SERIES HEATLESS AIR DRYER dryer system. Open and check visually; if desiccant
MAINTENANCE is contaminated with oil or broken, replace the
desiccant.
2. Inspect and clean the 4-way switching valve, purge
solenoid valve and shuttle valve. Repair or replace
as necessary.
Disconnect power and depressurize unit
completely before starting maintenance Mufflers
procedures. Purge mufflers are installed to reduce the noise level. The
mufflers tend to plug up and increase back pressure over
time due to oil carryover and contaminants from
General compressor, or due to desiccant dust at the initial start-up.
Clean the exhaust mufflers. Replace mufflers if there is any To eliminate back pressure, replace muffler after one
back pressure on the tower in the regeneration cycle. month operation and/or when back pressure increases to
5 PSIG in the regenerating tower.
No lubrication is required, or should be used on any of
the components.
Desiccant Replacement Procedure
Daily Quincy uses Activated Alumina Grade A 1/8" diameter
for all standard QDTS Mini Series Heatless Regenerative
1. Check auto drain on prefilter every shift. Air Dryers.
2. Follow the start-up procedure. Filling Procedure:
1. Make sure the dryer is depressurized.
Weekly
2. Remove the upper and lower interconnecting pipe
1. Check the shifting, purge and repressurization
and valves.
operation.
3. Remove the Desiccant retaining screens on both ends
2. Check the operating conditions; inlet pressure, inlet
of the desiccant chambers. Remove all desiccant.
temperature and the flow rate.
4. Using a flash light, inspect the inside of each vessel
3. Check the moisture indicator. BLUE color indicates
to be sure they are empty.
DRY conditions. If the color is PINK, refer to the
Troubleshooting Guide on Page 21 for probable 5. Install the bottom desiccant screens and make sure
cause. (Optional equipment.) they are secured tightly.
4. Check the purge mufflers for blockage. Possible 6. Begin filling the towers.
indication is back pressure on tower under
7. Install the top desiccant screens, and all of the
regeneration. Replace if necessary.
interconnecting pipe and valves.
5. Check the pressure drop across prefilter and
8. Refer to the start-up procedure listed in the manual.
afterfilter. Replace the elements if the pressure drop
exceeds 7 PSID.
QDTS-SERIES
PROCESS & INSTRUMENT DRAWING
OUTLET
SHUTTLE
VALVE
FIXED
ORIFICE
AIR IN
PURGE
4 WAY VALVE
INLET
VALVE
PRESSURE PRESSURE
VESSEL VESSEL
March 2004
Back to TOC 15
DEWPOINT DISPLAY KEY FUNCTIONS
OPEN SENSOR CONDITION
DIGITAL DISPLAY KEY FUNCTIONS
When message oPEn1 is displayed, the dewpoint sensor
BUTTON is likely to be disconnected from the hygrometer.
SETPOINT PROGRAMMING 2. Press (↓) several times to get message VALY and the
value flashing.
Standard Settings. Setpoints are factory preset.
3. Press (↓) and (↑) simultaneously to reset the Peak or
1. Press PROG and (↓) buttons simultaneously to enter Valley value while displayed.
into the Setpoint Setting Mode.
2. SP1 Adjust value for the Setpoint 1, press PROG to
continue. SP1 set at -40°F (Demand Control).
3. SP2 Adjust value for the Setpoint 2, press PROG
several times to exit. SP2 set at -20°F (High Humidity
Alarm).
4. SP3 Not used.
Settings for models both Low Dewpoint Options. Setpoints
are factory preset.
1. SP1 set at -100°F (Demand Control)
2. SP2 set at -80°F (High Humidity Alarm)
3. SP3 Not used.
L N G
March 2004
Back to TOC 17
OPTIONS LISTING WITH EXPLANATION (QDTH MODELS ONLY)
AUDIBLE ALARM PANEL LIGHTS
The Audible Alarm consists of a buzzer with reset push The Panel Light option consists of four lights: Left Tower
button and ON/OFF selector switch. Drying, Right Tower Drying, Left Tower Regenerating, and
Right Tower Regenerating. These lights are for dryer
The audible alarm provides an audible warning to alert
sequence indication.
an operator that the dryer is not functioning properly. This
option is used with options such as “Failure to Shift Alarm”
or “High Humidity Alarm.”
PLC CONTROLLER
PLC Controller can be added to control the operation of
FAILURE TO SHIFT ALARM standard regenerative dryers. Typically Square D or Allen
Bradley PLCs are used.
The Failure to Shift Alarm consists of an alarm light that
illuminates if the desiccant towers fail to shift at a
prescribed time. Dry contacts are provided for remote
annunciation.
