Professional Documents
Culture Documents
Theoretical Concepts:
Distance protection, is a non-unit system of protection offering considerable economic and
technical advantages.
Distance protection is comparatively simple to apply and it can be fast in operation for faults
located along most of a protected circuit. It can also provide both primary and remote back-up
functions in a single scheme. It can easily be adapted to create a unit protection scheme when
applied with a signalling channel.
In this form it is eminently suitable for application with high-speed auto-reclosing, for the
protection of critical transmission lines.
The distance relay is based on evaluation of apparent impedance seen by the relay which is defined
as the ratio of phase voltage to line current of a transmission line (Zapp).
For the unloaded system, I = 0, and the apparent impedance seen by the relay
rel ay is infinite.
For a loaded system, the apparent impedance seen by the relay reduces to some finite value
(Zload+Zline) where Zload is the load impedance and Zline is the line impedance.
For a fault at a per-unit distance ‘m’, the impedance seen by the relay
rela y drops to a m*Zline as shown
in figure below.
The apparent impedance seen by the relay (Zapp) reduces drastically in the presence of a line fault.
The distance relay compares the ratio of phase voltage to line current with the positive sequence
impedance (Z1) of the transmission line.
If the fraction Zapp/Z1 is less than set value, it indicates a fault in the zone of set vale. This ratio
also indicates the distance of the fault from the relay.
Because, impedance is a complex number, the distance protection is inherently directional. The
first quadrant is the forward direction i.e. impedance of the transmission line to be protected lies
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 1 of 117
ETAP Workshop Notes
in this quadrant. However, if only magnitude information is used, non-directional impedance relay
results.
Figures below shows a characteristic of an impedance relay and ‘mho relay’ both belonging to this
class.
The impedance relay trips if the magnitude of the impedance is within the circular region.
Since in impedance relay, the circle spans all the quadrants, it leads to non-directional protection
scheme.
Thus, the trip law for the impedance relay can be written as follows:
|Zapp| = |VR| / |IR| < |Zset| ; then trip; else restrain.
While impedance relay has only one design parameter, Zset; ‘mho relay’ has two design
parameters Zn, λ.
As shown in the Figure, θ is the angle of transmission line, and λ is also called ‘torque angle’ or
characteristic angle.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 2 of 117
ETAP Workshop Notes
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 3 of 117
ETAP Workshop Notes
Relays measure the positive sequence impedance of the line up to the fault point (Refer
derivation of impedance in next page for the equations)
Phase to ground distance elements
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 6 of 117
ETAP Workshop Notes
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 7 of 117
ETAP Workshop Notes
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 8 of 117
ETAP Workshop Notes
Load Characteristics
Load – Mostly Resistive;
0.8 Leading Power factor [-37 degree]
0.8 Lagging power factor [+37 degree]
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 9 of 117
ETAP Workshop Notes
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 10 of 117
ETAP Workshop Notes
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 11 of 117
ETAP Workshop Notes
Quadrilateral Characteristics
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 12 of 117
ETAP Workshop Notes
Lenticular characteristic
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 13 of 117
ETAP Workshop Notes
Under-Reach Overview
A distance relay will under-reach if the impedance presented to the relay is greater than the
impedance to the fault.
One of the cause of under-reaching is the effect of fault current infeed at remote busbars as
per details shown in figures below for both with & without infeeds:
Because of no infeed as shown in SLD above, the relay will operate for faults upto its reach of Z A
+ZC.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 14 of 117
ETAP Workshop Notes
In this example the relay at A will not measure the correct impedance for a fault on line
section ZC due to current infeed I B.
which is more than reach setting Z A + ZC for a fault at reach point ZA+ ZC
Therefore relay Under-Reaches.
Consider the relay setting to be Z L1. The impedance seen by an uncompensated relay for a
fault at ZL1,
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 15 of 117
ETAP Workshop Notes
Under-Reach occurs if the apparent impedance is greater than the reach impedance setting
of the relay.
Over-Reach occurs if the apparent impedance is less than the reach setting of the relay.
