TX Firm # F-19205
© 2022
L
Gandy Residence
ARCH ARCHITECT / ARCHITECTURAL PL PLATE S020 FRAMING INFORMATION SHEET
HEX HEXIGON, HEXAGONAL PLF POUNDS PER LINEAR FOOT S021 FRAMING INFORMATION SHEET
Lubbock, TX 79413
BET BETWEEN HORIZ HORIZONTAL PSF POUNDS PER SQUARE FOOT S030 SHEARWALL INFORMATION SHEET
BF BOTH FACES HP HIGH POINT PSI POUNDS PER SQUARE INCH S031 SHEARWALL INFORMATION SHEET
BLDG BUILDING HSS HOLLOW STRUCTURAL SECTION PT POINT S101 SLAB FORMING PLAN
BM BEAM HT HEIGHT S102 FOUNDATION PLAN
BOT BOTTOM R RADIUS S201 1ST FLOOR FRAMING PLAN
BPL BASE PLATE ID INSIDE DIAMETER RE REFERENCE S202 CEILING JOIST FRAMING PLAN
BS BOTH SIDES IF INSIDE FACE REBAR REINFORCING BAR S203 ROOF RAFTER FRAMING PLAN
B/ST BOTTOM OF STEEL IN INCH / INCHES REINF REINFORCE(ING) S301 SHEARWALL PLAN
INT INTERIOR REQ REQUIRED S401 FOUNDATION SECTIONS
C CHANNEL REV REVISION S402 FRAMING SECTIONS
CANT CANTILEVER JT JOINT RSRS ROOF SHEATHING RING SHANK NAIL
CJ CONSTRUCTION JOIST
F
Title
Sheet
A
S000
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
CODES AND STANDARDS DESIGN LOADS CONCRETE SPECIFICATIONS CONCRETE MASONRY UNIT SPECIFICATIONS
1. WHERE DOCUMENTS ARE REFERENCED IN THE GENERAL AND DESIGN NOTES, THEY SHALL 1. FLOOR LIVE LOADS 40 PSF 1. ALL CONCRETE MIX SHALL BE DESIGNED BY A QUALIFIED REGISTERED ENGINEER AND LAB 1. MASONRY WORK SHALL COMFORM TO ALL REQUIREMENTS OF TMS 402 (FORMERLY
M
BE THE LATEST APPLICABLE EDITIONS, UNLESS NOTED OTHERWISE. CONCRETE MIX DESIGN DATA RESULTS SHALL BE SUBMITTED TO THE STRUCTURAL DESIGNATED AS ACI 530), "BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES"
2. ROOF LIVE LOAD 20 PSF ENGINEER OF RECORD A MINIMUM OF 5 DAYS PRIOR TO THE START OF WORK. AND TMS 602 (FORMERLY DESIGNATED AS ACI 530.1), "SPECIFICATIONS FOR MASONRY
2. ALL WORK SHALL CONFORM TO THE REQUIREMENTS OF THE 2015 INTERNATIONAL 2. TABLE OF MIX DESIGN REQUIREMENTS STRUCTURES."
RESIDENTIAL CODE WITH CITY OF LUBBOCK AMENDMENTS, INCLUDING REFERENCE 3. ROOF SNOW LOAD 15 PSF 5575 Stousland Rd.
STANDARDS, ADDENDA, AND APPENDICES. 2. CONCRETE MASONRY UNITS SHALL CONFORM TO ASTM C90, TYPE-I (MOISTURE College Station, TX 77845
STRENGTH TEST AGE MAXIMUM EXPOSURE AIR
MEMBER TYPE/LOCATION CONTROLLED), MEDIUM WEIGHT (115 PCF) UNITS. (832) 423-2977
f'c (psi) (days) AGGREGATE CLASS CONTENT
3. IN ADDITION, THE FOLLOWING CODES, STANDARDS, AND SPECIFICATIONS SHALL APPLY www.laymonconsulting.com
WHERE MORE STRINGENT AND AS MODIFIED BY THE BUILDING CODE: 5.9 psf 3. MORTAR SHALL CONFORM TO ASTM C270. MORTAR TYPE SHALL BE TYPE M OR TYPE S.
SLAB-ON-GRADE 3,000 28 1" - 0 - 112%
MASONRY CEMENT AND RETARDANT ADDITIVES SHALL NOT BE USED. TX Firm # F-19205
A. ACI 310 "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE AND FOOTINGS 3,000 28 1" - 0 - 112%
COMMENTARY" ROOF TRUSS MASONRY ASSEMBLAGE SCHEDULE
B. AISC "STEEL CONSTRUCTION MANUAL" © 2022
COMPRESSIVE STRENGTH OF
L
C. ASCE 7: MINIMUM DESIGN LOADS AND ASSOCIATED CRITERIA FOR BUILDINGS AND MORTAR COMPRESSIVE STRENGTH OF
BALANCED LOAD DIAGRAM MASONRY ASSEMBLAGE, f'm TYPE INDIVIDUAL MASONRY UNIT
Laymon Consulting, LLC
OTHER STRUCTURES NOTES
All rights reserved
D. NDS: NATIONAL DESIGN SPECIFICATIONS FOR WOOD CONSTRUCTION 1. W/C RATIO: WATER-CEMENTITIOUS MATERIAL RATIOS SHALL BE BASED ON THE TOTAL
4. WIND LOAD WEIGHT OF CEMENTITIOUS MATERIALS. MAXIMUM RATIOS ARE CONTROLLED BY THE
1,500 PSI M OR S 1,900 PSI The arrangements
E. AWS D1.1 "STRUCTURAL WELDING CODE - STEEL"
F. AWS D1.4 "STRUCTURAL WELDING CODE - REINFORCING STEEL" BASIC DESIGN WIND SPEED, V 106 MPH STRENGTH NOTED ABOVE AND DURIBILITY REQUIREMENTS GIVEN IN ACI 318 SECTION 4.3 depicted herein are the
2,000 PSI M OR S 2,800 PSI
G. ACI 530/530/1 "BUILDING CODE REQUIREMENTS AND SPECIFICATIONS FOR MASONRY ASD WIND SPEED, VASD 90 MPH sole property of Laymon
STRUCTURES AND RELATED COMMENTARIES" RISK CATEGORY II 2. CEMENTITIOUS MATERIALS: 2,500 PSI M OR S 3,750 PSI Consulting, LLC and may
H. ACI 305.1 "SPECIFICATIONS FOR HOT WEATHER CONCRETING" WIND EXPOSURE CATEGORY B A. THE USE OF FLY ASH, OTHER POZZOLANS, SILICA FUME, OR SLAG SHALL CONFORM 3,000 PSI M OR S 4,800 PSI not be reproduced in any
I. ACI 306.1 "SPECIFICATIONS FOR COLD WEATHER CONCRETING" INTERNAL PRESSURE COEF ± 0.18 TO ACI 318 SECTIONS 4.3.1 AND 4.4.2. THE MAXIMUM AMOUNT OF FLY ASH SHALL BE form without written
COMPONENT & CLADDING PRESSURES (ASD): 20% OF TOTAL CEMENTITIOUS CONTENT, UNLESS REVIEWED AND APPROVED permission.
ZONE 1 16.0/-16.0 PSF OTHERWISE BY THE STRUCTURAL ENGINEER OF RECORD.
ZONE 2 16.0/-16.0 PSF B. FLY ASH SHALL CONFORM TO ASTM C618, CLASS F 4. GROUT SHALL CONFORM TO ASTM C476, SHALL COMPLY WITH ARTICLE 2.2 OF TMS 602,
K
a 5. SLUMP: CONFORM TO ACI 301 SECTION 4.2.2.2. SLUMP SHALL BE DETERMINED AT POINT 8. JOINT REINFORCEMENT SHALL CONFORM TO ASTM A951 AND SHALL BE NINE (9) GAUGE
3. SCALES NOTED ON THE DRAWINGS ARE FOR GENERAL INFORMATION ONLY. NO 2 4 3 5
a OF PLACEMENT. LADDER OR TRUSS TYPE. LAP SPLICES SHALL BE 12" MINIMUM.
INFORMATION SHALL BE OBTAINED BY SCALING FROM THE DRAWINGS. 4 3 5 4
4 5 5 a 6. CHLORIDE CONTENT: CONFORM TO ACI318 SECTION 4.3.1. 9. SECOND HAND UNITS SHALL NOT BE ALLOWED.
4. IN THE EVENT THAT CERTAIN DETAILS OF THE CONSTRUCTION ARE NOT FULLY SHOWN OR
NOTED ON THE DRAWINGS, THEIR CONSTRUCTION SHALL BE OF THE SAME TYPE AS FOR 5 5 a
7. NON-CHLORIDE ACCELERATOR: NON-CHLORIDE ACCELERATOR ADMIXTURE MAY BE 10. ALL REINFORCING IN MASONRY SHALL BE ACCURATELY LOCATED PRIOR TO GROUTING AND
SIMILAR CONDITIONS THAT ARE SHOWN OR NOTED, SUBJECT TO THE APPROVAL OF THE a a USED AT AMBIENT TEMPERATURES BELOW 50°F AT THE CONTRACTOR'S OPTION. THE POSITION MAINTAINED DURING GROUTING.
STRUCTURAL ENGINEER OF RECORD. a a
8. ACI 318 SECTION 4.2.1 EXPOSURE CLASSES SHALL BE ASSUMED TO BE F0, S0, P0, AND C0 11. ALL CELLS AND COURSES WITH REINFORCING SHALL BE FILLED SOLID WITH GROUT.
5. GEOTECHNICAL DOCUMENT INFORMATION CAN BE FOUND IN THE "DESIGN LOADS" SECTION UNLESS DIFFERENT EXPOSURE CLASSES ARE LISTED IN THE ABOVE TABLE THAT MODIFY ADDITIONAL CELLS AND COURSES MAY REQUIRE GROUTING AS SHOWN ON PLAN OR IN THE
OF THESE GENERAL NOTES. THESE BASE REQUIREMENTS. CMU INFORMATION SHEET. ARCHITECTURAL DRAWINGS MAY ALSO REQUIRE ADDITIONAL
5. EARTHQUAKE LOAD CELLS AND COURSES TO BE FILLED BASED ON FIRE AND SOUND REQUIREMENTS.
6. OPENINGS, POCKETS, ETC., LARGER THAN 6" SHALL NOT BE PLACED IN CONCRETE SLABS
H
RISK CATEGORY II 3. CONCRETE WORK SHALL CONFORM TO THE REQUIREMENTS OF ACI 301, LATEST EDITION.
AND WALLS UNLESS SPECIFICALLY DETAILED ON THE STRUCTURAL DRAWINGS. NOTIFY THE SEISMIC IMPORTANCE FACTOR 1.0 12. GROUT LIFTS AND POUR HEIGHTS SHALL NOT EXCEED 5FT 4IN, UNLESS OTHERWISE NOTED
STRUCTURAL ENGINEER OF RECORD WHEN DRAWINGS BY OTHERS SHOW OPENINGS, SS 0.076 4. CONCRETE SHALL BE PLACED CAREFULLY SO AS NOT TO DEVIATE TENDONS AND OR APPROVED BY THE STRUCTURAL ENGINEER OF RECORD.
POCKETS, ETC., LARGER THAN 6" WHICH ARE NOT SHOWN ON THE STRUCTURAL DRAWINGS S1 0.03 REINFORCEMENT FROM THEIR DESIGN LOCATIONS.
BUT WHICH ARE LOCATED IN STRUCTURAL ELEMENTS. SITE CLASS D 13. GROUT SHALL BE PLACED CONTINUOUSLY AND LIFTS SHALL NOT BE PLACED MORE THAN
SDS 0.081 5. CONCRETE SHALL BE PROPERLY VIBRATED, ESPECIALLY AROUND POST-TENSIONING ONE HOUR APART. GROUT IN VERTICAL CELLS SHALL BE MECHANICALLY VIBRATED
7. DEPRESSIONS IN SLABS SHALL NOT BE PLACED UNLESS SPECIFICALLY SHOWN ON THE SD1 0.072
Gandy Residence
ANCHORS AND IN CONGESTED AREAS. IMMEDIATELY AFTER POURING AND AGAIN FIVE(5) MINUTES LATER. RODDING OF THE GROUT
STRUCTURAL DRAWINGS. NOTIFY THE STRUCTURAL ENGINEER OF RECORD WHEN SEISMIC DESIGN CATEGORY A IS NOT ACCEPTABLE.
DRAWINGS BY OTHERS SHOW DEPRESSIONS WHICH ARE NOT SHOWN ON THE STRUCTURAL 6. THE FORMING AND SHORING SYSTEM SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR
Lubbock, TX 79413
DRAWINGS. 6. GEOTECHNICAL INFORMATION AND SHOULD BE DESIGNED BY A COMPETENT DESIGNERS EMPLOYED BY THE FORM 14. CMU WALLS SHALL BE CONSTRUCTED PLUMB AND LEVEL
GEOTECHNICAL FIRM NONE SUPPLIER.
8. ALL SUSPENDED LOADS (MEP DRAWINGS, INTERIOR DRAWINGS, FIRE PROTECTION
REPORT DATE 7. CONCRETE FOR CYLINDERS AND SLUMP TEST SHALL BE TAKEN EVERY 50CY OF CONCRETE GENERAL CONTRACTOR.
ENGINEER OF RECORD PRIOR TO INSTALLATION, UNLESS SPECIFICALLY DETAILED ON THE BEARING CAPACITY 1,500 PSF (ASSUMED TOTAL LOAD) AT THE POINT OF PLACEMENT.
