Solenoid valves
Type EVU
Approvals yy UL Recognized Component (Canadian and US) yy Pressure Equipment Directive (PED) 2014/68/EU
Min.
6 W AC 14 W DC [°C] [bar] [m3/h]
2
) MOPD for media in gas form is approx. 8 bar higher.
3
) For coil 208-240 V, 60 Hz, MOPD is 17 bar.
Rated capacity
[kW]
Liquid Suction vapour Hot gas
Type
R404A/
R404A/
R404A/
R407C
R407C
R407C
R410A
R410A
R410A
R134a
R134a
R134a
R507
R507
R507
R22/
R22/
R22/
EVU 1 2.01 1.85 1.40 2.01 0.23 0.16 0.20 0.29 0.93 0.73 0.75 1.40
EVU 2 4.02 2.96 2.24 3.22 0.45 0.33 0.40 0.58 1.85 1.47 1.51 2.79
EVU 3 6.03 5.55 4.20 6.03 0.68 0.49 0.60 0.87 2.78 2.20 2.26 4.19
EVU 4 10.05 9.25 7.00 10.05 1.30 0.82 1.00 1.45 4.63 3.67 3.77 6.99
EVU 5 13.07 12.03 9.10 13.07 1.46 1.06 1.30 1.89 6.01 4.77 4.90 9.81
EVU 6 16.08 14.80 11.20 16.08 1.80 1.30 1.60 2.32 7.40 5.86 6.02 11.18
EVU 8 20.10 18.50 14.00 20.10 2.25 1.63 2.00 2.90 9.25 7.33 7.53 13.97
Rated liquid and suction capacity is based on:
- evaporating temperature te = -10 °C,
- liquid temperature ahead of the valve tl = 25 °C,
- pressure drop in valve ∆p = 0.15 bar.
Single pack
1 product in a box with installation guide
Multi pack
box with x pieces single pack
(can be split)
Industrial pack
x pieces in one box (cannot be split)
Capacity
Liquid capacity Qo [kW]
Liquid capacity Ql [kW]
Type at pressure drop across valve ∆p [bar]
R22 / R407C
EVU 1 1.64 2.01 2.33 2.85 3.29 3.68
R134a
EVU 1 1.52 1.85 2.14 2.63 3.03 3.39
R22 / R407C 0.76 0.82 0.88 0.92 0.96 1.00 1.05 1.10 1.16 1.22 1.30
R134a 0.73 0.79 0.86 0.90 0.95 1.00 1.06 1.12 1.19 1.27 1.37
When sizing valves, the plant capacity must be multiplied by a correction factor depending on liquid
temperature tl ahead of valve / evaporator.
When the corrected capacity is known, the selection can be made from the table.
Capacity
Liquid capacity Qo [kW]
Liquid capacity Ql [kW]
Type at pressure drop across valve ∆p [bar]
(continued)
0.10 0.15 0.20 0.30 0.40 0.50
R404A / R507
EVU 1 1.52 1.40 1.62 1.99 2.29 2.57
R410A
EVU 1 1.52 2.01 2.33 2.85 3.29 3.68
R404A 0.65 0.72 0.81 0.86 0.93 1.00 1.09 1.20 1.33 1.51 1.74
R507C 0.65 0.73 0.81 0.87 0.93 1.00 1.08 1.19 1.31 1.47 1.69
R410A 0.73 0.79 0.86 0.90 0.95 1.00 1.06 1.14 1.23 1.33 1.47
When sizing valves, the plant capacity must be multiplied by a correction factor depending on liquid
temperature tl ahead of valve / evaporator.
When the corrected capacity is known, the selection can be made from the table.
Capacity
Pressure drop Suction vapour capacity Qe [kW]
Suction vapour
Type across valve ∆p at evaporating temperature te [°C]
capacity Qe [kW]
[bar]
-40 -30 -20 -10 0 10
R22 / R407C
0.10 0.09 0.11 0.15 1.19 0.23 0.26
R22 / R407C 0.90 0.93 0.96 1.00 1.04 1.08 1.13 1.18 1.24
When sizing valves, the plant capacity must be multiplied by a correction factor depending on liquid
temperature tl ahead of valve / evaporator.
When the corrected capacity is known, the selection can be made from the table.
