TEST RECORD OF MITSUBISHI GENERATOR SET

Messrs

MODEL :
CUSTOMER : PROJECT No. :

BAROMETRIC FUEL OIL SPECIFIC


DIVISION TEST DATE WEATHER FUEL OIL LUB. OIL
PRESS. GRAVITY
FINE CLOUDY LIGHT OIL SAE 30
MFR'S TEST
RAINY SNOWY HEAVY OIL SAE 40

FINE CLOUDY LIGHT OIL SAE 30


WITNESS
RAINY SNOWY HEAVY OIL SAE 40

ENGINE SPECIFICATION GENERATOR SPECIFICATION


MAKER : MAKER :

MODEL & SERIAL No. : MODEL & SERIAL No. :

RATED OUTPUT : RATED OUTPUT :


kW rpm kVA kW
CLY.No. X BORE X STROKE VOLTAGE : CURRENT :
Cyl. X mm V A
TOTAL DISPLACEMENT : FREQUENCY : POWER FACTOR :
L Hz ø
INJECTION TIMING : PHASE : POLES :
BTDC
HEAT DIRECT
COOLING METHOD : RADIATOR RULE : MFG DATE :
EXCHANGER COOLING
IP23
STARTING METHOD : RADIATOR SPECIFICATION
ELECTRIC MODEL/PART NUMBER &
GOV. TYPE MECHANICAL HYDRAULIC ELECTRIC SERIAL NO:
STATUS
TURBO MODEL :
OK NOT OK
INJ. PUMP MODEL OR PART No. :

ENG, MFG. DATE GOVERNOR


TRIMMER SETTING
SETTING
CON-ROD RANK DR Rated Speed: -
GAIN
I Low idle:
D Rated Volt: 4-80

APPROVED BY

CHECKED BY

TESTED BY
E N G IN E N U M B E R
V Confirmation at WITNESS TES

P R O T E C T IV E D E V IC E T E S T @ Confirmation working by means of


making contact
ENGINE TRIP
No ITEM SETTING WORKING INDICATION
STOP SIGNAL
1 EMERGENCY STOP Press Button CLOSE √ OPEN √
2 L/O LOW OIL PRESS BAR PRESSURE NORMAL 6 - 7 BAR 3,91 ALARM 1,5 √
3 C/W HIGH TEMP CELCIUS NORMAL 69 -92 96 ALARM 101 √
4 OVERSPEED RPM 1499 - 1501 1650 1750 √
E N G IN E N U M B E R
LO AD TEST STANDARD TEST
START
TIME
FINISH REMARKS
Minutes
LOAD %
OUTPUT KW
VOLTAGE V
L1 A
LOAD CURRENT L2 A
L3 A
POWER FACTOR
G ENERATO R

FREQUENCY Hz
o
INLET C
COOLING AIR TEMP o
OUTLET C
o
AMBIENT TEMP C

SPEED Rpm

o
COOLING WATER TEMP C
LUBE OIL PRESS Bar
o
INLET AIR TEMP C
E N G IN E

o
EXHAUST GAS TEMP C
o
RADIATOR INLET C
DC VOLTAGE ALTERNATOR VDC
E N G IN E N U M B E R
LO AD TEST BURN TEST 8 HO URS
START 1 3 :0 0 1 4 :0 0 1 5 :0 0 1 6 :0 0 1 7 :0 0 1 8 :0 0 1 9 :0 0 2 0 :0 0 2 1 :0 0
TIME
FINISH 1 4 :0 0 1 5 :0 0 1 6 :0 0 1 7 :0 0 1 8 :0 0 1 9 :0 0 2 0 :0 0 2 1 :0 0 2 2 :0 0 REMARKS
Minutes 60 60 60 60 60 60 60 60 60
LOAD % 100 100 100 100 100 100 100 100 100
OUTPUT KW
VOLTAGE V
L1 A
LOAD CURRENT L2 A
L3 A
POWER FACTOR
G ENERATO R

FREQUENCY Hz
o
INLET C
COOLING AIR TEMP o
OUTLET C
o
AMBIENT TEMP C

SPEED Rpm

o
COOLING WATER TEMP C
LUBE OIL PRESS Bar
E N G IN E

o
INLET AIR TEMP C
o
EXHAUST GAS TEMP C
o
RADIATOR INLET C
DC VOLTAGE ALTERNATOR VDC
E N G IN E N U M B E R

GOVERNOR TEST

2
t2

3
1
5

t1

DIV POSI- T 1 0 % [0 K W ] 25% [450 KW ] T 2 2 5 % [4 5 0 K W ] 50% [900 KW ] Remakrks


