AUTOPILOT
PR-9000 setting
Part of Jumper & Dip Switch

TOKYO KEIKI INC.


Jun, 2017
Contents

1. Heading Control Unit


1-1. HCCPU PWB --------------- 1-3
1-2. HCTRM PWB --------------- 4
1-3. ADNCT2 PWB --------------- 5-6
2. Heading Control Interface Unit
2-1. HIFCPU PWB --------------- 7-9
2-2. HIFIO PWB --------------- 10 - 12
3. Heading Control Terminal Unit
3-1. HIFTRM PWB --------------- 13 - 14
4. Steering Gear Control Unit
4-1. SGCPU PWB --------------- 15 - 19
4-2. ESQC PWB --------------- 20 - 23
4-3. DSQC PWB --------------- 24 - 26
5. Steering Gear Terminal Unit
5-1. SGTRM PWB --------------- 27
6. Annunciator Unit
6-1. ANNM PWB -------------- 28 – 29
6-2. ANNS PWB -------------- 30
7. Repeater Unit -------------- 31 - 32
8. Remote Control Unit
8-1. DLIF PWB -------------- 33
8-2. RCCPU PWB -------------- 34
8-3. JVIF PWB -------------- 35
8-4. RCPIF PWB -------------- 36 - 37
2017.4.20
TOKYO KEIKI INC. PR-9000 setting Made by Service engineering section
(HCCPU)
1. HCU(Heading Control Unit)
1-1. HCCPU PWB
Front panel of HCU

HCU back side

S1

S2

S3

E2

Fig1. HCCPU PWB (11329401-) Layout E6

Table1. Table of ship type and ship length

Ship type Ship length

0: Container / PCC

1: Small ship Lpp < 100m

2: Tanker Lpp ≥ 250m

3: Tanker Lpp < 250m

4: Bulk Carrier Lpp ≥ 240m

5: Bulk Carrier 180m ≤ Lpp < 240m

6: Bulk Carrier Lpp < 180m

7: Other ship
8: Ship with high effectiveness
(Small / medium size ship)

1
2017.4.20
TOKYO KEIKI INC. PR-9000 setting Made by Service engineering section
(HCCPU)

Table2. Settings of internal Counter rudder adjustment


Upper item: Internal Counter
0 1 2 3 4 5 6 7 8 rudder adjustment value
Ship

Ship with high effectiveness


(S1-6 to 8)...(*)1

Tanker(Lpp<250m)
Tanker(Lpp≥250m)

(Small/Medium size ship)


Container/PCC

(240>Lpp≥180)
(Lpp<100m)

(Lpp<180m)
(Lpp≥240m)

Bulk carrier
Bulk carrier

Bulk carrier
Small ship

Other ship
Lower item: Automatic weather
adjustment control step range
(S2-1 to 3)…(*)2
D.W.T

5,000 - 1 1 1/2 1 0/1


9,999 1 1 2 1 1
10,000 - 1/2 2 2 2 1/2
49,999 2 2 2 2 2
50,000 - 2 3 3 2 2 3 2
99,999 2 2/3 2/3 2 2 2 2
100,000 - 2 3 3 2 2/3
199,999 2 3 3 2 2/3
200,000 - 2/3 3/4 2/3 3
299,999 2/3 3 2/3 3
300,000 - 3 4/5 3
499,999 3 3 3
500,000 - 3/4 5 3/4
more 3 3 3

1-1-1. Settings of HCCPU Dip switches


No.1 HCU
All settings of Dip switches below are loaded at Autopilot starting-up. default setting

Some settings noted are available to change during Autopilot operating condition. S1
Pay special attention to change the setting while operating.
8

Table of DipSW(S1) 7

Switch number
6
Switch number
5
Setting content 1 2 3 4 5 6 7 8
4
System number of No.1 HCU OFF
3
HCU No.2 HCU ON O 2
PR-9000 OFF OFF N 1
PR-9000-ZZ ON OFF
Equipment type
Successor of TIF-6 OFF ON
Successor of PR-2000 ON ON : SW position
ADPT function Without ADPT function OFF
setting With ADPT function ON
Without No.2 SGCS OFF No.2 HCU
No.2 SGCS exist default setting
With No.2 SGCS ON
0: (2 - 15 sec) OFF OFF OFF S1
1: (10 - 30 sec) ON OFF OFF 8
Counter rudder 2: (20 - 50 sec) OFF ON OFF 7
adjustment
Switch number

3: (40 - 80 sec) ON ON OFF 6


(*)1 Reffer to
4: (50 - 100 sec) OFF OFF ON 5
table 2 upper
5: (70 - 140 sec) ON OFF ON 4
stage
6: (90 - 180 sec) OFF ON ON 3
7: (120 - 240 sec) ON ON ON O 2
N 1
Note: Setting of " Counter rudder adjustment " are available to change during
Autopilot operating condition.
: SW position

2
2017.4.20
TOKYO KEIKI INC. PR-9000 setting Made by Service engineering section
(HCCPU)
Table of DipSW(S2)
Switch number HCU
Setting content 1 2 3 4 5 6 7 8 default setting
0: (0.2°) OFF OFF OFF
1: (0.3°) ON OFF OFF S2
Automatic weather 2: (0.4°) OFF ON OFF
adjustment control 3: (0.5°) ON ON OFF 8
step ranges (deg) 4: (0.6°) OFF OFF ON 7

Switch number
(*)2 Table2 5: (0.8°) ON OFF ON 6
6: (1.0°) OFF ON ON 5
7: (1.5°) ON ON ON 4
35° OFF OFF OFF 3
O 2
40° ON OFF OFF N
1
Maximum rudder 45° OFF ON OFF
angle 60° ON ON OFF
70° OFF OFF ON
: SW position
Vec-twins rudder ON OFF ON
Single OFF
Number of rudder
Twins ON
2 systems OFF
Number of HCU
1 system ON

Table of DipSW(S3)
Switch number
Setting content 1 2 3 4 5 6 7 8
HCU
OFF default setting
Not used Initially set to "OFF"
ON
PTKM sentence With PTKM sentence input OFF S3
input status (*)3 Without PTKM sentence input ON 8
OFF 7
Not used Initially set to "OFF"

Switch number
ON 6
OFF 5
Not used Initially set to "OFF"
ON 4
ACE function Without ACE function OFF 3
setting With ACE function ON O 2
OFF N
1
Not used Initially set to "OFF"
ON
OFF
Not used Initially set to "OFF"
ON : SW position
OFF
Not used Initially set to "OFF"
ON
(*)3 When it connects with Tokyo-keiki's Gyro-compass and using resolver signal
magnetic compass, set to "OFF".
When it connects with other company heading sensor and using serial signal
magnetic compass, set to "ON". Default
setting

1-1-2. Settings of HCCPU Jumper E2 1 2


Jumper Default Setting content
When connected with
E2 1-2 Open Connected 1-2 Short Initially set 1-2 Open E6 1 2
Emulator
E6 1-2 Short Not used
: Short

3
TOKYO KEIKI INC. 2017.4.20
PR-9000 setting Made by service engineering section
(HCTRM/ADNCT2)
1-2. HCTRM PWB
HCU front panel

HCU back side

E1

Fig 2. HCTRM PWB (113292402-) Layout

All settings of Dip switches and jumpers below are loaded at Autopilot starting-up.
Some settings noted are available to change during Autopilot operating condition.
Pay special attention to change the setting while operating.

