Plumbing system noise is a common irritant to building owners and tenants. Three main factors contribute to this problem: 1) lack of awareness
on the part of owners/developers and design teams regarding the application of specific products and practical installation solutions; 2)
lack of contractor awareness and training regarding the application of specific solutions; and 3) design teams fearful of uncertain solutions
and seemingly uncontrollable expenses. On many high-end projects, building design teams and contractors have faced litigation because of
insufficient or poorly installed attempts at plumbing noise mitigation.
However, the plumbing industry has made much advancement regarding the issue of plumbing noise mitigation. Resources are available
from a product and service standpoint that can help the engineering community find application solutions, plumbing installation detail drawings,
and third-party laboratory test data to recognized International Organization for Standardization (ISO) standards.
To a building occupant or perspective buyer, the perceived quality of a building is based on numerous observations. A building deemed
excessively noisy will likely be viewed as low quality. In the extreme, this could make what developers consider an otherwise Class A property
unmarketable. In cases where building occupants are dissatisfied with the comfort of a building, one of the common complaints includes
noise from adjoining tenants. Noise through floor and ceiling systems and through walls is the main issue. The noise sources and solutions
vary widely. Issues can be very difficult and costly to remedy, especially after the fact. A quiet building does not usually happen accidentally,
and steps to ensure success must be planned from the early stages of design and specification. Attention to acoustics and the successful
implementation of effective noise control are added value.
Table 10-1 provides recommended noise criteria (NC) levels for interior spaces. TABLE 10-1
Recommended Background Noise Criteria for
Plumbing system noise mitigation is inconsistently addressed in many buildings, Interior Spaces
although it can be one of the most intrusive and difficult sounds to mitigate. Varying
levels of plumbing noise are expected and tolerated without complaint by many people. Space Type Noise Criteria
Noise generated within a tenant’s or owner’s own space and resulting from their use Conference room, training room NC 30
of plumbing fixtures is often tolerated. Conversely, intrusive plumbing noise from an
adjoining space that results in sleep disturbance or interruption, or even in some cases Fitness center NC 40
where it is simply identifiable, may be regarded as annoying. In multifamily residential Lobby and circulation areas NC 40
buildings, plumbing noise is a significant source of complaint.
Tenant shell space NC 40
Consideration should be given to the planned future use of shelled spaces. For
example, a PVC roof drainage system may not be the right choice for a future planned Restroom, locker NC 45
sound-sensitive space. Parking 70 dBA
Table 10-2 lists comparative noise levels common to various environments.
Source: 2019 ASHRAE Handbook—HVAC Applications, Chapter 48
Note: For verification purposes, these criteria apply 5 feet above the floor and
NOISE at least 3 feet from sound-reflective surfaces.
Noise issues within a building fall into one of two categories: airborne noise and structure-
borne noise. Airborne noise sources include voices, amplified music, televisions, and
radios. The ability of a construction (such as a door, wall, or window) to reduce airborne noise passing through it is quantified by the metric
transmission loss, which is usually measured over a number of different frequency bands that are used to generate a single-figure, Sound
Transmission Class (STC) rating. The higher the STC, the better the system is at isolating airborne noise. However, the use of STC ratings
is generally not recommended for noise from plumbing and other building systems because the frequency content of this noise is dissimilar
to that of the human voice.
Structure-borne noise is produced when part of the building fabric transmits vibration, which is subsequently heard as radiated noise.
Examples are footsteps on hard floor surfaces like tile or bare timber, banging doors, scraping furniture, and plumbing noise. Controlling
structure-borne noise is usually achieved through vibration isolation.
FIGURE 10-1 Additionally, piping must be isolated from contact with the edges of
Pipe Isolation Through Framing Member the floor penetration, whether wood, concrete, or metal pan decking. This
typically is done with the use of acoustical sealant within the annular space
surrounding the piping. When the floor system carries a fire rating, the
sealant and UL assembly must meet or exceed the required fire rating.
