15.1.

Determine the required cooling water flowrate for the conditions in the following Table:
Steam supply Enthalpy XSteam_Excel_v2.4
Pressure: 10 bar a
Temperature: 300 °C 3051.70 kJ/kg
Mass flowrate: 10000 kg/h
Cooling Water supply
Pressure: 15 bar a
Temperature: 150 °c 632.88 kJ/kg
Required steam conditions
Pressure: 10 bar a
Temperature: 5 °C
Sat tempe + 179.89
Sat tempe + 5 : 184.89 °C 2790.40 kJ/kg

mcw = 1211.12 kg/h


total steam: 11211.12 kg/h

Mass flowrate: 8919.72 kg/h initial superheated steam


CWS: 1080.28 kg/h Cooling water
Total steam: 10000.00 kg/h Desuperheated steam