When an earth fault occurs in the system, the voltage applied to the earth fault element of
the relay in one circuit includes an induced voltage proportional to the zero sequence
current in the other circuit.
Consider the system in Figure below with a ground fault F1 towards end B.
The zero sequence current IL0C in the healthy line CD at C, is in the same direction as the
fault current IL0A at A and I L0B at B is in the opposite direction.
At end B,
voltage thehence
and zero sequence
a reducedvoltage induced
apparent opposes
impedance. the voltage at B, resulting in a reduced
(Over-Reach)
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 16 of 117
ETAP Workshop Notes
For a solid phase to earth fault at the theoretical reach of the relay, the voltage and current
in the faulty phase at the relaying
rela ying point are given by:
I A I A1 I A2 I A0
The voltage and current fed into the relay are given by:
VR =VA
I R = I A +KR I A0 + KM IB0
where:
KR is the residual compensation factor
KM is the mutual compensation factor
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 17 of 117
ETAP Workshop Notes
A distance relay is said to over-reach when the apparent impedance presented to it is less
than the impedance to the fault.
Percentage over-reach is defined by the equation:
100*(ZF- ZR) / ZR
where:
ZR = intended relay reach (relay reach setting)
ZF = effective reach
An example of the over-reaching effect is when distance relays are applied on parallel
lines and one line is taken out of service
ser vice and earthed at each end.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 18 of 117
ETAP Workshop Notes
It is apparent from the above formulae that the relay has a tendency to over-reach.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 19 of 117
ETAP Workshop Notes
Care should be taken when Zone 1 settings are selected for the distance protection of lines
in which this condition may be encountered.
To overcome this possible over-reaching effect, some utilities reduce the reach of earth
fault relays to a % of ZL1 when lines are taken out of service for maintenance.
However, the probability of having a fault on the first section of the following line while
one line is out of service is very small, and many Utilities do not reduce the setting under
this condition. It should be noted that the
t he use of mutual compensation would not overcome
the over-reaching effect since earthing clamps are normally placed on the line side of the
current transformers.
This phenomenon is Usually associated with three terminal line applications and
paralleling of line segment.
In the Example shown above,
Voltage as seen by relay VG = 2(1) + 2(1) = 4 V
Current as seen by relay IG = 2 A
ZG (As seen by Relay) = VG / IG = 4/2
ZG (As seen by Relay) = 2 ohms
As per settings fault is outside of Zone Z1 but due to Out-Feed effect, Relay will
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 21 of 117
ETAP Workshop Notes
Cross
tower country faults
structures and are
maymore likely
result duetotooccur
bush on double
fires undercircuit lineslightning,
the lines, located onasthe same
well as
broken conductors.
Cross country faults result in unusual current distributions that compromise the seen
impedance by units not directly involved in the fault loop, giving fault selector problems
for close-in faults as shown
The above type of A-B-G cross country faults are difficult to distinguish for a distance
relay and undesired three pole tripping may occur during simultaneous line to ground faults
on two different phases of a double circuit line.
For an A-G fault on feeder 1 and a B-G on feeder 2, the relays at end R will correctly
measure that it is a single phase fault. Relays at end S could determine an A-B-G fault and
would issue a three pole trip if the zone 2 element is for instance picked-up whilst receiving
a permissive trip from the remote end.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 22 of 117
ETAP Workshop Notes
Duringonly
might severe
be power swing
regained if theconditions
swinging from which
sources are anot
system is unlikely
separated to recover,
at an ideal stain
stability
location bility
the
system to ensure load generation balance is available in the sections split.
This type of disturbance cannot normally be correctly identified by an distance protection.
It is therefore usual to prevent distance protection
protecti on schemes from operating during stable or
unstable power swings, in order to avoid cascade tripping.
The main purpose of the power-swing blocking function is to differentiate faults from
power swings and block distance or other rela
relayy elements from operating during stable or
unstable power swings.
However, faults that occur during a power swing must be detected and cleared with a high
degree of selectivity and dependability.
