Professional Documents
Culture Documents
: 26071-100-V1A-MCAG-00315
2024.02.01
Toto.S
FABRICATION MATERIALS
Pipesystem data:
Section- Starting- Endnode Length Height Pipetype Diameter Fitting Component Nb of containers
No: node [m] [m] [mm] ** * code coefficient HFC227ea quantity
Legend of pipetypes
Type Pipeclass Pipe roughness
12 EN-10255 M hose
23 Schedule 40 black pipe
21 Schedule 40 galvanized
Legend of components
Code Type Resistance coefficient
752 RGS-MAM-50 valve + hose + check valve (bank). D=48mm 6.700
VdS SCHADENVERH?UNG HFC227ea -Calculationprogram Version 7.4 Page: 3
Licenced to: RG Systems, Grupo Komtes Serial no: [dongle]
File: C:\Program Files (x86)\VdS\HFC227ea\Projects\RDMP\BD16\RB\BD16_SWITCHGEAR ROOM (BANK A) - version 1.prj2023-09-25
- Results
Nozzle data:
Legend of nozzles:
Type Number of C1 C2 C3 C4 C5 C6
orifices
1 FEDR HFC-227ea 1 0.00010 0.71022 0.00000 0.00000 0.00000 0.00000
VdS SCHADENVERH?UNG HFC227ea -Calculationprogram Version 7.4 Page: 4
Licenced to: RG Systems, Grupo Komtes Serial no: [dongle]
File: C:\Program Files (x86)\VdS\HFC227ea\Projects\RDMP\BD16\RB\BD16_SWITCHGEAR ROOM (BANK A) - version 1.prj2023-09-25
- Results
Zone Total Volume of Calculated Total Max. Over- Design Extinguish- Design Design Design
volume building volume surface pressure temp. conc. factor conc. quantity
[m3] parts [m3] [m3] [mbar] [캜] [% Vol] [% Vol] [kg]
1 MAIN ROOM 1305.0 0.0 1305.0 0.0 1.000 20.0 5.2 1.35 7.0 719.65
Regulation rule for calculation of HFC227ea quantities: NFPA 2001, Edition 2012
Calczone no. 1: Class C Fire, NFPA 2001 (Edition 2012)
Altitude above sealevel: 1.0 m
Atmospheric correction factor: 1.000
Further information:
Design with included gas discharge time
Design with predeterminated orifice diameters
VdS SCHADENVERH?UNG HFC227ea -Calculationprogram Version 7.4 Page: 5
Licenced to: RG Systems, Grupo Komtes Serial no: [dongle]
File: C:\Program Files (x86)\VdS\HFC227ea\Projects\RDMP\BD16\RB\BD16_SWITCHGEAR ROOM (BANK A) - version 1.prj2023-09-25
- Results
Calculation results:
Discharge time:
Discharge time air: 0.4 s
Total gas discharge time: 0.4 s
Two-phase discharge time: 9.5 s
Total discharge time: 10.0 s
System information:
Container working pressure: 22.1 bar abs
Container working temperature: 17.5 캜
Total network volume: 390.3 l
Medium pipe content: 362.8 kg HFC227ea
Filling portion in pipe system: 0.50 kg HFC227ea /kg HFC227ea -storage
VdS SCHADENVERH?UNG HFC227ea -Calculationprogram Version 7.4 Page: 6
Licenced to: RG Systems, Grupo Komtes Serial no: [dongle]
File: C:\Program Files (x86)\VdS\HFC227ea\Projects\RDMP\BD16\RB\BD16_SWITCHGEAR ROOM (BANK A) - version 1.prj2023-09-25
- Results
Pipe system:
Section- Starting- Endnode Pressure Flowrate Pipedimension
No: node [bar abs] [kg/s] Di [mm] DN
Nozzle data:
Concentrations:
Component list:
Nozzle-type Number C1 C2 C3 C4 C5 C6
12 48.00 -- 0.100
23 102.30 4 2.300
21 102.30 4 35.100
21 77.90 3 10.000
21 62.70 2-1/2 13.600
-90 102.30 4 1
-90 102.30 4 6
-90 62.70 2-1/2 4
PS
FABRICATION MATERIALS
Pipesystem data:
Section- Starting- Endnode Length Height Pipetype Diameter Fitting Component Nb of containers
No: node [m] [m] [mm] ** * code coefficient HFC227ea quantity
Legend of pipetypes
Type Pipeclass Pipe roughness