DEMAND CONTROL “DC”
The Demand Control (DC) is an energy saver that can
extend the drying cycle without purging, during periods of
HIGH HUMIDITY ALARM lower moisture loads. The DC system offers, in one
compact package, the utmost in flexibility and accuracy
The High Humidity Alarm consists of an alarm light
sensing the actual dewpoint of the outlet air. The
controlled by a hygrometer that senses the dewpoint at the
hygrometer senses the dewpoint at the outlet of the dryer
outlet of the air dryer. This alarm illuminates when the
at the end of the drying cycle, and extends the drying
dewpoint reaches -20°F and above. A small amount of
cycle until the preset adjustable dewpoint setpoint is
sample air is required for operation. Dry contacts are
reached. During this extended drying cycle, the purge
provided for remote annunciation.
valves are closed and the opposite tower is pressurized
Calibration: To maintain accuracy, replace the probe and prepared for the drying cycle. The demand control
every two years. option reduces purge loss and extends valve life. This
option consists of the following:
Probe Replacement: Turn the normal/demand selector
switch to the normal position. This will disable the contacts • Digital Dewpoint Display
for Demand Control. Isolate and depressurize the probe
• Adjustable Setpoints
chamber. Replace the probe. Pressurize the probe
chamber and turn the power back on. • Demand Cycle Light
• High Humidity Alarm Light with Dry Contact
MOISTURE INDICATOR • 4-20mA Output
(All types of regenerative dryers)
Calibration: To maintain accuracy, the probe should be
The moisture indicator consists of a small, clear, recalibrated annually. Recalibrated probes are
polycarbonate filter filled with a color change silica gel. It available through your local distributor.
is located at the outlet of the dryer. When the dewpoint is
below -10°F, the desiccant is blue. When the dewpoint is Probe Replacement: Isolate and depressurize the
above -10°F, the desiccant is pink. A small amount of probe chamber. Disconnect the sensor cable from the
sample air is required for operation. sensor. Remove, and replace the probe. Pressurize the
probe chamber and connect the sensor cable. A small
amount of sample air (approximately 2-10 SCFH) should
expel out the chamber needle valve.
FILTER
HOUSING SILICA GEL
March 2004
Back to TOC 19
Table 1 — Troubleshooting Guide for QDTH Series Heatless Regenerative Dryers, continued
Table 2 — Troubleshooting Guide for QDTS Mini Series Heatless Regenerative Dryers
March 2004
Back to TOC 21
QDTS-5 Parts List
115 Volt / 1 Phase / 60 Hz
PART DESCRIPTION PART NO. QTY.
4-WAY AIR INLET VALVE, 0.25" QVA-001409 1
AIR OUTLET SHUTTLE VALVE, 0.25" QVA-000253 1
PURGE VALVE, 0.25" QVA-003110 1
EXHAUST MUFFLER QRG-000172 1
PRESSURE GAUGE, 1.5" QGM-000041 2
SEQUENCE CONTROLLER, 10 MIN. QEC-002016 1
PREFILTER ELEMENT CPNE00010 1*
AFTERFILTER ELEMENT CSNE00010 1*
DESICCANT, 1/8" QSORB-125 6 LBS
22
Back to TOC
QDTS-10 Parts List
115 Volt / 1 Phase / 60 Hz
PART DESCRIPTION PART NO. QTY.
4-WAY AIR INLET VALVE, 0.5" QVA-001410 1
AIR OUTLET SHUTTLE VALVE, 0.5" QVA-000254 1
PURGE VALVE, 0.5" QVA-003758 1
EXHAUST MUFFLER QRG-000174 1
PRESSURE GAUGE, 1.5" QGM-000041 2
SEQUENCE CONTROLLER, 10 MIN. QEC-002016 1
PREFILTER ELEMENT CPNE00010 1*
AFTERFILTER ELEMENT CSNE00010 1*
DESICCANT, 1/8" QSORB-125 18 LBS
23
Back to TOC
QDTS-15 Parts List
115 Volt / 1 Phase / 60 Hz
PART DESCRIPTION PART NO. QTY.
4-WAY AIR INLET VALVE, 0.5" QVA-001410 1
AIR OUTLET SHUTTLE VALVE, 0.5" QVA-000254 1
PURGE VALVE, 0.5" QVA-003758 1
EXHAUST MUFFLER QRG-000174 1
PRESSURE GAUGE, 1.5" QGM-000041 2
SEQUENCE CONTROLLER, 10 MIN. QEC-002016 1
PREFILTER ELEMENT CPNE00020 1*
AFTERFILTER ELEMENT CSNE00020 1*
DESICCANT, 1/8" QSORB-125 18 LBS
24
Back to TOC
QDTS-25 Parts List
115 Volt / 1 Phase / 60 Hz
PART DESCRIPTION PART NO. QTY.