Capacity
Pressure drop Suction vapour capacity Qe [kW]
Suction vapour
Type across valve ∆p at evaporating temperature te [°C]
capacity Qe [kW]
(continued) [bar]
-40 -30 -20 -10 0 10
R134a
0.10 0.06 0.08 0.11 0.14 0.18 0.21
R134a 0.88 0.92 0.96 1.00 1.05 1.10 1.16 1.23 1.31
When sizing valves, the plant capacity must be multiplied by a correction factor depending on liquid
temperature tl ahead of valve / evaporator.
When the corrected capacity is known, the selection can be made from the table.
Capacity
Pressure drop Suction vapour capacity Qe [kW]
Suction vapour
Type across valve ∆p at evaporating temperature te [°C]
capacity Qe [kW]
(continued) [bar]
-40 -30 -20 -10 0 10
R404A / R507
0.10 0.08 0.10 0.14 0.16 0.20 0.25
R404A 0.84 0.89 0.94 1.00 1.07 1.16 1.26 1.40 1.57
R507 0.84 0.89 0.94 1.00 1.07 1.16 1.26 1.39 1.57
When sizing valves, the plant capacity must be multiplied by a correction factor depending on liquid
temperature tl ahead of valve / evaporator. When the corrected capacity is known, the selection can be
made from the table.
Capacity
Pressure drop Suction vapour capacity Qe [kW]
Suction vapour
Type across valve ∆p at evaporating temperature te [°C]
capacity Qe [kW]
(continued) [bar]
-40 -30 -20 -10 0 10
R410A
0.10 0.12 0.16 0.20 0.24 0.29 0.33
R410A 0.89 0.92 0.96 1.00 1.05 1.11 1.18 1.26 1.37
When sizing valves, the plant capacity must be multiplied by a correction factor depending on liquid
temperature tl ahead of valve / evaporator. When the corrected capacity is known, the selection can be
made from the table.
R22
0.10 0.30 0.31 0.33 0.34 0.35
0.20 0.43 0.45 0.46 0.43 0.49
EVU 1 0.40 0.60 0.64 0.66 0.69 0.70
0.80 0.83 0.85 0.93 0.99 0.99
1.60 1.16 1.24 1.30 1.35 1.36
0.10 0.60 0.63 0.65 0.68 0.70
0.20 0.85 0.90 0.93 0.85 0.98
EVU 2 0.40 1.20 1.28 1.33 1.38 1.40
0.80 1.65 1.70 1.85 1.98 1.98
1.60 2.33 2.48 1.60 2.70 2.73
0.10 0.90 0.94 0.98 1.01 1.05
0.20 1.28 1.35 1.39 1.28 1.46
EVU 3 0.40 1.80 1.91 1.99 2.06 2.10
0.80 2.48 2.55 2.78 2.96 2.96
1.60 3.49 3.71 3.90 4.05 4.09
0.10 1.50 1.57 1.63 1.69 1.75
0.20 2.13 2.25 2.32 2.13 2.44
EVU 4 0.40 3.00 3.19 3.32 3.44 3.50
0.80 4.13 4.25 4.63 4.94 4.94
1.60 5.82 6.19 6.50 6.75 6.82
0.10 1.95 2.03 2.11 2.20 2.27
0.20 2.76 2.92 3.01 2.76 3.17
EVU 5 0.40 3.90 4.15 4.31 4.47 4.55
0.80 5.36 5.52 6.01 6.42 6.42
1.60 7.56 8.05 8.45 8.77 8.86
0.10 2.40 2.50 2.60 2.70 2.80
0.20 3.40 3.60 3.70 3.40 3.90
EVU 6 0.40 4.80 5.10 5.30 5.50 5.60
0.80 6.60 6.80 7.40 7.90 7.90
1.60 9.30 9.90 10.40 10.80 10.90
0.10 3.00 3.13 3.25 3.38 3.50
0.20 4.25 4.50 4.63 4.25 4.88
EVU 8 0.40 6.00 6.38 6.63 6.88 7.00
0.80 8.25 8.50 9.25 9.88 9.88
1.60 11.63 12.38 13.00 13.50 13.63
An increase in hot gas temperature th of 10 K, based on th = tc 25 °C, reduces valve capacity approx. 2% and vice versa.
A change in evaporating temperature te changes valve capacity; see correction factor table below.
When sizing valves, the table value must be multiplied by a correction factor depending on
evaporating temperature te.