STRUCTURAL DRAWINGS. THE CONTRACTOR SHALL SUBMIT ONE COMPOSITE PLAN PER
FLOOR LEVEL WHICH INCLUDES ALL POINT LOADS OF ALL TRADES. ALL LOADS EXCEEDING a. STRUCTURAL ENGINEER IS NOT RESPONSIBLE FOR SUBSURFACE CONDITIONS 8. THE MAXIMUM SLUMP IN CONCRETE SHALL NOT EXCEED 5"
300 POUNDS SHALL BE INCLUDED IN THOSE PLANS. ENCOUNTERED IN THE FIELD DIFFERENT FROM THOSE ASSUMED FOR DESIGN.
9. THE INFORMATION SHOWN FOR NON-STRUCTURAL ELEMENTS/FINISHED IS GIVEN FOR b. GEOTECHNICAL TESTING/INSPECTION AGENCY SHALL CERTIFY THE BEARING
9. WATER MAY NOT BE ADDED TO THE BATCH AT THE SITE UNLESS IT IS SPECIFICALLY NOTED
THAT IT MAY BE ADDED ON THE TICKET PROVIDED BY THE READY-MIX COMPANY. IN NO CASE
LOOSE LINTEL SPECIFICATIONS
REFERENCE ONLY. THE CONTRACTOR SHALL REFER TO THE ARCHITECTURAL DRAWINGS MEDIUM BEFORE STARTING CONSTRUCTION. 1. SEE STRUCTURAL STEEL SPECIFICATIONS FOR ANGLE STANDARDS AND GALVANIZING
MAY MORE WATER BE ADDED TO THE MIX THAN IS ALLOWED ON THE TICKET.
FOR THIS INFORMATION. REQUIREMENTS.
10. UNREINFORCED AND CONVENTIONALLY REINFORCED CONCRETE SHALL HAVE
10. CLADDING/FACADE/STAIR CONNECTIONS TO THE STRUCTURE SHALL NOT INTRODUCE 2. LOOSE LINTELS SHALL BE SIZED BASE ON THE FOLLOWING CLEAR SPANS:
CONSTRUCTION JOINTS OR CONTROL JOINTS AS SHOWN ON THE DRAWINGS AND
TORSION AND UNACCEPTABLE LOAD ECCENTRICITIES TO STRUCTURAL MEMBERS. SUCH 7. FLOOD LOAD N/A COORDINATED WITH THE ARCHITECT. IF JOINTS ARE NOT SHOWN, A MINIMUM SPACING OF
CONDITIONS SHALL BE BROUGHT TO THE ATTENTION OF THE STRUCTURAL ENGINEER OF
F
(30 x SLAB THICKNESS (in)) MAY BE USED. CONTROL JOINTS SHOULD BE SAWED AS SOON AS CLEAR SPAN SIZE
RECORD, WHO MAY REQUIRE ADDITIONAL BRACING TO BE PROVIDED BY THE PRACTICALLY POSSIBLE. JOINTS SHOULD BE SAWED AS SOON AS THE CONCRETE WILL
CLADDING/FACADE CONTRACTOR AT NO ADDITIONAL COST TO THE CONTRACTOR. WITHSTAND THE ENERGY OF SAWING WITHOUT RAVELING OR DISLODGING AGGREGATE
L 3 12 x 3 12 x 5 16 LLV
REINFORCING STEEL SPECIFICATIONS PARTICLES. 0'-0" UP TO 4'-0"
1. ALL REINFORCING STEEL SHALL BE NEW DOMESTIC DEFORMED BILLET STEEL CONFORMING OVER 4'-0" UP TO 8'-0" L 5 x 3 12 x 5 16 LLV
11. HORIZONTAL JOINTS IN THE FOUNDATION SHALL NOT BE ALLOWED, UNLESS NOTED ON THE
TO ASTM A615, GRADE 60 BARS.
BUILDING PAD SPECIFICATIONS DRAWINGS. OVER 8'-0" UP TO 11'-0" L 6 x 3 12 x 5 16 LLV
1. THE BUILDING PAD SHALL BE PREPARED SUCH THAT THE PVR DOES NOT EXCEED 1". REFER 2. WELDED WIRE FABRIC (WWF) SHALL CONFORM TO ASTM A185 AND SHALL BE PROVIDED IN
TO THE GEOTECHNICAL REPORT RECOMMENDATIONS. 12. PRIOR TO CONSTRUCTING FORMS OR PLACING CONCRETE, CONTRACTOR SHALL VERIFY
FLAT SHEETS. ROLLED SHEETS ARE NOT ACCEPTABLE. LAP FABRIC TWO MESHES, BUT NOT 3. SIZES SHOWN ABOVE ARE BASED ON A MAXIMUM OF 5'-0" OF BRICK ABOVE THE LINTEL.
FINISHED WITH ARCHITECT.
LESS THAN 12", AT SPLICE LOCATIONS.
2. ALL FOOTINGS AND GRADE BEAMS SHALL BEAR A MINIMUM OF 24" BELOW FINISHED GRADE. 4. LOOSE LINTELS SUPPORTING MORE THAN 5''-0" OF BRICK ABOVE THE LINTEL OR WITH SPANS
13. PRIOR TO CONSTRUCTING FORMS OR PLACING CONCRETE, CONTRACTOR SHALL NOTIFY
3. DETAILING OF CONCRETE REINFORCEMENT BARS AND ACCESSORIES SHALL CONFORM TO LONGER THAN 11'-0" WILL BE SHOWN ON THE FRAMING PLANS. IF THESE LNTELS ARE NOT
E
3. THE CONTRACTOR SHALL EXCAVATE, PREPARE, AND COMPACT THE BUILDING PAD IN SUBCONTRACTORS TO BE SURE SLEEVES, CONDUIT, CHASES, EMBEDDED ITEMS, BOLTS,
THE RECOMMENDATIONS OF ACI 315. CALLED OUT ON THE PLANS, CONTACT THE STRUCTURAL ENGINEER OF RECORD FOR THE
ACCORDANCE WITH THE GEOTECHNICAL REPORT. BLOCK-OUTS, ETC. ARE FULLY AND PROPERLY INSTALLED. CONTRACTOR SHALL NOTIFY THE
CORRECT LINTEL SIZE TO USE.
4. COMPLETE REINFORCING PLACEMENT DRAWINGS, PREPARED IN ACCORDANCE WITH ACI 315, STRUCTURAL ENGINEER OF RECORD OR OWNER'S REPRESENTATIVE AT LEAST 48 HOURS
4. THE CONTRACTOR SHALL ADVISE THE STRUCTURAL ENGINEER OF RECORD OF ANY SITE SHALL BE REVIEWED BY THE STRUCTURAL ENGINEER OF RECORD AND AVAILABLE ON THE PRIOR TO PLACING CONCRETE TO ALLOW TIME FOR OBSERVATIONS OF FORMS AND
5. LINTEL ANGLES SHALL BEAR A MINIMUM OF 8" ONTO THE BRICK ON EACH END. CONTACT THE
CONDITIONS WHICH MAY NOT BE DESCRIBED ON THE PLANS OR IN THE GEOTECHNICAL JOB SITE PRIOR TO AND DURING THE PLACING OF CONCRETE REINFORCING.
STRUCTURAL ENGINEER OF RECORD IS A SMALLER BEARING LENGTH IS REQUIRED.
REPORT. .
5. ALL REINFORCING BAR BENDS SHALL BE MADE COLD. 14. CONCRETE SHALL BE PROTECTED FROM RAIN AND SNOW.
5. SLABS SHALL NOT BE PLACED ON ANY UNCONSOLIDATED FILL OF ANY SIZE UNLESS THE FILL
HAS BEEN CONSIDERED IN THE DESIGN OF THE FOUNDATION. 6. WELDING OF REINFORCING BARS SHALL NOT BE PERMITTED WITHOUT PRIOR APPROVAL 15. AFTER FINISHING, CONCRETE SHALL BE CURED BY KEEPING CONCRETE DAMP AND COVERED
FROM THE STRUCTURAL ENGINEER OF RECORD. IF WELDING IS PERMITTED, IT SHALL WITH PLASTIC OR BURLAP FOR A MINIMUM OF 72 HOURS. A CRING COMPOUND MAY BE USED Issued For Date
6. UNLESS SPECIFIED OTHERWISE IN THE GEOTECHNICAL REPORT, ALL FILL MATERIAL SHALL CONFORM TO THE REQUIREMENTS OF AWS D1.4. INSTEAD IF APPROVED BY THE STRUCTURAL ENGINEER OF RECORD.
BE COMPACTED TO 95% PROCTOR DENSITY AS DETERMINED BY ASTM D698 AND SHALL BE Construction 10/24/2022
D
LAYERED WITH CONSOLIDATED LAYERS OF NO MORE THAN 8" IN THICKNESS. 7. ALL REINFORCING STEEL SHALL BE SUPPORTED USING CHAIRS (PLASTIC, METAL, OR 16. REPAIR HONTCOMBS, SPALLS, RUNS, AND OTHER DAMAGED AREAS AS DIRECTED BY THE
CEMENTITIOUS BLOCKS) AT 48" O.C. EACH WAY. STRUCTURAL ENGINEER OF RECORD.
7. IF ANY PORTION OF THE STRUCTURE IS PLACED ON DEEP FILL, THE STRUCTURAL ENGINEER
OF RECORD SHALL BE NOTIFIED PRIOR TO CONSTRUCTION. 8. ALL SPLICE LOCATIONS ARE SUBJECT TO APPROVAL AND SHALL BE MADE ONLY WHERE
INDICATED ON THE DRAWINGS.
8. TRENCHES FOR BURIED PLUMBING SHALL NOT RUN ALONG OR UNDER THE GRADE BEAMS
EXCEPT TO CROSS AT RIGHT ANGLES. TRENCH BACKFILL SHALL BE THOROUGHLY 9. REINFORCING BAR SPACING GIVEN ARE MAXIMUM ON CENTER. BARS MAY NOT BE BUNDLED
COMPACTED. OR SPACED FARTHER APART UNLESS APPROVED BY THE STRUCTURAL ENGINEER OF
RECORD.
9. ALL SLEEVES THROUGH CONCRETE SHALL BE SCHEDULE 40 GALVANIZED STEEL PIPE OR
PVC. 10. SECURELY TIE ALL BARS IN POSITION BEFORE PLACING CONCRETE.
C
10. GRADE BEAMS AND FOOTINGS SHALL BE CLEAN AND PER PLAN IN SIZE AND LOCATION. 11. END HOOKS, DEVELOPMENT LENGTHS, AND SPLICES SHALL CONFORM TO THE
DIFFERENT SIZES AND LOCATIONS SHALL BE BROUGHT TO THE ATTENTION OF THE REQUIREMENTS OF ACI 318.
STRUCTURAL ENGINEER OF RECORD.
12. MINIMUM COVERAGE FOR REINFORCING STEEL SHALL BE AS FOLLOWS:
11. LOOSE SOILS, CLODS, MUD, STANDING WATER, ICE OR FROST, ORGANICS AND VEGETATION, A. CONCRETE CAST AGAINST EARTH 3"
AND TRASH SHALL BE REMOVED FROM THE GRADE BEAMS, FOOTINGS, AND BUILDING PAD B. CONCRETE CAST AGAINST FORMS 2"
PRIOR TO CONCRETE PLACEMENT. C. FOOTINGS 2" TOP
3" BOTTOM
12. PROVIDE A MINIMUM 10 MIL VAPOR RETARDER OR VAPOR BARRIER OVER THE PREPARED D. SLAB-ON-GRADE CENTER IN SLAB
BUILDING PAD. LAPPING, WHEN REQUIRED, SHALL BE A MINIMUM OF 12" AND SHALL BE
TAPED AT THE JOINTS TO PROVIDE A CONTINUOUS SHEET UNDER THE ENTIRE SLAB.
SECURE THE VAPOR RETARDER/BARRIER TO THE SIDES OF THE GRADE BEAMS AND CUT
B
ALONG THE BOTTOM OF THE GRADE BEAMS TO PREVENT BRIDGING AND MOVEMENT OF THE
RETARDER/BARRIER DURING CONCRETE PLACEMENT.
LC Project No.: 1803.011
Scale: None
Specifications
A
S001
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
LUMBER SPECIFICATIONS
1. DIMENSIONAL LUMBER SHALL BE SOUTHERN YELLOW PINE OR DOUGLAS FIR-LARCH, KILN
M
5. UNLESS NOTED ON THE PLANS, PSL LUMBER MAY NOT BE SUBSTITUTED WITH ANY OTHER
ENGINEERED LUMBER WITHOUT APPROVAL FROM THE STRUCTURAL ENGINEER OF RECORD.
6. FINGER JOINTED STUDS ARE ACCEPTABLE PROVIDED THE LUMBER IS OF THE SAME SPECIES
AND GRADE AS NOTED ABOVE.
7. ALL STUDS SHALL BE BLOCKED HORIZONTALLY AT MID-HEIGHT (THIRD POINTS ON THE FIRST
FLOOR OF A 4-STORY BUILDING) WHEN SUBJECTED TO CONSTRUCTION LOADING PRIOR TO
BEING SHEATHED.
9. WOOD IN CONTACT WITH CONCRETE, EARTH, WITHIN 8" FROM EXPOSED EARTH, OR EXPOSED
TO WEATHER, SHALL BE PRESSURE TREATED IN ACCORDANCE WITH THE AMERICAN WOOD
PRESERVER'S ASSOCIATION (AWPA) STANDARD U1-02.
10. UNLESS NOTED OTHERWISE, FASTENING SHALL BE PER IBC TABLE 2304.9.1 (IBC 2012).
2. FLAT ROOF DECKING SHALL BE 23 32" APA RATED 48/24 SHEATHING EXPOSURE 1 GRADE T&G
PLYWOOD/OSB.
3. DECKING BELOW ROOF MOUNTED MECHANICAL UNITS SHALL BE 23 32" APA RATED 48/24
SHEATHING EXPOSURE 1 GRADE T&G PLYWOOD/OSB.
4. FLOOR DECKING SHALL BE 23 32" APA RATED STURD-I-FLOOR 24 O.C. EXPOSURE 1 GRADE T&G
PLYWOOD/OSB.
