ISSUED FOR ADDENDUM

NOTE:
THIS MAIN SCHEMATIC FOR CONCEPT AND
EQUIPMENT QUANTITY REFERENCE.

ROOF 4
PP-RF-SL-01
MTS
[PHASE 1]

FROM TOU-SDP-G-B
MAIN ELECTRICAL SCHEME ( TOTAL 12 MW IT LOAD) FROM SDP-G-A
PP-RF-PL-01 [PHASE 1]
MTS

ROOF 4
EQUIPMENT DETAILS TO BE REFERRED TO
RESPECTIVE SINGLE LINE DIAGRAM.
TO PP-RF-PL-01 TO PP-RF-SL-01
Cooling Tower-5

Cooling Tower-1 Cooling Tower-4 Cooling Tower-2


LP-RF-A PP-RF-AC-A1 PP-RF-AC-B2 LP-RF-B
Cooling Tower-3

PP-RF-AC-A3 PP-RF-AC-B4
ROOF 2
T2 ROOF 2

LP-L3-DH-A1 LP-L3-DH-B2
CABLE TOU (TAP-OFF-UNIT)
LP-L3-DH-A3 LP-L3-DH-B4
PDU-L3-B6-3-12
WITH ISOLATION MCCB
PDU-L3-A5-3-11
TO 9 NOS. DATA HALL 3-1 FWU LP-L3-A LP-L3-B TO 9 NOS. DATA HALL 3-1 FWU
TO 5 NOS. DATA HALL 3-1 DEHUM TO 5 NOS. DATA HALL 3-1 DEHUM
PDU-L3-B6-3-10
PDU-L3-A5-3-09
PP-L3-AC-A

PDU-L3-A5-2-07 3 MW PDU-L3-B6-2-08
PP-L3-AC-B

PP-FWU-L3-A1 PP-U-L3-A PP-U-L3-B PP-FWU-L3-B2


(PHASE 3) PDU-L3-A5-2-05 PDU-L3-B6-2-06 (PHASE 3)

PDU-L3-A5-1-03
DATA HALL 3-1 PDU-L3-B6-1-04
IDFA-L3-A1 IDFA-L3-B2
PDU-L3-A5-1-01 (PHASE 3) PDU-L3-B6-1-02

IDFB-L3-A3 IDFB-L3-B4
PDU-L3-A7-3-11 PDU-L3-B8-3-12

PDU-L3-A7-3-09 PDU-L3-B8-3-10
IDFC-L3-A5 IDFC-L3-B6
TO 9 NOS. DATA HALL 3-2 FWU
TO 5 NOS. DATA HALL 3-2 DEHUM

PDU-L3-A7-2-07 3 MW PDU-L3-B8-2-08
TO 9 NOS. DATA HALL 3-2 FWU
TO 5 NOS. DATA HALL 3-2 DEHUM

IDFD-L3-A7 PDU-L3-A7-2-05 PDU-L3-B8-2-06 IDFD-L3-B8

JULY 2022
PP-FWU-L3-A3
(PHASE 4) PDU-L3-A7-1-03
DATA HALL 3-2 PDU-L3-B8-1-04
PP-FWU-L3-B4

(PHASE 4)

PDU-L3-A7-1-01
(PHASE 4) PDU-L3-B8-1-02

(LEVEL 3 )
LEVEL 3 LEVEL 3

LP-L2-DH-A1 LP-L2-DH-B2
TO 9 NOS. DATA HALL 2-1 FWU TO 9 NOS. DATA HALL 2-1 FWU
TO 5 NOS. DATA HALL 2-1 DEHUM TO 5 NOS. DATA HALL 2-1 DEHUM
LP-L2-DH-A3 LP-L2-DH-B4