R134a
0.10 0.24 0.25 0.26 0.26 0.26
0.20 0.34 0.36 0.37 0.38 0.37
EVU 1 0.40 0.47 0.51 0.53 0.54 0.53
0.80 0.66 0.70 0.73 0.77 0.76
1.60 0.95 1.01 1.05 1.07 1.03
0.10 0.47 0.50 0.52 0.53 0.52
0.20 0.67 0.71 0.74 0.75 0.74
EVU 2 0.40 0.93 1.02 1.06 1.07 1.06
0.80 1.32 1.41 1.47 1.54 1.52
1.60 1.90 2.01 2.09 2.13 2.12
0.10 0.70 0.75 0.78 0.79 0.78
0.20 1.01 1.07 1.11 1.13 1.11
EVU 3 0.40 1.40 1.53 1.58 1.61 1.59
0.80 1.98 2.11 2.20 2.31 2.28
1.60 2.85 3.02 3.12 3.20 3.17
0.10 1.18 1.25 1.30 1.32 1.31
0.20 1.68 1.78 1.85 1.88 1.86
EVU 4 0.40 2.33 2.55 2.64 2.68 2.65
0.80 3.31 3.52 3.67 3.85 3.80
1.60 4.76 5.03 5.23 5.33 5.29
0.10 1.53 1.62 1.68 1.72 1.70
0.20 2.18 2.31 2.40 2.44 2.41
EVU 5 0.40 3.03 3.32 3.43 3.48 3.44
0.80 4.30 4.57 4.77 5.00 4.94
1.60 6.18 6.54 6.80 6.92 6.88
0.10 1.88 1.99 2.07 2.11 2.09
0.20 2.69 2.84 2.95 3.00 2.97
EVU 6 0.40 3.73 4.08 4.28 4.28 4.23
0.80 5.29 5.60 5.86 6.16 6.08
1.60 7.61 8.05 8.37 8.52 8.46
0.10 2.35 2.49 2.59 2.64 2.61
0.20 3.36 3.55 3.69 3.75 3.71
EVU 8 0.40 4.66 5.10 5.28 5.35 5.29
0.80 6.61 7.03 7.33 7.70 7.60
1.60 9.51 10.06 10.46 10.65 10.58
An increase in hot gas temperature th of 10 K, based on th = tc 25 °C, reduces valve capacity approx. 2% and vice versa.
A change in evaporating temperature te changes valve capacity; see correction factor table below.
When sizing valves, the table value must be multiplied by a correction factor depending on
evaporating temperature te.
R404A / R507
0.10 0.27 0.27 0.27 0.26 0.23
0.20 0.38 0.39 0.38 0.36 0.33
EVU 1 0.40 0.54 0.55 0.54 0.52 0.47
0.80 0.74 0.76 0.75 0.74 0.67
1.60 1.05 1.07 1.05 1.01 0.90
0.10 0.54 0.55 0.54 0.51 0.47
0.20 0.76 0.77 0.76 0.73 0.66
EVU 2 0.40 1.09 1.10 1.09 1.03 0.94
0.80 1.49 1.51 1.51 1.48 1.34
1.60 2.09 2.13 2.11 2.03 1.80
0.10 0.81 0.82 0.81 0.77 0.70
0.20 1.14 1.16 1.14 1.09 0.99
EVU 3 0.40 1.63 1.64 1.63 1.55 1.41
0.80 2.23 2.27 2.26 2.22 2.01
1.60 3.14 3.20 3.16 3.04 2.70
0.10 1.35 1.37 1.35 1.28 1.17
0.20 1.90 1.93 1.91 1.82 1.65
EVU 4 0.40 2.72 2.74 2.72 2.58 2.35
0.80 3.72 3.78 3.77 3.70 3.36
1.60 5.23 5.33 5.17 5.07 4.50
0.10 1.75 1.77 1.75 1.66 1.51
0.20 2.46 2.50 2.50 2.36 2.14
EVU 5 0.40 3.53 3.56 3.56 3.35 3.05
0.80 4.83 4.91 4.91 4.81 4.36
1.60 6.80 6.93 6.92 6.56 5.85
0.10 2.16 2.18 2.15 2.05 1.86
0.20 3.03 3.08 3.05 2.90 2.64
EVU 6 0.40 4.34 4.38 4.35 4.13 3.76
0.80 5.94 6.05 6.02 5.92 5.37
1.60 8.37 8.52 8.43 8.10 7.20
0.10 2.70 2.73 2.69 2.56 2.33
0.20 3.79 3.85 3.81 3.63 3.30
EVU 8 0.40 5.43 5.48 5.44 5.16 4.70
0.80 7.43 7.56 7.53 7.40 6.70
1.60 10.46 10.65 10.54 10.13 9.00
An increase in hot gas temperature th of 10 K, based on th = tc 25 °C, reduces valve capacity approx. 2% and vice versa.