1-2-1. Settings of HCTRM PWB Jumpers


Jumper Default Setting content
When HCU has When HCU has
1-2 Short 1-2 Short abnormality, HCUSW 1-2 Open
abnormality, ANN controls
HCU alert buzzer. (Except controls HCU alert buzzer.
3-4 Short for PR-9000-ZZ) 3-4 Short (Including PR-9000-ZZ) 3-4 Open
E1
When HCU has When HCU has
5-6 Short 5-6 Short 5-6 Open
abnormality, ANN controls abnormality, HCUSW
HCU alert LED. (Except for controls HCU alert LED.
7-8 Short PR-9000-ZZ) 7-8 Short (Including PR-9000-ZZ) 7-8 Open

Default setting

E1
1 3 5 7
2 4 6 8

: Short

4
TOKYO KEIKI INC. 2017.4.20
PR-9000 setting Made by service engineering section
(HCTRM/ADNCT2)

1-3. ADNCT2 PWB


HCU front panel

HCU back side

S2
S1

E10

E1
Fig3. ADNCT2 PWB (11329404-) Layout

Table3. Limit index settings of ADPT and ACE (*) 4

Limit index Ship type Range of Lpp (m) Period (sec.) Setting

5 O
A-1 180 - (160 - 250) 6 N
Example: LNG / LPG tanker, 7
Container carrier
5 O
A-2 Vehicle carrier 120 - 179 (100 - 160) 6 N
[Set the ship not included in B-1/B- 7
2]
5 O
A-3 - 119 (60 - 100) 6 N
7

O
5
B-1 A ship of which draft condition 185 - (200 - 320) 6
N
varies in full or ballast loading. 7
Example: Oil tanker, Chemical
tanker, Product tanker, Tanker
5 O
miscellaneous, Bulk carrier. 6
B-2 - 184 (120 - 200) N
[For tanker other than LNG/LPG] 7

5 O
0 Not specified (No limitation) 6 N
7

5
TOKYO KEIKI INC. 2017.4.20
PR-9000 setting Made by service engineering section
(HCTRM/ADNCT2)
1-3-1. Settings of ADNCT2 Dip switch
Table of Dip sw(S1)
Switch number
Setting content 1 2 3 4 5 6 7 8
Software update Normal OFF Default
(Connected with PC) For update ON setting
Setting of integral Default setting OFF
rudder control gain S1
Gain to be doubled ON
O
OFF 1 N
for factry always set to "OFF"
ON 2

Switch number
OFF 3
for factry always set to "OFF" 4
ON
A-1: (160 - 250 sec) ON OFF OFF 5
Setting of limit index 6
A-2: (100 - 160 sec) OFF ON OFF
for ADPT or ACE 7
A-3: (60 - 100 sec) ON ON OFF
function 8
(*)4 Reffer to B-1: (200 - 400 sec) OFF OFF ON
Table3 B-2: (120 - 200 sec) ON OFF ON
Not specified OFF OFF OFF
OFF : SW position
Not used Initially set to "OFF"
ON

(*)1 For checking automatic steering, watch ship's heading at ADPT-OPN steering mode after changing its
course by ADPT auto steering.
When the ship doesn't approach or keep the set course smoothly (when 1 or 2 degrees course deviation
from the set course is kept for 20 minutes or more), set Dip switch(S1-2) to "ON" at chance of the ADNCT2
re-adjustment.
The integral rudder control gain is doubled when S1-2 set to "ON".

(*)2 Countermeasure when yawing is generated.


Measure the yawing period when the yawing is generated by any chance. Set the limit index again as the
measured period is corresponding to the period in the note column of above table.
Example:
Change the setting to A1 in the ship as being set to A-2 when the yawing period is 180 sec(longer than 160
sec), or change the setting to A-3 when the yawing period is 60sec(shorter than 100 sec).
Change the setting to B-1 in the ship as being set to B-2 when the yawing period is 240 sec
(longer than 200 sec).

(!!) Dip switch(S2) is not used.

1-3-2. Settings of ADNCT2 jumper


Jumper Default Setting content
Default
For reset of CPU on the setting
E1 1-2 Open At reset 1-2 Short Normal 1-2 Open
ADNCT2 PWB
Connect with PC At
1-2 Short 1-2 Short 1-2 Open:not used 2
(At version up) connection E1
1
E10 3-4 Open Not used
E10
5-6 Open Not used
6 4 2
5 3 1

: Short

6
2017.6.22
TOKYO KEIKI INC. PR-9000 setting Made by service engineering section
(HCIFU)

2. HCIFU(Heading Control Interface Unit)


2-1 HIFCPU PWB

S4 S3 S2

S1

Fig4-1. HIFCPU PWB (11329405-) Layout

S4 S3 S2

S1

Fig4-2. HIFCPU PWB(11329416-) Layout

All settings of Dip switches and jumpers below are loaded at Autopilot starting-up.
Some settings noted are available to change during Autopilot operating condition.
Pay special attention to change the setting while operating.

7
2017.6.22
TOKYO KEIKI INC. PR-9000 setting Made by service engineering section
(HCIFU)
2-1-1. Settings of HIFCPU Dip switches
Table of Dip SW(S1)
Switch number
Setting content 1 2 3 4 5 6 7 8
Invalid setting of order Valid(No alarm) OFF
signal alert Invalid(Alarm) ON Default setting
Specific use Normal OFF
for production Production use ON S1
Connect with Not connected OFF 8
TCS simulator Connected ON 7

Switch number
Inhibit OFF 6
Input ALR sentence
Permit ON 5
OFF 4
Not used
ON 3
STBD + (Ver1.12.0~) OFF O 2
Polarity of order signal output
(for ZZ type)
N
STBD - (Ver1.12.0~) ON 1
System number of ZZ Single (Ver1.16.0~) OFF
ZZ type (for ZZ type) ZZ Dual (Ver1.16.0~) ON
Mode switch(FU/NFU) Case of normal mode switch type OFF : SW position
(!!) Mode switch is special type Case of FU/NFU switch type (Ver1.13.8) ON
OFF
Not used
ON

Table of Dip SW(S2)


Switch number
Setting content 1 2 3 4 5 6 7 8
AGTXT sentence output Valid OFF
(*)5 Invalid ON
Default setting
OFF
Not used
ON S2
OFF
Not used 8
ON
OFF 7

Switch number
Not used 6
ON
5
OFF
Not used 4
ON
O 3
OFF
Not used N 2
ON
1
ALF with added sentence Not output OFF
outputs (*)6 Output ON
Input baudrate of No.1 Except for 4800bps OFF : SW position
heading sensor 4800bps ON

Note: Setting of "Input baud rate of No.1 Heading sensor" is available to input or change rappropriately with input
specifications.

(*)5 Autopilot transmits AGTXT sentence from [PTX1+/-], [PTX2+/-] of HIFTRM after setting

(*) 6
When this setting set to "OFF", ALF sentence keeps outputting.
When this setting set to "ON", The detail of ALF sentence changes to special sentence.(for Nautical safety)
Software Ver: Ver 1.13.42 and Ver1.14.8 (ANNM, HCCPU and SGCPU must be change special software.)

8
2017.6.22
TOKYO KEIKI INC. PR-9000 setting Made by service engineering section
(HCIFU)
Table of Dip sw(S3)
Switch number
Setting content 1 2 3 4 5 6 7 8
AGTXT sentence output Valid OFF
(*)7 Invalid ON Default setting
OFF
Not used S3
ON
OFF 8
Not used
ON 7

Switch number
OFF 6
Not used
ON 5
OFF 4
Not used
ON O 3
OFF N 2
Not used
ON 1
ALF with added sentence Not output OFF
outputs (*)8 Output ON
: SW position
Input baudrate of No.2 Except for 4800bps OFF
heading sensor 4800bps ON

Note: Setting of "Input baud rate of No.2 Heading sensor" is available to input or change rappropriately with input
specifications.

(*)7 Autopilot transmits AGTXT sentence from [PTX1+/-], [PTX2+/-] of HIFTRM after setting
"E1 and E2" of HIFIO PWB to "IEC61162-1" and Dip SW S2-1 to "ON".

(*) 8
When this setting set to "OFF", ALF sentence keeps outputting.
When this setting set to "ON", The detail of ALF sentence changes to special sentence.(for Nautical safety)
Software Ver: Ver 1.13.42 and Ver1.14.8 (ANNM, HCCPU and SGCPU must be change special software.)