LP-L2-A
PDU-L2-A1-3-11
[PHASE 1A] 1 MW PDU-L2-B2-3-12
[PHASE 1A]
LP-L2-B

PP-FWU-L2-A1 PP-L2-AC-A
PDU-L2-A1-3-09
[PHASE 1A] (PHASE 1A) PDU-L2-B2-3-10
[PHASE 1A]
PP-L2-AC-B PP-FWU-L2-B2

(PHASE 1) (PHASE 1)
PDU-L2-A1-2-07 PDU-L2-B2-2-08

PP-U-L2-A
PDU-L2-A1-2-05
2 MW PDU-L2-B2-2-06
PP-U-L2-B

PDU-L2-A1-1-03
DATA HALL 2-1 PDU-L2-B2-1-04
IDFA-L2-A1 IDFA-L2-B2
PDU-L2-A1-1-01 (PHASE 1) PDU-L2-B2-1-02

IDFB-L2-A3 IDFB-L2-B4
PDU-L2-A3-3-11 PDU-L2-B4-3-12

PDU-L2-A3-3-09 PDU-L2-B4-3-10
IDFC-L2-A5 IDFC-L2-B6

TO 9 NOS. DATA HALL 2-2 FWU


TO 5 NOS. DATA HALL 2-2 DEHUM
PDU-L2-A3-2-07 3 MW PDU-L2-B4-2-08 TO 9 NOS. DATA HALL 2-2 FWU
TO 5 NOS. DATA HALL 2-2 DEHUM

IDFD-L2-A7 PDU-L2-A3-2-05 PDU-L2-B4-2-06 IDFD-L2-B8

PDU-L2-A3-1-03
DATA HALL 2-2 PDU-L2-B4-1-04
PP-FWU-L2-A3 PP-FWU-L2-B4
TO GEN-L2-CH-2-MTS TO GEN-L2-CH-1-MTS
(PHASE 2) (PHASE 2)

[PHASE 1]
TO GEN-L2-CH-4-MTS PDU-L2-A3-1-01
(PHASE 2) PDU-L2-B4-1-02 TO GEN-L2-CH-3-MTS

[PHASE 1]
GEN-L2-CH-1 [PHASE 2] [PHASE 3] GEN-L2-CH-2
0.4kV/2.25MVA GEN-L2-CH-3 GEN-L2-CH-4 0.4kV/2.25MVA
TO GEN-L2-CH-1-MTS 0.4kV/2.5MVA
(LEVEL 2 ) 0.4kV/2.5MVA TO GEN-L2-CH-2-MTS

G G G G
TO GEN-L2-CH-3-MTS TO GEN-L2-CH-4-MTS

LEVEL 2 LEVEL 2

T2 ADDENDUM 2 07/2022 ZTW


T1 ISSUED FOR TENDER 05/2022 ZTW

Rev Description Date By

Client:

LOAD BANK
CONNECTION
LOAD BANK
CONNECTION
LOAD BANK
CONNECTION
LOAD BANK
CONNECTION
LOAD BANK
CONNECTION
LOAD BANK
CONNECTION
LOAD BANK
CONNECTION
LOAD BANK
CONNECTION
PT. DATACENTER INDONESIA
SUKSES MAKMUR
Jalan Prof. Doktor Soepomo, SH nomor 2
UDB-G-A5-2
[PHASE 3]
UDB-G-A7-2
[PHASE 4]
UDB-G-A1-2
[PHASE 1]
UDB-G-A3-2
[PHASE 2]
UDB-G-B4-2
[PHASE 2]
UDB-G-B2-2
[PHASE 1]
UDB-G-B8-2
[PHASE 4]
UDB-G-B6-2
[PHASE 3]
RT 010, RW 15, Kel. Menteng Dalam, Kec. Tebet
LOAD BANK
CONNECTION
LOAD BANK
CONNECTION
LOAD BANK
CONNECTION
LOAD BANK
CONNECTION
LOAD BANK
CONNECTION
LOAD BANK
CONNECTION
LOAD BANK
CONNECTION
LOAD BANK
CONNECTION
LOAD BANK
CONNECTION
LOAD BANK
CONNECTION
LOAD BANK
CONNECTION
LOAD BANK
CONNECTION
LOAD BANK
CONNECTION
LOAD BANK
CONNECTION
LOAD BANK
CONNECTION
LOAD BANK
CONNECTION
Jakarta Selatan
Project Manager