4-WAY AIR INLET VALVE, 0.5" QVA-001410 1
AIR OUTLET SHUTTLE VALVE, 0.5" QVA-000254 1
PURGE VALVE, 0.5" QVA-003758 1
EXHAUST MUFFLER QRG-000174 1
PRESSURE GAUGE, 1.5" QGM-000041 2
SEQUENCE CONTROLLER, 10 MIN. QEC-002016 1
PREFILTER ELEMENT CPNE00030 1*
AFTERFILTER ELEMENT CSNE00030 1*
DESICCANT, 1/8" QSORB-125 40 LBS
25
Back to TOC
QDTS-35 Parts List
115 Volt / 1 Phase / 60 Hz
PART DESCRIPTION PART NO. QTY.
4-WAY AIR INLET VALVE, 0.5" QVA-001410 1
AIR OUTLET SHUTTLE VALVE, 0.5" QVA-000254 1
PURGE VALVE, 0.5" QVA-003758 1
EXHAUST MUFFLER QRG-000174 1
PRESSURE GAUGE, 1.5" QGM-000041 2
SEQUENCE CONTROLLER, 10 MIN. QEC-002016 1
PREFILTER ELEMENT CPNE00030 1*
AFTERFILTER ELEMENT CSNE00030 1*
DESICCANT, 1/8" QSORB-125 40 LBS
26
Back to TOC
QDTS-50 Parts List
115 Volt / 1 Phase / 60 Hz
PART DESCRIPTION PART NO. QTY.
4-WAY AIR INLET VALVE, 0.5" QVA-001410 1
AIR OUTLET SHUTTLE VALVE, 0.5" QVA-000254 1
PURGE VALVE, 0.5" QVA-003758 1
EXHAUST MUFFLER QRG-000174 1
PRESSURE GAUGE, 1.5" QGM-000041 2
SEQUENCE CONTROLLER, 10 MIN. QEC-002016 1
PREFILTER ELEMENT CPNE00060 1*
AFTERFILTER ELEMENT CSNE00060 1*
DESICCANT, 1/8" QSORB-125 56 LBS
27
Back to TOC
QDTH-50 Parts List
115 Volt / 1 Phase / 60 Hz
PART DESCRIPTION PART NO. QTY.
2-WAY AIR INLET VALVE, 0.75" QVA-000246 2
2-WAY PURGE VALVE, 0.5" QVA-003758 2
AIR OUTLET SHUTTLE VALVE, 0.75" QVA-002811 1
PURGE CHECK VALVE QVA-002109 2
RELIEF VALVE QVA-001531 2
EXHAUST MUFFLER QRG-000174 2
PRESSURE GAUGE, 2.5" QGM-000373 2
PILOT AIR FILTER ELEMENT QRG-000231 1
3-WAY SOLENOID VALVE QVA-001411 4
ON/OFF SWITCH, NEMA 4 QEC-001634 1
FUSE, 1 AMP QEC-002411 1
SEQUENCE CONTROLLER, 10 MIN. QEC-002520 1
INLET VALVE KIT, DIAPHRAGM & SEALS QVA-001932 2
INLET VALVE KIT, DIAPHRAGM ONLY QVA-000308 2
PREFILTER ELEMENT CPNE00060 1*
AFTERFILTER ELEMENT CSNE00060 1*
DESICCANT, 1/8" QSORB-125 66 LBS
28
Back to TOC
QDTH-75 Parts List
115 Volt / 1 Phase / 60 Hz
PART DESCRIPTION PART NO. QTY.
2-WAY AIR INLET VALVE, 1" QVA-000342 2
2-WAY PURGE VALVE, 0.5" QVA-003758 2
AIR OUTLET SHUTTLE VALVE, 1" QVA-002808 1
PURGE CHECK VALVE QVA-002109 2
RELIEF VALVE QVA-001531 2
EXHAUST MUFFLER QRG-000174 2
PRESSURE GAUGE, 2.5" QGM-000373 2
PILOT AIR FILTER ELEMENT QRG-000231 1
3-WAY SOLENOID VALVE QVA-001411 4
ON/OFF SWITCH, NEMA 4 QEC-001634 1
FUSE, 1 AMP QEC-002411 1
SEQUENCE CONTROLLER, 10 MIN. QEC-002520 1
INLET VALVE KIT, DIAPHRAGM & SEALS QVA-001932 2
INLET VALVE KIT, DIAPHRAGM ONLY QVA-000308 2
PREFILTER ELEMENT CPNE00125 1*
AFTERFILTER ELEMENT CSNE00125 1*
DESICCANT, 1/8" QSORB-125 100 LBS
29
Back to TOC
QDTH-100 Parts List
115 Volt / 1 Phase / 60 Hz
PART DESCRIPTION PART NO. QTY.