Table of Dip SW(S4)


Switch number
Setting content 1 2 3 4 5 6 7 8
GPS information Valid OFF
(Latitude/Longitude) Invalid ON
OFF Default setting
GPS information(SOG/COG)
ON
S4
OFF
Not used
ON 8
OFF 7 Switch number
Not used
ON 6
OFF 5
Not used 4
ON
OFF 3
Not used O 2
ON N
ALF with added sentence Not output OFF 1
outputs (*)9 Output ON
Input baudrate of No.3 Except for 4800bps OFF : SW position
heading sensor 4800bps ON

Note: Setting of "Input baud rate of No.3 Heading sensor" is available to input or change rappropriately with input
specifications.

(*) 9
When this setting set to "OFF", ALF sentence keeps outputting.
When this setting set to "ON", The detail of ALF sentence changes to special sentence.(for Nautical safety)
Software Ver: Ver 1.13.42 and Ver1.14.8 (ANNM, HCCPU and SGCPU must be change special software.)

9
2017.4.20
TOKYO KEIKI INC. PR-9000 setting Made by service engineering section
(HIFIO)
2-2. HIFIO PWB

E14 E11 E1 E2 E7 E6 E3 E12 E8 E9 E13

Fig5. HIFIO PWB (11329404-) Layout

All settings of Dip switches and jumpers below are loaded at Autopilot starting-up.
Some settings noted are available to change during Autopilot operating condition.
Pay special attention to change the setting while operating.

10
2017.4.20
TOKYO KEIKI INC. PR-9000 setting Made by service engineering section
(HIFIO)
2-2-1. Settings of HIFIO jumpers
Jumper Default Setting content Default
Baudrate select of No.1 HCS
setting
1-2 Open 1-2 Open 1-2 Short
serial signal (At HC mode) IEC61162-1 IEC61162-2
E1 E1
This setting is same as E5 of 4800bps 38400bps
3-4 Short ESQC or DSQC 3-4 Short 3-4 Open 1 3
Baudrate select of No.2 HCS
2 4
1-2 Open 1-2 Open 1-2 Short
serial signal (At HC mode) IEC61162-1 IEC61162-2
E2 This setting is same as E6 of 4800bps 38400bps E2
3-4 Short ESQC or DSQC 3-4 Short 3-4 Open
Output select of 1 3
1-2 Short 2 4
OPTX+/-
Output select of
3-4 Open
OPTX+/-
Output select of E3
E3 5-6 Open No other setting is available.
OPTX+/-
Output select of 1 3 5 7 9
7-8 Open
OPTX+/-
2 4 6 8 10
Output select of
9-10 Open
OPTX+/-
1-2 Open No.1 HCS main Normal: 1-2 Open Normal: 1-2 Short
power failure output Close Open
3-4 Short (At alert: Open) 3-4 Short (At alert: Close) 3-4 Open

5-6 Open No.2 HCS main Normal: 5-6 Open Normal: 5-6 Short
power failure output Close Open
7-8 Short (At alert: Open) 7-8 Short (At alert: Close) 7-8 Open
E6 E6
9-10 Open No.1 HCS system Normal: 9-10 Open Normal: 9-10 Short
Close Open 1 3 5 7 9 11 13 15
failure output 11-12 11-12
11-12 Short (At alert: Open) (At alert: Close) 2 4 6 8 10 12 14 16
Short Open
13-14 13-14
13-14 Open Normal: Normal:
No.2 HCS system Open Short
failure output Close 15-16 Open 15-16
15-16 Short (At alert: Open) (At alert: Close)
Short Open
1-2 Open Off heading alert Normal: 1-2 Open Normal: 1-2 Short
output Close Open
3-4 Short (At alert: Open) 3-4 Short (At alert: Close) 3-4 Open

5-6 Open Heading monitor alert Normal:


5-6 Open Normal: 5-6 Short E7

output Close Open


7-8 Short (At alert: Open) 7-8 Short (At alert: Close) 7-8 Open 1 3 5 7 9 11 13 15
E7 2 4 6 8 10 12 14 16
9-10 Open Off course alert Normal: 9-10 Open Normal: 9-10 Short
output Close 11-12 Open 11-12
11-12 Short (At alert: Open) (At alert: Close)
Short Open
13-14 Open
Not used
15-16 Short

1-2 Short HC/TC 1-2 Short HC/TC 1-2 Open


Mode contact signal
mode: mode:
output for BNWAS
3-4 Open Close 3-4 Open Open 3-4 Short
E8
5-6 Open Operation contact At 5-6 Open At 5-6 Short
operating: operating: 1 3 5 7 9 11 13 15
output for BNWAS
7-8 Short (Count down is reset) Close 7-8 Short Open 7-8 Open 2 4 6 8 10 12 14 16
E8
(*)10 Case of ZZ type: At HCS 9-10 Short At HCS
9-10 Short 9-10 Open
HCS ready contact ready: ready:
11-12 11-12
11-12 Open signal output Close Open
Open Short : Short
Case of ZZ type: 13-14 13-14
13-14 Short
HCS ready contact Normal: Short Normal: Open
signal output Close 15-16 Open 15-16
15-16 Open
(No.2 HCS equipped) Open Short

11
2017.4.20
TOKYO KEIKI INC. PR-9000 setting Made by service engineering section
(HIFIO)
Jumper Default Setting content
Default
1-2 Short Option contact signal 1-2 Short 1-2 Open setting
Normal: Normal:
output
Close
3-4 Open (OPOUT1/OPOUT2) 3-4 Open Open 3-4 Short

5-6 Short Option contact signal 5-6 Short Normal: 5-6 Open E9
Normal:
output
Close Open 3 5 7 9 11 13 15
7-8 Open (OPOUT3/OPOUT4) 7-8 Open 7-8 Short 1
E9 2 4 6 8 10 12 14 16
9-10 Short Normal:
9-10 Short
Normal:
9-10 Open
ACK signal output
(AOUT1/AOUT2) Close 11-12 Open 11-12
11-12 Open
Open Short
13-14 Short
Not used
15-16 Open
E11
1-2 Open
1 3
E11 Not used
2 4
3-4 Open

1-2 Open 1-2 Short 1-2 Open 1-2 Open

3-4 Open 3-4 Short 3-4 Open 3-4 Open


E12
5-6 Short 5-6 Open 5-6 Short Single 5-6 Open
E12 HCS type Dual ZZ Dual HCS HCS or 5 7
1 3 9 11
7-8 Short 7-8 Open 7-8 Short Single ZZ 7-8 Open
2 4 6 8 10 12
9-10 Open 9-10 Open 9-10 Open 9-10 Short
11-12 11-12 11-12
11-12 Open
Open Open Short
1-2 Short 1-2 Short 1-2 Open

3-4 Open 3-4 Open 3-4 Short

5-6 Short 5-6 Short 5-6 Open


Settings between
7-8 Open HCU and SGCU 7-8 Open 7-8 Short E13
E13 internal Dual HCS
9-10
Single HCS
9-10 Short 9-10 Open 1 3 5 7 9 11 13 15
communication Short
(HCS system fail output) 2 4 6 8 10 12 14 16
11-12 11-12
11-12 Open
Open Short
13-14 13-14
13-14 Short
Short Open
15-16 15-16
15-16 Open
Open Short
1-2 Short 1-2 Short 1-2 Open

3-4 Open 3-4 Open 3-4 Short

5-6 Short 5-6 Short 5-6 Open


Settings between
7-8 Open HCU and SGCU 7-8 Open 7-8 Short E14
E14 internal Dual HCS Single HCS
9-10 Short communication 9-10 Short 9-10 Open 1 3 5 7 9 11 13 15
(HCS system fail output) 11-12 11-12 2 4 6 8 10 12 14 16
11-12 Open
Open Short
13-14 13-14
13-14 Short
Short Open
15-16 15-16
15-16 Open : Short
Open Short

(*)10 In case HIFCPU software version is Ver1.11.5,


change to "Close" at operating by setting E8 to 5-6 short.