12 EN-10255 M hose
23 Schedule 40 black pipe
21 Schedule 40 galvanized
Legend of components
Code Type Resistance coefficient
742 RGS-MAM-40 valve + hose + check valve (bank). D=32mm 6.700
VdS SCHADENVERH?UNG HFC227ea -Calculationprogram Version 7.4 Page: 3
Licenced to: Siex, Grupo Komtes Serial no: [dongle]
File: C:\Program Files (x86)\VdS\HFC227ea\Projects\RDMP\BD16\RB\BD16_SWITCHGEAR ROOM (BANK B) - version 1.prj2024-01-19
- Results
Nozzle data:
Legend of nozzles:
Type Number of C1 C2 C3 C4 C5 C6
orifices
1 FEDR HFC-227ea 1 0.00010 0.71022 0.00000 0.00000 0.00000 0.00000
VdS SCHADENVERH?UNG HFC227ea -Calculationprogram Version 7.4 Page: 4
Licenced to: Siex, Grupo Komtes Serial no: [dongle]
File: C:\Program Files (x86)\VdS\HFC227ea\Projects\RDMP\BD16\RB\BD16_SWITCHGEAR ROOM (BANK B) - version 1.prj2024-01-19
- Results
Zone Total Volume of Calculated Total Max. Over- Design Temp. Extinguish-Design Design Design
volume building volume surface pressure temp. corr. conc. factor conc. quantity
[m3] parts [m3] [m3] [mbar] [캜] factor [% Vol] [% Vol] [kg]
1 MAIN ROOM 1090.8 0.0 1090.8 0.0 1.000 20.0 1.000 5.2 1.35 7.0 601.48
Regulation rule for calculation of HFC227ea quantities: NFPA 2001, Edition 2018
Calczone no. 1: Class C Fire, NFPA 2001 (Edition 2012)
Altitude above sealevel: 1.0 m
Atmospheric correction factor: 1.000
Further information:
Design with included gas discharge time
Design with predeterminated orifice diameters
VdS SCHADENVERH?UNG HFC227ea -Calculationprogram Version 7.4 Page: 5
Licenced to: Siex, Grupo Komtes Serial no: [dongle]
File: C:\Program Files (x86)\VdS\HFC227ea\Projects\RDMP\BD16\RB\BD16_SWITCHGEAR ROOM (BANK B) - version 1.prj2024-01-19
- Results
Calculation results:
Discharge time:
Discharge time air: 0.3 s
Total gas discharge time: 0.3 s
Two-phase discharge time: 9.7 s
Total discharge time: 10.0 s
System information:
Container working pressure: 17.8 bar abs
Container working temperature: 16.4 캜
Total network volume: 295.2 l
Medium pipe content: 237.4 kg HFC227ea
Filling portion in pipe system: 0.39 kg HFC227ea /kg HFC227ea -storage
VdS SCHADENVERH?UNG HFC227ea -Calculationprogram Version 7.4 Page: 6
Licenced to: Siex, Grupo Komtes Serial no: [dongle]
File: C:\Program Files (x86)\VdS\HFC227ea\Projects\RDMP\BD16\RB\BD16_SWITCHGEAR ROOM (BANK B) - version 1.prj2024-01-19
- Results
Pipe system:
Section- Starting- Endnode Pressure Flowrate Pipedimension
No: node [bar abs] [kg/s] Di [mm] DN
Nozzle data:
Concentrations:
Component list:
Nozzle-type Number C1 C2 C3 C4 C5 C6
12 32.00 -- 0.100
23 102.30 4 1.400
21 102.30 4 25.300
21 77.90 3 10.000
21 62.70 2-1/2 6.200
21 52.50 2 6.600
-90 102.30 4 1
-90 102.30 4 9
-90 62.70 2-1/2 2
-90 52.50 2 2
1 PIPE, ASTM A53 GR.B, SHC40 2.1/2 - - 19.5 M HOT DIP GAL'V
2 PIPE, ASTM A53 GR.B, SHC40 2 - - 4M HOT DIP GAL'V
PERTAMINA
3 PIPE, ASTM A53 GR.B, SHC40 1.1/2 - - 2.5 M HOT DIP GAL'V
4 90˚ ELBOW, ASTM A234-WPB, SCH 40 2.1/2 - - 4 EA HOT DIP GAL'V
5 90˚ ELBOW, ASTM A234-WPB, SCH 40 1.1/2 - - 4 EA HOT DIP GAL'V
6 REDUCER, ASTM A234-WPB, SCH 40 2.1/2 x 2 - - 2 EA HOT DIP GAL'V
7 REDUCER, ASTM A234-WPB, SCH 40 2 x 1.1/2 - - 4 EA HOT DIP GAL'V
8 TEE, ASTM A234-WPB, SCH 40 2.1/2 - - 1 EA HOT DIP GAL'V
9 TEE, ASTM A234-WPB, SCH 40 2 - - 2 EA HOT DIP GAL'V