A change in evaporating temperature te changes valve capacity; see correction factor table below.
When sizing valves, the table value must be multiplied by a correction factor depending on
evaporating temperature te.
R410A
0.10 0.47 0.49 0.49 0.49 0.47
0.20 0.67 0.70 0.70 0.62 0.66
EVU 1 0.40 0.95 0.99 1.00 1.00 0.95
0.80 1.30 1.32 1.40 1.43 1.33
1.60 1.84 1.92 1.96 1.96 1.84
0.10 0.95 0.97 0.98 0.98 0.95
0.20 1.34 1.40 1.40 1.23 1.32
EVU 2 0.40 1.90 1.99 2.00 2.00 1.89
0.80 2.61 2.64 2.79 2.85 2.67
1.60 3.68 3.84 3.93 3.92 3.68
0.10 1.42 1.46 1.47 1.47 1.42
0.20 2.02 2.09 2.10 1.85 1.98
EVU 3 0.40 2.84 2.97 3.00 2.99 2.84
0.80 3.01 2.95 4.19 4.30 4.00
1.60 5.51 5.76 5.89 5.87 5.52
0.10 2.37 2.43 2.46 2.45 2.37
0.20 3.36 3.49 3.50 3.08 3.30
EVU 4 0.40 4.74 4.95 5.01 4.99 4.73
0.80 6.52 6.59 6.99 7.17 6.67
1.60 9.19 9.60 9.82 9.79 9.20
0.10 3.08 3.15 3.19 3.18 3.07
0.20 4.37 4.54 4.54 4.00 4.28
EVU 5 0.40 6.16 6.43 6.51 6.49 6.14
0.80 8.47 8.57 9.08 9.31 8.67
1.60 11.95 12.47 12.76 12.73 11.96
0.10 3.79 3.88 3.93 3.92 3.78
0.20 5.38 5.58 5.59 4.93 5.27
EVU 6 0.40 7.58 7.91 8.01 7.98 7.56
0.80 10.43 10.54 11.18 11.46 10.67
1.60 14.70 15.35 15.70 15.66 14.72
0.10 4.74 4.85 4.91 4.90 4.73
0.20 6.75 6.98 6.99 6.16 6.59
EVU 8 0.40 9.48 6.98 10.01 9.98 9.45
0.80 13.04 13.18 13.97 14.33 13.34
1.60 18.38 19.19 19.63 19.58 18.40
An increase in hot gas temperature th of 10 K, based on th = tc 25 °C, reduces valve capacity approx. 2% and vice versa.
A change in evaporating temperature te changes valve capacity; see correction factor table below.
When sizing valves, the table value must be multiplied by a correction factor depending on
evaporating temperature te.