12
2017.4.20
TOKYO KEIKI INC. PR-9000 setting Made by service engineering section
(HCTU)
3. HCTU(Heading Control Teminal Unit)
3-1 HIFTRM PWB

For connecting with


SGCU

For PR-9000-ZZ
E2

Fig6. HIFTRM PWB (1132907-) Layout

E1

E3

All settings of Dip switches and jumpers below are loaded at Autopilot starting-up.
Some settings noted are available to change during Autopilot operating condition.
Pay special attention to change the setting while operating.

13
2017.4.20
TOKYO KEIKI INC. PR-9000 setting Made by service engineering section
(HCTU)
3-1-1. Settings of HIFTRM jumpers
Jumper Default Setting content
Input signal of optional Default
1-2 Short 1-2 Short 1-2 Open setting
function(OPIN1)
Input signal of optional
3-4 Open 3-4 Open PR-9000- 3-4 Short E1
function(OPIN2)
E1 Input signal of optional
Normal ZZ with 2
5-6 Short 5-6 Short HCS units 5-6 Open 7 8
function(OPIN3)
5 6
Input signal of optional
7-8 Open 7-8 Open 7-8 Short 3 4
function(OPIN4)
1 2
Received HCS uses
1-2 Short 1-2 Short 1-2 Open
Received GPS serial from signal from
signal Gyrocompa Gyrocompa E2
3-4 Short 3-4 Short 3-4 Open
ss ss
Received HCS uses 11 12
5-6 Short 5-6 Short 5-6 Open 9 10
Received Speed LOG from signal from
E2 7 8
serial signal Gyrocompa Gyrocompa
7-8 Short 7-8 Short 7-8 Open 5 6
ss ss
Received HCS uses 3 4
9-10 Short 9-10 Short 9-10 Open 1 2
Received Speed LOG from signal from
pulse signal Gyrocompa 11-12 Gyrocompa 11-12
11-12 Short
ss Short ss Open
1-2 Short ACK serial signal output 1-2 Short Not 1-2 Open
(ACK_TX+/ACK_TX-) Transmit
transmit
3-4 Short (!!) Do not use this function. 3-4 Short 3-4 Open
E3
5-6 Short ACK serial signal receive 5-6 Short Not 5-6 Open
(ACK_RX+/ACK_RX-) Receive 15 16
receive 7-8 Open 13 14
7-8 Short (!!) Do not use this function. 7-8 Short
E3 11 12
9-10 Open ANNU serial signal 9-10 Open 9-10 Short 9 10
Not 7 8
output (BN_TX) Transmit
transmit 11-12 11-12 5 6
11-12 Open (!!) for Class Notation
Open Open 3 4
13-14 13-14 1 2
13-14 Open ANNU serial signal Not Open Short
output (BN_RX) Transmit
transmit 15-16 15-16
15-16 Open (!!) for Class Notation
Open Open : Short

14
2017.4.20
TOKYO KEIKI INC. PR-9000 setting Made by service engineering section
(SGCPU)
4. SGCU(Steering Gear Control Unit)
4-1. SGCPU PWB

S12

E3
S11

S13

E1
S14

E2

Fig7-1. SGCPU-E PWB(11329418-) Layout

15
2017.4.20
TOKYO KEIKI INC. PR-9000 setting Made by service engineering section
(SGCPU)

E4

E5
S12 E3

S11
S13

E1
S14

E2

Fig7-2. SGCPU-D PWB(11329419-) Layout

E4

E5
S12 E3

S11
S13

E1
S14

E2

Fig7-3. SGCPU-F PWB(11329420-) Layout

16
2017.4.20
TOKYO KEIKI INC. PR-9000 setting Made by service engineering section
(SGCPU)
All settings of Dip switches and jumpers below are loaded at Autopilot starting-up.
Some settings noted are available to change during Autopilot operating condition.
Pay special attention to change the setting while operating.

4-1-1. Settings of SGCPU Dip switches


Table of Dip SW(S11)
Switch number
Setting content 1 2 3 4 5 6 7 8
Not used - -
Both SGCPU
35° OFF OFF OFF default setting
40° ON OFF OFF S11
45° OFF ON OFF
60° 1 O
Maximum rudder ON ON OFF
N
angle 70° OFF OFF ON 2

Switch number
Vec-twins 25° ON OFF ON 3
Vec-twins 35° OFF ON ON 4
Unused ON ON ON 5
Not equipped OFF OFF OFF 6
35° ON OFF OFF 7
Narrow rudder angle 40° OFF ON OFF 8
(Equipped with Max 45° ON ON OFF
rudder angle 50° OFF OFF ON
selection unit) : SW position
55° ON OFF ON
60° OFF ON ON
65° ON ON ON
Not detected OFF
Detect HLA
Detected ON

Table of Dip SW(S12)


Switch number
Setting content 1 2 3 4 5 6 7 8
Both SGCPU
Not output OFF
AGTXT output default setting
Output ON
At normal OFF S12
For factry
For factry ON 1 O
OFF N
Unused Usually set to "OFF" 2
Switch number

ON 3
Invalid (Ver1.12.2~) OFF 4
Wheel override function
Valid (Ver1.12.2~) ON 5
OFF 6
Unused Usually set to "OFF"
ON 7
Setting of input HLA Normal Open (Ver1.11.9~) OFF 8
contact signal Normal Close (Ver1.11.9~) ON
Forced selection of rudder Invalid (Ver1.13.7~) OFF
limit circuit by ship's speed Valid (Ver1.13.7~) ON : SW position
At installing FU/NFU mode Not installed(Normal mode switch) (Ver1.13.9~) OFF
switch Installed(Special mode switch) (Ver1.13.9~) ON

17
2017.4.20
TOKYO KEIKI INC. PR-9000 setting Made by service engineering section
(SGCPU)
Table of Dip SW(S13)
Switch number No.1SGCPU
Setting content 1 2 3 4 5 6 7 8 default setting
Select RC type Override OFF
S13
(Remote control) Use RCPIF ON
Select SGCU No.1 system OFF 1 O
N
system number No.2 system ON 2

Switch number
D type OFF OFF OFF 3
L type ON OFF OFF 4
E type OFF ON OFF 5
P type ( Not used ) 6
ON ON OFF
Rudder control type 7
FR type OFF OFF ON
FP type ON OFF ON 8
Unused OFF ON ON
Unused ON ON ON
2 systems OFF : SW position
Number of HCU
1 system ON
Single rudder OFF
Number of Rudder No.2SGCPU
Twin rudders ON default setting
Number of pump 1 pump OFF
(*)11 2 pumps ON S13
1 O
!!) Load timing of Dipsw is at starting up Autopilot. N
2

Switch number
3
(*)11 This is the number of pumps per system , not the total pumps. 4
Example): 5
A pump per system : The setting is to be "OFF" both of No.1 SGCPU and No.2 SGCPU. 6
Total 3 pumps : The setting is to be "ON" for No.1 SGCPU and "OFF" for No.2 SGCPU.
7
Total 4 pumps : The setting is to be "ON" both of No.1 SGCPU and No.2 SGCPU.
8

Table of Dip SW(S14)


Switch number
Setting content 1 2 3 4 5 6 7 8
Both SGCPU
None OFF OFF OFF OFF Default setting
1 unit ON OFF OFF OFF
2 units OFF ON OFF OFF S14
Number of UID 3 units ON ON OFF OFF 1 O
(UID: User Input 4 units OFF OFF ON OFF N
2
Switch number

Device) 5 units ON OFF ON OFF 3


6 units OFF ON ON OFF 4
7 units ON ON ON OFF 5
8 units OFF OFF OFF ON 6
Not used OFF OFF 7
Steering modes to
HC/TC modes ON OFF 8
allow override
Any mode other than NFU mode OFF ON
operation
All modes ON ON
Helm unit dimmer Available OFF
control by ANN (*)9 : SW position
Not available ON
Nautical safety Not nautical safety (*) This function is NOT available. OFF
Nautical safty (*) This function is NOT available. ON

(*)12 The Helm unit is available to use as an override unit for specific
application. Then DipSW set to "ON".

