NF C 15-100 standard
Guide 2023
se.com/en
Summary
Implementation examples
• Design a GTL........................................................ .........................28
• Distribution tables .............................................. ..................30
• Communication boxes .............................................. .............34
• The provisions of the decree apply to new buildings for which the
building permit application is submitted from 1erJuly 2012 and to existing
buildings from 1erJanuary 2015.
• This concerns homes with more than two dwellings (as well as tertiary
buildings) with secure access parking spaces (private garages, enclosed and
covered car parks, etc.)
Click
se.com/en
or scan
the QR code
Minimum equipment
The facilities concerned The NF C
15-100 standard applies:
• new buildings
• new installations in existing buildings:
- total renovation
- modifications, extensions (and existing parts concerned).
• more informationupage 18
Stay
• When the kitchen is open to the living
room, the surface area of the living 1 Or Or 5 including 1 2
room is equal to the total surface area • the power supply can end up in the • 5 mini with 1 per 4 m2 • near at least one
minus 8 m2 ceiling, on a wall, on the floor, or via a (ex: 7 for stay 27m2) power outlet
controlled socket • customization possible • at a heighty1.30 m
• lighting control between 0.90 and 1.30 m • for living room > 28 m2, with 1 mini of 7
• + 1 in the immediate vicinity of the lighting
control
(can be counted in the 5)
• customization possible for stay > 40
m2, with 1 mini of 7
Bathroom -
1 Or 1 +1
• the power supply can end up in the ceiling, • authorized outside volume
on a wall, on the floor • + 1 in the room between 0.90 and 1.30 m,
• controlled power outlet prohibited in the immediate vicinity of the lighting
• lighting control between 0.90 and 1.30 m control if the latter is inside
Traffic, WC -
Kitchen
1 Or Or 6 including 1 1, 2 or more
• the power supply can end up in the • 6 including 4 above the work surface • minimum 1 for a T2
ceiling, on a wall, on the floor, or via a • If surfacey4 m², 3 bases are allowed • minimum 2 in different
controlled socket • in the immediate vicinity of the lighting rooms for a T3 or larger
• lighting control between 0.90 and 1.30 m control (may be counted in the 6)
• near at least one power
Bedrooms outlet
• at a heighty1.30 m
1 Or Or 3 +1
• the power supply can end up in the • installation on the outskirts
ceiling, on a wall, on the floor, or via a • + 1 in the immediate vicinity of the lighting
controlled socket control
• lighting control between 0.90 and 1.30 m
1 2 3 Or
• dedicated to for washing machine, dryer,
• at a heighty1.30 m
multimedia uses dishwasher or oven
or direct feed
• socket base at a heighty1.30 m
• for the washing machine and dryer:
• conditions for installing the water
- near water inlets and outlets
heater in the bathroomupages 14 and 24
- excluding volume only if they are in the
• for each of the following applications
bathroom.
when planned:
• when the location of the freezer is defined,
- electric water heater
provide a specialized circuit with 1 specific 30 mA
- electrical outlet circuit of the
differential device, preferably with reinforced
technical housing duct
immunity (example: Vigi Fsi circuit breaker)
- - boiler and its auxiliaries
• At a heighty1.30 m
- heat pump
- air conditioner
- electric heater (see 10.1.3.5)
1 Or - bathroom heater
for the stove or hob (32 A mono or 20 A tri) - pool
- external circuits (powering one or more
- • Socket base at one heighty1.30 m uses not attached to the building, for
example lighting, automatic gate, etc.)
- - -
- - - -
Control device
10.1.3.8.1
• Each room equipped with a lighting point must have at least one control circuit.
The room control device must be fixed and may be manual or automatic.
• All manual functional control devices must be located at a height between 0.90 m
and 1.30 m from the ground.
• Are concerned :
- switches controlling lighting, roller shutters, room thermostats, etc.
Lighting point
Non-specialized power outlets
10.1.3.2
10.1.3.3.2
• At least 1 point (generally on the ceiling), equipped with a DCL base + DCL socket.
• 6 bases powered from a dedicated outlet, 4 of which
• Special case (10.1.3.2.2.): in the event of a total renovation or technical
are to be distributed above the work surface(s).
impossibilities of ceiling construction. the power supply for the lighting in the
• Installation prohibited above the sink and fires or
room can come to the walls or to a controlled socket or both.
hotplates
• If the kitchen surface isy4m2, 3 bases are allowed.