UDB-G-A5-3
[PHASE 3]
UDB-G-A5-1
[PHASE 3]
UDB-G-A7-3
[PHASE 4]
UDB-G-A7-1
[PHASE 4]
UDB-G-A1-3
[PHASE 1A]
UDB-G-A1-1
[PHASE 1]
UDB-G-A3-3
[PHASE 2]
UDB-G-A3-1
[PHASE 2]
UDB-G-B4-1
[PHASE 2]
UDB-G-B4-3
[PHASE 2]
UDB-G-B2-1
[PHASE 1]
UDB-G-B2-3
[PHASE 1A]
UDB-G-B8-1
[PHASE 4]
UDB-G-B8-3
[PHASE 4]
UDB-G-B6-1
[PHASE 3]
UDB-G-B6-3
[PHASE 3] PT. DATACENTER INDONESIA
UPS-G-A5-3 UPS-G-A5-2 UPS-G-A5-1 UPS-G-A7-3 UPS-G-A7-2 UPS-G-A7-1 UPS-G-A1-3 UPS-G-A1-2 UPS-G-A1-1 UPS-G-A3-3 UPS-G-A3-2 UPS-G-A3-1 UPS-G-B4-1 UPS-G-B4-2 UPS-G-B4-3 UPS-G-B2-1 UPS-G-B2-2 UPS-G-B2-3 UPS-G-B8-1 UPS-G-B8-2 UPS-G-B8-3 UPS-G-B6-1 UPS-G-B6-2 UPS-G-B6-3
SUKSES MAKMUR
1200kVA / 1080 kW
(EOL 10 MIN)
1200kVA / 1080 kW
(EOL 10 MIN)
1200kVA / 1080 kW
(EOL 10 MIN)
1200kVA / 1080 kW
(EOL 10 MIN)
1200kVA / 1080 kW
(EOL 10 MIN)
1200kVA / 1080 kW
(EOL 10 MIN)
1200kVA / 1080 kW
(EOL 10 MIN)
1200kVA / 1080 kW
(EOL 10 MIN)
1200kVA / 1080 kW
(EOL 10 MIN)
1200kVA / 1080 kW
(EOL 10 MIN)
1200kVA / 1080 kW
(EOL 10 MIN)
1200kVA / 1080 kW
(EOL 10 MIN)
1200kVA / 1080 kW
(EOL 10 MIN)
1200kVA / 1080 kW
(EOL 10 MIN)
1200kVA / 1080 kW
(EOL 10 MIN)
1200kVA / 1080 kW
(EOL 10 MIN)
1200kVA / 1080 kW
(EOL 10 MIN)
1200kVA / 1080 kW
(EOL 10 MIN)
1200kVA / 1080 kW
(EOL 10 MIN)
1200kVA / 1080 kW
(EOL 10 MIN)
1200kVA / 1080 kW
(EOL 10 MIN)
1200kVA / 1080 kW
(EOL 10 MIN)
1200kVA / 1080 kW
(EOL 10 MIN)
1200kVA / 1080 kW
(EOL 10 MIN)
Jalan Prof. Doktor Soepomo, SH nomor 2
[PHASE 3] [PHASE 3] [PHASE 3] [PHASE 4] [PHASE 4] [PHASE 4] [PHASE 1A] [PHASE 1] [PHASE 1] [PHASE 2] [PHASE 2] [PHASE 2] [PHASE 2] [PHASE 2] [PHASE 2] [PHASE 1] [PHASE 1] [PHASE 1A] [PHASE 4] [PHASE 4] [PHASE 4] [PHASE 3] [PHASE 3] [PHASE 3] RT 010, RW 15, Kel. Menteng Dalam, Kec. Tebet
Jakarta Selatan

ATS ATS ATS ATS ATS ATS ATS ATS ATS ATS ATS ATS ATS ATS ATS ATS
Architects:
[PHASE 1]

[PHASE 2]

[PHASE 2]
USB-G-A5 USB-G-A7 USB-G-A1 USB-G-A3 USB-G-B4 USB-G-B2 USB-G-B8 USB-G-B6
[PHASE 4]

[PHASE 3]
[PHASE 4]
[PHASE 3] [PHASE 4] [PHASE 1] [PHASE 2] [PHASE 2] [PHASE 1] [PHASE 4] [PHASE 3]