18
2017.4.20
TOKYO KEIKI INC. PR-9000 setting Made by service engineering section
(SGCPU)
4-1-2. Settings of SGCPU jumpers
Jumper Default Setting content
1-2 Short 1-2 Short 1-2 Open
Default
E1 setting
3-4 Open From 3-4 Open Input 3-4 Short
E1
Input feedback signal repeat analog
1-2 Short back unit 1-2 Short signal 1-2 Open 2 1
E2 4 3
3-4 Open 3-4 Open 3-4 Short
E2
1-2 Short 1-2 Short Other than 1-2 Open 2 1
Output order signal Resolver
E3 resolver 4 3
from Helm unit signal
3-4 Open 3-4 Open signal 3-4 Short E3

1-2 Short Output rudder order


D type 1-2 Short 1-2 Open 2 1
E4 signal 4 3
(PD signal)
3-4 Open (Stbd rudder) (*)13 3-4 Open 3-4 Short E4
FR/FP Current
type 4-20mA 2 1
1-2 Short Output rudder order 1-2 Short 1-2 Open
E5 (Analog 4 3
signal
voltage)
3-4 Open (Port rudder) (*)13 3-4 Open 3-4 Short E5
2 1
(*)13 SGCPU-E has no jumper for "E4" and "E5".
4 3

: Short

19
2017.4.20
TOKYO KEIKI INC. PR-9000 setting Made by service engineering section
(ESQC)

4-2. ESQC PWB

E11 E8
E12
E13

E10

E4

E3

E2

E1

E9 E7
E5
E6

Fig8-1. ESQC PWB (11329422-) Layout

20
2017.4.20
TOKYO KEIKI INC. PR-9000 setting Made by service engineering section
(ESQC)

E12 E11
E20 E8 E13

E10

E4
E3

E2

E1
E21 E5
E6 E7

Fig8-2. ESQC-E1 PWB (11329437-) Layout

E12 E11
E20 E8 E13

E10

E4
E3

E2

E1
E21 E5
E6 E7

Fig8-3. ESQC-E2 PWB (11329438-) Layout

All settings of Dip switches and jumpers below are loaded at Autopilot starting-up.
Some settings noted are available to change during Autopilot operating condition.
Pay special attention to change the setting while operating.

21
2017.4.20
TOKYO KEIKI INC. PR-9000 setting Made by service engineering section
(ESQC)
4-2-1 Settings of ESQC jumpers
Jumper Default Setting content Default
1-2 Open 1-2 Open 1-2 Short setting
Output steering mode At At
3-4 Short signal selecting 3-4 Short selecting 3-4 Open E1
E1 (Dry contact) applicable applicable 8 6 4 2
5-6 Open SGTRM: 5-6 Open 5-6 Short
mode: mode: 7 5 3 1
MDCN1/MDCN2
(!!) With the specific software Open Close
7-8 Short 7-8 Short 7-8 Open

1-2 Open 1-2 Open 1-2 Short


Output steering mode At At E2
3-4 Short signal selecting 3-4 Short selecting 3-4 Open
(Dry contact) 8 6 4 2
E2 applicable applicable
5-6 Open SGTRM: 5-6 Open 5-6 Short 7 5 3 1
mode: mode:
MDCN3/MDCN4
(!!) With the specific software Open Close
7-8 Short 7-8 Short 7-8 Open

1-2 Open 1-2 Open 1-2 Short


E3
Output alert signal
3-4 Short Normal: 3-4 Short Normal: 3-4 Open 8 6 4 2
(Dry contact)
E3 Close Open 7 5 3 1
SGTRM:
5-6 Open (At alert: Open) 5-6 Open (At alert: Close) 5-6 Short
ALCN1/ALCN2

7-8 Short 7-8 Short 7-8 Open

1-2 Open 1-2 Open 1-2 Short


Output "RUN" dry E4
3-4 Short During 3-4 Short During 3-4 Open
contact signal 8 6 4 2
E4 running: running:
5-6 Open SGTRM: 5-6 Open Open 5-6 Short 7 5 3 1
Close
RNCN1/RNCN2
7-8 Short 7-8 Short 7-8 Open
E5
1-2 Open Baudrate select of No.1 HCS 1-2 Open 1-2 Short
serial signal (Except for HC IEC61162-1 IEC61162-2 4 2
E5 mode) 4800bps 38400bps 3 1
3-4 Short Same as for E1 of HIFIO 3-4 Short 3-4 Open

1-2 Open Baudrate select of No.2 HCS 1-2 Open 1-2 Short E6
serial signal (Except for HC IEC61162-1 IEC61162-2
E6 4 2
mode) 4800bps 38400bps
3-4 Short Same as fpr E2 of HIFIO 3-4 Short 3-4 Open 3 1

1-2 Short Output NFU dry 1-2 Short 1-2 Open


Other than E7
contact signal Twin
E7 3-4 Short (For VDR) Twin 3-4 Short 3-4 Open 6 4 2
rudders
SGTRM: rudders 5 3 1
5-6 Short NFUC/NFUP/NFUS 5-6 Short 5-6 Open
Output steering mode E8 2
E8 1-2 Short At NFU 1-2 Short At all modes 1-2 Open
signal (For VDR) 1
1-2 Open 1-2 Open 1-2 Short E9

3-4 Open 3-4 Open 3-4 Short 8 6 4 2


E9 (*)14 Not used Not used Not used 7 5 3 1
5-6 Open 5-6 Open 5-6 Short
: Short
7-8 Open 7-8 Open 7-8 Short

(*)14 E9 is deleted since ESQC-E1 and ESQC-E2.

22
2017.4.20
TOKYO KEIKI INC. PR-9000 setting Made by service engineering section
(ESQC)

Jumper Default Setting content


1-2 Open 1-2 Open 1-2 Short Default
Output power failure setting
(For No.1/No.2 power)
3-4 Short Normal: 3-4 Short Normal: 3-4 Open E10
E10 Close Open
5-6 Open (At alert: Open) 5-6 Open (At alert: Close) 5-6 Short 8 6 4 2
Output power failure
7 5 3 1
(For No.3/No.4 power)
7-8 Short 7-8 Short 7-8 Open

1-2 Short 1-2 Short 1-2 Open 1-2 Open


E11
No.1 No.2
3-4 Open Communic 3-4 Open 3-4 Open ESQC 3-4 Open 8 6 4 2
ESQC
E11 -ation with Dual HCU
5-6 Open 5-6 Open with single 5-6 Short with single 5-6 Open 7 5 3 1
HCU
HCU HCU
7-8 Open 7-8 Open 7-8 Open 7-8 Short
E12
1-2 Short Communication with 1-2 Short 1-2 Open 4 2
E12 another SGCU 3 1
3-4 Open (Transmit and receive) 3-4 Open 3-4 Short
Normal Not used E13
1-2 Short Communication with 1-2 Short 1-2 Open 4 2
E13 No.1 and No.2 HCU 3 1
3-4 Open (Transmit and receive) 3-4 Open 3-4 Short

1-2 Short 1-2 Short 1-2 Open


E20
E20 3-4 Open 3-4 Open 3-4 Short
No.1 No.2 8 6 4 2
ESQC system number
(*)15 5-6 Short ESQC 5-6 Short ESQC 5-6 Open 7 5 3 1

7-8 Open 7-8 Open 7-8 Short

1-2 Short 1-2 Short 1-2 Open


E21

E21 3-4 Short 3-4 Short 3-4 Open 8 6 4 2


E1,E2,E3,
Steering control type E0 Type 7 5 3 1
(*)15 5-6 Short 5-6 Short L type 5-6 Open

7-8 Short 7-8 Short 7-8 Open

(*)15 E20 and E21 are added since ESQC-E1 and ESQC-E2.
: Short

23
2017.4.20
TOKYO KEIKI INC. PR-9000 setting Made by service engineering section
(DSQC)
4-3. DSQC PWB

E7 E19 E17 E8
E10

E4
E3

E2

E1

E5
E9
E6

E20
E11 E12 E13 E14
E18
E15

E16

Fig9. DSQC PWB (11329423-) Layout

All settings of Dip switches and jumpers below are loaded at Autopilot starting-up.
Some settings noted are available to change during Autopilot operating condition.
Pay special attention to change the setting while operating.