2-WAY AIR INLET VALVE, 1" QVA-000342 2
2-WAY PURGE VALVE, 0.5" QVA-003758 2
AIR OUTLET SHUTTLE VALVE, 1" QVA-002808 1
PURGE CHECK VALVE QVA-002109 2
RELIEF VALVE QVA-001531 2
EXHAUST MUFFLER QRG-000174 2
PRESSURE GAUGE, 2.5" QGM-000373 2
PILOT AIR FILTER ELEMENT QRG-000231 1
3-WAY SOLENOID VALVE QVA-001411 4
ON/OFF SWITCH, NEMA 4 QEC-001634 1
FUSE, 1 AMP QEC-002411 1
SEQUENCE CONTROLLER, 10 MIN. QEC-002520 1
INLET VALVE KIT, DIAPHRAGM & SEALS QVA-001932 2
INLET VALVE KIT, DIAPHRAGM ONLY QVA-000308 2
PREFILTER ELEMENT CPNE00150 1*
AFTERFILTER ELEMENT CSNE00150 1*
DESICCANT, 1/8" QSORB-125 130 LBS
30
Back to TOC
QDTH-150 Parts List
115 Volt / 1 Phase / 60 Hz
PART DESCRIPTION PART NO. QTY.
2-WAY AIR INLET VALVE, 1.5" QVA-000243 2
2-WAY PURGE VALVE, 0.75" QVA-000230 2
AIR OUTLET SHUTTLE VALVE, 1.5" QVA-002880 1
PURGE CHECK VALVE QVA-002109 2
RELIEF VALVE QVA-001531 2
EXHAUST MUFFLER QRG-000175 2
PRESSURE GAUGE, 2.5" QGM-000373 2
PILOT AIR FILTER ELEMENT QRG-000231 1
3-WAY SOLENOID VALVE QVA-001411 4
ON/OFF SWITCH, NEMA 4 QEC-001634 1
FUSE, 1 AMP QEC-002411 1
SEQUENCE CONTROLLER, 10 MIN. QEC-002520 1
INLET VALVE KIT, DIAPHRAGM & SEALS QVA-001933 2
INLET VALVE KIT, DIAPHRAGM ONLY QVA-000697 2
PURGE VALVE KIT, DIAPHRAGM & SEALS QVA-001932 2
PURGE VALVE KIT , DIAPHRAGM ONLY QVA-000308 2
PREFILTER ELEMENT CPNE00150 1*
AFTERFILTER ELEMENT CSNE00150 1*
DESICCANT, 1/8" QSORB-125 200 LBS
31
Back to TOC
QDTH-200 Parts List
115 Volt / 1 Phase / 60 Hz
PART DESCRIPTION PART NO. QTY.
2-WAY AIR INLET VALVE, 1.5" QVA-000243 2
2-WAY PURGE VALVE, 1" QVA-000231 2
AIR OUTLET SHUTTLE VALVE, 1.5" QVA-002880 1
PURGE CHECK VALVE QVA-002110 2
RELIEF VALVE QVA-001524 2
EXHAUST MUFFLER QRG-000175 2
PRESSURE GAUGE, 2.5" QGM-000373 2
PILOT AIR FILTER ELEMENT QRG-000231 1
3-WAY SOLENOID VALVE QVA-001411 4
ON/OFF SWITCH, NEMA 4 QEC-001634 1
FUSE, 1 AMP QEC-002411 1
SEQUENCE CONTROLLER, 10 MIN. QEC-002520 1
INLET VALVE KIT, DIAPHRAGM & SEALS QVA-001933 2
INLET VALVE KIT, DIAPHRAGM ONLY QVA-000697 2
PURGE VALVE KIT, DIAPHRAGM & SEALS QVA-001932 2
PURGE VALVE KIT , DIAPHRAGM ONLY QVA-000308 2
PREFILTER ELEMENT CPNE00200 1*
AFTERFILTER ELEMENT CSNE00200 1*
DESICCANT, 1/8" QSORB-125 260 LBS
32
Back to TOC
QDTH-250 Parts List
115 Volt / 1 Phase / 60 Hz
PART DESCRIPTION PART NO. QTY.
2-WAY AIR INLET VALVE, 1.5" QVA-000243 2
2-WAY PURGE VALVE, 1" QVA-000231 2
AIR OUTLET SHUTTLE VALVE, 1.5" QVA-002880 1
PURGE CHECK VALVE QVA-002110 2
RELIEF VALVE QVA-001524 2
EXHAUST MUFFLER QRG-000175 2
PRESSURE GAUGE, 2.5" QGM-000373 2
PILOT AIR FILTER ELEMENT QRG-000231 1
3-WAY SOLENOID VALVE QVA-001411 4
ON/OFF SWITCH, NEMA 4 QEC-001634 1
FUSE, 1 AMP QEC-002411 1
SEQUENCE CONTROLLER, 10 MIN. QEC-002520 1
INLET VALVE KIT, DIAPHRAGM & SEALS QVA-001933 2
INLET VALVE KIT, DIAPHRAGM ONLY QVA-000697 2
PURGE VALVE KIT, DIAPHRAGM & SEALS QVA-001932 2
PURGE VALVE KIT , DIAPHRAGM ONLY QVA-000308 2
PREFILTER ELEMENT CPNE00300 1*
AFTERFILTER ELEMENT CSNE00300 1*
DESICCANT, 1/8" QSORB-125 330 LBS
33
Back to TOC
QDTH-300 Parts List
115 Volt / 1 Phase / 60 Hz
PART DESCRIPTION PART NO. QTY.