Gandy Residence
5. WOOD SHEATHING FOR SHEARWALLS AND MISCELLANEOUS USES SHALL BE A MINIMUM 7 16"
APA RATED 24/16 SHEATHING EXPOSURE 1 OSB.
Lubbock, TX 79413
6. PROVIDE A 1 4" GAP EVERY 80 FEET IN PLYWOOD/OSB DECKING AND SHEATHING RUNS
LONGER THAN 80 FEET.
7. EXTERIOR GYPSUM SHEARWALLS SHALL BE 12" MINIMUM TYPE X EXTERIOR RATED GYP
FASTENER SPECIFICATIONS
1. ALL CONNECTORS SHALL MEET THE FOLLOWING REQUIREMENTS:
CONNECTOR STANDARD
F
2. BOLT HOLES SHALL BE 132" TO 116" LARGER THAN THE BOLT DIAMETER. HOLES SHALL BE
ACCURATELY ALIGNED AND BOLTS SHALL NOT BE FORCIBLY DRIVEN.
E
3. LAG SCREW AND WOOD SCREWS LEAD HOLES, WHEN NECESSARY TO AVOID SPLITTING OF
THE WOOD MEMBERS, SHALL HAVE A DIAMETER OF 60% OF THE SHANK DIAMETER. THE
THREADED PORTION OF THE SCREW SHALL BE INSERTED INTO THE LEAD HOLE BY TURNING
WITH A WRENCH OR SCREW DRIVER, NOT BY DRIVING WITH A HAMMER.
8d 0.131" 2 12"
10d 0.148" 3"
16d 0.162" 3 12"
5. TOE-NAILS SHALL BE DRIVEN AT AN ANGLE OF APPROXIMATELY 30° WITH THE MEMBER BEING
TOE-NAILED AND STARTED APPROXIMATELY 13 THE LENGTH OF THE NAIL FROM THE MEMBER
END.
MATERIAL TO BE FASTENED
MANUFACTURER.
S002
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
CONVENTIONALLY REINFORCED FOUNDATION INFORMATION SHEET 10. THE SLAB CONSTRUCTION AND THE THICKNESS OF THE SLAB BETWEEN GRADE BEAMS IS SHOWN IN THE FOLLOWING NOTE: 19. ALL GRADE BEAM INTERSECTIONS AT CORNERS AND T'S NEED TO BE TIED TOGETHER WITH ADDITIONAL REBAR PER THE DETAILS BELOW.
CONSTRUCTION
1. CONVENTIONALLY REINFORCED FOUNDATIONS SHALL BE CONSTRUCTED AS SHOWN ON THE FOUNDATION PLANS WITHIN THIS SET OF DRAWINGS.
1. ALL SLAB-ON-GRADE SHALL HAVE A MINIMUM
5575 Stousland Rd.
2. MATERIAL SPECIFICATIONS FOR REINFORCING STEEL AND CONCRETE CAN BE FOUND IN THE SPECIFICATION SECTION AT THE BEGINNING OF THIS THICKNESS AS SHOWN BELOW, UNLESS NOTED
College Station, TX 77845
SET. OTHERWISE ON THE PLAN, AND SHALL BE
(832) 423-2977
REINFORCED WITH REINFORCING STEEL AS SHOWN PROVIDE STANDARD
GRADE BEAM REINFORCING www.laymonconsulting.com
3. THE BUILDING PAD SHALL BE CONSTRUCTED PER THE SPECIFICATIONS AT THE BEGINNING OF THIS SET AND PER THE GEOTECHNICAL REPORT. BELOW AND PLACED MID-HEIGHT IN THE SLAB. HOOKS FOR TOP STEEL
BOTH MUST BE FOLLOWED. IF THERE ARE ANY QUESTIONS OR CONFLICTS, CONTACT THE STRUCTURAL ENGINEER OF RECORD FOR OF THE GRADE BEAMS
TX Firm # F-19205
CLARIFICATION. 2. ALL SLABS SHALL BE PLACED OVER A 10 MIL VAPOR (TYP)
RETARDER OVER A SUBGRADE PREPARED PER THE LOCATED FIRST
GEOTECHNICAL REPORT. TIES/STIRRUPS WITHIN 2" OF
4. FOUNDATION SLAB EDGES AND GRADE BEAMS ARE SHOWN THUS: © 2022
THE INTERSECTION (TYP)
L
EQ
GRADE BEAM SLAB CORNER BARS TO MATCH GRADE BEAM The arrangements
REINFORCING. EACH LEG TO BE 30" LONG. depicted herein are the
4 12"
PLACE ON TOP & BOTTOM OF GRADE BEAM. sole property of Laymon
Consulting, LLC and may
not be reproduced in any
EQ
20. WHEN A GRADE BEAM JOGS WITHIN THE 30" OF THE CORNER REINFORCING, CONTINUE THE REINFORCING AROUND THE JOG AND EXTEND 30"
form without written
PAST THE LAST TURN AS SHOWN BELOW.
#3 REBAR permission.
30"
CHAIRS @ 48" O.C. VAPOR RETARDER
K
(MAX) MAY BE
PLASTIC, METAL,
PREPARED SUBGRADE
< 30"
OR BRICK
5. SOME PORTIONS OF THE FOUNDATION MAY REQUIRE FOOTINGS TO SUPPORT POINT LOADS ON THE FOUNDATION OR HOLDOWNS OR ANCHORS
REQUIRING THICKER CONCRETE FOR UPLIFT PURPOSES. FOOTINGS ARE SHOWN AS BELOW AND ARE LABELED WITH "F#". 11. GRADE BEAM AND FOOTING SIZES AND REINFORCING ARE SHOWN IN THE FOUNDATION SIZE SCHEDULE BELOW.
Gandy Residence
Lubbock, TX 79413
H/4
CONVENTIONALLY
STEP 2: VAPOR RETARDER INSTALLATION ADD #5 T&B OF PENETRATION AND EACH FACE
F
RB-1 RB-1 OF GRADE BEAM (4 TOTAL) EXTENDED 48db GRADE BEAM REINFORCING
REINFORCED GRADE BEAM
12. THIS IS NOT TO BE CONSIDERED AN EXHAUSTIVE LIST OF EVERYTHING REQUIRED TO INSTALL THE VAPOR RETARDER. THIS IS A LIST PROVIDED BEYOND THE PENETRATION
CALLOUT. DIFFERENT
RB-1
RB-2
RB-1
BY THE STRUCTURAL ENGINEER OF RECORD FOR INSTALLATION ISSUES THAT CAN POTENTIALLY AFFECT THE STRUCTURAL INTEGRITY OF THE
NUMBER SIGNIFY
FOUNDATION. THE GENERAL CONTRACTOR AND THE SUBCONTRACTORS ARE SOLELY RESPONSIBLE FOR THE PROPER INSTALLATION OF THE
H/2
H
14. WHEN REQUIRED, THE VAPOR RETARDER SHOULD BE LAPPED TO PROVIDE A CONTINUOUS SHEET UNDER THE ENTIRE FOUNDATION. THE JOISTS
SHALL BE TAPED COMPLETELY.
H/4
15. CARE MUST BE TAKEN TO ENSURE THAT THE VAPOR RETARDER MATERIAL DOES NOT BECOME ENTANGLED OR HUNG UP IN THE REINFORCEMENT,
E
16. THE VAPOR RETARDER SHOULD BE SECURED TO THE SIDES OF THE GRADE BEAMS AND CUT ALONG THE BOTTOM OF THE GRADE BEAM. CUTTING
8. IN SOME PARTS OF THE COUNTRY FROST DEPTH PROTECTION IS REQUIRED. FROST BEAMS ARE GRADE BEAMS OR CONTINUOUS WALL FOOTINGS ALONG THE BOTTOM OF THE GRADE BEAM PREVENTS "BRIDGING" FROM OCCURRING.
6" MIN
THAT EXTEND DOWN TO THE FROST LINE REQUIRED BY THE LOCAL REGION TO KEEP MOISTURE AND FROST FROM MIGRATING UNDER THE ADDL (3) TIES (U-SHAPED)
FOUNDATION AND CAUSING IT TO HEAVE. THEY SHALL ALWAYS BE AROUND THE PERIMETER OF THE FOUNDATION AS WELL AS UNDER AREAS 17. IT IS NOT NECESSARY FOR THE VAPOR RETARDER BE EXTENDED OUTSIDE THE FOUNDATION PERIMETER. @3" O.C. ON EACH SIDE
SEPARATING CONDITIONED AND UNCONDITIONED AIR WITHIN THE BUILDING. FROST BEAM LOCATIONS ARE SHOWN ON THE FOUNDATION PLAN OF THE PENETRATION
WITH A HATCHED AREA. ALLOWABLE PENETRATION ZONE
PIPE Ø + 8" PIPE Ø + 8"
VAPOR RETARDER SECURE TO THE
SIDES WITH NAILS Issued For Date
24. SLAB REINFORCING SHALL BE PLACED ON CHAIRS OR BRICKS PRIOR TO PLACEMENT OF CONCRETE. PULLING REBAR UP INTO THE CONCRETE AS Construction 10/24/2022
D
FROST BEAM THE CONCRETE IS BEING PLACED IS NOT ACCEPTABLE AND THE FOUNDATION WILL BE REJECTED. ALL DAMAGED CHAIRS SHALL BE REPLACED
PRIOR TO THE PLACEMENT OF CONCRETE.
25. ADDITIONAL SLAB REINFORCING NOT SHOWN ON THE PLANS WILL BE REQUIRED AT THE CORNERS AND AT OPENINGS LARGER THAN 12".
SLAB REINFORCING
ROUND OR
48db TYP
CORNER BAR, 24"x24"
TO MATCH SLAB RECTANGULAR
EXTERIOR CUT DOWN THE REINFORCING SIZE OPENING
GRADE BEAM MIDDLE TO AVOID
BRIDGING NO BRIDGING
C
OPENING
> 1'-0"
9. ADDITIONAL REINFORCING MUST BE PLACED AT RE-ENTRANT CORNERS TO MITIGATE CRACKING AT THOSE CORNERS DUE TO CONCRETE
SHRINKAGE. RE-ENTRANT CORNERS OCCUR AROUND THE PERIMETER OF THE FOUNDATION, AT CONSTRUCTION AND CONTROL JOISTS WITH SLAB EDGE
STEP 3: REINFORCING STEEL INSTALLATION
JOGS IN THEM, AND AT FOUNDATION DROPS AND STEPS. REINFORCING IS (2) #4 x 5'-0" LONG REBAR PLACED AT A 45° ANGLE TO THE CORNER,
PLACED MID-DEPTH IN THE SLAB, AND SPACED AS SHOWN: 18. THIS IS NOT TO BE CONSIDERED AN EXHAUSTIVE LIST OF EVERYTHING REQUIRED TO INSTALL THE REINFORCING STEEL. THIS IS A LIST PROVIDED
BY THE STRUCTURAL ENGINEER OF RECORD FOR INSTALLATION ISSUES AND REQUIREMENTS THAT CAN POTENTIALLY AFFECT THE STRUCTURAL 2" CLR
INTEGRITY OF THE FOUNDATION. THE GENERAL CONTRACTOR AND THE SUBCONTRACTORS ARE SOLELY RESPONSIBLE FOR THE PROPER (TYP)
48db TYP
INSTALLATION OF THE REINFORCING STEEL. EXTERIOR SLAB EDGE CORNER REINFORCING
CORNER
B
4'-0" LONG
CORNER MATCH SLAB REINFORCING SIZE.
3"
Scale: None
RE-ENTRANT STEEL
S010
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
FRAMING INFORMATION SHEET 6. COLUMNS AND POSTS SHALL BE USED UNDER THE ENDS OF ALL HEADERS, BEAMS, AND GIRDER TRUSSES. AT A MINIMUM, A (2)2x STUD PACK
SHALL BE USED.
7. UNLESS NOTED OTHERWISE, ALL HEADERS, BEAMS, AND GIRDER TRUSSES SHALL BE SUPPORTED WITH A SP224 OR SP226, DEPENDING ON THE
STEP 1: HOW TO READ THE PLANS
M
WALL THICKNESS SUPPORTING THE HEADER, BEAM, OR GIRDER TRUSS. 10. FOR MULTIFAMILY PROJECTS, THE INDIVIDUAL APARTMENT UNITS TYPICALLY STACK ONE ON TOP OF THE OTHER. THE OVERALL BUILDING FLOOR
PLANS WILL SHOW A UNIT STACK CONDITION INDICATING THE UNIT TYPE ON THE FLOOR LEVEL BEING FRAMED OVER THE UNIT TYPE ON THE
1. MATERIAL SPECIFICATIONS FOR LUMBER GRADE AND SPECIES, FASTENERS, DECKING AND SHEATHING, AND WOOD SHRINKAGE CONCERNS CAN 8. COLUMN/POST STACKING CONDITION WILL BE CALLED OUT ON THE PLAN AND WILL INDICATE THE FLOOR LEVEL AND COLUMN/POST SIZE FLOOR BELOW (SHOWN IN THE BACKGROUND) AND WHERE THAT FRAMING PLAN CAN BE LOCATED WITHIN THE DRAWING SET.
BE FOUND IN THE SPECIFICATION SECTION AT THE BEGINNING OF THIS SET. REQUIRED AS SHOWN IN THE FRAMING PLAN EXAMPLE TO THE LEFT. 5575 Stousland Rd.
