You are on page 1of 5

Preliminary Load Calculation

Total Area Cooling load


(GFA) density Cooling load
Floor m 2
W/m2 kW TR
Total GFA 32,000 110 3,520 1,001

Total Cooling Load 3,520 1,001

Safety Factor 10% 3,872 1,101

Considering diversity 85% 3,291 936

Estimated Number of heat exchangers 2

Estimated Number of Chilled water pumps 2 +1

Estimated flow rate of each pump Delta T = 9.0°C 702 GPM


Estimated flow rate of each pump Delta T = 9.0°C 44.3 LPS

Estimated power for each pump 21 KW


454.56
72.73
72.73
72.73
869.73
12960.75
22.05

14525.28

You might also like