Saudi Electricity Company

Construction Standard for Overhead Lines Issue Date: Nov/2021 Page: 1 of 10


Part 24: Low Voltage Circuit to Consumer Meter Box SDCS-01-24

SDCS-01-24
Rev.0

CONSTRUCTION STANDARD FOR OVERHEAD LINES


PART 24: LOW VOLTAGE CIRCUIT TO CONSUMER
METER BOX

This document contains proprietary information developed by and for exclusive use of Saudi Electricity
Company (SEC) Distribution Network. Your acceptance of the document is an acknowledgment that it
must be used for the identified purpose/application and during the period indicated. It cannot be used or
copied for any other purposes nor released to others without prior written authorization of SEC
Distribution Sector. SEC shall assume no responsibility for any type of misuse and/or misapplication, and
any arm resulting there from. SEC also reserves the right take any necessary actions to protect its interest
against unauthorized use.

Recommended by: Approved by:

MUSAB. M. ALBURIKAN SALEH ALI SHANNAN

Standards and Specifications Project Engineering and Control


Division Manager (A) Department Manager
Saudi Electricity Company
Construction Standard for Overhead Lines Issue Date: Nov/2021 Page: 2 of 10
Part 24: Low Voltage Circuit to Consumer Meter Box SDCS-01-24

SDCS-01-24
Rev.0

CONSTRUCTION STANDARD FOR OVERHEAD LINES


PART 24: LOW VOLTAGE CIRCUIT TO CONSUMER
METER BOX

Department /
No. Name Signature Date
Sector

1 Mofeed M.Almajed Dept. - EOA 10/11/2021

2 Dept. - SOA
Saeed S Altazza 9/11/2021

3 Saeid A. Fallatah Dept. - WOA 7/11/2021

4 Alhajaj Aldosari Dept. - COA 12/11/2021

Name Abdullah T. Alshaikh Abdullah A. Al maraan Edwin M.. Porciuncula Mohamed S. Maali Ahmed Al-Haj
Signature
Saudi Electricity Company
Construction Standard for Overhead Lines Issue Date: Nov/2021 Page: 3 of 10
Part 24: Low Voltage Circuit to Consumer Meter Box SDCS-01-24

Revision History
# Date Revision Revised By Major Revision Description
No.
1
2
3
4
5
6
7
8
9
10
Saudi Electricity Company
Construction Standard for Overhead Lines Issue Date: Nov/2021 Page: 4 of 10
Part 24: Low Voltage Circuit to Consumer Meter Box SDCS-01-24

Table of Contents
1 Introduction ........................................................................................................................ 5
2 Revisions and additions ..................................................................................................... 5
3 Service conditions and system parameters ........................................................................ 5
4 LV Overhead Connections Network Configuration .......................................................... 5

List of Drawings:
Figure 1. OH Main Feeder with Service Drop 50 mm2 Quadruplex Conductor ................................... 6
Figure 2. Service Entrance drop on Consumers Wall/Building typical from all L. V. Structures .......... 7
Figure 3. Service Entrance drop on Consumer’s Wall typical from all L. V. Structures ....................... 9

List of Tables:
Table 1. Service Entrance drop on Consumer’s Wall/Building typical from all L. V. Structures .......... 8
Table 2. Service Entrance drop on Consumer’s Wall typical from all L. V. Structures ....................... 10
Saudi Electricity Company
Construction Standard for Overhead Lines Issue Date: Nov/2021 Page: 5 of 10
Part 24: Low Voltage Circuit to Consumer Meter Box SDCS-01-24

1 Introduction
This construction standard specifies the minimum requirements for Low Voltage overhead
connections to the customers meter box.

This standard is intended to assist the field engineers and technicians to achieve uniform
standard in construction to ensure a satisfactory and economical level of service without
operating restrictions so that the operational errors are minimized for safety and reliability of
the system.

2 Revisions and additions


This construction standard is subject to revision as new material and methods of
construction are developed. The latest revision of this construction standard shall be
applicable.

3 Service conditions and system parameters


For installation of Low Voltage Circuit overhead connections to the customers meter box,
the service conditions and system requirements shall be as given in the latest revision of
SEC General Requirements for All Equipment/Material Specification No. 01-SDMS-01

4 LV Overhead Connections Network Configuration


There are two configurations for customer low voltage overhead connections to the
customers meter box as following:
Saudi Electricity Company
Construction Standard for Overhead Lines Issue Date: Nov/2021 Page: 6 of 10
Part 24: Low Voltage Circuit to Consumer Meter Box SDCS-01-24

4.1 OH main LV feeder with 50 mm2 QUADRUPLEX conductor as service drop


connection.

This type of configuration is shown in Figure 1. For this condition, Quadruplex


Conductor 120 mm2 shall be used as main OH LV feeder from PMT LV cabinet to
customer location, and Quadruplex Conductor 50 mm2 shall be used as service drop
connection from that location to the customer meter/meters box.

