Identifying the electrical The different connections

auxiliaries

Install Connectors on a fixed device


b Standard connectors are shown in the table below.
For information on non-standard connectors, contact the field office.
b For connector dimensions, see the catalogue.
Standard Connectors
Rear-connected Rear-connected Front-connected
"T" Vertical (RCTV) "T" Horizontal (RCTH) Flat (FCF)

DB106460

DB106461

DB106463
Install Bussing
Bussing requirements by circuit breaker and connector are shown in the table below.
Note: the fitter is responsible for the bus wiring toward the connectors. The bus must be
supported by the framework of the commutation equipment, without any weight on the
connectors.

Bus Size Required


Circuit Breaker Connectors Bus Per Connector
Rating Number Size
800 A RCTV 1 6 x 76 mm
(0.25 x 3 in.)
RCTH 2 6 x 38 mm
(0.25 x 1,5 in.)
FCF 3 6 x 38 mm
(0.25 x 1,5 in.)
1200 A RCTV 1 6 x 76 mm
(0.25 x 3 in.)
RCTH 3 6 x 38 mm
(0.25 x 1,5 in.)
FCF 4 6 x 38 mm
(0.25 x 1,5 in.)

26 GHD12331AA - 06/2009