The PSB function is designed to detect power swings, differentiate power swings from
faults, and block distance relay elements from tripping during power swings.
In such situations, the PSB function therefore should unblock and allow the distance relay
elements to operate and clear any
an y faults that occur in their zone of protection during a power
swing condition. Most PSB elements are based on traditional methods that monitor the rate
of change of the positive-sequence impedance.
This detection method is based on the fact that it takes a certain time for the rotor angle to
advance because of system inertias. In other words, the rate of change of the impedance
vector is slow during stable or unstable power swings, because it takes a finite time for the
generator rotors to change position with respect to each other because of their large inertias.
inerti as.
On the contrary, the rate of change of the impedance vector is very fast during a system
fault.
Actual implementation of measuring the impedance rate of change is normally performed
though the use of two impedance measurement elements together with a timing device.
If the measured impedance stays between the two impedance measurement elements for a
predetermined time, the relay declares a power-swing blocking condition and issues a
power-swing blocking signal to block
block the distance relay element operation.
The ohm impedance elements divide the R/X impedance diagram into three zones, A, B
and C.
As the impedance changes during a power swing, the point representing the impedance
moves along the swing locus, entering the three zones in turn and causing the ohm units to
operate
sequenceinissequence.
completedWhen the below:
as shown impedance enters the third zone the pole slip detection
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 23 of 117
ETAP Workshop Notes
Only an unstable power swing condition can cause the impedance vector to move
successively through the three zones.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 24 of 117
ETAP Workshop Notes
Procedure:
OTI File location: Distance Protection NPAG > NPAG DIST.oti
ETAP Library from C :> ETAP 1800 > lib > etaplib1800.lib
Review the System shown below:
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 25 of 117
ETAP Workshop Notes
2. Add Positive and zero sequence impedance details for each OHL (Over Head Line) as
follows:
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 26 of 117
ETAP Workshop Notes
3. In ETAP file, add the distance relay at Line1 of ABC bus. Pick up the Schneider Electric
make, P441 type distance relay from the default library.
li brary. This is quadrilateral type relay.
rela y.
5. Similarly add the relay2 of Schneider Electric make, P441 type at the end of
o f Line1 at XYZ
bus. Connect this relay2 to 2000/1A CT2 and 230kV / 120V PT2.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 27 of 117
ETAP Workshop Notes
6. Disable the over current (OCR) and over load (OLR) settings
setti ngs for relay1 and relay2.
7. The distance relay has the feature to add digital input (DI) & digital output (DO) along
with CT & PT inputs. Set the inputs to relay1 as shown below:
Current Transformer (CT) input:
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 28 of 117
ETAP Workshop Notes
8. Go to the output page and assign each output of relay1 (DO1 to DO4) to trip CB1.
Note:
The screen displays that DO1 output has assigned to trip CB1 on logic operation.
Now, similarly
similarl y assi
assign
gn the DO2 to DO4 output by cl
clicking
icking it individually to trip CB1 on
logic operation.
9. In similar manner give the inputs to relay2 as well. Assign each output of relay2 (DO1 to
DO4) to trip the CB2.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 29 of 117
ETAP Workshop Notes
Pick up DO1
option from the
drop down list
11. See the calculation of Zero sequence compensation factor (Kz0), Zone1, Zone 2 and zone3
settings as below:
Compensation factor of line1 at ABC (relay1):
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 30 of 117
ETAP Workshop Notes
Sometimes, the two requirements are in conflict. In this case, both requirements can be met. A
setting of the whole of the line between substations ABC and XYZ, plus 50% of the adjacent line
section to substation PQR is used. Hence, Zone 2 reach of line1 at ABC (relay1):
The resistive reach setting represents the maximum amount of additional fault resistance (in excess
of the line impedance) for which a zone will trip, regardless of the fault within the zone.
Warrington formulae:
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 31 of 117
ETAP Workshop Notes
Where,
Ra = arc resistance
r esistance (ohms)
L= spacing between two conductor (meters)
I = arc current (A)
Load Impedance:
To give maximum expected load current, the minimum load impedance calculated is 130 ohm.