2-WAY AIR INLET VALVE, 2" QVA-000247 2
2-WAY PURGE VALVE, 1" QVA-000231 2
AIR OUTLET CHECK VALVE, 2" QVA-000051 2
PURGE CHECK VALVE QVA-002111 2
RELIEF VALVE QVA-001524 2
EXHAUST MUFFLER QRG-000176 2
PRESSURE GAUGE, 2.5" QGM-000373 2
PILOT AIR FILTER ELEMENT QRG-000231 1
3-WAY SOLENOID VALVE QVA-001411 4
ON/OFF SWITCH, NEMA 4 QEC-001634 1
FUSE, 1 AMP QEC-002411 1
SEQUENCE CONTROLLER, 10 MIN. QEC-002520 1
INLET VALVE KIT, DIAPHRAGM & SEALS QVA-001934 2
INLET VALVE KIT, DIAPHRAGM ONLY QVA-000468 2
PURGE VALVE KIT, DIAPHRAGM & SEALS QVA-001932 2
PURGE VALVE KIT , DIAPHRAGM ONLY QVA-000308 2
PREFILTER ELEMENT CPNE00300 1*
AFTERFILTER ELEMENT CSNE00300 1*
DESICCANT, 1/8" QSORB-125 390 LBS
34
Back to TOC
QDTH-350 Parts List
115 Volt / 1 Phase / 60 Hz
PART DESCRIPTION PART NO. QTY.
2-WAY AIR INLET VALVE, 2" QVA-000247 2
2-WAY PURGE VALVE, 1" QVA-000231 2
AIR OUTLET CHECK VALVE, 2" QVA-000051 2
PURGE CHECK VALVE QVA-002111 2
RELIEF VALVE QVA-001524 2
EXHAUST MUFFLER QRG-000176 2
PRESSURE GAUGE, 2.5" QGM-000373 2
PILOT AIR FILTER ELEMENT QRG-000231 1
3-WAY SOLENOID VALVE QVA-001411 4
ON/OFF SWITCH, NEMA 4 QEC-001634 1
FUSE, 1 AMP QEC-002411 1
SEQUENCE CONTROLLER, 10 MIN. QEC-002520 1
INLET VALVE KIT, DIAPHRAGM & SEALS QVA-001934 2
INLET VALVE KIT, DIAPHRAGM ONLY QVA-000468 2
PURGE VALVE KIT, DIAPHRAGM & SEALS QVA-001932 2
PURGE VALVE KIT , DIAPHRAGM ONLY QVA-000308 2
PREFILTER ELEMENT CPNE00425 1*
AFTERFILTER ELEMENT CSNE00425 1*
DESICCANT, 1/8" QSORB-125 460 LBS
35
Back to TOC
QDTH-400 Parts List
115 Volt / 1 Phase / 60 Hz
PART DESCRIPTION PART NO. QTY.
2-WAY AIR INLET VALVE, 2" QVA-000247 2
2-WAY PURGE VALVE, 1.5" QVA-000232 2
AIR OUTLET CHECK VALVE, 2" QVA-000051 2
PURGE CHECK VALVE QVA-002111 2
RELIEF VALVE QVA-000110 2
EXHAUST MUFFLER QRG-000178 2
PRESSURE GAUGE, 2.5" QGM-000373 2
PILOT AIR FILTER ELEMENT QRG-000231 1
3-WAY SOLENOID VALVE QVA-001411 4
ON/OFF SWITCH, NEMA 4 QEC-001634 1
FUSE, 1 AMP QEC-002411 1
SEQUENCE CONTROLLER, 10 MIN. QEC-002520 1
INLET VALVE KIT, DIAPHRAGM & SEALS QVA-001934 2
INLET VALVE KIT, DIAPHRAGM ONLY QVA-000468 2
PURGE VALVE KIT, DIAPHRAGM & SEALS QVA-001933 2
PURGE VALVE KIT , DIAPHRAGM ONLY QVA-000697 2
PREFILTER ELEMENT CPNE00425 1*
AFTERFILTER ELEMENT CSNE00425 1*
DESICCANT, 1/8" QSORB-125 530 LBS
36
Back to TOC
QDTH-500 Parts List
115 Volt / 1 Phase / 60 Hz
PART DESCRIPTION PART NO. QTY.