Control device
10.1.3.8.1 • 1 additional base identified for the hood can be
• Each room equipped with a lighting point must have at least one control circuit. placed above the cooking hobs provided it is
The room control device must be fixed and may be manual or automatic. installed at least 1.80 m away.
• An uncontrolled 16 A 2P+E socket outlet must be
• A lighting control switch must be located at the entrance to each room. placed in the immediate vicinity of the lighting control
device.
• All manual functional control devices must be located at a height between 0.90 m • The axis of the power socket bases must be located at a
and 1.30 m from the ground. height less than or equal to 1.30 m from the ground, with the
• Are concerned : exception of the additional base dedicated to the hood.
- switches controlling lighting, roller shutters, room thermostats, etc.
Unica System+
Discover the offer
• on the sitese.com/fr/usp
• on the online catalogflipbook.se.com/gamme/usp
Bedroom/office
Lighting point
10.1.3.2
• at least 1 point (generally on the ceiling), equipped with
a DCL base + DCL socket.
• special case (10.1.3.2.2.): in the event of a total
renovation or technical impossibilities of ceiling
construction, the power supply for the lighting in the
room may end up at the level of the walls or a
controlled power outlet or both.
Communication socket
11.2.1.1
• For T2, 1 RJ45 socket base.
• For T3 and above, at least 1 RJ45 socket base in 2
bedrooms or offices.
• The axis of the communication socket bases must be located
at a height less than or equal to 1.30 m from the ground.
• RJ45 socket (11.2.1.1.): location near a 16 A power
socket base.
• Optional coaxial television socket.
Odace
Discover the offer:
+
• on the sitese.com/fr/oda
• on the online catalog
flipbook.se.com/gamme/oda uHow to replace a socket with an Odace e-reader?
Use materials
701.3.7 / 701.3.1
• Authorized in volumes 0 - 1:
- if SELV 12 Vac or 30 Vcc
- and IP X7 in volume 0
- and IP X4, IP X5 in volume 1
• Authorized in volume 2: if class II - DCL if IP X4.
• Cannot be installed on aprons, benches and bathtub
or shower niches.
• All manual functional control devices must be located at a height between 0.90 m responsibility of the project manager.
and 1.30 m from the ground. • See also the “Specialized circuits for large household
• If this equipment is provided, the corresponding power points must be made on . if the lighting is timed, the switching off must
a specialized departure. be gradual.
- gradual or stepwise reduction, or by any other
Control device system of notice of extinction.
- lighting and service control equipment and devices,
10.1.3.8.1
and access control or communication systems between
• Each room equipped with a lighting point must have at least one control circuit.
visitors and occupants:
The room control device must be fixed and may be manual or automatic.
. identified by an indicator light,
. more than 0.40 m from a recessed corner of walls or
• A lighting control switch must be located at the entrance to each room.
any other obstacle to the approach of a wheelchair, .
• All manual functional control devices must be located at a height between 0.90 m
at a height of between 0.90 m and 1.30 m.
and 1.30 m from the ground.
- lighting control devices can be either automatic or
• Are concerned :
manual.
- switches controlling lighting, roller shutters, room thermostats, etc.
• Schneider Electric strongly recommends the
installation of arc detection devices complying with the
- access control or communication system devices, etc.
IEC 62606 standard for the protection of circuits where
• Control and service devices located on accessible exterior paths must be
the risk of fire outbreaks is greatest:
identifiable, in particular by special lighting or visual contrast.
- the circuits taken from bedrooms and living rooms
• This includes access control or communication systems between visitors and
which are requested and unsupervised departures
occupants.
- circuits exposed to attacks (protruding cables,
• A warning light meets this requirement.
outdoors, etc.).
VMC - 1.5mm2 2A
special cases 1.5mm2 up to 16 A
Resi9
Discover the offer:
• on the sitese.com/fr/ri9x
• on the online catalog
flipbook.se.com/gamme/ri9x
Resi9 XP
Discover the offer:
• on the sitese.com/fr/ri9p
• on the catalog
flipbook.se.com/gamme/ri9p
Specialized tours
Every major appliance must be powered by a specialized circuit. At least
• In black: normative provisions relating to NF
4 specialized circuits must be provided (10.1.3.4.).
C 15-100 and the regulations in force.
1 cooking circuit • In fuchsia: regulations relating to accessibility for
disabled people
• 1 cooker or hob supply circuit alone on connection box or 32 A single or 20 A three • In blue: recommendations and comments
socket.
3 circuits
with 16 A socket base
• For powering appliances such as washing machines, dishwashers, dryers and
independent ovens.