The resistive reaches will be set to avoid the minimum load impedance by a 40% margin for the
phase elements, leading to a maximum
maximum resistive reach setting of 78ohm.
78ohm.
Therefore, the resistive reach setting lies between 8ohm (more than arc resistance Ra) and 78ohm
(less than min load impedance).
This ensures that load does not encroach into quadrilateral characteristics of Schneider Electric
make P441 type distance relay.
While each zone can have its own resistive reach setting, for this simple example they can all be
set equal. Hence Phase fault resistive reach
reach settings are as follows:
The margin for avoiding the minimum load impedance need only be 20%.
Hence the settings are
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 32 of 117
ETAP Workshop Notes
12. The above calculated values of zero sequence compensation factor, zone1, zone2 and zone3
settings, phase & earth fault resistive reach settings etc. are summarized in below table. These
values are need to be entered into relay1 & relay2.
Settings (on
Label Unit
primary base)
Line Angle 79.41 degrees
Z1 38.74 Ohms
R1Ph 78 Ohms
tZ1 0 s
Z2 62.95 Ohms
R2Ph 78 Ohms
tZ2 0.25 s
KZ3/4 Res Comp 0.792
Z3 83.29 Ohms
tZ3 0.8 s
Z4 200 Ohms
tZ4 1 s
Note: In this example all the settings are calculated on primary base.
Hence in ETAP, primary impedance settings are entered but in relay, the secondary base settings
also can be entered.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 33 of 117
ETAP Workshop Notes
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 34 of 117
ETAP Workshop Notes
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 35 of 117
ETAP Workshop Notes
13. The direction of relay should be forward (Forward means looking towards Transmission
line). The CT polarity should be towards busbar at both the ends of Transmission line.
14. The settings for Zone P directional; Zone Q directional & series compensated line are
ignored in this exercise. These values have to be calculated properly and entered into relay
as per requirement.
15. Go to the scheme logic page of the relay 1 and see the logic applied to relay1 (allowing
permissive Under-Reach transfer tripping):
Note: Please see the subsequent pages where all the steps are shown in picture
format.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 36 of 117
ETAP Workshop Notes
Click to add
new row
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 37 of 117
ETAP Workshop Notes
Go to Output heading
Double click on Z1
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 38 of 117
ETAP Workshop Notes
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 39 of 117
ETAP Workshop Notes
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 40 of 117
ETAP Workshop Notes
16. For permissive Under-Reach tripping the signal logic implemented above
above is as follows:
DO1
DO3
DO4
DO1
DO1 of re
remo
mote
te rela
rela is DI di ital
ital in ut for
for lloc
ocal
al rela
rela
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 41 of 117
ETAP Workshop Notes
After selecting the fault location, go to the next page to activate the associated relay.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 42 of 117
ETAP Workshop Notes
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 43 of 117
ETAP Workshop Notes
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 44 of 117
ETAP Workshop Notes
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 45 of 117
ETAP Workshop Notes
20. You can also see the R-X diagram in star Z view.
Select the Line1 and then click on create star Z view.
Enable the relay 1 and associated protected zones i.e. Z1, Z1X, Z2 & Z3
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 46 of 117
ETAP Workshop Notes
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 47 of 117
ETAP Workshop Notes
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 48 of 117
ETAP Workshop Notes
i. 3 phase fault on Line -1 (ABC to XYZ) with source at Substation ABC and PQR
(Continued)
It can be observed that when fault location is at 0% from ABC, i.e., at the start of the line,
Zone-1 of Relay1 picks up and the associated Circuit Breaker CB1 operates
instantaneously (60ms, i.e., addition of Relay pickup delay
dela y and Circuit breaker operation
time).
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 49 of 117
ETAP Workshop Notes
i. 3 phase fault on Line -1 (ABC to XYZ) with source at Substation ABC and PQR
(Continued)
Also Zone-2 of Relay2 picks up and as per the Permissive Under-Reach tripping logic
(Zone 1 of Relay1 picks up along with Zone 2 of Relay2), Relay2 also gives tripping
signal to the associated Circuit Breaker CB2 which also operates instantaneously.
o Now move the slider to attain the fault location at 25% from Substation
Substation ABC.