Failure to eliminate contact in the annular space can negate any attempt
at effective vibration isolation. Clearly express this requirement within
the project specification and installation detail pages. (See Figures 10-4
and 10-5.)
A number of methods can be used to reduce noise from piping to
support hangers and thus to the supporting structure. One method is the
use of spring or rubber-isolated hanger rod attachments at the structure
above. Another method is by isolating the noise transfer by installing
felt, rubber, or neoprene material within the hanger (between the pipe
and the hanger). When applying isolation lining between the hanger and
the piping, use only materials engineered and tested for this application.
Also, give consideration to where the isolators are located. If they are
located within a present or future return air plenum, verify that they are
ASTM E84 compliant. As a caution, some pipe support products contain
plasticizers such as plasticized vinyl, which may have a detrimental effect
FIGURE 10-2 on the drainage piping (e.g., CPVC lab drainage materials).
Resilient Pipe Isolation
FIGURE 10-4
Riser Clamp Isolation
NEOPRENE OR
RUBBER RISER PAD
FIGURE 10-5
Vertical Cast Iron Stacks and Water Risers
FIGURE 10-10
Surface-Mounted Pipe Clamp FIGURE 10-13
Riser Clamp Isolation
FIGURE 10-11
Horizontal/Vertical Piping Isolation
FIGURE 10-14
Vertical Cast Iron Stacks and Water Risers
FIGURE 10-18
Water, Vent, Waste
FIGURE 10-17
Horizontal Overhead
FIGURE 10-19
Horizontal Joist Bay Support
FIGURE 10-29
Icemaker Box
FIGURE 10-26
Typical Floor-Mounted Toilet Flange
FIGURE 10-27
Floor-Mounted Bathtub or Shower Isolation
FIGURE 10-30
Laundry Outlet Box
FIGURE 10-35
Bathtub/Shower Rough-In
FIGURE 10-32
Sound-Deadening Pads Reduce Noise
from Stainless Sinks
Note: The sound-deadening pads are made of a rubber compound and FIGURE 10-36
significantly reduce noise from clanging dishes and from running water Shower Rough-In
and disposals.
Source: Reprinted with the permission of Kohler. All rights reserved.
FIGURE 10-33
Typical Bathtub Spout
TABLE 10-3
Recommended Isolator Types and Static Deflections for Pumps
Indicated Floor Span, ft (m)
Slab on Grade
Power Up to 20 ft (6 m) 20–30 ft (6–9 m) 30–40 ft (9–12 m)
Pump Speed,
Range,
Type rpm Minimum Minimum Minimum Minimum
hp (kW) Base Isolator Base Isolator Base Isolator Base Isolator
Deflection, Deflection, Deflection, Deflection,
Typea Typeb Typea Typeb Typea Typeb Typea Typeb
in. (mm) in. (mm) in. (mm) in. (mm)
Packaged
0.75 0.75 1.50 2.50
pump All All A 3 A 3 A 3 C 3
(19) (19) (38) (64)
systems
a. Base Type: A = No base; isolators attached directly to equipment; B = Structural steel rails or base; C = Concrete inertia base
b. Isolator Type: 1 = Neoprene or rubber pad (not used); 2 = Neoprene or rubber mount/floor isolator or hanger; 3 = Spring floor isolator or hanger
Source: ASHRAE Handbook—HVAC Applications, Chapter 48
FIGURE 10-42
FIGURE 10-40 General Mounting Detail for End-Suction, Close-
Spring-Mount Isolator Coupled Pump
FIGURE 10-41
Neoprene Pad Isolator
FIGURE 10-43
Examples of Flex Connectors
be carefully considered. Coordination with the project architect and the plumbing/mechanical design team should occur early in the design
stage. For some projects, an acoustical consulting firm may be an essential addition to the project team. These specialists, or acousticians, are
typically members of the Acoustical Society of America and/or the Institute of Noise Control Engineering.