24
2017.4.20
TOKYO KEIKI INC. PR-9000 setting Made by service engineering section
(DSQC)
4-3-1. Settings of DSQC jumpers
Jumper Default Setting content
1-2 Open Output steering mode 1-2 Open 1-2 Short Default setting
signal At At
3-4 Short (Dry contact)
selecting 3-4 Short selecting 3-4 Open
E1 applicable applicable E1
SGTRM:
5-6 Open MDCN1/MDCN2 mode: 5-6 Open mode: 5-6 Short 8 6 4 2
(!!) With the specific Close Open 7 5 3 1
7-8 Short software 7-8 Short 7-8 Open

1-2 Open Output steering mode 1-2 Open 1-2 Short E2


signal At At
3-4 Short selecting 3-4 Short selecting 3-4 Open 8 6 4 2
(Dry contact)
E2 applicable applicable 7 5 3 1
SGTRM:
5-6 Open MDCN3/MDCN4 mode: 5-6 Open mode: 5-6 Short
(!!) With the specific Close Open
7-8 Short software 7-8 Short 7-8 Open

1-2 Open 1-2 Open 1-2 Short E3


8 6 4 2
Output alert signal
3-4 Short 3-4 Short Normal: 3-4 Open 7 5 3 1
(Dry contact) Normal:
E3
5-6 Open SGTRM: Close 5-6 Open Open 5-6 Short
ALCN1/ALCN2

7-8 Short 7-8 Short 7-8 Open


E4
1-2 Open 1-2 Open 1-2 Short
8 6 4 2
Output "RUN" dry
3-4 Short During 3-4 Short During 3-4 Open 7 5 3 1
contact signal
E4 running: running:
5-6 Open SGTRM: 5-6 Open Open 5-6 Short
Close
RNCN1/RNCN2 E5
7-8 Short 7-8 Short 7-8 Open 4 2
3 1
1-2 Open Baudrate select of No.1 1-2 Open IEC61162-2 1-2 Short
HCS serial signal(Except for IEC61162-1
E5 E6
HC mode) 4800bps 38400bps
3-4 Short Same as for E1 of HIFIO 3-4 Short 3-4 Open
4 2
Baudrate select of No.2 3 1
1-2 Open 1-2 Open IEC61162-2 1-2 Short
HCS serial signal (Except for IEC61162-1
E6
HC mode) 4800bps 38400bps E7
3-4 Short Same as for E2 of HIFIO 3-4 Short 3-4 Open
6 4 2
1-2 Short Output NFU dry 1-2 Short 1-2 Open 5 3 1
contact signal Other than
Twin
E7 3-4 Short (For VDR) Twin 3-4 Short 3-4 Open 2
rudders E8
SGTRM: rudders 1
5-6 Short NFUC/NFUP/NFUS 5-6 Short 5-6 Open
E9
Output steering mode
E8 1-2 Short At NFU 1-2 Short At all modes 1-2 Open 4 2
signal (For VDR) 3 1
1-2 Short 1-2 Short From 1-2 Open
Signal output to
E9 From ANN Control
external equipment
3-4 Open 3-4 Open box 3-4 Short E10
8 6 4 2
1-2 Open 1-2 Open 1-2 Short 7 5 3 1
Output power failure
(For No.1/No.2 power)
3-4 Short Normal: 3-4 Short Normal: 3-4 Open
E10 Close Open
5-6 Open (At alert: Open) 5-6 Open (At alert: Close) 5-6 Short : Short
Output power failure
(For No.3/No.4 power)
7-8 Short 7-8 Short 7-8 Open

25
2017.4.20
TOKYO KEIKI INC. PR-9000 setting Made by service engineering section
(DSQC)

Jumper Default Setting content


Default
1-2 Short 1-2 Short 1-2 Open 1-2 Open setting

3-4 Open Communic 3-4 Open No.1 3-4 Open No.2 3-4 Open
E11 -ation with Dual HCU DSQC with DSQC with E11
5-6 Open HCU 5-6 Open single HCU 5-6 Short single HCU 5-6 Open
8 6 4 2

7-8 Open 7-8 Open 7-8 Open 7-8 Short 7 5 3 1

1-2 Short Communication with 1-2 Short 1-2 Open


E12 another SGCU E12
3-4 Open (Transmit and receive) 3-4 Open 3-4 Short 4 2
3 1
1-2 Short Communication with 1-2 Short 1-2 Open
E13 No.1 and No.2 HCU E13
3-4 Open (Transmit and receive) 3-4 Open 3-4 Short
Normally 4 2
Unused
Communication with used 3 1
1-2 Short 1-2 Short 1-2 Open
E14 control box of another
E14
3-4 Open system (receive) 3-4 Open 3-4 Short
4 2
1-2 Short Communication with 1-2 Short 1-2 Open 3 1
E15 own control box
E15
3-4 Open (Transmit and receive) 3-4 Open 3-4 Short
4 2
1-2 Short Autopilot monitor No.1 Normally 1-2 Short 1-2 Open 3 1
and No.2 control box or
3-4 Short by dry contact signal Connects 3-4 Short 3-4 Open
SGTRM: CBTX+/CBTX- Unused : Short
dry
5-6 Short (CH1) 5-6 Short 5-6 Open
SGTRM: CBTX+/CBTX-
contact
7-8 Short (CH2) signal 7-8 Short 7-8 Open Default
E16 setting
Transmits serial signal
9-10 Open 9-10 Open 9-10 Short
to No.1 and No.2
control box 11-12 11-12 E16
11-12 Open
SGTRM: CBTX+/CBTX- Open Serial Short
Unused 13-14 16 14 12 10 8 6 4 2
Receives serial signal 13-14 signal
13-14 Open
from No.1 and No.2 Open Short 15 13 11 9 7 5 3 1
control box 15-16 15-16
15-16 Open
SGTRM: CBRX+/CBRX- Open Short
1-2 Short 1-2 Short 1-2 Open E17
Dry contact Serial
E17 Signal GND with E16 4 2
signal signal
3-4 Open 3-4 Open 3-4 Short 3 1

1-2 Short Autopilot monitor No.3 1-2 Short 1-2 Open


and No.4 control box by Normally
3-4 Short dry contact signal or 3-4 Short 3-4 Open
SGTRM: CBTX+/CBTX- Connects Serial signal
5-6 Short (CH1) dry contact 5-6 Short 5-6 Open
SGTRM: CBTX+/CBTX- signal
E18
7-8 Short (CH2) 7-8 Short 7-8 Open
E18 16 14 12 10
Transmits serial signal 8 6 4 2
9-10 Open 9-10 Open 9-10 Short
to No.3 and No.4 15 13 11 9 7 5 3 1
control box 11-12 11-12
11-12 Open
SGTRM: CBTX+/CBTX- Open Serial Short
Unused
Receives serial signal 13-14 signal 13-14
13-14 Open
from No.3 and No.4 Open Short
control box 15-16 15-16 E19
15-16 Open
SGTRM: CBRX+/CBRX- Open Short
4 2
1-2 Short 1-2 Short 1-2 Open
Dry contact Serial 3 1
E19 Signal GND with E18
signal signal
3-4 Open 3-4 Open 3-4 Short
E20
1-2 Short 1-2 Short 1-2 Open
E20
8 6 4 2
(Added 3-4 Open 3-4 Open 3-4 Short
DSQC system No.1 No.2 7 5 3 1
since
number DSQC 5-6 Short DSQC 5-6 Open
suffix_0 5-6 Short
5)
7-8 Open 7-8 Open 7-8 Short :Short

26
2017.4.20
TOKYO KEIKI INC. PR-9000 setting Made by service engineering section
(SGTU)
5. SGTU(Steering Gear Terminal Unit)
5-1. SGTRM PWB

Added from last


digit number _3.
E1

Fig10-1. SGTRM PWB(11329426 03) Fig10-2. SGTRM PWB(11329426 02)

All settings of Dip switches and jumpers below are loaded at Autopilot starting-up.
Some settings noted are available to change during Autopilot operating condition.
Pay special attention to change the setting while operating.

