MET INSTRUMENTS CALIBRATION CENTRE

A uNn OF VOLTECH ENGINEERS PVT, LTD.

�ET
1S0/IEC 17025 : 2017 - NABL Accredited Laboratory
At 5th Floor, 'Voltech Eco Tower',
No.2/429, Mount Poonamallee Road, Ayyappanthangal,
Chennai - 600056, Tamil Nadu.
Phone +91-44-43978021
CALIBRATION SERVICES Fax +91-44-42867746
CERTIFICATE NUMBER
CC2904

Email meticc@voltechgroup.com
Web www.voltechgroup.com
GST No: 33AACCV0108M1ZK

CALIBRATION CERTIFICATE
SRF No: 75 Certificate No :MET/23/L/308
Mis.Voltech Engineers Pvt Ltd,
Customer Name And Address "Voltech Eco Tower"No.2/429,Mount Poonamalle
Road,Ayyapanthangal,Chennai-600 056
Customer Reference DC No.: 1303
ULR Number CC-290423000000308F
Details of the lnstrument
Description High Voltage Test Kit
Make Sudharsan
Model 30/40KV
Serial number 18/96
Identification Number VE-4749
Range Vide Respective Calibration Table
Resolut!cf! Vide Respectiv:.:: Calibration Table
Accuracy Vide Respective Calibration Table
Equipment Received on 15.03.2023
Condition of the equipment on receipt Good
Date of calibration 22.03.2023
Date of next calibration suggested 21.03.2024
Date of Certificate issued 23.03.2022
Calibration Environments
Tempernture 24.3°C
Relative humidity 55%RH
Master Instrument Details Master I
Description High Voltage Probe With Multimeter
Make Agilent
Type / Model 34136A
Serial number 20140105/29930160
Report Number TSC/22-23/20097-7
Calibration valid till 09.08.2023
Traceable to Transcal Bangalore
Method of Calibration
I. The instrument was calibrated as per W0rk Instruction no. MET!CC/WI-E12

--, ----�
2. The Standards used are traceable to National / I
Calibrated By

'�)
V Mohan K.Saravanakumar
Team Member Quality Manager
Page OJ of 02
tncT tlt$numcilrs cnuonnflofl cctTRC

ffi
n u|nof uoll€(fi cllclxc€ffi pw. ltD.
ISO/IEC 17025 : 2017 - NABL Accredited Laboratory
At 5th Floor, 'Voltech Eco Tower',
No.21429, Mount Poonamallee Road, Ayyappanthangal,
Chennai - 600056, Tamil Nadu.
CALIBRATION SERVICES :
Phone +91-44-43978021
Fax : +91-44-42867746 CERTIFICATE NUMBER
cc2904
Email : meticc@voltechgroup.com
Web : www.voltechgroup.com
GST No : 33AACCV0108M1ZK

CAII BRATION CERTI FI CATE

Certificate No :MET/23 lL/308


DeniehJoltasc
UUC Mean Deviation Expanded Coverage
Range Standard Reading Deviation
Value Allowed (+) Uncertainty Factor
KV KV KV KV o/
KV /o K
l.l89l I -0. I 89 0.500 2.3812 2.00
10 10.218 l0 -0.218 1.000 2.4236 2"00
20 20.t48 20 -0.148 1.000 2.5104 2.00
g0 30.633 30 -0.633 1.50 2.5425 2.00
35 3s.695 35 -0.695 1.80 2.7022 2.00

AC High Voltase@s0k
IIUC Mean Deviation Expanded Coverage
Range Standard Reading Deviation
Value Allowed (+) Uncertainty Factor
KV KV KV KV o/
KV /o K
I 1.0199 I -0.0199 0.300 0.8327 2.00
t0 10.208 l0 -0.2080 0.500 l. I 553 2.00
t5 r5.1 13 l5 -0.1 1 3 ' 0.s00 1.1562 2.00
20 20.299 20 -0.299 r.00 2.0835 2.00
25 25.289 25 -0.289 2.80 5.6306 2.00
Remarks
1. The above UUC was calibrated at Lab"

2. UUC is defined as Unit Under Calibration.


3. The Expanded uncertainty of measurement evaluated at a confidence level of approx.-9|%o
4. The Calibration Certificate shall not be reproduced except in full without written approval of MET ICC.
5. The Uncertainty evaluation has been carried out in accordance with ISOAEC 1702 5:2017 requirements
6. The above Expanded Uncertainty inclucies Repeatability,Accuracy and Resolution
7. The above results relate only to the items calibrated and Catibration points are taken as per customer requirements

Calibrated By
o4
K.Saravanakumar

You might also like