FIRE PROTECTION VALVE PPV-K90

Fire protection valve PPV-K90


Application:
Fire protection valves PPV are used for preventing
the fire from spreading in air conditioning and
ventilating systems. They are installed at crossings
of ventilating ducts through partition walls and
ceilings which divide a building into fire
compartments. When installed in a fire partition
wall, the fire resistance is 90 min, otherwise 60 min
only. It is used for air-in-and outlet. The air flow
quantity can be regulated by a special regulating
system. A thermo link device activates the valve
at 70°C and springs shut the air flow and fire
spread through the ventilating ducts is stopped. The
operation of the thermo release device and of the
fire valve can be controlled by pulling out the
central part of the valve. The fire protection valve
Sizes and dimensions has been approved by ZAG Institute (Ljubljana,
Slovenia), by IBS (Institut für Brandschutztechnik
Linz, Austria) and by LTM (Zagreb, Croatia).
Size φD φD1 φD2
100 98 164 158
Description:
125 123 189 183 The fire protection valve PPV consists of an
160 158 224 218 installation frame (1) and a special inner part (2).
200 198 264 258 The central part can be pulled out by a special
1 3 2 bayonet pin or the distance can be set towards
x
housing and thus the air flow quantity can be
adjusted. The size of opening is 10 or 20 mm. The
installation frame and the guiding tube are made of
steel profile (painted in white colour). A shut-off
plate is made of special fire resisting material in
white colour. All inner parts are galvanized and
hence non-corrosive.

Assembly parts
1. Installation frame
φD1
φD

φD2

2. Inside shut-off part


3. Seal
4. Thermo link device 70° C

4 3

150

Installation
The fire protection valve is installed directly in a
wall or ceiling. All positions are possible under
condition that the thickness of a concrete wall is
minimum 100 mm or 120 mm for masonry wall
respectively.
φD+90 φD+90
φD+90
FIRE PROTECTION VALVE PPV-K90 INSTALLATION

Installation in light partition walls:


The minimum fire resistance of the partition wall
should be 90 min. When installing, you should
follow instructions.

Components
1. PPV-K90
2. Insulation
3. Fire resistant gypsum board
4. Self-tapping screws
5. Profile 50x30x1.5 mm

Note:
Only item 1 is supplied.
When installing drill the holes for self-tapping
screws.

Application in the kitchen Application in toilets


FIRE PROTECTION VALVE PPV-K90 TECHNICAL DATA

min.115

Adjustment
3 1 2 It is possible to order extension tube, in case
when the wall is thicker than normal.

1. Installation frame
2. Valve
3. Duct

115+250

30

300

Inlet charackteristics Pressure drop diagram

2
100

1
20 200
125

0
0

5
160

16

20
10

12
15 200 150

0
0

5
100

16

20
10

12
125 50
10 160 100
200
X X=10

)
(dB
6

WA
60

L
5 40
50
Pressure drop Δpt (Pa)

4 40
Throw distance L (m)

3 30
vL =0.25 m/s 30 Δpt
20
2
20
X=20

15
Δpt

1 20
50 100 150 200 300 400 500 10
50 100 150 200 300 400 500
Air flow Q (m3/h)
Air flow Q (m3/h)

Q(m3/h)
Q (m3/h) Air flow
VL (m/s) Maximal velocity O,5 m/s at distance L
Δp (Pa) Total pressure drop
LwA (dB) Sound power level
L (m) Throw distance
L(m) L(m)
x (mm) Width of the opening
vL(m/s)

Ordering example:
Fire protection valve: PPV-K90
Size: 125
Pcs: 15