2-WAY AIR INLET VALVE, 2" QVA-000247 2
2-WAY PURGE VALVE, 1.5" QVA-000232 2
AIR OUTLET CHECK VALVE, 2" QVA-000051 2
PURGE CHECK VALVE QVA-002111 2
RELIEF VALVE QVA-000110 2
EXHAUST MUFFLER QRG-000178 2
PRESSURE GAUGE, 2.5" QGM-000373 2
PILOT AIR FILTER ELEMENT QRG-000231 1
3-WAY SOLENOID VALVE QVA-001411 4
ON/OFF SWITCH, NEMA 4 QEC-001634 1
FUSE, 1 AMP QEC-002411 1
SEQUENCE CONTROLLER, 10 MIN. QEC-002520 1
INLET VALVE KIT, DIAPHRAGM & SEALS QVA-001934 2
INLET VALVE KIT, DIAPHRAGM ONLY QVA-000468 2
PURGE VALVE KIT, DIAPHRAGM & SEALS QVA-001933 2
PURGE VALVE KIT , DIAPHRAGM ONLY QVA-000697 2
PREFILTER ELEMENT CPNE00500 1*
AFTERFILTER ELEMENT CSNE00500 1*
DESICCANT, 1/8" QSORB-125 680 LBS
37
Back to TOC
QDTH-650 Parts List
115 Volt / 1 Phase / 60 Hz
PART DESCRIPTION PART NO. QTY.
2-WAY AIR INLET VALVE, 2" QVA-000247 2
2-WAY PURGE VALVE, 1.5" QVA-000232 2
AIR OUTLET CHECK VALVE, 2" QVA-000051 2
PURGE CHECK VALVE QVA-002112 2
RELIEF VALVE QVA-000110 2
EXHAUST MUFFLER QRG-000178 2
PRESSURE GAUGE, 2.5" QGM-000373 2
PILOT AIR FILTER ELEMENT QRG-000231 1
3-WAY SOLENOID VALVE QVA-001411 4
ON/OFF SWITCH, NEMA 4 QEC-001634 1
FUSE, 1 AMP QEC-002411 1
SEQUENCE CONTROLLER, 10 MIN. QEC-002520 1
INLET VALVE KIT, DIAPHRAGM & SEALS QVA-001934 2
INLET VALVE KIT, DIAPHRAGM ONLY QVA-000468 2
PURGE VALVE KIT, DIAPHRAGM & SEALS QVA-001933 2
PURGE VALVE KIT , DIAPHRAGM ONLY QVA-000697 2
PREFILTER ELEMENT CPNE00650 1*
AFTERFILTER ELEMENT CSNE00650 1*
DESICCANT, 1/8" QSORB-125 650 LBS
DESICCANT, 1/4" QSORB-250 170 LBS
38
Back to TOC
QDTH-750 Parts List
115 Volt / 1 Phase / 60 Hz
PART DESCRIPTION PART NO. QTY.
2-WAY AIR INLET VALVE, 2.5" QVA-000241 2
2-WAY PURGE VALVE, 1.5" QVA-000232 2
AIR OUTLET CHECK VALVE, 2.5" QVA-002069 2
PURGE CHECK VALVE QVA-002112 2
RELIEF VALVE QVA-000111 2
EXHAUST MUFFLER QRG-000178 2
PRESSURE GAUGE, 2.5" QGM-000373 2
PILOT AIR FILTER ELEMENT QP-025-10 1
3-WAY SOLENOID VALVE QVA-001411 4
ON/OFF SWITCH, NEMA 4 QEC-001634 1
FUSE, 1 AMP QEC-002411 1
SEQUENCE CONTROLLER, 10 MIN. QEC-002520 1
INLET VALVE KIT, DIAPHRAGM & SEALS QVA-001935 2
INLET VALVE KIT, DIAPHRAGM ONLY QVA-000489 2
PURGE VALVE KIT, DIAPHRAGM & SEALS QVA-001933 2
PURGE VALVE KIT , DIAPHRAGM ONLY QVA-000697 2
PREFILTER ELEMENT CPNE00800 1*
AFTERFILTER ELEMENT CSNE00800 1*
DESICCANT, 1/8" QSORB-125 740 LBS
DESICCANT, 1/4" QSORB-250 180 LBS
39
Back to TOC
QDTH-1000 Parts List
115 Volt / 1 Phase / 60 Hz
PART DESCRIPTION PART NO. QTY.