6300A 3P3W+50%E IP66 BUSDUCT 6300A 3P3W+50%E IP66 BUSDUCT 6300A 3P3W+50%E IP66 BUSDUCT 6300A 3P3W+50%E IP66 BUSDUCT
[PHASE 1]
P T. Esenef
RUMAH INDONET
jl.Rempoa Raya no.11
[PHASE 3] [PHASE 3]
6300A 3P3W+50%E IP66 BUSDUCT 6300A 3P3W+50%E IP66 BUSDUCT 6300A 3P3W+50%E IP66 BUSDUCT 6300A 3P3W+50%E IP66 BUSDUCT 6300A 3P3W+50%E IP66 BUSDUCT 6300A 3P3W+50%E IP66 BUSDUCT Tangerang 15412
tel. 73882525
[PHASE 3]

[PHASE 1]

[PHASE 1]

[PHASE 3]
LB CONNECTION

LB CONNECTION

LB CONNECTION

LB CONNECTION

LB CONNECTION
20/0.4 kV 20/0.4 kV 20/0.4 kV 20/0.4 kV 20/0.4 kV 20/0.4 kV 20/0.4 kV 20/0.4 kV
TRF-G-A5
4.0 MVA
TRF-G-A7
4.0 MVA
TRF-G-A1
4.0 MVA
TRF-G-A3
4.0 MVA
TRF-G-B4
4.0 MVA
TRF-G-B2
4.0 MVA
TRF-G-B8
4.0 MVA
TRF-G-B6
4.0 MVA
Structure :
TO GEN-G-8-MTS [PHASE 3] [PHASE 4] [PHASE 1] [PHASE 2] [PHASE 2] [PHASE 4] [PHASE 3] TO GEN-G-8-MTS
[PHASE 1]
TO GEN-G-7-MTS TO GEN-G-7-MTS

TO GEN-G-6-MTS
CPG-G-1 CPG-G-3 CPG-G-RS CPG-G-4 CPG-G-2 TO GEN-G-6-MTS
PT. PERKASA CARISTA ESTETIKA
[PHASE 3]
TO GEN-G-5-MTS
[PHASE 1] [PHASE 1] [PHASE 4] [PHASE 2] TO GEN-G-5-MTS C O N S U L T I N G E N G I N E E R S
TO GEN-G-4-MTS TO GEN-G-4-MTS

TO GEN-G-3-MTS TO GEN-G-3-MTS
0.4kV/2.25MVA 0.4kV/2.25MVA 0.4kV/2.25MVA 0.4kV/2.25MVA 0.4kV/2.25MVA 0.4kV/2.25MVA 0.4kV/2.25MVA 0.4kV/2.25MVA 0.4kV/2.25MVA 0.4kV/2.25MVA
TO GEN-G-2-MTS GEN-G-1 G G GEN-G-2 GEN-G-5 G G GEN-G-6 GEN-G-RS-1 G G GEN-G-RS-2 GEN-G-7 G G GEN-G-8 GEN-G-3 G G GEN-G-4 TO GEN-G-2-MTS
[PHASE 1] [PHASE 3] [PHASE 3] [PHASE 1] [PHASE 1] [PHASE 4] [PHASE 4] [PHASE 2] [PHASE 2]
[PHASE 1]
TO GEN-G-1-MTS TO GEN-G-1-MTS

TO GEN-G-RS-1-MTS TO GEN-G-RS-1-MTS

TO GEN-G-RS-2-MTS TO GEN-G-RS-2-MTS

M&E Consultant:
SPARE

SPARE

[PHASE 1] [PHASE 2]
MVP-G-CSR-A
[PHASE 1]
MVP-G-CSR-B
[PHASE 1]
[PHASE 3] [PHASE 1]
DSCO GROUP PTE LTD
CPG-G-CH-1 CPG-G-CH-3 CPG-G-CH-4 CPG-G-CH-2
3 HarbourFront Place
LP-G-A1 LP-G-B2 #04-02 HarbourFront Tower Two
PLN INC 1 PLN INC 2
LP-G-A3 LP-G-B4 Singapore 099254
TEL : 6216 0022 FAX : 6216 0020
LP-G-A5 LP-G-B6
LB CONNECTION

LB CONNECTION

LB CONNECTION

LB CONNECTION
[PHASE 1] [PHASE 2]
Project:
[PHASE 3] [PHASE 1]

[PHASE 1] [PHASE 2]
MDFA-G-A1
ATS
LMDP-G-CH-1 ATS
LMDP-G-CH-3 ATS
[PHASE 3]
LMDP-G-CH-4 ATS
[PHASE 1]
LMDP-G-CH-2
MDFA-G-B2
PROPOSED NEW ERECTION OF A 3 STOREY
MDFB-G-A3 MDFB-G-B4
H2-02 DATA CENTRE AT PERTIWI LESTARI
FROM LMDP-G-CH-2