UNIT ON THE FLOOR LEVEL BEING FRAMED College Station, TX 77845
2. FRAMING PLANS SHOW THE FRAMING FOR THE FLOOR/ROOF LEVEL CALLED OUT BELOW EACH PLAN. THE BACKGROUND SHOWN FOR THOSE 9. COLUMNS AND POSTS ARE CALLED OUT AS TWO LETTERS FOLLOWED BY A SERIES OF NUMBERS. THE TWO LETTERS HELP TO INDICATE THE TYPE
PLANS IS FOR THE WALLS BELOW SO THAT YOU MAY KNOW WHICH WALLS ARE TO BE USED TO SUPPORT THE TRUSSES/JOISTS. (CAUTION: DO XX UNIT ON THE FLOOR LEVEL BELOW (832) 423-2977
OF COLUMN: "SP" INDICATES A STUD PACK WITH CONVENTIONAL LUMBER STUDS, "WP" INDICATES A SOLID WOOD POST, AND "EP" AND
NOT CONFUSED THIS WITH THE SHEARWALL PLANS WHICH SHOW THE BACKGROUND OF THE FLOOR IN WHICH THOSE WALLS ARE CONSTRUCTED. XX (ON THE BACKGROUND PLAN) www.laymonconsulting.com
ENGINEERED POST MADE OF STRUCTURAL COMPOSITE LUMBER. THE NUMBERS ARE USED TO INDICATE AS SIZE. FOR EXAMPLE, 224 IS A (2) 2x4,
SEE SHEETS S030 AND S031 FOR SHEARWALL INFORMATION.) BEARING WALLS, HEADERS, BEAMS, AND TRUSSES/JOISTS ARE DEPICTED AS 410 IS A 3 12" X 9 1 4", ETC. THE FULL LIST AND A DESCRIPTION OF EACH MARK IS LISTED BELOW. X/Sxxx
FOLLOWS: LOCATION IN THE DRAWING SET TX Firm # F-19205
THE FRAMING PLAN CAN BE FOUND
HEADER SIZE. SEE
BEARING WALL NOTE 4 BELOW. HEADER
COLUMN SCHEDULE © 2022
L
326 326 11. ROOF TRUSSES LIKE TO BE FRAMED IN THE DIRECTION OF THE SLOPE. HOWEVER, THERE ARE AREAS ON ROOFS WHERE THAT IS NOT ALWAYS Laymon Consulting, LLC
CONVENTIONAL LUMBER POSSIBLE. THOSE AREAS ARE TYPICALLY CALLED "OVERFRAME" AREAS AND ARE SHOWN ON THE PLANS WITH A DOTTED HATCHING. WE HAVE All rights reserved
MARK SIZE MARK SIZE DONE OUR BEST TO HIGHLIGHT THESE AREAS TO HELP THE TRUSS MANUFACTURER KNOW WHERE THESE OCCUR. THE TRUSS MANUFACTURER The arrangements
SP224 (2) 2x4 STUD PACK SP424 (4) 2x4 STUD PACK WILL HAVE THE OPTION TO EITHER BUILD THESE AREAS INTO THE MAIN TRUSSES SHOWN ON THE PLANS OR TO CROSS FRAME ON TOP OF THE depicted herein are the
SP226 (2) 2x6 STUD PACK SP426 (4) 2x6 STUD PACK MAIN TRUSSES WITH CAP OR OVERFRAME TRUSSES. sole property of Laymon
SP324 (3) 2x4 STUD PACK SP524 (5) 2x4 STUD PACK Consulting, LLC and may
TRUSS/JOIST SP326 (3) 2x6 STUD PACK SP526 (5) 2x6 STUD PACK OVERFRAME AREA not be reproduced in any
form without written
permission.
COLUMN/POST BEARING WALL SOLID LUMBER
CALLOUT MARK SIZE MARK SIZE
K
.
24" O.C
2ND: SP324 TRUSS DESIGNATION WP46 4x6 SYP #2 WP88 8x8 SYP #2
1ST: SP424 AND SPACING
FT-1 @
NOTE 4 BELOW. EP47 3 12" x 7" PSL EP77 7" x 7" PSL
6 FT
3RD DOWN 2 1
4TH DOWN 2 2
3. FLUSH BEAMS ARE BEAMS THAT ARE ABOVE OR SIT ON TOP OF THE BEARING PLATES. DROP BEAMS ARE BEAMS THAT ARE FRAMED BELOW THE 4" O.C.
BEARING PLATE BUT NOT OVER A DOOR OR WINDOW. HEADERS ARE ALSO FRAMED BELOW THE PLATE BUT ARE SPECIFICALLY OVER A DOOR OR TOP 1 1 RT-1 @ 2
A WINDOW. 2ND DOWN 1 1
8 FT
3RD DOWN 2 2
Gandy Residence
4. BEAMS ARE HEADERS WILL BE MARKED ON PLAN WITH A 3- OR 4-DIGIT NUMBER WHEN THE BEAM IS TO BE CONSTRUCTED WITH CONVENTIONAL TOP
4TH DOWN 2 2
LUMBER OR A 2-, 3-, OR 4-DIGIT NUMBER PRECEDED WITH THE LETTER "E" WHEN THE BEAM IS TO BE CONSTRUCTED WITH AND ENGINEERED 2ND DOWN
TOP 2 1
Lubbock, TX 79413
LUMBER SUCH AS PARALLEL STRAND LUMBER (PSL) AND LAMINATED VENEER LUMBER (LVL). THE BEAM/HEADER SCHEDULE IS SHOWN BELOW.
2ND DOWN 2 2 3RD DOWN
10 FT
3RD DOWN 2 2 4TH DOWN
CONVENTIONAL LUMBER 10. THE TRUSS PLACEMENT SHOWN ON THE PLAN IS ONLY APPROXIMATE AND IS SOLELY INTENDED TO SHOW THE TRUSS SPAN DIRECTION, SPACING
MARK SIZE MARK SIZE REQUIREMENTS, AND SUPPORT LOCATIONS. THE ACTUAL TRUSS DESIGN AND PLACEMENT REQUIREMENTS AND DIMENSIONS ARE SHOWN ON
226 (2) 2x6 426 (4) 2x6 THE TRUSS MANUFACTURER'S DRAWINGS.
228 (2) 2x8 428 (4) 2x8
11. TRUSSES ARE LABELED BASED ON THEIR LOCATION, SIZES, AND LOADING REQUIREMENTS. TRUSS LABELING IS A WAY FOR THE PLANS TO HELP
2210 (2) 2x10 4210 (4) 2x10
THE TRUSS MANUFACTURER AND THE GENERAL CONTRACTOR KNOW WHERE TRUSS LOADING OR DEPTH REQUIREMENTS CHANGE. TRUSSES
2212 (2) 2x12 4212 (4) 2x12 ARE DESIGNATED AS "_T-#" WITH THE "_T" INDICATING A GENERAL LOCATION AND THE "#" INDICATING A DIFFERENT TYPE OF LOADING OR DEPTH
326 (3) 2x6 526 (5) 2x6 FOR THAT LOCATION.
328 (3) 2x8 528 (5) 2x8 A. BT = BALCONY TRUSS STEP 2: FRAMING REQUIREMENTS FOR ROOF AND FLOOR TRUSSES
3210 (3) 2x10 5210 (5) 2x10 B. CT = CORRIDOR TRUSS
F
C. DT = DRAG TRUSS (SEE SHEETS S009 AND S010) 12. ROOF TRUSSES SHALL BE PLACED AS SHOWN AND DIMENSIONED ON THE APPROVED TRUSS MANUFACTURER DRAWINGS.
3212 (3) 2x12 5212 (5) 2x12
D. FT = FLOOR TRUSS
ENGINEERED LUMBER E. GT = GIRDER TRUSS 13. ALL ROOF TRUSSES SHALL BE ATTACHED TO A WALL, BEAM, OR GIRDER TRUSS AT ALL BEARING POINTS WITH A CLIP OR HANGER CAPABLE OF
MARK SIZE MARK SIZE F. RT = ROOF TRUSS WITHSTANDING THE UPLIFT LOAD SHOWN ON EACH TRUSS PROFILE SHEET PROVIDED BY THE TRUSS MANUFACTURER. THE TRUSS
E46 E612 5 1 4" x 11 7 8" PSL/LVL MANUFACTURER DRAWINGS APPROVED BY LAYMON CONSULTING WILL TYPICALLY SHOW THE CLIP ATTACHMENT REQUIREMENTS. CONTACT
E48 3 12" x 7 1 4" PSL/LVL E614 5 1 4" x 14" PSL/LVL EXAMPLE 1 LAYMON CONSULTING IF YOU NEED HELP WITH THIS INFORMATION. AT A MINIMUM, ALL ROOF TRUSSES SHALL BE ATTACHED WITH A SIMPSON
1 1 FT-1 IS A 18" DEEP FLOOR TRUSS WITH A 40 PSF LIVE LOAD ON THE TOP CHORD H2.5A CLIP AT ALL BEARING LOCATIONS.
E410 3 2" x 9 4" PSL/LVL E616 5 1 4" x 16" PSL/LVL
FT-2 IS A 24" DEEP FLOOR TRUSS WITH A 40 PSF LIVE LOAD ON THE TOP CHORD
E411 3 12" x 11 1 4" PSL/LVL E618 5 1 4" x 18" PSL/LVL FT-3 IS A 18" DEEP FLOOR TRUSS WITH A 100 PSF LIVE LOAD ON THE TOP CHORD
E412 1 7
3 2" x 11 8" PSL/LVL E78 7" x 7 1 4" PSL/LVL C.
" O.
E414 1
3 2" x 14" PSL/LVL E710 7" x 9 1 4" PSL/LVL EXAMPLE 2 8'-0
E416 3 12" x 16" PSL/LVL E711 7" x 11 14" PSL/LVL CT-1 IS A 17 1 4" DEEP CORRIDOR TRUSS WITH A 100 PSF LIVE LOAD ON THE TOP CHORD
E
1 CT-2 IS A 15" DEEP CORRIDOR TRUSS WITH A 100 PSF LIVE LOAD ON THE TOP CHORD
E418 3 2" x 18" PSL/LVL E712 7" x 11 7 8" PSL/LVL
1 1
E66 5 4" x 5 2" PSL/LVL E714 7" x 14" PSL/LVL 8. THE TRUSSES ARE TO BE DESIGNED WITH THE LOADING SHOWN ON THE PLANS. THE DESIGN LOADS FOR THE PROJECT, SUCH AS WIND SPEED, 8'-0" O.C.
1 1
E68 5 4" x 7 4" PSL/LVL E716 7" x 16" PSL/LVL RISK CATEGORY, AND SNOW LOADS ARE SHOWN ON THE SPECIFICATIONS SHEETS UNDER THE "DESIGN LOADS" SPECIFICATION. THE DEAD AND
E610 5 1 4" x 9 1 4" PSL/LVL E718 7" x 18" PSL/LVL LIVE LOAD REQUIREMENTS FOR THIS SPECIFIC PROJECT FOR THE TOP AND BOTTOM CHORDS OF EACH TRUSS TYPE ARE SHOWN IN THE TRUSS
E611 5 1 4" x 11 1 4" PSL/LVL LOADING SCHEDULE BELOW.
LINE LINE LINE
PLATE PLATE PLATE
5. BEARING WALL CONSTRUCTION FOR THIS SPECIFIC PROJECT CAN BE FOUND IN THE BEARING WALL SCHEDULE BELOW.
A. ALL EXTERIOR WALLS SHALL BE CONSIDERED LOAD BEARING, EVEN IF NOT SHOWN AS HATCHED ON THE FRAMING PLANS.
B. PARTY WALLS ARE USED IN MULTIFAMILY CONSTRUCTION AND ARE THOSE WALLS THAT SEPARATE TWO APARTMENT UNITS AND
TRUSS LOADING SCHEDULE SIMPSON H2.5A SIMPSON H2.5A Issued For Date
(OR AS SHOWN ON APPROVED (OR AS SHOWN ON APPROVED
CONTAIN AN AIRSPACE BETWEEN THE WALLS. TOP CHORD BOTTOM CHORD Construction 10/24/2022
MARK DEPTH TRUSS MANUFACTURER DRAWINGS) TRUSS MANUFACTURER DRAWINGS)
D
i. AN EXCEPTION TO THIS ARE PARTY WALLS THAT SHARE A SILL PLATE AND BEARING PLATE WITH NARROWER STAGGERED STUDS DL LL DL LL
BETWEEN THE PLATES.
FT-1 18" 20 PSF 40 PSF 5 PSF 0 PSF
C. CORRIDOR WALLS ARE ANY WALLS THAT ARE SHARED BY AND SEPARATE THE APARTMENT UNIT AND THE CORRIDOR/BREEZEWAY. EXTERIOR BEARING POINT INTERIOR BEARING POINT INTERIOR BEARING POINT
D. INTERIOR WALLS ARE ALL LOAD BEARING WALLS CONTAINED WITHIN THE APARTMENT UNIT. RT-1 VARIES 20 PSF 20 PSF 5 PSF 0 PSF
NOTES: 14. INSTALL STRONGBACKS ACROSS ROOF TRUSS WEBS AND CHORDS AS DEPICTED ON THE TRUSS MANUFACTURER DRAWINGS. THIS IS NEEDED TO
1. DL = DEAD LOAD; LL = LIVE LOAD ENSURE THE TRUSSES AND TRUSS MEMBERS DO NOT BUCKLE AND FAIL.
BEARING WALL SCHEDULE 2. REFER TO MEP DRAWINGS FOR MECHANICAL UNIT 15. PROVIDE TEMPORARY BRACING ACROSS THE TOP AND BOTTOM CHORDS IN THE FORM OF 2x4 PLANKS RUNNING PERPENDICULAR AND ATTACHED
LOCATIONS AND LOADING. TO THE TOP AND BOTTOM CHORDS AT 8'-0" ON CENTER UNTIL THE ROOF DECKING AND THE CEILING MATERIAL HAVE BEEN ATTACHED. SEE THE
DETAIL ABOVE FOR A GRAPHICAL DEPICTION.