2-WAY AIR INLET VALVE, 2.5" QVA-000241 2
2-WAY PURGE VALVE, 1.5" QVA-000232 2
AIR OUTLET CHECK VALVE, 2.5" QVA-002069 2
PURGE CHECK VALVE, 2" QVA-002113 2
RELIEF VALVE QVA-000095 2
EXHAUST MUFFLER QRG-000178 2
PRESSURE GAUGE, 2.5" QGM-000373 2
PILOT AIR FILTER ELEMENT QP-025-10 1
3-WAY SOLENOID VALVE QVA-001411 4
ON/OFF SWITCH, NEMA 4 QEC-001634 1
FUSE, 1 AMP QEC-002411 1
SEQUENCE CONTROLLER, 10 MIN. QEC-002520 1
INLET VALVE KIT, DIAPHRAGM & SEALS QVA-001935 2
INLET VALVE KIT, DIAPHRAGM ONLY QVA-000489 2
PURGE VALVE KIT, DIAPHRAGM & SEALS QVA-001933 2
PURGE VALVE KIT , DIAPHRAGM ONLY QVA-000697 2
PREFILTER ELEMENT CPNE01000 1*
AFTERFILTER ELEMENT CSNE01000 1*
DESICCANT, 1/8" QSORB-125 1150 LBS
DESICCANT, 1/4" QSORB-250 300 LBS
40
Back to TOC
QDTH-1250 Parts List
115 Volt / 1 Phase / 60 Hz
PART DESCRIPTION PART NO. QTY.
2-WAY AIR INLET VALVE, 3" QVA-000242 2
2-WAY PURGE VALVE, 2.5" QVA-000562 2
AIR OUTLET CHECK VALVE, 3" QVA-002065 2
PURGE CHECK VALVE, 2" QVA-002113 2
RELIEF VALVE QVA-000095 2
EXHAUST MUFFLER QRG-000179 2
PRESSURE GAUGE, 2.5" QGM-000373 2
PILOT AIR FILTER ELEMENT QP-025-10 1
3-WAY SOLENOID VALVE QVA-001411 4
ON/OFF SWITCH, NEMA 4 QEC-001634 1
FUSE, 1 AMP QEC-002411 1
SEQUENCE CONTROLLER, 10 MIN. QEC-002520 1
INLET VALVE KIT, DIAPHRAGM & SEALS QVA-001936 2
INLET VALVE KIT, DIAPHRAGM ONLY QVA-000644 2
PURGE VALVE KIT, DIAPHRAGM & SEALS QVA-001935 2
PURGE VALVE KIT , DIAPHRAGM ONLY QVA-000489 2
PREFILTER ELEMENT CPNE01300 1*
AFTERFILTER ELEMENT CSNE01300 1*
DESICCANT, 1/8" QSORB-125 1350 LBS
DESICCANT, 1/4" QSORB-250 350 LBS
41
Back to TOC
QDTH-1500 Parts List
115 Volt / 1 Phase / 60 Hz
PART DESCRIPTION PART NO. QTY.
2-WAY AIR INLET VALVE, 3" QVA-000242 2
2-WAY PURGE VALVE, 2.5" QVA-000562 2
AIR OUTLET CHECK VALVE, 3" QVA-002065 2
PURGE CHECK VALVE, 2" QVA-002113 2
RELIEF VALVE QVA-000095 2
EXHAUST MUFFLER QRG-000179 2
PRESSURE GAUGE, 2.5" QGM-000373 2
PILOT AIR FILTER ELEMENT QP-025-10 1
3-WAY SOLENOID VALVE QVA-001411 4
ON/OFF SWITCH, NEMA 4 QEC-001634 1
FUSE, 1 AMP QEC-002411 1
SEQUENCE CONTROLLER, 10 MIN. QEC-002520 1
INLET VALVE KIT, DIAPHRAGM & SEALS QVA-001936 2
INLET VALVE KIT, DIAPHRAGM ONLY QVA-000644 2
PURGE VALVE KIT, DIAPHRAGM & SEALS QVA-001935 2
PURGE VALVE KIT , DIAPHRAGM ONLY QVA-000489 2
PREFILTER ELEMENT CPNE01503 1*
AFTERFILTER ELEMENT CSNE01500 1*
DESICCANT, 1/8" QSORB-125 1640 LBS
DESICCANT, 1/4" QSORB-250 400 LBS
42
Back to TOC
QDTH-1800 Parts List
115 Volt / 1 Phase / 60 Hz
PART DESCRIPTION PART NO. QTY.
2-WAY AIR INLET VALVE, 4" QVA-000339 2
2-WAY PURGE VALVE, 2.5" QVA-000562 2
AIR OUTLET CHECK VALVE, 4" QVA-002070 2
PURGE CHECK VALVE, 3" QVA-002065 2
RELIEF VALVE QVA-000096 2
EXHAUST MUFFLER QRG-000179 2
PRESSURE GAUGE, 2.5" QGM-000373 2
PILOT AIR FILTER ELEMENT QP-025-10 1
3-WAY SOLENOID VALVE QVA-001411 4
ON/OFF SWITCH, NEMA 4 QEC-001634 1
FUSE, 1 AMP QEC-002411 1
SEQUENCE CONTROLLER, 10 MIN. QEC-002520 1
INLET VALVE KIT, DIAPHRAGM & SEALS QVA-001937 2
INLET VALVE KIT, DIAPHRAGM ONLY QVA-000598 2
PURGE VALVE KIT, DIAPHRAGM & SEALS QVA-001935 2
PURGE VALVE KIT , DIAPHRAGM ONLY QVA-000489 2
PREFILTER ELEMENT CPNE02004 1*
AFTERFILTER ELEMENT CSNE02004 1*
DESICCANT, 1/8" QSORB-125 1840 LBS
DESICCANT, 1/4" QSORB-250 460 LBS
43
Back to TOC
QDTH-2100 Parts List
115 Volt / 1 Phase / 60 Hz
PART DESCRIPTION PART NO. QTY.