Party and Plumbing Walls
Ideally, plumbing walls should not be located near quiet rooms. Party walls should be constructed to minimize sound transfer from one tenant
to another or from common areas to tenant spaces and vice versa. Consider designs and configurations including increased physical separation
(air space) between walls, staggered studs, dense insulation within wall cavities, multiple layers of sheetrock, and a variety of resilient channel
configurations.
RESOURCES
• ISO 3822: Acoustics—Laboratory tests on noise emission from appliances and equipment used in water supply installations—Part
1: Method of measurement
• Sound & Vibration Magazine
• UPC Section 609.10
• IPC Section 604.9
• 2019 ASHRAE Handbook—HVAC Applications, Chapter 48: Noise and Vibration Control
• Noise and Vibration Control, Leo L. Beranek, McGraw-Hill
• Handbook of Acoustical Measurements and Noise Control, Cyril M. Harris, McGraw-Hill
• Noise and Vibration Control in Buildings, Robert S. Jones, McGraw-Hill
• Noise Control in Building Services, Alan Fry, Sound Research Laboratories
• ASTM E413: Classification for Rating Sound Insulation
• ASTM E90: Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and
Elements
Expiration date: Continuing education credit will be given for this examination through March 31, 2024.
Thank you to Robert Bernstein, CPD for authoring this month’s quiz.
1. A type of drainage system piping that is commonly used to mitigate 7. The most noise in gravity drainage is generated when:
noise is: A.) Liquids and solids hit fittings at changes of direction
A.) PVC Schedule 40 or 80 B.) Vent systems are insufficient to relieve pressure build ups
B.) Copper tube C.) Velocity exceeds 5 feet per second
C.) Cast Iron Soil Pipe D.) Pressure exceeds 60 PSI
D.) Galvanized steel
8. Which contributes to noise generation in domestic water systems?
2. Pipe lagging can be done by installing: A.) Defective gas pressure regulators
A.) A layer of dense limp material surrounding the insulation B.) Staggered studs
B.) A layer of carpet padding secured by duct tape C.) Obstructions in valves and equipment
C.) An additional layer of foam rubber or fiberglass insulation D.) Insufficient storage capacity
D.) Securing piping to structure with aircraft cable and lag bolts
9. Inertia base devices serve to:
3. Using Sound Transmission Class ratings is recommended for A.) Reduce effects of reaction forces
plumbing noise because: B.) Weigh twice as much as the items
A.) Plumbing noise is structure-borne C.) Raise the center of gravity of the isolated system
B.) Plumbing noise is airborne D.) All of the above
C.) Both A & B
D.) Neither A nor B 10. Stainless steel sinks can be equipped with ____ to reduce noise.
A.) Isolated pipe clamps
4. A method to minimize noise from plumbing in party walls is: B.) Steel springs
A.) Pipe in Muzak to adjacent spaces C.) Acoustical anchor points
B.) Increase physical separation between walls D.) Sound deadening pads
C.) Install lagging on walls
D.) All of the above 11. CPVC expands and contracts:
A.) Half as much as copper tubing
5. A packaged pump system installed on Slab on Grade construction B.) 4 times as much as copper tubing
should be provided with: C.) Twice as much as copper tubing
A.) Concrete inertia base, and spring floor isolator or hanger D.) A quarter the rate of copper tubing
B.) No base, and spring floor isolator or hanger
C.) No base, and neoprene or rubber pads 12. When deflections of 6” or more are required, _____ should be used.
D.) Concrete inertia base, and neoprene or rubber pads A.) Inertia base devices
B.) Bladder tanks
6. Noise from expansion and contraction due to temperature changes is C.) Air springs
especially a problem with : D.) Pre-compressed glass fiber pads
A.) Ferrous piping
B.) Thermoplastic piping
C.) Core and Shell construction
D.) Unconditioned structures