GANDY RESIDENCE 3. REFER TO MEP DRAWINGS FOR ANY CHASES
REQUIRED FOR DUCT WORK OR PLUMBING. 16. INSTALL STRONGBACK ACROSS FLOOR TRUSS BOTTOM CHORDS AT NO MORE THAN 10'-0" INTERVALS. STRANGBACK LAP SPLICES SHALL BE 4'-0"
C
FLOOR LOCATION SIZE QTY. & SPA. BLOCKING IN LENGTH. SOME STRONGBACK INSTALLATION OPTIONS ARE SHOWN BELOW. OTHER OPTIONS CAN BE APPROVED BY LAYMON CONSULTING
EXTERIOR 2x6 (1) @ 16" o.c. MID 4. REFER TO ARCHITECTURAL DRAWINGS FOR ANY EITHER THROUGH AN RFI OR DURING A FIELD VISIT.
1st 2x4 (1) @ 12" o.c. 1
3 PT.
APPURTENANCES HANGING FROM TRUSSES.
INTERIOR
2x6 (1) @ 16" o.c. MID
5. SEE FRAMING PLANS FOR ANY ADDITIONAL LINE
LOADS OR POINT LOADS SHOWN ON THE PLANS
TO BE SUPPORTED BY THE TRUSSES.
B
2x VERTICAL ATTACHED
2x STRONGBACK WITH (2) 8D COMMON 2x STRONGBACK
ATTACHED WITH (2) 8d NAILS AT EACH END ATTACHED WITH (2) 8d
COMMON NAILS 2x STRONGBACK COMMON NAILS LC Project No.: 1803.011
ATTACHED WITH (2) 8d
COMMON NAILS None
Scale:
9. THERE ARE SOME AREAS THAT MAY REQUIRE THE TRUSSES TO CARRY BEARING WALL LOADS FROM ABOVE. THOSE AREAS ARE SHOWN ON THE
FRAMING PLANS WITH A DASHED LINE ACROSS THE TRUSSES AS WELL AS THE DEAD AND LIVE LINE LOADS ON THOSE TRUSSES. 17. BROKEN OR MIS-INSTALLED TRUSSES SHALL BE REPAIRED IN ACCORDANCE WITH THE TRUSS MANUFACTURER'S REQUIREMENTS. IT IS
RECOMMENDED THAT A COPY OF THE REQUIRED TRUSS REPAIR BE ATTACHED TO THE REPAIRED TRUSS FOR EASY ACCESS TO ANY CITY OR
ENGINEERING INSPECTOR. Framing
240 PLF DL; 400 PLF LL
18. SEE THE SHEARWALL INSTRUCTION SHEETS FOR ADDITIONAL BRACING REQUIREMENTS IN THE TRUSS CAVITIES OVER THE SHEARWALLS. Information
A
S020
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
STEP 3: FRAMING REQUIREMENTS FOR WALLS 27. UNDER NO CIRCUMSTANCE SHOULD ADDITIONAL 2x BLOCKING BE USED TO "PAD UP" TO THE FLOOR DECKING. THIS CAUSES A SUBSTANTIAL 30. HEADERS ARE INSTALLED DIRECTLY ABOVE THE DOOR OR WINDOW OPENING WITH CRIPPLE STUDS PLACED BETWEEN THE BEARING PLATES AND
AMOUNT OF ADDITIONAL WOOD SHRINKAGE THAT WILL NOT BE ACCOUNTED FOR. THE DETAIL BELOW SHALL NOT BE USED. THE HEADER. CRIPPLE STUDS SHOULD BE THE SAME SIZE AND SPACING AS THE STANDARD STUDS WITHIN THE WALL ON EITHER SIDE OF THE
19. STUDS SHALL BE SIZED AND SPACED AS SHOWN IN THE "BEARING WALL SCHEDULE" ON THIS SHEET. THE STUDS SHALL HAVE A SINGLE SILL/SOLE OPENING. VERTICAL BLOCKING SHALL BE PLACED IN THE FLOOR CAVITY TO TRANSFER THE LOAD FROM THE HEADER POSTS ABOVE TO BELOW.
PLATE AND A DOUBLE BEARING PLATE, AT A MINIMUM. SOME DETAILS MAY REQUIRE ADDITIONAL PLATES. REFER TO THE DETAILS IN THE BACK THE VERTICAL BLOCKING SHALL MATCH THE SAME MATERIAL AND SIZE AS THE POSTS ABOVE.
M
OF THIS SET AS WELL AS THE ARCHITECTURAL DRAWINGS FOR ANY ADDITIONAL PLATING AND BLOCKING REQUIREMENTS.
SPACING, S
STUDS VERTICAL BLOCKING TO POST ABOVE 5575 Stousland Rd.
MATCH MATERIAL AND College Station, TX 77845
HORIZONTAL BLOCKING POST ABOVE SIZE OF POST ABOVE (832) 423-2977
USED TO "PAD UP" FLOOR DECKING
www.laymonconsulting.com
FLOOR DECKING
TX Firm # F-19205
FLOOR TRUSS
PLATE © 2022
L
1
2 S SPACING, S
2x6 SILL PLATE
21. ALL WALL INTERSECTIONS AND CORNERS SHALL HAVE A MINIMUM OF THREE STUDS, IN ANY ORIENTATION, TYING THE INTERSECTING WALLS THIS DETAIL IS NOT TO BE USED.
TOGETHER. HEADER
22. SILL PLATES MUST BE ATTACHED TO THE FOUNDATION/DECKING WITH ANCHOR ATTACHMENTS AS SHOWN ON SHEET S031, NOTE 14.
POST BELOW
23. BEARING AND EXTERIOR WALL STUDS SHALL BE CAPPED WITH DOUBLE TOP PLATES INSTALLED TO PROVIDE OVERLAPPING AT CORNERS AND AT
INTERSECTIONS WITH OTHER PARTITIONS. END JOINTS IN DOUBLE TOP PLATES SHALL BE OFFSET NOT LESS THAN 48 INCHES AND SHALL BE 28. DROP BEAMS SHOULD BE PLACED DIRECTLY UNDER THE BEARING PLATES. THE BLOCKING IN THE FLOOR CAVITY TRANSFERRING THE LOAD HEADER CONSTRUCTION (LAYMON CONSULTING PREFERRED METHOD)
NAILED IN ACCORDANCE WITH THE "IBC FASTENING SCHEDULE" SHOWN ON THIS SHEET. FROM ABOVE TO THE DROP BEAM SHALL BE PLACED VERTICALLY AND SHALL MATCH THE MATERIAL AND SIZE OF THE POST ABOVE. IF NEEDED,
THE DROP BEAM CAN COME UP INTO ONE OF THE BEARING PLATES PROVIDED THE TOP BEARING PLATE IS ATTACHED TO THE DROP BEAM PER
THE "IBC FASTENING SCHEDULE" SHOWN ON THIS SHEET.
J
Gandy Residence
TOP PLATE, TO TRUSS
END NAIL
3-3" x 0.131" NAILS
25. THERE ARE MANY OPTIONS IN HOW A BEAM OR HEADER IS FRAMED AND SUPPORTED. THE DETAILS AND OPTIONS SHOWN BELOW ARE THE
Lubbock, TX 79413
BEARING PLATE 16d COMMON (3 12" x 0.162") @ 6" O.C.;
PREFERENCES OF LAYMON CONSULTING. OTHER DETAILS MAY BE USED AND APPROVED FOR USE THROUGH THE RFI PROCESS OR THROUGH FLAT BLOCKING TO TRUSS AND WEB FILLER FACE NAIL
SITE VISITS. 3" x 0.131" NAILS @ 6" O.C.
3-10d COMMON (3" x 0.148");
26. FLUSH BEAMS SHOULD SIT DIRECTLY ON THE TOP BEARING WITH THE REQUIRED POST BELOW DIRECTLY UNDER THE BEAM END AND BEARING 3-16d BOX (3 12" x 0.135");
PLATE. ANY LOAD TRANSFERS COMING FROM ABOVE SHOULD OCCUR THROUGH VERTICAL BLOCKING BETWEEN THE FLOOR DECK AND THE POST BELOW 2. ROOF TRUSS TO TOP PLATE TOENAIL
4-10d BOX (3" x 0.128");
FLUSH BEAM AND LOCATED DIRECTLY UNDER THE POST ABOVE. THE BLOCKING SHOULD MATCH THE SAME MATERIAL AND SIZE AS THE POST
DROP BEAM BELOW DOUBLE BEARING PLATE (LAYMON CONSULTING PREFERRED METHOD) 4-3" x 0.131" NAILS
ABOVE. ALTERNATIVELY, THE FLUSH BEAM AND BLOCKING CAN REVERSE POSITIONS WITH THE FLUSH BEAM DIRECTLY UNDER THE FLOOR
DECKING. HOWEVER, THE BLOCKING BELOW THE FLUSH BEAM WILL NEED TO MATCH THE POST BELOW, NOT ABOVE.
WALL
DESCRIPTION OF BUILDING ELEMENT NUMBER AND TYPE OF FASTENER SPACING AND LOCATION
TOP PLATES ON EITHER END OF THE DROP BEAM WITH STRAPS ON BOTH SIDES OF THE DROP BEAM AS SHOWN BELOW.
11. TOP PLATES, LAP AT CORNERS AND
3-10d BOX (3" x 0.128"); FACE NAIL
INTERSECTIONS
POST ABOVE 3-3" x 0.131" NAILS
AND SIZE BELOW FLOOR TRUSS 13. RIM JOIST, BAND JOIST, OR BLOCKING TO TOP
10d BOX (3" x 0.128"); 6" O.C., TOENAIL
PLATE, SILL, OR OTHER FRAMING BELOW
3" x 0.131" NAILS
32" O.C., FACE NAIL AT TOP AND
20d COMMON (4" x 0.192")
CONNECTION
BOTTOM STAGGERED ON
FLUSH BEAM OPPOSITE SIDES
1
14. BUILT-UP GIRDERS AND BEAMS, 2x
BEARING PLATE 24" O.C., FACE NAIL AT TOP AND
LUMBER LAYERS 10d BOX (3" x 0.128");
BOTTOM STAGGERED ON
POST BELOW (MUST USE A CONNECTION 1 OPTION IN 3" x 0.131" NAILS
OPPOSITE SIDES
CONJUNCTION WITH A CONNECTION 2
BEARING PLATE
CONNECTION
OPTION) AND:
DROP BEAM 8d COMMON (2 12" x 0.131"); ENDS AND AT EACH SPLICE,
B
2
FLUSH BEAM HIGH 10d BOX (3" x 0.128"); FACE NAIL
3" x 0.131" NAILS
SIMPSON CS16x30" POST BELOW LC Project No.:
2-8d COMMON (2 12" x 0.131"); 1803.011
CENTERED ON BUTT JOINT
(4 TOTAL) DROP BEAM INTERFERING WITH BOTH BEARING PLATES 15. BRIDGING OR BLOCKING TO TRUSS 2-10d BOX (3" x 0.128"); EACH END, TOENAIL
2-3" x 0.131" NAILS Scale: None
NOTES:
1. THIS FASTENING SCHEDULE DOES NOT NEGATE THE USE OF UPLIFT CLIPS AND STRAPS. SEE PLANS AND DETAILS FOR
ANY ADDITIONAL UPLIFT REQUIREMENTS. Framing
Information
A
S021
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
SHEARWALL DRAWING INFORMATION SHEET 7. HOLDOWNS AND STRAPS CAN BE ADJUSTED WITHIN 12" FROM THE ENDS FOR SHEARWALLS 20' IN LENGTH AND GREATER AND WITHIN 6" FROM
THE ENDS FOR SHEARWALLS LESS THAN 20' IN LENGTH.
11. WHEN ROOF TRUSSES ARE PERPENDICULAR TO THE SHEARWALL, SUCH AS AT CORRIDORS AND EXTERIOR WALLS, BRACING AND BLOCKING ARE
USED TO TRANSFER THE SHEAR DOWN INTO THE SHEARWALLS.
8. HOLDOWNS AND STRAPS MUST BE ATTACHED TO THE SAME ENDS POSTS, AND THOSE END POSTS MUST STACK, THROUGHOUT THE HEIGHT OF 12. TO DETERMINE THE NUMBER OF BRACES REQUIRED OVER A SHEARWALL, USE THE CHART BELOW SHOWING THE LENGTH OF SHEARWALL THAT
STEP 1: HOW TO READ THE PLANS
M
THE SHEARWALL STACK. ONE BRACE CAN HANDLE. KEEP ADDING A BRACE UNTIL THE SUM OF THE LENGTHS IS GREATER THAN ACTUAL LENGTH OF THE SHEARWALL.
1. SHEARWALLS SHALL BE CONSTRUCTED AS SHOWN ON THE SHEARWALL PLANS WITHIN THIS SET OF DRAWINGS. EXAMPLE
SHEARWALL BELOW = GW13 (20)
5575 Stousland Rd.
2. SHEARWALL LOCATIONS ARE SHOWN WITH A SOLID DARK LINE ON THE SIDE OF THE STUD WALL THE SHEARWALL IS TO BE CONSTRUCTED. (1) BRACE FOR A GW13 WILL ACCOMODATE 10'-8" OF SHEARWALL. THIS IS NOT ENOUGH.
College Station, TX 77845
STEP 2: GETTING SHEAR FROM THE ROOF TO THE SHEARWALLS (2) BRACES WILL ACCOMODATE (10'-8") x 2 = 21'-4" OF SHEARWALL. THIS IS LONGER THAN THE 20' SHEARWALL.
THEREFORE, 2 BRACES WILL BE NEEDED OVER THIS SHEARWALL.