INDUSTRIAL ESTATE, KARAWANG,


FROM LMDP-G-CH-1
SPARE

SPARE

SPARE

PP-CRAH-G-A3

PP-CRAH-G-A1

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

PP-CRAH-G-B4

PP-CRAH-G-B2

SPARE

SPARE

SPARE
TO SDP-G-B MTS

TO SDP-G-A MTS
SPK PUMP

SPK JOCKEY PUMP


[PHASE 1] [PHASE 1]
MDFC-G-A5 SDP-G-A MTS
ELECTRICAL SCHEME (OVERALL MECHANICAL + BUILDING UTILITIES LOAD) MTS
SDP-G-B MDFC-G-B6 JAWA BARAT INDONESIA
PP-G-FP-A
PP-G-FCC
PP-G-FUEL-A

MAKE-UP WATER-A
PP-G-AC-A
PP-G-MV-A
LP-G-EXT-A
LP-G-CSR-A
PP-G-SEC-A

PP-G-SEC-B
LP-G-CSR-B
LP-G-EXT-B
PP-G-AC-B
PP-G-MV-B
MAKE-UP WATER-B

LP-G-LOCC
PP-G-FUEL-B
PP-G-FP-B
4 x SPARE

4 x SPARE
MDFD-G-A7 MDFD-G-B8

GEN LP GEN LP
Title:
ELECTRICAL SERVICES
LIFT
[PHASE 1] [PHASE 1] LIFT
AC / MV L2, L3, RF UPS-G-UT-A UPS-G-UT-B AC / MV L2, L3, RF
GEN LP [PHASE 3] [PHASE 1] [PHASE 1] [PHASE 1] [PHASE 2] GEN LP L2, L3, RF

(EOL 5 MIN) MCC-G-CH-5 (EOL 5 MIN)

MAIN ELECTRICAL SCHEMATIC


MCC-G-CH-1 MCC-G-CH-2 MCC-G-CH-3 MCC-G-CH-4
ATS ATS ATS
UDB-G-UT-A UDB-G-UT-B
[PHASE 1] [PHASE 1]
LB LB LB LB LB
ISO-TX CONNECTION CONNECTION CONNECTION CONNECTION CONNECTION ISO-TX
200kVA 200kVA
CONNECTION

CONNECTION
LOAD BANK

LOAD BANK
SPARE
SPARE

SPARE

(BMS/SEC/PM CTL)

(BMS/SEC/PM CTL)

SPARE
SPARE

SPARE
TO PP-U_LOCC-G-A

TO PP-U-G-A

TO PP-U-G-A

TO PP-U_LOCC-G-B
UPS-G-CH-5

UPS-G-CH-1

UPS-G-CH-2

UPS-G-CH-3

UPS-G-CH-4
160kVA

160kVA
(EOL 5 MIN)

(EOL 5 MIN)
50kVA

(EOL 5 MIN)
50kVA

(EOL 5 MIN)
50kVA

(EOL 5 MIN)
TO CHILLER CONTROL
TO CPOS
TO CHWP-5

TO CWP-5

TO2200RT CH-5

TO2200RT CH-5

TO CHILLER CONTROL
TO CPOS
TO CHWP-1

TO CWP-1

TO 735RT CH-1

TO CHILLER CONTROL
TO CPOS
TO CHWP-2

TO CWP-2

TO 735RT CH-2

TO CHILLER CONTROL
TO CPOS
TO CHWP-3

TO CWP-3

TO 735RT CH-3

TO CHILLER CONTROL
TO CPOS
TO CHWP-4

TO CWP-4

TO2200RT CH-4

Project no: Cad Drawing no.


1265E-201
TO CT-5

TO CT-1

TO CT-2

TO CT-3

TO CT-4
TO CT-5

TO CT-1

TO CT-2

TO CT-3

TO CT-4

1265
Designed Drawn 3021/1265/E/201
ZTW ZTW rev.
T1 T2
Checked Approved Scale Date
TCY KMF NTS MARCH 2022

GROUND GROUND