Figure 1. OH Main Feeder with Service Drop 50 mm2 Quadruplex Conductor


Saudi Electricity Company
Construction Standard for Overhead Lines Issue Date: Nov/2021 Page: 7 of 10
Part 24: Low Voltage Circuit to Consumer Meter Box SDCS-01-24

All Dimensions are in Millimeter

Figure 2. Service Entrance drop on Consumers Wall/Building typical from all L. V. Structures
Saudi Electricity Company
Construction Standard for Overhead Lines Issue Date: Nov/2021 Page: 8 of 10
Part 24: Low Voltage Circuit to Consumer Meter Box SDCS-01-24

Serial REFRENCES
Qty BILL OF MATERIAL DESCRIPTION
No. SPECS FIG ITEM NO.

1 1 BOX, M, 1 CUST UP TO 150A, 380V, OTDR 42-SDMS-01 ------ 908421001

2 1 PIPE, SERVICE DROP, GS, 70MMIDX76MMODX3MLG 20-SDMS-02 Fig.59 908202229


3 4 CLAMP,SERV MAST,GS,76MMDIAX60MMWDX4MMTH (ON WALL) 20-SDMS-02 Fig.60 908202102
4 1 CLAMP,TOP SERV MAST,GS,76X40X6X176/230MM 20-SDMS-02 Fig.57 908202101
5 1 HEAD,SERV ENT,AL,SLIP-ON W/2BLT,76MM OD 20-SDMS-02 Fig.58 908202194
6 2 GRIP,WEDGE,AA,50-120SQMM ACSR/AW 20-SDMS-02 Fig.56 908202190
7 2 TIE,CABLE,PA,40-230MM,7.8MMWD 20-SDMS-02 Fig.63 908202070
8 4 CONNECTOR,SLV,50SQMM, AL W/ NYL JKT 20-SDMS-02 Fig.34 908202066
9 4 CONNECTOR,PG,AL,120SQMM,50SQMM,COMP 20-SDMS-02 Fig.39 908202210
10 3 COVER,H-TAP,HI-DENSITY PLST,40X47X140MM 20-SDMS-02 Fig.40 908202184
11 1 BOLT,EYE,GS,16MM DIA,180MM LG,SHOULDER 20-SDMS-02 Fig.16 908202198
12 1 CONDUIT,PVC,70MM ODX1110MM LG,W/CPLG 20-SDMS-02 Fig.62 908202104
CABLE, PWR, 600V/1KV, QUADRUPLEX, 3x50MM2 AL + 1x50MM2
13 25m 11-SDMS-02 ------ 908112050
ACSR/AW

USING SERVICE MAST ON WALL SUPPORT

Table 1. Service Entrance drop on Consumer’s Wall/Building typical from all L. V. Structures
Saudi Electricity Company
Construction Standard for Overhead Lines Issue Date: Nov/2021 Page: 9 of 10
Part 24: Low Voltage Circuit to Consumer Meter Box SDCS-01-24

All Dimensions are in Millimeter

Figure 3. Service Entrance drop on Consumer’s Wall typical from all L. V. Structures
Saudi Electricity Company
Construction Standard for Overhead Lines Issue Date: Nov/2021 Page: 10 of 10
Part 24: Low Voltage Circuit to Consumer Meter Box SDCS-01-24

REFRENCES
Serial Qty BILL OF MATERIAL DESCRIPTION
No. SPECS FIG ITEM NO.

1 1 BOX, M, 1 CUST UP TO 150A, 380V, OTDR 42-SDMS-01 ------ 908421001

2 1 PIPE, SERVICE DROP, GS, 70MMIDX76MMODX3MLG 20-SDMS-02 Fig.59 908202229


3 2 CLAMP,SERV MAST,GS,76MMDIAX60MMWDX4MMTH (ON WALL) 20-SDMS-02 Fig.60 908202102
4 2 CLAMP, SERV MAST ,GS,76MMDIA,M16X254MM (THROUGH WALL) 20-SDMS-02 Fig.61 908202103
5 1 CLAMP,TOP SERV MAST,GS,76X40X6X176/230MM 20-SDMS-02 Fig.57 908202101
6 1 HEAD,SERV ENT,AL,SLIP-ON W/2BLT,76MM OD 20-SDMS-02 Fig.58 908202194
7 2 GRIP,WEDGE,AA,50-120SQMM ACSR/AW 20-SDMS-02 Fig.56 908202190
8 2 TIE,CABLE,PA,40-230MM,7.8MMWD 20-SDMS-02 Fig.63 908202070
9 4 CONNECTOR,SLV,50SQMM, AL W/ NYL JKT 20-SDMS-02 Fig.34 908202066
10 4 CONNECTOR,PG,AL,120SQMM,50SQMM,COMP 20-SDMS-02 Fig.39 908202210
11 3 COVER,H-TAP,HI-DENSITY PLST,40X47X140MM 20-SDMS-02 Fig.40 908202184
12 1 CONDUIT,PVC,70MM ODX1110MM LG,W/CPLG 20-SDMS-02 Fig.62 908202104
13 1 BOLT,EYE,GS,16MM DIA,180MM LG,SHOULDER 20-SDMS-02 Fig.16 908202198
CABLE, PWR, 600V/1KV, QUADRUPLEX, 3x50MM2 AL + 1x50MM2
14 25m 11-SDMS-02 ------ 908112050
ACSR/AW

USING SERVICE MAST THROUGH SUPPORT

Table 2. Service Entrance drop on Consumer’s Wall typical from all L. V. Structures