(832) 423-2977
SHEARWALL ON THIS SHEARWALL ON BOTH www.laymonconsulting.com
SIDE OF THE WALL ONLY SIDES OF THE WALL 9. FOR ROOF TRUSSES PARALLEL TO THE SHEARWALL, A DRAG TRUSS MUST BE PLACED DIRECTLY OVER THE SHEARWALL IN ORDER TO TRANSFER
13. THE BRACE ALSO MUST BE BELOW A CERTAIN ANGLE IN ORDER FOR IT TO BE EFFECTIVE. A BRACE THAT IS TOO VERTICAL WILL NOT WORK. THE
THE LOAD FROM THE ROOF DOWN TO THE SHEARWALL. THE FORCE THE DRAG TRUSS IS TO BE DESIGNED FOR CAN BE CALCULATED BY TX Firm # F-19205
SECOND CHART BELOW INDICATES THE NUMBER OF TRUSS BAYS THE BRACE MUST CROSS (ASSUMING TRUSSES ARE AT 24" O.C.) DEPENDING ON
MULTIPLYING THE SHEAR VALUE OF THE SHEARWALL BELOW THE DRAG TRUSS, WHICH IS GIVEN IN THE "SHEARWALL SCHEDULE" UNDER NOTE 4,
THE ROOF HEIGHT DIRECTLY OVER THE SHEARWALL.
BY THE LENGTH OF THE SHEARWALL, WHICH IS DEMONSTRATED IN NOTE 3.
© 2022
L
LTP4 SPACING
BELOW
4. AFTER FINDING THE SHEARWALL MARK ON THE PLAN AND UNDERSTANDING WHICH SIDE OF THE WALL THE SHEATHING AND NAILING IS REQUIRED, GW11 4'-6" O.C.
REFER TO THE "SHEARWALL SCHEDULE" FOR THE SHEATHING AND FASTENING REQUIREMENTS. GW12 3'-6" O.C.
GW13 3'-0" O.C. PROVIDE MID-HEIGHT BLOCKING
(2)2x4 (WHEN H £ 12'-0")
PW21 1'-4" O.C. WITH (4) 0.131" x 3" NAIL ON
H
DRAG TRUSS (2)2x6 OTHERWISE
SHEARWALL SCHEDULE EACH SIDE WHEN H > 12'-0"
TOP OF PLATE
TYPE EDGE FIELD VALUE
TOP OF PLATE
(8)0.131" x 3" NAILS
EACH SIDE (16 TOTAL)
EXTERIOR GYPSUM DRAG TRUSS
J
1
GW1 2" NO A 7" 7" 100 PLF
1
GW2 2" YES A 4" 4" 175 PLF
5 B, C, or D
GW3 8" YES 4" 7" 200 PLF SIMPSON LTP4 PER
SPACING NOTED
INTERIOR GYPSUM ABOVE ALONG ENTIRE
GW11 5 C, D, or E SHEARWALL LENGTH.
8" NO 7" 7" 115 PLF 2x10 BLOCKING
5 C, D, or E
GW12 8" NO 4" 4" 145 PLF
SIMPSON LTP4 PARTYWALL
5 C, D, or E
GW13 8" YES 4" 4" 175 PLF
BASE LAYER SPACED PER
5
8" YES C, D, or E 9" 9" SCHEDULE
GW14* 250 PLF SHEARWALL BELOW (2)SIMPSON LTP4 WITH
H
FACE LAYER A
5 SHEARWALL (2)SIMPSON A35 (OPPOSITE SIDE)
8" - F, G, or H 7" 7" -
AIRSPACE PER ARCH SHEATHING
SIDE
PLYWOOD/OSB
PW21 7
16" YES I 6" 12" 365 PLF DRAG TRUSSES OVER PARTY WALL SHEARWALLS
7
PW22 16" YES I 4" 12" 532 PLF
Gandy Residence
7
PW23 16" YES I 3" 12" 685 PLF
7
PW24 16" YES J 3" 12" 840 PLF
Lubbock, TX 79413
CLIP SPACING
FASTENERS: 2x10 BLOCKING
A. 0.120" x 1 3 4", 7 16" HEAD, DIAMOND-POINT, GALV. NAIL SHEARWALL TYPE
TOP OF PLATE
TOP OF PLATE
* GW14 IS (2) LAYERS OF 5 8" GYPSUM WALLBOARD.
DRAG TRUSS 2x10 BLOCKING
F
5. SHEARWALLS REQUIRE ANCHORAGE AT EACH END WITH EITHER A STRAP CONNECTING THE SHEARWALL ABOVE THE FLOOR CAVITY TO THE
SHEARWALL BELOW OR WITH A HOLDOWN CONNECTING THE SHEARWALL TO THE FOUNDATION. THE SHEARWALL STRAPS AND HOLDOWNS ARE SIMPSON LTP4 PER
SHOWN AT THE ENDS OF EACH WALL WITH THE FOLLOWING MARKS: S# FOR STRAPS AND HD# FOR HOLDOWNS. SPACING NOTED
ABOVE ALONG ENTIRE (2) SIMPSON A35
HOLDOWN CALLOUT AT STRAP CALLOUT AT THE SIMPSON LTP4 SHEARWALL LENGTH. (2) SIMPSON LTP4
THE END OF A SHEARWALL END OF A SHEARWALL SPACED PER
HD2 PW21 (20) S3 SCHEDULE NO SHEARWALL PARTYWALL
SHEATHING
SIDE
SECTION A
6. REFER TO THE "STRAP/HOLDOWN SCHEDULE" FOR CONSTRUCTION AND FASTENING REQUIREMENTS FOR THE NOTED STRAPS AND HOLDOWNS. DRAG TRUSS OVER INTERIOR WALL WITH SHEARWALL SHEATHING ON ONE SIDE ONLY
STRAP/HOLDOWN SCHEDULE NUMBER OF BRACES REQUIRED BRACE TRUSS BAY SPAN LENGTH
CLIP SPACING
SHEARWALL TYPE A35 & LTP4 SHEARWALL TYPE MAX. LENGTH PER TRUSS HEIGHT MIN. # OF TRUSS
STRAPS
4. STRAPS WILL BUCKLE IF ATTACHED AT BOTH ENDS
BELOW BRACE OVER SHEARWALL BAYS PER BRACE Issued For Date
PRIOR TO ALLOWING FOR WOOD SHRINKAGE AND BELOW SPACING
SIMPSON END/TOT. MIN. No. NAILS CONSTRUCTION SETTLEMENT TO OCCUR. GW11 4'-6" O.C. GW11 17'-4" 7'-0" 2 Construction 10/24/2022
MARK
D
PRODUCT LENGTH DF/SYP SPF/HF GW12 3'-6" O.C. GW12 13'-4" 10'-0" 3
S1 CS20 9"/42" (14) 0.131"x2.5" (16) 0.131"x2.5" 5. NUMBER OF NAILS SHOWN IS THE TOTAL NUMBER GW13 3'-0" O.C. GW13 10'-8" 14'-0" 4
S2 CS16 15"/54" (22) 0.131"x2.5" (26) 0.131"x2.5" OF NAILS FOR THE ENTIRE LENGTH OF THE STRAP. PW21 5'-4" 17'-0" 5
PW21 1'-4" O.C.
(30) 0.131"x2.5" (36) 0.131"x2.5" FOR THE NUMBER OF NAILS REQUIRED AT EACH DRAG TRUSS
S3 CS14 19"/62" 20'-0" 6
END, DIVIDE THE NUMBER SHOWN BY 2. THE LENGTHS SHOWN ABOVE ARE
S4 CMSTC16 25"/74" (50) 0.148"x2.5" (58) 0.148"x2.5"
FOR A SINGLE BRACE. IF THE THE NUMBER OF BAYS SHOWN
S5 CMST14 34"/92" (66) 0.148"x2.5" (76) 0.148"x2.5" 6. STRAPS S1, S2, AND S3 CAN BE ATTACHED TO THE SHEARWALL IS LONGER THAN THE ABOVE ARE A MINIMUM IN ORDER TO
S6 CNST12 44"/112" (86) 0.148"x2.5" (98) 0.148"x2.5" FACE OF A SINGLE STUD. STRAPS S4, S5, AND S6 LENGTH SHOWN, THAN ANOTHER
TOP OF PLATE
3. THE ANCHORS SHALL BE DRILLED & EPOXIED WITH SIDE ENTIRE SHEARWALL LENGTH.
STRAPS: SIMPSON SET-3G. INSTALL PER MANUFACTURER
REQUIREMENTS.
1. STRAP TOTAL LENGTHS ARE BASED ON USING 18" DRAG TRUSS OVER INTERIOR WALL WITH SHEARWALL SHEATHING ON BOTH SIDES LC Project No.: 1803.011
FLOOR TRUSSES. ADJUST THE LENGTHS AS
REQUIRED FOR DIFFERENT DEPTHS. 4. ANCHORS ARE TO BE ALL-THREAD RODS, A193, Gr.
B7 OR BETTER. Scale: None
2. END LENGTH REFERS TO THE LENGTH OF STRAP
ABOVE THE TOP OF SILL PLATE OR BELOW THE 5. ANCHOR DEPTHS TO BE DRILLED AS SHOWN BASED
ON EITHER A FOUNDATION EDGE LOCATION OR
BOTTOM OF BEARING PLATE WHEN CROSSING THE
FLOOR CAVITY. FOUNDATION INTERIOR LOCATION. Shearwall
3. LAP SPLICES ARE NOT ALLOWED WITHOUT PRIOR 6. DIFFERENT PRODUCTS AND MANUFACTURERS ARE Information
A
APPROVAL FROM THE EOR. NOT ALLOWED WITHOUT APPROVAL FROM THE
EOR.
S030
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
SHEARWALL DRAWING INFORMATION SHEET (CONTINUED) 20. FOLLOWING THE PREVIOUS INSTRUCTIONS, NOTES, SCHEDULES, AND CHARTS WILL ENSURE THAT THE SHEARWALL STACK, FROM FOUNDATION
TO ROOF DECK, IS PROPERLY CONSTRUCTED AND WILL SATISFY THE CONTINUOUS LOAD PATH REQUIREMENTS OF THE BUILDING CODE. THE
STEP3: TRANSFERING SHEAR THROUGH THE FLOOR CAVITY OVERALL SHEARWALL STACK SHOULD LOOK SIMILAR TO THIS DETAIL:
M
14. IN ORDER TO TRANSFER THE SHEAR FROM THE SHEARWALL INTO THE FLOOR DECKING, OR FROM THE SHEARWALL INTO THE FOUNDATION, THE
SHEAR BLOCK SCHEDULE
SILL PLATE MUCH BE ATTACHED WITH THE APPROPRIATE FASTENERS AT CERTAIN SPACING. USING THE TABLE BELOW, FIND THE SHEARWALL SHEARWALL LENGTH
MARK THAT THE SILL PLATE BELONGS TO AND ATTACH IT AS FOLLOWS: DRAG TRUSS 5575 Stousland Rd.
MARK 4' 6' 8' 10' 12' 14' 16' 18' 20' 22' 24' 26' 28' 30' 32' 34' 36' 38' 40' 42' 44' 46' 48'
DESIGN BY TRUSS MANUFACTURER College Station, TX 77845
NO. OF BLOCKS REQUIRED BASED ON SHEARWALL LENGTH
(832) 423-2977
GW11 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3
www.laymonconsulting.com
SILL ATTACHMENT SCHEDULE GW12 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 4 4 4 4
GW13 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 4 4 4 4 4 5 5 TX Firm # F-19205
ATTACH. TO FDN. SPA. ATTACH. TO DECK SPA.
MARK 1 GW14 2 2 2 2 2 2 2 3 3 3 3 4 4 4 4 5 5 5 5 6 6 6 6
2"Ø BOLTS 0.145"Ø PAF 8d NAIL 16d NAIL PLATES CONNECTING DRAG TRUSS TO SHEARWALL
PW21 2 2 2 2 3 3 3 4 4 4 5 5 6 6 6 7 7 7 8 8 9 9 9 RE: SCHEDULES
PW22 2 2 2 3 4 4 5 5 6 6 7 7 8 8 9 9 10 11 11 12 12 13 13
© 2022
L
GW1 48" O.C. 20" O.C. 14" O.C. 19" O.C. Laymon Consulting, LLC
PW23 2 2 3 4 5 5 6 7 7 8 9 9 10 11 11 12 13 13 14 15 16 16 17
GW2 48" O.C. 11" O.C. 8" O.C. 10" O.C. All rights reserved
PW24 2 3 4 5 5 6 7 8 9 10 11 11 12 13 14 15 16 16 17 18 19 20 21
GW3 48" O.C. 10" O.C. 7" O.C. 9" O.C. The arrangements
DETAIL depicted herein are the
GW11 48" O.C. 17" O.C. 12" O.C. 16" O.C. sole property of Laymon
(12) 0.131" x 3" NAILS
GW12 48" O.C. 13" O.C. 9" O.C. 13" O.C. (2 ROWS OF 6) 20 12" Consulting, LLC and may
not be reproduced in any
SHEARWALL
GW13 48" O.C. 11" O.C. 8" O.C. 10" O.C.
RE: PLAN
TRIMMABLE ENDS TO form without written
GW14 48" O.C. 8" O.C. 5" O.C. 7" O.C. SILL ATTACHMENT TO DECK
ALLOW FOR FIELD permission.
2,000 LBS ADJUSTMENTS RE: SCHEDULE
PW21 32" O.C. 5" O.C. 3" O.C. 5" O.C. END POST
DRAG FORCE
K
PW22 22" O.C. 3" O.C. (2)@5" O.C. 3" O.C. (3 TYPICAL, UNO)
PW23 18" O.C. 3" O.C. (2)@4" O.C. (2)@5" O.C.
PW24 14" O.C. (2)@5" O.C.* (2)@3" O.C. (2)@4" O.C.
FLOOR CAVITY
STRAP
NOTES:
RE: PLAN
1. SPACING SHOWN ABOVE IS A MAXIMUM SPACING.
TIGHTER SPACING IS ACCEPTABLE, BUT IN NO CASE
SHALL BE CLOSER THAN 3" O.C.