In this condition, it can be observed that Zone-1 of Relay1 picks up and the associated
Circuit Breaker CB1 operates instantaneously.
Also Zone-1 of Relay2 picks up and the associated Circuit Breaker CB2 operates
instantaneously.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 50 of 117
ETAP Workshop Notes
i. 3 phase fault on Line -1 (ABC to XYZ) with source at Substation ABC and PQR
(Continued)
o Now move the slider to attain the fault location at 80% from Substation
Substation ABC.
In this condition, it can be observed that Zone-1 of Relay2 picks up and the associated
Circuit Breaker CB2 operates instantaneously.
Also Zone-2 of Relay1 picks up and as per the Permissive Under-Reach tripping logic
(Zone 1 of Relay2 picks up along with Zone 2 of Relay1), Relay1 also gives tripping
signal to the associated Circuit Breaker CB1 which also operates instantaneously.
The same sequence of operation can be observed when the fault location is at 100% from
Substation ABC (at Substation XYZ).
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 51 of 117
ETAP Workshop Notes
o Creating fault on Line -2 (XYZ to PQR): Sliding fault step is chosen as 5%.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 52 of 117
ETAP Workshop Notes
In this condition, it can be observed that Zone-2 of Relay1 picks up and the associated
Circuit Breaker CB1 operates after a time delay of 310ms, i.e., addition of time delay of
250ms for Zone 2 operation and Relay pickup delay and Circuit breaker operation time.
o Now move the slider to attain the fault location at 50% from Substation
Substation XYZ.
In this condition, it can be observed that only Zone-3 of Relay1 picks up and the
associated Circuit Breaker CB1 operates after a time delay
dela y of 860ms, i.e., addition of time
delay of 800ms for Zone 3 operation and Relay
Rela y pickup delay and Circuit breaker operation
time.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 53 of 117
ETAP Workshop Notes
o Creating fault on Line -3 (PQR to Grid U2): Sliding fault step is chosen as 5%.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 54 of 117
ETAP Workshop Notes
iii. 3 phase fault on Line -3 (PQR to Grid U2) with source at Substation ABC and
PQR (Continued)
In this condition, it can be observed that only Zone-3 of Relay1 picks up and the
associated Circuit Breaker CB1 operates after a time delay
dela y of 860ms, i.e., addition of time
delay of 800ms for Zone 3 operation and Relay pickup delay and Circuit breaker operation
time.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 55 of 117
ETAP Workshop Notes
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 56 of 117
ETAP Workshop Notes
iv. 3 phase fault on Line -2 (XYZ to PQR) with source at Substation ABC, XYZ and
PQR (INFEED EFFECT) (UNDER-REACH OF RELAY) (Continued)
o Creating fault on Line -2 (XYZ to PQR): Sliding fault step is chosen as 5%.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 57 of 117
ETAP Workshop Notes
iv. 3 phase fault on Line -2 (XYZ to PQR) with source at Substation ABC, XYZ and
PQR (INFEED EFFECT) (UNDER-REACH OF RELAY) (Continued)
In this condition, it can be observed that Zone-2 of Relay1 picks up and the associated
Circuit Breaker CB1 operates after a time delay of 310ms, i.e., addition of time delay of
250ms for Zone 2 operation and Relay pickup delay and Circuit breaker operation time.
o Now move the slider to attain the fault location at 15% from Substation
Substation XYZ.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 58 of 117
ETAP Workshop Notes
iv. 3 phase fault on Line -2 (XYZ to PQR) with source at Substation ABC, XYZ and
PQR (INFEED EFFECT) (UNDER-REACH OF RELAY) (Continued)
In this condition, it can be observed that only Zone-3 of Relay1 picks up and the
associated Circuit Breaker CB1 operates after a time delay
dela y of 860ms, i.e., addition of time
delay of 800ms for Zone 3 operation and Relay pickup delay and Circuit breaker operation
time.
