HVAC Load Calculation E20 Form Sheet
HVAC Load Calculation E20 Form Sheet
= 0.20
= 0.80
CFM Ventilation
30.00 No = 2.00 = 60.00
22.00 Sqft x 11.17 = 245.74
= 184.96
128.23 x 184.96 x1/60 = 395.30
CFM Infiltration
1.00 x cfm/door = 0.00
1.00 x cfm/door = 0.00
1.00 x 1.00 cfm/door = 1.00
1.00 x cfm/ft = 0.00
1.00
Supply CFM from Machine
= 0.92
Apparatus Dew Point (ADP)
=
= 56.30
Dehumidified Rise
= 6.48
= 699.94 CFM
= 328.97 L/s
= 1.24 TR
= 1.24 TR
HVAC LOAD CALCULATION - E20 FORM SHEET
PROJECT
LOCATION U.A.E (DUBAI)
CLIENT XYZ
CONSULTANT ABC
126.00
Area or Sun Gain or
Item
Quantity Temp. Diff.
ROOM HEAT Q= U*A*Δ
ROOM SENSIBLE HEAT
Solar Gain - Glass Area ΔT
Glass - N 15.00 SqFt x 13.00
Glass - NE SqFt x
Glass - E SqFt x
Glass - SE SqFt x
Glass - S SqFt x
Glass - SW SqFt x
Glass - W 15.00 SqFt x 145.00
Glass - NW SqFt x
Skylight SqFt x
Solar & Transmission Gain - Walls & Roof
Wall - N 225.00 SqFt x 26.50 F
Wall - NE SqFt x F
Wall - E SqFt x F
Wall - SE SqFt x F
Wall - S SqFt x F
Wall - SW SqFt x F
Wall - W 250.00 SqFt x 35.50 F
Wall - NW SqFt x F
Roof 360.00 SqFt x 49.00 F
Transmission Gain - Except Walls & Roof
All Glass 30.00 SqFt x 32.00 F
Partition 150.00 SqFt x 27.00 F
Ceiling SqFt x F
Floor 360.00 SqFt x 27.00 F
INFILTRATION AND BY PASSED AIR
Infiltration CFM x 32.00 T.Diff
Outside Air 31.60 CFM x 32.00
Internal Heat
People 2.00 Nos. x 230.00 Btu/Hour Per Person
Lighting 360.00 SqFt x 1.00 W/SqFt
Equipments 1.00 200.00 Watts
Power kW/Hp x
Sub Total
Factor
Effective Room Sensible Heat
ROOM LATENT HEAT
Infiltration 0.00 CFM x 12.00 Gr/Lb
Outside Air 31.60 CFM x 12.00 Gr/Lb
People 2.00 Nos. x 120.00 Btu/Hour Per Person
Sub Total
Factor
Effective Room Latent Heat
EFFECTIVE ROOM TOTAL HEAT
OUTSIDE AIR HEAT
Sensible 31.60 CFM x 32.00 F(TD)
Latent 31.60 CFM x 12.00 Gr/Lb
OUTSIDE AIR TOTAL HEAT
GRAND SUB-TOTAL HEAT
Factor
GRAND TOTAL HEAT
= 0.12
= 0.88
FM Ventilation
No = 2.00 = 10.00
Sqft x 360.00 = 21.60
=
x 0.00 x1/60 = 0.00
CFM Infiltration
x cfm/door = 0.00
x cfm/door = 0.00
x 1.00 cfm/door = 0.00
x cfm/ft = 0.00
0.00
y CFM from Machine
= 0.97
tus Dew Point (ADP)
=
= 54.70
humidified Rise
= 17.86
= 478.78 CFM
= 225.03 L/s
= 0.92 TR
= 0.92 TR