SHEARWALL
SILL ATTACHMENT TO FDN SHEAR BLOCK
RE: PLAN
4. PAF (POWER ACTUATED FASTENER) SHALL BE HILTI RE: SCHEDULE RE: SCHEDULE
X-CP 72 P8 S23. 2. SHEAR BLOCKS ARE TO BE SPACED EQUALLY, AS MUCH AS IS POSSIBLE, ALONG THE LENGTH OF THE
SHEARWALL.
3 END POST
5. PAF AND BOLTS SHALL BE NO CLOSER THAN 1 4"
FROM THE EDGE OF CONCRETE. 3. SHEAR BLOCKS ARE TO BE PLACED DIRECTLY OVER THE SHEARWALL, BETWEEN TRUSSES, AND ATTACHED TO (3 TYPICAL, UNO)
H
5. IF THE LENGTH SHOWN ON THE PLAN FALLS BETWEEN TWO NUMBERS SHOWN ABOVE, USE THE LARGER
Gandy Residence
LENGTH.
Lubbock, TX 79413
3 6. IF THE LENGTH SHOWN ON THE PLAN IS LONGER THAN SHOWN IN THE ABOVE CHART, CONTACT THE
1 STRUCTURAL ENGINEER OF RECORD FOR THE REQUIRED NUMBER OF SHEAR BLOCKS. SHEARWALL LENGTH
RE: PLAN
SILL PLATE
1 SPLICE 8. IF THE TOTAL NUMBER OF SHEAR BLOCKS REQUIRED EXCEEDS THE NUMBER OF SPACES BETWEEN TRUSSES
4"
PROVIDED, CONTACT THE STRUCTURAL ENGINEER OF RECORD FOR A SOLUTION. STEP 4: TRANSFERRING SHEAR AROUND OPENINGS
4" 3 1 3 4" 4" 4 1 21. THERE WILL BE INSTANCES WHERE A WINDOW OPENING OR TWO ARE WITHIN THE SHEARWALL AND INDICATED ON THE PLAN WITH "FTAO" OR
"FORCE TRANSFER AROUND OPENINGS". WHEN THIS IS SHOWN ON THE PLAN, STRAPS AND BLOCKING WILL BE REQUIRED ALONG THE LENGTH OF
1'-0" 4 1'-0" 1'-0" 3 THE SHEARWALL AT THE TOP AND BOTTOM OF THE OPENINGS. THE STRAPS REQUIRED ARE NOTED IN THE CHART BELOW.
19. BLOCKING IN THE FLOOR CAVITY NEEDS TO BE PROVIDED BETWEEN THE END POSTS OF THE WALLS ABOVE AND BELOW THE FLOOR CAVITY.
NOTES BELOW ARE A FEW SCENARIOS WHICH MAY OCCUR. 22. THE STRAPS CAN BE APPLIED OVER OR BENEATH THE PLYWOOD SHEATHING. IT MAY ALSO BE DESIRED TO ROUTE OUT THE STUDS SO AS NOT TO
HAVE A BULGE IN THE SHEATHING OR WALL FINISH.
F
SHEARWALL BELOW THE DRAG TRUSS, WHICH IS GIVEN IN THE "SHEARWALL SCHEDULE" UNDER NOTE 4, BY THE LENGTH OF THE SHEARWALL,
WHICH IS DEMONSTRATED IN NOTE 3. THIS IS THE SAME PROCESS USED TO DETERMINE THE LOAD FOR THE ROOF DRAG TRUSS AS NOTED IN
NOTE 9.
FLOOR TRUSS AWAY FLOOR TRUSS IN LINE
18. THE DRAG TRUSS SHALL BE ATTACHED TO THE TOP PLATE OF THE WALL BELOW WITH THE SAME SILL ATTACHMENT FASTENER AND SPACING AS
IS REQUIRED FOR THE SHEARWALL BELOW THE DRAG TRUSS. THIS CAN BE FOUND IN THE "SILL ATTACHMENT SCHEDULE" SHOWN IN NOTE 14. FROM END POST WITH END POST OPENING IN SHEARWALL
PROVIDE BLOCKING AT STRAP FOR THE
REQ'D LENGTH SHOWN BELOW AT THE TOP
SHEARWALL END AND BOTTOM OF THE OPENING
POST ABOVE
SHEARWALL ABOVE DRAG TRUSS
FTAO REQUIRED STRAPS
SILL PLATE
C
BEARING PLATE
SHEARWALL BELOW DRAG TRUSS
LC Project No.: 1803.011
SHEARWALL END
POST BELOW
Scale: None
S031
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
7. ONE COURSE OF BOND BEAM IS REQUIRED AT THE TOP OF ANY CMU WALL. THIS BOND BEAM IS TO BE FULLY GROUTED AND REINFORCED PER 13. SILLS SHALL UTILIZE ONLY ONE COURSE OF BOND BEAMS FULLY GROUTED AND REINFORCED WITH (2)#4 EXTENDING 24" BEYOND THE OPENINGS.
THE "CMU WALL SCHEDULE" IN NOTE 4. THE REINFORCING AT CORNERS AND INTERSECTIONS SHALL BE PER THE DETAIL BELOW. THE PROVIDE A TYPICAL HOOK IF THE MINIMUM LENGTH OF 24" IS NOT AVAILABLE.
1. CONCRETE MASONRY UNIT (CMU) WALLS SHALL BE CONSTRUCTED AS SHOWN WITHIN THIS SET OF DRAWINGS. REINFORCING FOR THIS BOND BEAM MUST STOP WITHIN 2" OF A CONTROL JOINT. SEE NOTE 14 FOR CONTROL JOINT DETAILS AND INFORMATION.
5575 Stousland Rd.
2. MATERIAL SPECIFICATIONS FOR CMU AND REINFORCING STEEL CAN BE FOUND IN THE SPECIFICATION SECTION AT THE BEGINNING OF THIS SET. LAP LENGTH College Station, TX 77845
LAP LENGTH
TOP OF SILL
RE: SCHED. RE: SCHED. (832) 423-2977
3. CMU IS SHOWN IN THE FRAMING PLANS AS THUS: BOND BEAM www.laymonconsulting.com
(2) #4 IN BOND BEAM
BREAK OUT BLOCK FULLY GROUTED
WALLS AS TX Firm # F-19205
LINTEL DESIGNATION CMU WALL DESIGNATION NECESSARY
CMU WALL VERT WALL REINF.
L-1 MW-1 L-1 © 2022
RE: SCHED
L
9. THE CMU WALL MUST CONTAIN BOND BEAMS SPACED NO MORE THAN 48" O.C. THESE BOND BEAMS SHALL BE FULLY GROUTED AND REINFORCED BOND BEAM
NOTE:
1. B.B. = BOND BEAM PER THE "CMU WALL SCHEDULE" IN NOTE 4. THE REINFORCING AT CORNERS AND INTERSECTIONS SHALL BE PER THE DETAIL IN NOTE 7 ABOVE.
THE REINFORCING FOR THIS BOND BEAM MUST STOP WITHIN 2" OF A CONTROL JOINT. SEE NOTE 14 FOR CONTROL JOINT DETAILS AND
2. CELL GROUT REFERS TO THE GROUTING INFORMATION.
REQUIREMENTS OF THE CELLS: ONLY AT REINFORCED
CELLS (RC) OR AT EVERY CELL (EC). 10. HORIZONTAL JOINT REINFORCING MUST BE PLACED AT EVERY OTHER JOINT (16" O.C.). THIS SHALL BE GALVANIZED 9GA WIRE REINFORCING,
EITHER LADDER TYPE OR TRUSS TYPE. LEGS MUST BE BENT AND LAPPED 12" AT WALL CORNERS AND INTERSECTIONS. SEE DETAILS IN NOTE 11
STRUCTURAL REINF SHALL
3. CELL GROUT REQUIREMENTS ARE STRUCTURAL BELOW.
CONTINUE THROUGH THE
REQUIREMENTS ONLY. ARCHITECT MAY HAVE MORE CONTROL JOINT
STRINGENT REQUIREMENTS. SEE ARCHITECTURAL 11. WALL INTERSECTIONS MAY BE ACHIEVED BY GROUTING THE WALL CELLS TOGETHER OR BY USING RIGID PARTITION ANCHORS SPACED AT 32" O.C.
DRAWINGS. BOND BEAM REINFORCING THROUGH
H
LAP LEGS 12" (TYP) LAP LEGS 12" (TYP) CONTROL JOINT @ FLOOR/ROOF
5. WITHIN EACH WALL COULD BE OPENINGS FOR DOOR AND WINDOWS. THESE OPENINGS WILL REQUIRE LINTELS DESIGNED AND CONSTRUCTED TO ℄ JOINT
CARRY THE DEAD AND LIVE LOADS OVER THE OPENINGS. THE FOLLOWING SCHEDULE INDICATES THE LINTEL CONSTRUCTION REQUIRED FOR
Gandy Residence
EACH LINTEL DESIGNATION SHOWN ON THE PLANS. TYP VERT REINF. VERT CONTROL JOINT, OMIT
RE: SCHED MORTAR, CAULK PER ARCH
Lubbock, TX 79413
TYP VERT REINF. BREAK OUT
CMU LINTEL SCHEDULE RE: SCHED WALL AND FILL
BOTH CELLS TERMINATE INTERMEDIATE
2. PROVIDE STANDARD HOOK FOR TOP REINFORCEMENT. BOND BEAM REINFORCING THROUGH
CONTROL JOINT @ ALL OTHER LOCATIONS
3. PROVIDE (1) #6 VERTICAL FOR THE FULL DEPTH OF THE
LINTEL IN EACH CALL ACROSS THE FULL BEARING
LENGTH AT EACH END.
LAP LEGS 12" (TYP) LAP LEGS 12" (TYP) ℄ JOINT
6. THE FULL CONSTRUCTION OF A CMU WALL IS SHOWN GRAPHICALLY BELOW. EACH PORTION OF THE WALL IS MARKED WITH A NOTE NUMBER ON VERT CONTROL JOINT, OMIT
TYP VERT REINF.
THIS SHEET TO EXPLAIN MORE FULLY THE DETAIL AND CONSTRUCTION FOR THAT MARKED PORTION OF THE WALL. TYPICAL WALL REINFORCING MORTAR, CAULK PER ARCH
RE: SCHED
E
AS CALLED FOR IN THE "CMU WALL SCHEDULE" ABOVE IS NOT SHOWN FOR CLARITY. CONTACT THE STRUCTURAL ENGINEER OF RECORD SHOULD
YOU HAVE ANY QUESTIONS REGARDING THIS WALL CONSTRUCTION.
TYP VERT REINF. TYP VERT REINF.
RE: SCHED BREAK OUT SIDE RE: SCHED
℄ CONTROL JOINT AND MIDDLE
WALLS AND FILL
FULLY GROUTED ALL THREE CELLS FULLY GROUTED PROVIDE CLOSED END BLOCKS TERMINATE LADDER REINF
NOTE 7 CELLS AT ALL RIGID PARTITION CELLS AT ALL AT CONTROL JOINT (TYP) 2" FROM CONTROL JOINT
VERT. REINF. ANCHOR @ 32" O.C. VERT. REINF.
NOTE 14 VERTICAL HEIGHT Issued For Date
T/WALL
HORIZONTAL JOINT REINFORCING Construction 10/24/2022
D
INTERSECTING WALLS W/ OFFSET CELLS RIGID PARTITION ANCHOR @ INTERSECTING WALLS 15. LAP SPLICE AND DEVELOPMENT LENGTH FOR REBAR WITHIN CMU WALLS SHALL BE AS FOLLOWS:
WALL NOTE 9
CORNER NOTE 14
REINFORCING LAP
SIZE LENGTH
#4 24"
C
#5 30"
4'-0" MAX
12. LINTELS SHALL BE REINFORCED PER THE "CMU LINTEL SCHEDULE" AND FULLY GROUTED TO THE DEPTH SHOWN IN THE "CMU LINTEL SCHEDULE". #6 36"
NOTE 12 NOTE 12 LINTEL REINFORCING SHALL EXTEND BEYOND THE OPENINGS FOR THE BEARING LENGTH DISTANCE CALLED FOR IN THE "CMU LINTEL SCHEDULE." #7 42"
NOTE 9 PLEASE NOTICE THE NOTE IN THE "CMU LINTEL SCHEDULE" REFERENCING THE NEED FOR ADDITIONAL VERTICAL REBAR ALONG THE BEARING #8 48"
LENGTH FOR LINTELS REQUIRING TOP REINFORCING.
NOTE 13 FULLY GROUTED
CELLS AT VERT
REINF
4'-0" MAX
RE: SCHED
HEADER HEIGHT
HEADER HEIGHT
HEADER HEIGHT
GROUT
T/FTG OR SLAB LINTEL LC Project No.: 1803.011
D
SOLID
SHEAR REINF.
D
NOTE
W W W
90° AND PARALLEL Information
A
TO WALL
TYPICAL WALL REINFORCING IS NOT SHOWN FOR CLARITY. REFERENCE THE "CMU WALL SCHEDULE" ABOVE FOR THE REQUIRED
REINFORCING SIZE AND SPACING
TYP LINTEL LINTEL W/ SHEAR REINFORCING VERT WAL REINF @ LINTEL
S040
M 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
TX Firm # F-19205
© 2022
L
1'-712"
1'-0"
1'-0"
2'-0"
2'-0"
1'-0"
1'-0"
J
4'-712"
1'-0"
2'-0"
2'-0"
2'-712"
3'-0"
3'-512"
2'-0"
1'-0"
712"
2"
512"
10'-10"
10'-41
9'-412"
2'-0"
2"
16'-512"
8'-41
7'-412"
7'-914"
14'-512"
8"
H
9'-25
9'-214"
2"
12'-51
2'-6" 5'-6"
7" 1'-5"
1'-51 4" 4'-03 4"
Gandy Residence
2"
1'-5"
51
Lubbock, TX 79413
2'-73 8"
4'-03 4"
512"
6'-43 8"
8"
37'-412"
37'-412"
9'-15
1'-514"
1'-0"
1'-1012"
5'-1"
32'-9"
8'-0"
8"
3'-27
1'-0"
NOTE: 6'-43 8" 8'-218" 2'-812"
1'-0"
5'-1012" SEE ARCH FOR SLAB DROPS, SLOPES, AND
19'-0"
F
1'-7"
1'-0"
24'-1012" ARCH PRIOR TO PLACING CONCRETE.