This represents Under-Reach of the Zone 2 of Relay1 which is because of the INFEED
effect, i.e., current infeed from source U3 at Substation XYZ.
Similarly, when you move the slider to attain fault location at 35% from Substation XYZ,
then it is observed that Zone 3 of Relay1 also does not pick up the fault.
This represents Under-Reach of the Zone 3 of Relay1 which is because of the INFEED
effect, i.e., current infeed from source U3 at Substation XYZ.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 59 of 117
ETAP Workshop Notes
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 60 of 117
ETAP Workshop Notes
o Now go to Relay-1, StarZ | Distance and make Residual Compensation factor (KZ1,
KZ2 and KZ3) as zero (0).
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 61 of 117
ETAP Workshop Notes
v. LG fault on Line -1 (ABC to XYZ) with source at Substation ABC and with
Residual Compensation factor (KZ1, KZ2 and KZ3) as zero (0) (Continued)
o Creating fault on Line -1 (ABC to XYZ): Sliding fault step is chosen as 5%.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 62 of 117
ETAP Workshop Notes
v. LG fault on Line -1 (ABC to XYZ) with source at Substation ABC and with
Residual Compensation factor (KZ1, KZ2 and KZ3) as zero (0) (Continued)
It can be observed that when fault location is at 0% from ABC, i.e., at the start
sta rt of the line,
Zone-1 of Relay1 picks up and the associated Circuit Breaker CB1 operates
instantaneously (60ms, i.e., addition of Relay pickup delay and Circuit breaker
b reaker operation
time).
o Now move the slider to attain the fault location at 45% from Substation
Substation ABC.
In this condition, it can be observed that Zone-1 of Relay1 does not pick up the fault. This
is because we have not considered Residual Compensation factor which results in Under-
Reach of the relay.
Similar results can be obtained for Zone-2 and Zone-3 by further increasing the distance
of fault location from Substation ABC.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 63 of 117
ETAP Workshop Notes
vi. LG fault on Line -1 (ABC to XYZ) with source at Substation ABC and
considering Residual Compensation factor (KZ1, KZ2 and KZ3).
o Creating fault on Line -1 (ABC to XYZ): Sliding fault step is chosen as 5%.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 64 of 117
ETAP Workshop Notes
vi. LG fault on Line -1 (ABC to XYZ) with source at Substation ABC and
considering Residual Compensation factor (KZ1, KZ2 and KZ3) (Continued)
It can be observed that when fault location is at 0% from ABC, i.e., at the start
sta rt of the line,
Zone-1 of Relay1 picks up and the associated Circuit Breaker CB1 operates
instantaneously (60ms, i.e., addition of Relay pickup delay and Circuit breaker
b reaker operation
time).
o Now move the slider to attain the fault location at 75% from Substation
Substation ABC.
Same sequence of operation as previous condition is seen in this condition which proves
satisfactory operation of Relay1.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 65 of 117
ETAP Workshop Notes
Spurious tripping of Distance Relay due to large loads falls within the Zone, said to be
tripping due to Load Encroachment.
With the present setting of the relay, the Quad Characterstics is as below:
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 66 of 117
ETAP Workshop Notes
o Connect a lump load at bus XYZ with only source at bus ABC (Grid U1) in service,
as shown below.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 67 of 117
ETAP Workshop Notes
o Now open Study Scenario and select “Load flow (No Fault)” under Study Type.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 68 of 117
ETAP Workshop Notes
Hence, in this case the load does not encroach the Relay
Rela y Characterstics and no maloperation
of relay is observed.
b) Case -1: Rload = 30 ohms
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 69 of 117
ETAP Workshop Notes
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 70 of 117
ETAP Workshop Notes
It can be observed that, as the load resistance is reduced to 30 ohms, Relay1 trips even if
there is no fault in the system.
This condition of Distance Relay is known as tripping due to load encroachment.
22. Distance Protection Settings of Other makes for the Example Transmission System:
For the Example Transmission System, settings for other makes has also been provided in
the same ETAP file as Revisions.