Capacity
Hot gas Cond. Hot gas capacity Gh [kg / s]
Hot gas capacity Gh [kg / s]
Type temp. th temp. tc at pressure drop across valve ∆p [bar]
[°C] [°C]
0.50 1 2 3 4 5 6 7 8
R22 / R407C
90 25 0.003 0.005 0.006 0.007 0.007 0.007 0.007 0.007 0.007
EVU 1 90 35 0.004 0.005 0.007 0.008 0.009 0.009 0.010 0.010 0.010
90 45 0.004 0.006 0.008 0.010 0.011 0.011 0.012 0.012 0.012
90 25 0.007 0.009 0.012 0.014 0.015 0.015 0.015 0.015 0.015
EVU 2 90 35 0.008 0.011 0.014 0.017 0.018 0.019 0.019 0.019 0.019
90 45 0.009 0.012 0.017 0.020 0.022 0.023 0.024 0.024 0.024
90 25 0.010 0.014 0.018 0.021 0.022 0.022 0.022 0.022 0.022
EVU 3 90 35 0.012 0.016 0.021 0.025 0.027 0.028 0.029 0.029 0.029
90 45 0.023 0.018 0.025 0.029 0.032 0.035 0.036 0.036 0.037
90 25 0.017 0.023 0.031 0.035 0.037 0.037 0.037 0.037 0.037
EVU 4 90 35 0.019 0.027 0.036 0.042 0.045 0.047 0.048 0.048 0.048
90 45 0.022 0.031 0.042 0.049 0.054 0.058 0.060 0.061 0.061
90 25 0.022 0.030 0.040 0.045 0.047 0.048 0.048 0.048 0.048
EVU 5 90 35 0.025 0.035 0.046 0.055 0.059 0.061 0.062 0.062 0.062
90 45 0.028 0.040 0.054 0.064 0.070 0.075 0.077 0.079 0.079
90 25 0.027 0.037 0.049 0.055 0.058 0.059 0.059 0.059 0.059
EVU 6 90 35 0.031 0.043 0.057 0.067 0.072 0.075 0.077 0.077 0.077
90 45 0.035 0.049 0.066 0.078 0.086 0.092 0.095 0.097 0.098
90 25 0.034 0.046 0.061 0.069 0.073 0.074 0.074 0.074 0.074
EVU 8 90 35 0.039 0.054 0.071 0.084 0.090 0.092 0.096 0.969 0.096
90 45 0.043 0.061 0.083 0.098 0.108 0.115 0.119 0.121 0.122
R134a
90 25 0.003 0.004 0.005 0.005 0.005 – – – –
EVU 1 90 35 0.004 0.005 0.006 0.007 0.007 0.007 0.007 – –
90 45 0.004 0.006 0.007 0.009 0.009 0.009 0.009 0.009 0.009
90 25 0.006 0.008 0.010 0.010 0.010 – – – –
EVU 2 90 35 0.007 0.010 0.012 0.014 0.014 0.014 0.014 – –
90 45 0.008 0.011 0.015 0.017 0.018 0.018 0.018 0.018 0.018
90 25 0.009 0.012 0.015 0.015 0.015 – – – –
EVU 3 90 35 0.011 0.014 0.018 0.021 0.021 0.021 0.021 – –
90 45 0.012 0.017 0.022 0.026 0.027 0.027 0.027 0.027 0.027
90 25 0.015 0.020 0.025 0.026 0.026 – – – –
EVU 4 90 35 0.018 0.024 0.031 0.035 0.035 0.035 0.035 – –
90 45 0.020 0.028 0.037 0.043 0.045 0.046 0.046 0.046 0.046
90 25 0.020 0.026 0.033 0.033 0.033 – – – –
EVU 5 90 35 0.023 0.031 0.040 0.045 0.046 0.046 0.046 – –
90 45 0.026 0.036 0.048 0.055 0.059 0.059 0.059 0.059 0.059
90 25 0.024 0.032 0.040 0.041 0.041 – – – –
EVU 6 90 35 0.028 0.038 0.049 0.055 0.056 0.056 0.056 – –
90 45 0.032 0.045 0.059 0.068 0.072 0.073 0.073 0.073 0.073
90 25 0.030 0.040 0.050 0.051 0.051 – – – –
EVU 8 90 35 0.035 0.048 0.061 0.069 0.070 0.070 0.070 – –
90 45 0.040 0.056 0.074 0.085 0.090 0.091 0.091 0.091 0.091
An increase in hot gas temperature of 10 K, reduces valve capacity approx. 2% and vice versa.
