1. BUSWAY PLUG-IN CIRCUIT BREAKER (PICB) SHALL BE SAME BRAND AS EXISTING. PLEASE SPECIFY BRAND. SPECIFY IF PICB ENCLOSURE IS NEW OR
EXISTING. COORDINATE PICB REPLACEMENT WITH BUSWAY SUPPLIER. DRAWING SHALL BE DONE BY BUSWAY SUPPLIER AS COMMENTED.
2. PLUG-IN UNIT ENCLOSURE SHALL HAVE POSITIVE GROUND CONNECTION TO THE BUSWAY. PLUG-UNIT SHALL BE MECHANICALLY INTERLOCKED TO
PREVENT REMOVAL WHILE THE SWITCH IS "ON" POSITION AND SHALL BE EQUIPPED WITH AN INTERLOCK TO PREVENT THE COVER FROM BEING
OPENED WHILE THE SWITCH IS "ON" POSITION AND TO PREVENT ACCIDENTAL "CLOSING" OF THE SWITCH WHILE THE COVER IS OPEN.
3. PROVIDE MOUNTING ELEVATION DETAIL. INDICATE MOUNTING HEIGHT OF PICB.
4. ALL ELECTRICAL WORKS HEREIN SHALL CONFORM TO BUILDING STANDARD AND TENANT FIT-OUT GUIDELINES. SEE OTHER NOTES AT PREVIOUS
COMMENTED AND APPROVED FIT-OUT ELECTRICAL PLANS. 04042023