OTI File Name: NPAG DIST.oti
The same can be seen as below:
REVISION CASE
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 71 of 117
ETAP Workshop Notes
Simulate the Revision files as explained before and analyse the results for all the cases.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 72 of 117
ETAP Workshop Notes
DISTANCE PROTECTION
ANNEXURE – 1
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 73 of 117
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 73 of 117
ANNEXURE – 1
DISTANCE RELAY UNDER-REACH AND OVER-REACH EFFECT DUE TO MUTUAL
COUPLING BETWEEN PARALLEL LINES:
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 74 of 117
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 75 of 117
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 76 of 117
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 77 of 117
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 78 of 117
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 79 of 117
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 80 of 117
S.
Configuration of Line-1 Ckt-1 X coordinate Y coordinate Unit
No.
1 Conductor A (A1) : -3.7 31.6 m
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 81 of 117
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 82 of 117
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 83 of 117
Select None as there is no Ground Wire in Line-1 Ckt-2, i.e., Group-2 (Refer Figure
-2 for details).
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 84 of 117
Deselect Ground Wires as there is no Ground Wire in Line-1 Ckt-2 and click OK.
The Configuration Page will be as shown below:
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 85 of 117
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 86 of 117
Now in Grouping Page, select Name under “Group” as “COUPL1”. and Click OK.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 87 of 117
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 88 of 117
7. Now to model Outgoing line from Bus XYZ to PQR, copy Transmission Line “Line-1 Ckt-
2” & Paste and rename it as Line-2.
8. Open Transmission Line “Line 2” and go to Grouping Page & Select Name under
a s NO COUPLING between Line-2 and
“Group” as “None”. and Click OK. This is done as
Line-1 is required.
9. In ETAP file, add the distance relay at Line1 of ABC bus. Pick up the Schneider Electric
make, P441 type distance relay from the default library. This is quadrilateral type relay.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 89 of 117
10. Connect this Relay1 to 100/1A CT1 and 132kV / 110V PT1.
11. Disable the over current (OCR) and over load (OLR) settings
setti ngs for Relay1.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 90 of 117
12. The distance relay has features to add digital input (DI) & digital output (DO) along with
CT & PT inputs. Set the inputs to Relay1 as shown below:
Current Transformer (CT) input:
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 91 of 117
14. Now go to StarZ | Distance Page of Relay1 and enter the settings as shown below:
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 92 of 117
b) Click on “Select” under Fault/Study Location and Select “Line -1 Ckt-2” and
select step as “1 %”.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 94 of 117
Now move the fault location to 93% of the Transmission Line “Line Ckt-2”. It
-1 Ckt-2”
“Line-1
can be observed Relay1 still operates instantaneously for the fault.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 96 of 117
k) Copy and Paste Generator “Ground -1” and rename it as “Ground -2”.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 102 of 117
“Line -1 Ckt-1”
For Earthing Transmission Line “Line-1 Ckt-1” at both ends without isolation it from
the circuit in ETAP, it has been earthed using a Generator with very small rated
voltage (0.01kV) and Solidly Earthed.
Now go to Study Case and follow the following steps:
Study Type: Sliding Fault
Click on “Select” under Fault/Study Location and Select “Line-2” and select step
as “1 %”.
Select Fault Type as “Line -to-Ground” and Click OK.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 103 of 117
Now move the fault location to 30% of the Transmission Line “Line
“Line--2”. It can be
observed Relay1 still operates instantaneously for the fault.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 105 of 117
ANNEXURE – 2
3. All the Lines have the same Impedance parameters. The length of the lines are entered as shown
below:
1 Line_1_Sec_1 30
2 Line_1_Sec_2 70
3 Line_2_Sec_1 35
4 Line_2_Sec_2 35
5 Line_3 60
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 108 of 117
From this, it can be concluded that Relay1 is set to cover 100% of Transmission Line
“Line_1” (Line_1_Sec_1 + Line_1_Sec_2) in Zone-1.
Zone-1.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 114 of 117
.
This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved Page 115 of 117