10 SUPPORT_PS01 - - - 12 EA -
11 SUPPORT_PS03 - - - 2 EA -
VdS SCHADENVERH?UNG HFC227ea -Calculationprogram Version 7.4 Page: 1
Licenced to: RG Systems, Grupo Komtes Serial no: [dongle]
File: C:\Program Files (x86)\VdS\HFC227ea\Projects\RDMP\BD16\RB\BD16_BATTERY ROOM (BANK B) - version 1.prj - Results
2023-09-25
Pipesystem data:
Section- Starting- Endnode Length Height Pipetype Diameter Fitting Component Nb of containers
No: node [m] [m] [mm] ** * code coefficient HFC227ea quantity
Legend of pipetypes
Type Pipeclass Pipe roughness
12 EN-10255 M hose
23 Schedule 40 black pipe
21 Schedule 40 galvanized
Legend of components
Code Type Resistance coefficient
742 RGS-MAM-40 valve + hose + check valve (bank). D=32mm 6.700
VdS SCHADENVERH?UNG HFC227ea -Calculationprogram Version 7.4 Page: 3
Licenced to: RG Systems, Grupo Komtes Serial no: [dongle]
File: C:\Program Files (x86)\VdS\HFC227ea\Projects\RDMP\BD16\RB\BD16_BATTERY ROOM (BANK B) - version 1.prj - Results
2023-09-25
Nozzle data:
Legend of nozzles:
Type Number of C1 C2 C3 C4 C5 C6
orifices
1 FEDR HFC-227ea 1 0.00010 0.71022 0.00000 0.00000 0.00000 0.00000
VdS SCHADENVERH?UNG HFC227ea -Calculationprogram Version 7.4 Page: 4
Licenced to: RG Systems, Grupo Komtes Serial no: [dongle]
File: C:\Program Files (x86)\VdS\HFC227ea\Projects\RDMP\BD16\RB\BD16_BATTERY ROOM (BANK B) - version 1.prj - Results
2023-09-25
Zone Total Volume of Calculated Total Max. Over- Design Extinguish- Design Design Design
volume building volume surface pressure temp. conc. factor conc. quantity
[m3] parts [m3] [m3] [mbar] [캜] [% Vol] [% Vol] [kg]
1 MAIN ROOM 399.3 0.0 399.3 0.0 1.000 20.0 5.2 1.35 7.0 220.19
Regulation rule for calculation of HFC227ea quantities: NFPA 2001, Edition 2012
Calczone no. 1: Class C Fire, NFPA 2001 (Edition 2012)
Altitude above sealevel: 1.0 m
Atmospheric correction factor: 1.000
Further information:
Design with included gas discharge time
Design with predeterminated orifice diameters
VdS SCHADENVERH?UNG HFC227ea -Calculationprogram Version 7.4 Page: 5
Licenced to: RG Systems, Grupo Komtes Serial no: [dongle]
File: C:\Program Files (x86)\VdS\HFC227ea\Projects\RDMP\BD16\RB\BD16_BATTERY ROOM (BANK B) - version 1.prj - Results
2023-09-25
Calculation results:
Discharge time:
Discharge time air: 0.5 s
Total gas discharge time: 0.5 s
Two-phase discharge time: 9.3 s
Total discharge time: 9.8 s
System information:
Container working pressure: 15.5 bar abs
Container working temperature: 15.5 캜
Total network volume: 145.8 l
Medium pipe content: 138.8 kg HFC227ea
Filling portion in pipe system: 0.62 kg HFC227ea /kg HFC227ea -storage
VdS SCHADENVERH?UNG HFC227ea -Calculationprogram Version 7.4 Page: 6
Licenced to: RG Systems, Grupo Komtes Serial no: [dongle]
File: C:\Program Files (x86)\VdS\HFC227ea\Projects\RDMP\BD16\RB\BD16_BATTERY ROOM (BANK B) - version 1.prj - Results
2023-09-25
Pipe system:
Section- Starting- Endnode Pressure Flowrate Pipedimension
No: node [bar abs] [kg/s] Di [mm] DN
Nozzle data:
Concentrations:
Component list:
Nozzle-type Number C1 C2 C3 C4 C5 C6
12 32.00 -- 0.100
23 102.30 4 1.400
21 102.30 4 6.100
21 62.70 2-1/2 23.400
21 52.50 2 4.100
21 40.90 1-1/2 4.800
-90 102.30 4 1
-90 102.30 4 3
-90 62.70 2-1/2 6
-90 40.90 1-1/2 4