5-1-1. Settings of SGTRM Jumpers


Jumper Setting content

J6(E1) Short Open Open Open


Steering gear E1,L E2,E3 E0,F
J7 D type Open Short Open Open
control type type type type
J8 Open Open Short Open

27
2017.6.22
TOKYO KEIKI INC. PR-9000 setting Made by service engineering section
(ANN)
6. ANN(Annunciator unit)
6-1 ANNM PWB

ANNS PWB

ANNM PWB

ANND PWB

S1

S1

E1

Fig11-1. ANNS PWB(11329414-) Fig11-2. ANNM PWB(11329411-) Fig11-3. ANND PWB(11329411-)


Layout Layout Layout

All settings of Dip switches and jumpers below are loaded at Autopilot starting-up.
Some settings noted are available to change during Autopilot operating condition.
Pay special attention to change the setting while operating.

28
2017.6.22
TOKYO KEIKI INC. PR-9000 setting Made by service engineering section
(ANN)
6-1-1. Settings of ANNM Dip switches
Table of Dip SW(S1)
Switch number
Setting content 1 2 3 4 5 7 68
1 pump OFF OFF
Number of pumps 2 pumps ON OFF
(For ANN display) 3 pumps OFF ON
4 pumps ON ON
At overriding,
No buzzer OFF
buzzer to be
provided
Buzzer ON
2 units OFF
Number of SGCU
1 unit ON
Inhibit OFF
Input ALR sentence
Permit ON
Output alert No output OFF
sentence Output ON
Reqirement of Normal type OFF
changing RC Spec. of Japan cost gaurde ON
mode Spec. of installation of KICS OFF
(*)16 Not used ON

(*)16
Spec. of Japan cost gaurde: If the rudder angle is within 5deg, then change to RC
mode.

S1
ON
Default
setting : SW position

1 2 3 4 5 6 7 8
Switch number

6-1-2. Setting of ANNM jumper


Jumper Default Setting content
Connected with
1-2 Open Connected 1-2 Short Normal 1-2 Open
Emulator
E1 3-4 Short
Not used
5-6 Open

Default
setting

E1
2 1
: Short
4 3
6 5

29
2017.6.22
TOKYO KEIKI INC. PR-9000 setting Made by service engineering section
(ANN)
6-1-3. Settings of ANNS Dip switches

Switch number
Setting content 1 2 3 4 5 6 7 8
ALF with added sentence Not output OFF
outputs (*)17 Output ON
OFF
Not used
ON
OFF
Not used
ON
OFF
Not used
ON
OFF
Not used
ON
OFF
Not used
ON
OFF
Not used
ON
OFF
Not used
ON

S1
ON
Default
setting : SW position

1 2 3 4 5 6 7 8
Switch number

(*) 17
When this setting set to "OFF", ALF sentence keeps outputting.
When this setting set to "ON", The detail of ALF sentence changes to special
sentence.(for Nautical safety)
Software Ver: Ver 1.13.42 and Ver1.14.8
(HIFCPU, HCCPU and SGCPU must be change special software.)

30
2017.4.20
TOKYO KEIKI INC. PR-9000 setting Made by service engineering section
(Repeater unit)
7.Repeater Unit

S1

8 7 65 4 3 21 S2
ON
8 7 65 4 3 21
Remove the cover ON S3
8 7 65 4 3 21
ON

Fig12. Repeater unit back side

All settings of Dip switches and jumpers below are loaded at Autopilot starting-up.
Some settings noted are available to change during Autopilot operating condition.
Pay special attention to change the setting while operating.

7-1. Settings of Repeater Unit Dip switches


Table of Dip SW(S1)
Switch number
Setting content 1 2 3 4 5 6 7 8
PR-9000 OFF OFF
PR-9000-ZZ ON OFF
Product type (*)18
Repeater OFF ON
Unused ON ON
OFF
Unused -
ON
OFF
Unused -
ON
OFF
Unused -
ON
OFF
Unused -
ON
OFF
Unused -
ON
OFF
Unused -
ON
S1 Switch number
(*)18 PR-9000: Display Heading, HCS info and ANN info.
PR-9000-ZZ: Display Heading and HCS info. 1 2 3 4 5 6 7 8
Default
Repeater: Display Heading setting
ON

: SW position

31
2017.4.20
TOKYO KEIKI INC. PR-9000 setting Made by service engineering section
(Repeater unit)

!!) Dip switch(S2) is not used.


Table of Dip SW(S3)
Switch number
Setting content 1 2 3 4 5 6 7 8
Condition of connecting Straight (Ver1.02~) OFF
pump(for monitor mode) Cross (Ver1.02~) ON
Display of heading data ***.* OFF
fault(Ver 1.02~) Display heading data by red color ON
Dimmer level at starting Dimmer of just before power off OFF
(Ver 1.02~) Intermediate luminance at starting ON
OFF
It is not used now
ON
for changing Flash ROM At normal OFF
software at changing Flash ROM software ON
CPU version is displayed OFF
Software version
System version is displayed (At normal) ON
At normal OFF
For debug
For debugging ON
For changing software At normal OFF
version For software update ON

S3 Switch number
1 2 3 4 5 6 7 8
Default
setting : SW position

ON

32
2017.4.20
TOKYO KEIKI INC. PR-9000 setting Made by service engineering section
(DLIF/RCCPU)
8. Remote control unit
8-1 DLIF PWB

DLIF PWB
RCPWR PWB RCCPU PWB

S1

SW1 SW2

Fig13-1. DLIF Fig13-2. RCCPU Fig13-3. RCPWR


PWB (11329468-) PWB (11329461-) PWB (11329472-)

All settings of Dip switches and jumpers below are loaded at Autopilot starting-up.
Some settings noted are available to change during Autopilot operating condition.
Pay special attention to change the setting while operating.

8-1-1. Setting of DLIF Dip switch


Table of Dip SW(S1) S1
SW number
Setting content 1 2 O
Default 1 N
Select of P/S lamp Stbd: Green, Port: Red ON OFF setting 2
color Stbd: Red, Port: Green OFF ON

Note: Setting is available appropriately.


: SW position

33
2017.4.20
TOKYO KEIKI INC. PR-9000 setting Made by service engineering section
(DLIF/RCCPU)
8-2. RCCPU PWB
8-2-1. Settings of RCCPU Dip switches
Table of Dip SW(SW1)
Switch number
Setting content 1 2 3 4 5 6 7 8
UID1 OFF OFF OFF
UID2 ON OFF OFF
UID3 OFF ON OFF
Channel number of
UID4 ON ON OFF
UID(User input
UID5 OFF OFF ON
Device)
UID6 ON OFF ON
UID7 OFF ON ON
UID8 ON ON ON
Invalid OFF
Porarity of Port/Stbd
Valid ON
Select of Override Unused OFF
unit Override unit ON
OFF
Not used -
ON
Single rudder OFF OFF
Twin rudders (Synchronize) ON OFF
Rudder type
Twin rudders (Independent) OFF ON
Unused ON ON

SW1Switch number
ON
Default
setting : SW position
1 2 3 4 5 6 7 8

Note: Setting is available appropriately.