4"
6'-93
20'-11"
20'-0"
2'-0"
16'-87 8"
13'-6"
1'-212"
8'-0"
10'-6"
E
612"
7'-7"
914"
512" 33 4"
Construction 10/24/2022
D
Slab Forming
Plan
A
S101
M 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
TX Firm # F-19205
© 2022
L
13
S401
J
6
S401 CMU PLAN NOTES:
1. ALL CMU TO BE 8"x8"x16" BLOCK.
RB-1
RB-2 RB-2 RB-2 RB-2 RB-1
2. SEE S040 FOR ADDITIONAL CMU INFORMATION.
RB-1
REINFORCING 5. VENT WIDTHS TO BE A MAXIMUM OF 32" WIDE.
7'-95 8"
REINFORCING S401
RB-2
RB-2
RB-2
H
RB-2
RB-1
2
RB-1
S401 RB-2
RB-1
RB-2
13
2
B-
Gandy Residence
S401
R
9
1
B-
1
Lubbock, TX 79413
B-
R
S401
1
R
F-
5
2
B-
RB-1 S401
R
7'-95 8"
RB-2
RB-2
RB-2
RB-2
G
B-
S401
1
3
B-
2
B-
R
S401
RB-1 R
RB-2
RE: 15/S401
RB-2
R
B-
2
R
B-
2
2
B-
R
10'-512"
13
B-
RB-1
RB-1
7 S401
S401 17
S401
RB-2
4 7'-95 8" RE: S010 FOR SLAB
F
11 THICKNESS AND
RB-2
RB-2
RB-2
RB-2
RB-2
S401
S401 REINFORCING RB-1
RB-1
RB-2
RB-1 RB-1
RB-1
EXTEND BOND BEAM
REBAR 30" INTO SLAB
RB-2
RB-1
RB-1 RB-1
18
12 16 S401
RB-1
S401 RB-1 S401
RB-1
RB-1
RB-1
10'-512"
RB-1
E
RB-2
RB-2
RB-2
RB-2
RB-2
8'-514"
RB-1
10
7'-012"
5'-712"
S401 RE: S010 FOR SLAB
RB-1
THICKNESS AND
REINFORCING
13'-0" 13'-9" 10'-93 4" 8'-512" 8'-512" 10'-13 4" 10'-11" 13'-5"
C
B
Foundation
Plan
A
S102
M 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
TX Firm # F-19205
© 2022
L
6
S401
3212
3212
3212
H
SLAB-ON-GRADE
SLAB-ON-GRADE
Gandy Residence
Lubbock, TX 79413
" O.C.
3212
3212
G
" O.C.
" O.C.
" O.C.
" O.C.
EATED) @ 16
3212
3212
EATED) @ 16
EATED) @ 16
EATED) @ 16
EATED) @ 16
3212
R
2x12 SYP #2 (T
R
R
7
2x12 SYP #2 (T
2x12 SYP #2 (T
2x12 SYP #2 (T
2x12 SYP #2 (T
S401 17
S401
3212
3212
3212
3212
3212
" O.C.
F
REATED) @ 16
SLAB-ON-GRADE
2x12 SYP #2 (T
16 SLAB-ON-GRADE
S401
E
3212
3212
3212
3212
3212
Issued For Date
FIELD FRAME STAIRS
Construction 10/24/2022
D
C
B
1st Floor
Framing Plan
A
S201
M 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
TX Firm # F-19205
© 2022
L
6x10 CEDAR #2
6x10 CEDAR #2
328
H
328
17
S402 328
326
Gandy Residence
Lubbock, TX 79413
8
226
226
32
32
10
10
32
326
3212
228
3212
6
22
F
226 226
326
E412
6x10 CEDAR #2
O.C.
#2 @ 16" 228
2x12 SYP
326
SUPPORT BEAM ON CORBELS
226
326
3212
E
228
Ceiling Joist
Framing Plan
A
S202
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
CEILING JOISTS
1. ALL CEILING JOISTS SHALL BE 2x8 SYP #2 @ 16" O.C.,
UNLESS NOTED OTHERWISE. 5575 Stousland Rd.
College Station, TX 77845
2. ATTACH CEILING JOISTS TO RAFTERS WITH (8) 16d (832) 423-2977
COMMON NAILS. www.laymonconsulting.com
ROOF RAFTERS
7. ALL ROOF RAFTERS SHALL BE 2x6 SYP #2 @ 16" O.C.,
UNLESS NOTED OTHERWISE.
2x6 @16" O.C. PONY WALL
8. ATTACH ROOF RAFTERS TO BEARING PLATES WITH
BETWEEN BOTTOM OF RAFTERS RE: 11/S402
8 6 8 SIMPSON H2.5A HURRICANE CLIPS.
AND TOP OF CEILING JOIST BELOW.
J
RIDGE BEAM
THE CUT END OF THE RAFTER, UNLESS NOTED
OTHERWISE.
O.C.
O.C.
11. COLLAR TIES SHALL NOT BE LESS THAN 1x4 AND
O.C.
H
#2 @ 16"
#2 @ 16"
24" OF THE RIDGE.
#2 @ 16"
E412
17 12. PROVIDE A CS20x48" LONG AT 48" O.C. MAXIMUM
2x10 SYP
2x8 SYP
2x10 SYP
6 THE TOPS OF OPPOSING RAFTERS.
Gandy Residence
RIDGE BEAM
S402
13. ROOF BRACING SHALL BE PROVIDED IN THE
Lubbock, TX 79413
FOLLOWING MANNER:
E616
WITH PURLIN BRACES AT 4'-0" O.C.
PURLINS C. ALONG ALL HIPS AND VALLEYS AT 8'-0" O.C.
D. ALONG ALL RIDGES AT 4'-0" O.C., UNLESS
O.C.
O.C.
HIP
3'-0"
#2 @ 16"
#2 @ 16"
HIP
PURLINS 9. PURLINS SHALL NOT BE SMALLER THAN THE
RIDGE 6
SUPPORTED RAFTER AND SHALL MATCH THE
S402
EY
SUPPORTED RAFTER IN SPECIES AND GRADE.
HIP
2x10 SYP
2x10 SYP
LL
PURLINS SHALL BE BRACED WITH 2x4 SYP #2 PURLIN
VA
BRACES SPACED NO MORE THAN 4'-0" O.C. AND
SLOPED NO GREATER THAN 45° FROM THE VERTICAL.
RIDGE
F
(2)2x BLOCKING 10. ROOF BRACING MAY ONLY BEAR UPON BEAMS AND
TOP PLATES OF WALLS. DO NOT BRACE UPON
(2) RAFTER CEILING JOISTS OR STRONG BACKS UNLESS
DESIGNATED AS A BRACE DESIGN SUPPORT.
RIDGE
11. DO NOT SUPPORT MASONRY ON RAFTERS.
(2) RAFTER
12. CHIMNEY WALLS SHALL BE CONSTRUCTED THROUGH
HIP
PURLINS
THE RAFTERS AND SUPPORTED ON WALLS OR BEAMS
7 BELOW AND SHALL NOT BE SUPPORTED AND
S402 CONSTRUCTED ON TOP OF THE RAFTERS.
E
RIDGE
6
6 7 S402
S402 S402
C
B
Roof Rafter
Framing Plan
A
S203
M 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
TX Firm # F-19205
© 2022
L
S4 PW21 S4 S4 PW21 S4
S5 PW23 S5
S5
S4
PW23
H
PW23
GW13
GW13
S4
Gandy Residence
S5
Lubbock, TX 79413
PW23
S4
S4
S4
F
PW23
S4
SIMPSON WSWH24X10
STRONG-WALL
S4
E
S5 PW23 S5
PW23
PW23
S4
NONE PW21 NONE Issued For Date
Construction 10/24/2022
D
C
B
Shearwall
Plan
A
S301
M 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
FOOTING
ROOF RAFTER
#4 NOSING
5575 Stousland Rd.
ROOF DECKING
SCHED.
College Station, TX 77845
DEPTH
(832) 423-2977
SCHED. DEPTH
(8) 0.131" x 3" NAILS
SCHED. DEPTH
www.laymonconsulting.com
PL. HT.
TX Firm # F-19205
LINE
PLATE
SCHED. REINF. SCHED.
VERIFY
SCHED. DEPTH
WIDTH
FIELD
SCHED. © 2022
L
RE: SECTION 6
FOR INFORMATION FOR INFORMATION
FOR INFORMATION
NOT SHOWN NOT SHOWN
NOT SHOWN
SIMPSON
1 MSTAM36 1 18" FLOOR DECKING 2 3 4 5
@ 32" O.C.
2x12 JOISTS
WOOD BEAM
FLOOR DECKING RE: PLAN
(2) 2x12
TREATED
RIM JOIST SIMPSON LUS210
#4 NOSING
J
SLAB THICK.
1 12" x 5 12"
SLAB REINF. RE: S010
RE: S010
PLACE TERMITE BRICKLEDGE BRICKLEDGE
SLAB THICK.
RE: S010 DOOR POCKET
FIN FL
SHIELD ON TOP
RE: S010
SLAB THICK.
1'-6" MIN.
RE: S010
OF CMU
VARIES
SLOPE
SLAB REINF.
FIN FL
FIN FL
RE: S010
8"
FLOOR JOIST
(4)#5 WITH FULLY
RE: PLAN
SCHED. DEPTH
GROUTED CELLS
8"
8"
SCHED. DEPTH
TERMITE SHIELD
SCHED. DEPTH
SCHED. DEPTH
1'-6" MIN
1'-6" MIN
1'-6" MIN
1'-6" MIN
COMPACTED BUILDING PAD
SCHED.
3"
BARRIER TO REDUCE
Gandy Residence
3"
SCHED. REINF.
3"
MOISTURE AND MOLD
SCHED. WIDTH 3" SCHED. REINF.
POTENTIAL TO THE
Lubbock, TX 79413
3"
6 7 8 9 10
SEE ARCH
#4 x 20" DOWELS @ 18" O.C.
SEE ARCH DRILL & EPOXY 8" INTO
FOUNDATION WITH SIMPSON 1'-35 8"
F
SET-3G EPOXY.
SLAB THICK
VARIES
RE: S010
FIN FL
SLAB REINF.
RE: S010
SLAB THICK.
#4 NOSING (TYP)
RE: S010
#5 IN THE CENTER OF
EACH CELL WITH FULLY
SLAB REINF.
FIN FL
GROUTED CELLS
RE: S010
SCHED. DEPTH
SLOPE
CONCRETE
AND PAVERS
3"
BY OTHERS
1'-0"
1'-35 8"
E
6"
COMPACTED BUILDING PAD
3"
#4 @ 18" O.C. EW
(2) #5 CONT.
3"
COMPACTED
1'-0"
11 12 13 15
SLAB THICK.
RE: S010
2x12 2x12
SLAB REINF.
FIN FL
RE: S010
8"
SCHED. DEPTH
SIMPSON LUS210
B
1'-6" MIN
16 17 18 S401
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
HR MAX.
2x4 COLLAR TIES
@ 4'-0" O.C. MAX
M
3
1
5575 Stousland Rd.
STAGGER 6" FROM College Station, TX 77845
3" 11 2"
SEE PLANS AND NOTES OPPOSITE SIDE INTERSECTING BEAM (832) 423-2977
FOR RAFTER SIZES
2"
2"
2"
2"
2"
www.laymonconsulting.com
ONLY BEAR POSTS ON CEILING JOIST
HR
SPAN WHERE NOTED ON THE PLANS
EQ
PURLIN SAME SIZE TX Firm # F-19205
AS RAFTER
HR MIN.
EQ
(2)2x6 STRONGBACK CONT.
TO DISTRIBUTE LOAD TO © 2022
L
2"
2"
2"
2"
2"
3
SIMPSON H2.5A O.C. DOWN TO TOP 0.131" x 3" NAIL All rights reserved
2
1 SUPPORTING BEAM
@ EACH RAFTER OF BEARING WALL @ 12" O.C. 2"Ø
THROUGH
0.131" x 3" NAIL BOLT W/ WASHERS The arrangements
@ 12" O.C. @ 16" O.C. SIMPSON SDS25600 depicted herein are the
sole property of Laymon
2-PLY CONNECTION 3-PLY CONNECTION 4-PLY+ CONNECTION ADDITIONAL CONNECTION AT INTERSECTING BEAMS Consulting, LLC and may
not be reproduced in any
LINE LINE
PLATE PLATE
1 4
J
ROOF DECKING
Gandy Residence
EXTERIOR SHEATHING
SIMPSON SP-2 @
EVERY OTHER STUD ROOF DECKING
Lubbock, TX 79413
ROOF DECKING
EXTERIOR WALL
6x10 CEDAR BEAM
ROOF RAFTER
RIDGE
BEAM
6 7 8
6x10 CEDAR BEAM
SIMPSON SDS25800
(2) INTO EACH BEAM
ROOF RAFTERS
6x10 CEDAR BEAM
SIMPSON SDS25800
6x10
CEDAR
BEAM LINE
PLATE
11
(5) 0.131"x3" NAILS
EXTERIOR WALL
EXTERIOR
SHEATHING FLOOR DECKING
PONY WALL
RIM JOIST
ROOF DECKING
B
LINE
PLATE
BEARING WALL
SIMPSON H2.5A
EXTERIOR SHEATHING
EXTERIOR WALL Framing
Sections
A
WOOD BEAM
RE: PLAN
17 S402