ITEM TION
MRF'S WITNESS MRF'S WITNESS MRF'S WITNESS MRF'S WITNESS
N0.
PRIMARY SET (Hz) 1
INSTANT (Hz) 2
STEADY (HZ) 3
INSTANT (Hz) 4
STEADY (HZ) 5
FREQ. RECOVERY TIME t1
(Sec) t2
2
REGULATION (%) 3
4
5
PRIMERY SET (V) 1
INSTANT (V) 2
STEADY (V) 3
INSTANT (V) 4
STEADY (V) 5
VOLT. t1
RECOVERY TIME
(Sec) t2
2
REGULATION (%) 3
4
5
E N G IN E N U M B E R

GOVERNOR TEST

2
t2

3
1
5

t1

DIV POSI- T 3 5 0 % [9 0 0 K W ] 75% [1350 KW ] T 4 7 5 % [1 3 5 0 K W ] 100% [1800 KW ] Remakrks


ITEM TION
MRF'S WITNESS MRF'S WITNESS MRF'S WITNESS MRF'S WITNESS
N0.
PRIMARY SET (Hz) 1
INSTANT (Hz) 2
STEADY (HZ) 3
INSTANT (Hz) 4
STEADY (HZ) 5
FREQ. RECOVERY TIME t1
(Sec) t2
2
REGULATION (%) 3
4
5
PRIMERY SET (V) 1
INSTANT (V) 2
STEADY (V) 3
INSTANT (V) 4
STEADY (V) 5
VOLT. t1
RECOVERY TIME
(Sec) t2
2
REGULATION (%) 3
4
5
E N G IN E N U M B E R

GOVERNOR TEST

2
t2

3
1
5

t1

DIV POSI- T 5 1 0 0 % [1 8 0 0 K W ] 0% [0 KW ] T 6 0 % [0 K W ] 50% [900 KW ]


ITEM TION
MRF'S WITNESS MRF'S WITNESS MRF'S WITNESS MRF'S WITNESS
N0.
PRIMARY SET (Hz) 1
INSTANT (Hz) 2
STEADY (HZ) 3
INSTANT (Hz) 4
STEADY (HZ) 5
FREQ. RECOVERY TIME t1
(Sec) t2
2
REGULATION (%) 3
4
5
PRIMERY SET (V) 1
INSTANT (V) 2
STEADY (V) 3
INSTANT (V) 4
STEADY (V) 5
VOLT. t1
RECOVERY TIME
(Sec) t2
2
REGULATION (%) 3
4
5
E N G IN E N U M B E R

GOVERNOR TEST

2
t2

3
1
5

t1

DIV POSI- T 7 5 0 % [9 0 0 K W ] 100% [1800 KW ] T 8 1 0 0 % [1 8 0 0 K W ] 50% [900 KW ]


ITEM TION
MRF'S WITNESS MRF'S WITNESS MRF'S WITNESS MRF'S WITNESS
N0.
PRIMARY SET (Hz) 1
INSTANT (Hz) 2
STEADY (HZ) 3
INSTANT (Hz) 4
STEADY (HZ) 5
FREQ. RECOVERY TIME t1
(Sec) t2
2
REGULATION (%) 3
4
5
PRIMERY SET (V) 1
INSTANT (V) 2
STEADY (V) 3
INSTANT (V) 4
STEADY (V) 5
VOLT. t1
RECOVERY TIME
(Sec) t2
2
REGULATION (%) 3
4
5
E N G IN E N U M B E R

GOVERNOR TEST

2
t2

3
1
5

t1

DIV POSI- T 9 5 0 % [9 0 0 K W ] 0% [0 KW ] T 1 0 0 % [0 K W ] 100% [1800 KW ]


ITEM TION
MRF'S WITNESS MRF'S WITNESS MRF'S WITNESS MRF'S WITNESS
N0.
PRIMARY SET (Hz) 1
INSTANT (Hz) 2
STEADY (HZ) 3
INSTANT (Hz) 4
STEADY (HZ) 5
FREQ. RECOVERY TIME t1
(Sec) t2
2
REGULATION (%) 3
4
5
PRIMERY SET (V) 1
INSTANT (V) 2
STEADY (V) 3
INSTANT (V) 4
STEADY (V) 5
VOLT. t1
RECOVERY TIME
(Sec) t2
2
REGULATION (%) 3
4
5
E N G IN E N U M B E R

GOVERNOR TEST

2
t2

3
1
5

t1

DIV POSI- T 1 1 1 0 0 % [1 8 0 0 K W ] 0% [0 KW ]
ITEM TION
MRF'S WITNESS MRF'S WITNESS
N0.
PRIMARY SET (Hz) 1
INSTANT (Hz) 2
STEADY (HZ) 3
INSTANT (Hz) 4
STEADY (HZ) 5
FREQ. RECOVERY TIME t1
(Sec) t2
2
REGULATION (%) 3
4
5
PRIMERY SET (V) 1
INSTANT (V) 2
STEADY (V) 3
INSTANT (V) 4
STEADY (V) 5
VOLT. t1
RECOVERY TIME
(Sec) t2
2
REGULATION (%) 3
4
5