Table of Dip SW(SW2)


Switch number
Setting content 1 2 3 4 5 6 7 8
Dial OFF OFF OFF OFF
Lever ON OFF OFF OFF
Tiller OFF ON OFF OFF
Standby JOY ON ON OFF OFF
Alarm JOY OFF OFF ON OFF
Select of steering
Vec-Twin JOY 25° ON OFF ON OFF
device
Unused OFF ON ON OFF
HELM ON ON ON OFF
Vec-Twin JOY 35° OFF OFF OFF ON
ANALOG NAV ON OFF OFF ON
DP system OFF ON OFF ON
OFF
Not used -
ON
OFF
Not used -
ON
Communication Unused OFF
procedure At normal ON
Normal OFF
Adjustment mode
At adjustment ON

SW2Switch number
ON
Default
setting : SW position
1 2 3 4 5 6 7 8

34
2017.6.22
TOKYO KEIKI INC. PR-9000 setting Made by service engineering section
(JVIF)
8-3 JVIF PWB

JVIF PWB
RCPWR PWB RCCPU PWB

Fig14-1. JVIF Fig14-2. RCCPU Fig14-3. RCPWR Fig14-4. JVIF


PWB(11329469_) PWB(11329461_) PWB(11329472_) PWB(113294690)
Layout Layout Layout Layout

8-3-1. Setting of JVIF PWB jumpers


Default
Jumper Default Setting content setting

1-2 Open Dry contact signal output of At 1-2 Open At 1-2 Short E1
Ready operating operating
8 6 4 2
E1 3-4 Short (CX1,CX2) : Close 3-4 Short : Open 3-4 Open
7 5 3 1
(*)19 5-6 Open Dry contact signal output of At 5-6 Open At 5-6 Short
Ready operating operating
7-8 Short (CX3,CX4) : Close 7-8 Short : Open 7-8 Open E2
Setting common of CX1 and Not 2
E2 1-2 Short Common 1-2 Short 1-2 Open
CX3(Internal connection) common 1
1-2 Open Dry contact signal output of At 1-2 Open At 1-2 Open
Ready operating operating E3
3-4 Short (CX5,CX6) : Close 3-4 Short : Open 3-4 Short
8 6 4 2
E3
Dry contact signal output of At 7 5 3 1
5-6 Open 5-6 Open At 1-2 Open
Ready operating operating
7-8 Short (CX7,CX8) : Close 7-8 Short : Open 3-4 Short E4
Setting common of CX5 and Not 2
E4 1-2 Short Common 1-2 Short 1-2 Open
CX7(Internal connection) common 1

(*)19 JVIF PWB(113294690) has only E1(1-2,3-4)

: Short

35
2017.04.20
TOKYO KEIKI INC. PR-9000 setting Made by service engineering section
(RCPIF PWB)

8-3. RCPIF PWB


E3 E2 E1 E4

E8
SW1

Fig14. RCPIF PWB


SW4 SW3 SW2
(11329475-)

E7

!!) For unit type Autopilot, RCPIF PWB is


equipped in
NSD box.
E6 E5

All settings of Dip switches and jumpers below are loaded at Autopilot starting-up.
Some settings noted are available to change during Autopilot operating condition.
Pay special attention to change the setting while operating.

8-3-1. Settings of RCPIF Dip switch


Table of Dip SW(SW1 and SW3)
Switch number
Setting content 1 2 3 4 5 6 7 8
No connection OFF OFF OFF OFF Default setting
Dial ON OFF OFF OFF
Lever OFF ON OFF OFF SW1/SW3
Tiller ON ON OFF OFF O
Select of steering 1
Cable RC OFF OFF ON OFF N

Switch number
device 2
Standby/Alarm JOY ON OFF ON OFF
3
Vec-twin JOY OFF ON ON OFF
4
Dial with ACK button ON ON ON OFF
5
Cable RC(for 60deg) OFF OFF OFF ON 6
Porarity of Invalid OFF
7
Port/Stbd Valid ON
8
Communication Unused OFF
procedure Normal ON
Single rudder OFF OFF
Twin rudders (Synchronize) ON OFF : SW position
Rudder type
Twin rudders (Independent) OFF ON
Unused ON ON

Table of Dip SW(SW2 and SW4)


Switch number
Setting content 1 2 3 4 5 6 7 8
None OFF OFF OFF OFF Default setting
Dial ON OFF OFF OFF
Lever OFF ON OFF OFF SW2/SW4
Tiller ON ON OFF OFF
Select of steering 1 O
device Cable RC OFF OFF ON OFF N
Switch number

2
Standby/Alarm JOY ON OFF ON OFF
3
Vec-twin JOY OFF ON ON OFF
4
Dial with ACK button ON ON ON OFF
5
Cable RC(for 60deg) OFF OFF OFF ON
6
Porarity of Invalid OFF
Port/Stbd Valid ON 7
Communication Unused OFF 8
procedure Normal ON
OFF
Not used -
ON : SW position
OFF
Not used -
ON

36
2017.04.20
TOKYO KEIKI INC. PR-9000 setting Made by service engineering section
(RCPIF PWB)

8-3-2. Settings of RCPIF jumpers


Default
Jumper Default Setting content setting

1-2 Short Input of 1-2 Short Input of 1-2 Open E1


potentio
Input signal of No.1 RC meter voltage 2 1
E1 3-4 Open 3-4 Open signal 3-4 Short
device signal 4 3
(JOY system
(Dial, Lever, 6 5
5-6 Open 5-6 Open etc) 5-6 Open
Tiller, RC)

1-2 Short Input of 1-2 Short 1-2 Open E2


Input of
potentio
Input signal of No.2 RC meter voltage 2 1
E2 3-4 Open 3-4 Open signal 3-4 Short 4 3
device signal
(JOY system 6 5
(Dial, Lever,
5-6 Open 5-6 Open etc) 5-6 Open
Tiller, RC)

1-2 Short Input of 1-2 Short Input of 1-2 Open E3


potentio
Input signal of No.3 RC meter voltage 2 1
E3 3-4 Open 3-4 Open signal 3-4 Short 4 3
device signal
(JOY system 6 5
(Dial, Lever,
5-6 Open 5-6 Open etc) 5-6 Open
Tiller, RC)

1-2 Short Input of 1-2 Short Input of 1-2 Open E4


potentio
Input signal of No.4 RC meter voltage 2 1
E4 3-4 Open 3-4 Open signal 3-4 Short
device signal 4 3
(JOY system
(Dial, Lever, 6 5
5-6 Open 5-6 Open etc) 5-6 Open
Tiller, RC)

1-2 Short 1-2 Short 1-2 Open E5


Output No.1 ready Normal: Normal: 2 1
E5 3-4 Open 3-4 Open 3-4 Short
contact signal Close Open 4 3
6 5
5-6 Open 5-6 Open 5-6 Open

1-2 Short 1-2 Short 1-2 Open E6


2 1
Output No.2 ready Normal: Normal:
E6 3-4 Open 3-4 Open 3-4 Short 4 3
contact signal Close Open 6 5
5-6 Open 5-6 Open 5-6 Open
Selection of RCPIF No.1 RCPIF
E7 1-2 Short 1-2 Short No.2 RCPIF
1-2 Open E7
2
system number (CH1 to CH4) (Ch5 to Ch8 )
1
E8 1-2 Open Not used
1
E8
2

: Short

37
AUTO PILOT PR-9000
Part of Jumper & Dip SW setting
Document No. SG16-SE001B
Issued: 1st Edition 24 May 2016
2nd Edition 3 Feb 2017
3rd Edition 24 Jun 2017

TOKYO KEIKI INC.


2-16-46, MINAMI-KAMATA, OHTA-KU, TOKYO
144-8551, JAPAN
Tel. (81) 3-3732-6583 FAX. (81) 3-3732-5050

Notice: This manual must not be copied or reproduced without expressed written
permission of TOKYO KEIKI.