Capacity
Hot gas Cond. Hot gas capacity Gh [kg/s]
Hot gas capacity Gh [kg / s]
Type temp. th temp. tc at pressure drop across valve ∆p [bar]
(continued)
[°C] [°C]
0.50 1 2 3 4 5 6 7 8
R404A / R507
90 25 0.004 0.006 0.008 0.009 0.010 0.010 0.010 0.010 0.010
EVU 1 90 35 0.005 0.007 0.009 0.011 0.012 0.012 0.012 0.013 0.013
90 45 0.005 0.008 0.010 0.012 0.014 0.014 0.015 0.015 0.016
90 25 0.009 0.012 0.016 0.018 0.019 0.019 0.020 0.020 0.020
EVU 2 90 35 0.010 0.014 0.018 0.021 0.023 0.023 0.025 0.025 0.025
90 45 0.011 0.015 0.020 0.024 0.027 0.027 0.029 0.031 0.032
90 25 0.013 0.012 0.023 0.027 0.029 0.029 0.030 0.030 0.030
EVU 3 90 35 0.014 0.020 0.027 0.031 0.035 0.035 0.037 0.038 0.038
90 45 0.016 0.023 0.030 0.036 0.041 0.041 0.044 0.046 0.048
90 25 0.022 0.030 0.039 0.045 0.048 0.048 0.050 0.050 0.050
EVU 4 90 35 0.024 0.034 0.045 0.053 0.058 0.058 0.062 0.063 0.063
90 45 0.027 0.038 0.051 0.060 0.068 0.068 0.073 0.077 0.080
90 25 0.028 0.038 0.051 0.059 0.062 0.062 0.064 0.065 0.065
EVU 5 90 35 0.031 0.044 0.059 0.069 0.075 0.075 0.080 0.082 0.082
90 45 0.035 0.049 0.066 0.079 0.088 0.088 0.094 0.099 0.104
90 25 0.034 0.047 0.062 0.072 0.077 0.077 0.079 0.080 0.080
EVU 6 90 35 0.038 0.054 0.072 0.085 0.093 0.093 0.098 0.101 0.101
90 45 0.043 0.061 0.082 0.097 0.108 0.108 0.116 0.122 0.128
90 25 0.043 0.059 0.078 0.090 0.096 0.096 0.099 0.100 0.100
EVU 8 90 35 0.048 0.068 0.090 0.106 0.116 0.116 0.123 0.126 0.126
90 45 0.054 0.076 0.102 0.121 0.135 0.135 0.145 0.153 0.160
R410A
90 25 0.005 0.007 0.010 0.013 0.015 0.017 0.018 0.018 0.018
EVU 1 90 35 0.006 0.008 0.012 0.015 0.017 1.019 0.021 0.022 0.022
90 45 0.007 0.010 0.014 0.017 0.019 0.021 0.024 0.025 0.027
90 25 0.008 0.011 0.016 0.019 0.022 0.025 0.027 0.027 0.027
EVU 2 90 35 0.009 0.013 0.018 0.022 0.025 0.028 0.031 0.033 0.033
90 45 0.010 0.014 0.020 0.025 0.029 0.032 0.035 0.038 0.041
90 25 0.012 0.017 0.023 0.029 0.033 0.037 0.040 0.040 0.040
EVU 3 90 35 0.013 0.019 0.027 0.033 0.038 0.042 0.046 0.050 0.050
90 45 0.015 0.022 0.030 0.037 0.043 0.048 0.053 0.057 0.061
90 25 0.020 0.028 0.039 0.048 0.055 0.062 0.067 0.067 0.067
EVU 4 90 35 0.022 0.031 0.044 0.054 0.063 0.070 0.077 0.083 0.083
90 45 0.025 0.036 0.051 0.062 0.072 0.080 0.088 0.095 0.101
90 25 0.026 0.036 0.051 0.062 0.072 0.080 0.087 0.087 0.087
EVU 5 90 35 0.029 0.041 0.058 0.071 0.082 0.091 0.100 0.108 0.108
90 45 0.033 0.047 0.066 0.081 0.093 0.104 0.114 0.123 0.132
90 25 0.031 0.044 0.063 0.077 0.088 0.099 0.107 0.107 0.107
EVU 6 90 35 0.036 0.050 0.071 0.087 0.101 0.112 0.123 0.133 0.133
90 45 0.041 0.057 0.081 0.099 0.115 0.128 0.140 0.152 0.162
90 25 0.039 0.055 0.078 0.096 0.111 0.124 0.134 0.134 0.134
EVU 8 90 35 0.044 0.063 0.089 0.109 0.126 0.141 0.154 0.166 0.166
90 45 0.051 0.072 0.101 0.124 0.143 0.160 0.176 0.190 0.203
An increase in hot gas temperature of 10 K, reduces valve capacity approx. 2% and vice versa.
1. Solder connection
5. Solder connection
2. Solder ring
4. Solder ring
3. Valve housing
6. Union nut
7. Armature tube
8. Return spring
9. Armature
10. Support ring
11. Pilot plate (servo)
12. Seat plate (servo)
13. Piston (servo)
32M18.10
Danfoss
The drawing is only representative.
EVU 1 – EVU 6
.FW
EVU 8
.FW