Other circuits
• Other specialized circuits must be implemented if the applications are planned
(10.1.3.4.):
- water heater,
- power outlet circuit of the technical housing duct,
- boiler and its auxiliaries,
- heat pump,
- air conditioner,
- electric heater,
- bathroom heater (e.g. towel dryer)
- pool,
- external circuits (power supply for one or more uses not attached to the
building, e.g. garden lighting, automatic gate, etc.),
- electric roller shutters,
- "banne" blinds,
- alarms, controls, etc.
- VMC when it is not collective,
- divisional tables,
- electric vehicle charging circuits,
- freezer.
• When the location of the freezer is defined, it is appropriate to provide 1 specialized
circuit with 1 30 mA differential device specific to this circuit, preferably with
reinforced immunity (possibility of power supply by separation transformer).
Resi9 XP
Discover the offer:
• on the sitese.com/fr/ri9p
• on the catalogonline flipbook.se.com/gamme/ri9p
Electric heater with pilot wire - electric vehicle charging infrastructure (IRVE)
where applicable.
• All heating circuits, including the pilot wire, are
Type A or Type AC • for other circuits.
placed per control zone under the same 30 mA.
Type B • instead of Type A for certain applications
powered through a three-phase rectifier.
Resi9 Resi9 XP
Discover the offer: Discover the offer:
• on the sitese.com/fr/ri9x • on the sitese.com/fr/ri9p
• on the catalog • on the catalog
flipbook.se.com/gamme/ri9x flipbook.se.com/gamme/ri9p
Outlets
Location
• At least 1 16 A power socket must be placed near each communications or
television socket. (10.4)
The axis of the bases must be located at a height less than or equal to 1.30
m from the ground, with the exception of the base dedicated to the hood.
Fixing power outlets For each room of the living unit of the accommodation, a 16 A 2P+E socket socket
(10.1.3.9.1.) which is not controlled must be placed in the immediate vicinity of the lighting
• Fixing by claws prohibited since 1erJune 2004. control device.
• Recommended use of mixed flush-mounting boxes.
Limitation of the number of 16 A socket bases, not
specialized in the same circuit (10.1.3.3.3.)
• 8 sockets, if 1.5 mm conductors2.
• 12 sockets, if 2.5 mm conductors2.
• 6 sockets with 2.5 mm conductors2for the dedicated kitchen circuit.
Unica
Discover the offer:
• on the sitese.com/fr/unic
• on the online catalog
uHow to install an Ovalis flush socket? flipbook.se.com/gamme/unic
The axis of the bases must be located at a height less than or equal to 1.30 m from the ground.
Video
Lighting
Minimum number of lighting circuits • In black: normative provisions relating to NF C 15-100 and
(10.1.3.2.4.) the regulations in force.
• At least 2 circuits for housing from 2 main • In fuchsia: regulations relating to accessibility for disabled people
rooms. • In blue: recommendations and comments
20
lux lux
20
• All manual functional control devices must
• A lighting device must make it possible, when natural lighting is not sufficient, to
be located at a height between 0.90 and 1.30
ensure an illuminance value measured on the ground of at least 20 lux at any point of
m from the ground.
the route.
• This concerns lighting control switches.
• This lighting device can be manually or automatically controlled.
• Control and service devices located on accessible exterior paths must be
• A lighting control device must be located at the
identifiable, in particular by special lighting or visual contrast.
entrance to each room.
• In the case of premises containing a bathtub or
• This includes access control or communication systems between visitors and
shower, the manual control device can, to comply with
occupants.
the rules relating to volumes, be placed outside.
• 1 LED meets this requirement.
Resi9 Resi9 XP
Discover the offer: Discover the offer:
• on the sitese.com/fr/ari9 • on the sitese.com/fr/xri9
• on the online catalogflipbook.se.com/gamme/ari9 • on the online catalogflipbook.se.com/gamme/xri9
Exemptions
• For exemptions, refer to article 10.1.3.2.5.
Multifix Air
Discover the offer:
• on the sitese.com/fr/mfa
• on the online catalogflipbook.se.com/gamme/mfa
Schemas (10.1.5.2)
• Establish a diagram, diagram or table for the user.
• A single-line diagram comprising the elements below meets this
obligation:
- nature and type of protection and control devices,
- adjustment current and sensitivity of protection and control devices,
- forecast power,
- nature of pipes for external circuits,
- number and section of conductors,
- application (lighting, sockets, etc.),
- serviced premises (bedroom 1, kitchen, etc.).
Video