2-WAY AIR INLET VALVE, 4" QVA-000339 2
2-WAY PURGE VALVE, 3" QVA-000567 2
AIR OUTLET CHECK VALVE, 4" QVA-002070 2
PURGE CHECK VALVE, 3" QVA-002065 2
RELIEF VALVE QVA-000096 2
EXHAUST MUFFLER QRG-000179 2
PRESSURE GAUGE, 2.5" QGM-000373 2
PILOT AIR FILTER ELEMENT QP-025-10 1
3-WAY SOLENOID VALVE QVA-001411 4
ON/OFF SWITCH, NEMA 4 QEC-001634 1
FUSE, 1 AMP QEC-002411 1
SEQUENCE CONTROLLER, 10 MIN. QEC-002520 1
INLET VALVE KIT, DIAPHRAGM & SEALS QVA-001937 2
INLET VALVE KIT, DIAPHRAGM ONLY QVA-000598 2
PURGE VALVE KIT, DIAPHRAGM & SEALS QVA-001936 2
PURGE VALVE KIT , DIAPHRAGM ONLY QVA-000644 2
PREFILTER ELEMENT CPNE02004 1*
AFTERFILTER ELEMENT CSNE02004 1*
DESICCANT, 1/8" QSORB-125 2200 LBS
DESICCANT, 1/4" QSORB-250 550 LBS
44
Back to TOC
QDTH-2600 Parts List
115 Volt / 1 Phase / 60 Hz
PART DESCRIPTION PART NO. QTY.
2-WAY AIR INLET VALVE, 4" QVA-000339 2
2-WAY PURGE VALVE, 3" QVA-000567 2
AIR OUTLET CHECK VALVE, 4" QVA-002070 2
PURGE CHECK VALVE, 3" QVA-002065 2
RELIEF VALVE QVA-000097 2
EXHAUST MUFFLER QRG-000179 2
PRESSURE GAUGE, 2.5" QGM-000373 2
PILOT AIR FILTER ELEMENT QP-025-10 1
3-WAY SOLENOID VALVE QVA-001411 4
ON/OFF SWITCH, NEMA 4 QEC-001634 1
FUSE, 1 AMP QEC-002411 1
SEQUENCE CONTROLLER, 10 MIN. QEC-002520 1
INLET VALVE KIT, DIAPHRAGM & SEALS QVA-001937 2
INLET VALVE KIT, DIAPHRAGM ONLY QVA-000598 2
PURGE VALVE KIT, DIAPHRAGM & SEALS QVA-001936 2
PURGE VALVE KIT , DIAPHRAGM ONLY QVA-000644 2
PREFILTER ELEMENT CPNE03004 1*
AFTERFILTER ELEMENT CSNE03004 1*
DESICCANT, 1/8" QSORB-125 2640 LBS
DESICCANT, 1/4" QSORB-250 660 LBS
45
Back to TOC
QDTH-3100 Parts List
115 Volt / 1 Phase / 60 Hz
PART DESCRIPTION PART NO. QTY.
ACTUATED 2-WAY INLET VALVE, 6" QVA-002664 2
ACTUATED 2-WAY PURGE VALVE, 3" QVA-002662 2
AIR OUTLET CHECK VALVE, 6" QVA-002664 2
PURGE CHECK VALVE QVA-002662 2
RELIEF VALVE QVA-000097 2
EXHAUST MUFFLER QRG-000179 2
PRESSURE GAUGE, 2.5" QGM-000373 2
PILOT AIR FILTER ELEMENT QP-025-10 1
4-WAY SOLENOID VALVE QVA-003042 4
ON/OFF SWITCH, NEMA 4 QEC-001634 1
FUSE, 1 AMP QEC-002411 1
SEQUENCE CONTROLLER, 10 MIN. QEC-002520 1
PREFILTER ELEMENT CPNE03006 1*
AFTERFILTER ELEMENT CSNE03006 1*
DESICCANT, 1/8" QSORB-125 3120 LBS
DESICCANT, 1/4" QSORB-250 780 LBS
46
Back to TOC
Notes
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
Quincy Compressor Products: 217.222.7700
E-mail: info@quincycompressor.com © 2006 Quincy Compressor, an EnPro Industries company
Website: www.quincycompressor.com All Rights Reserved. Litho in U.S.A.