You are on page 1of 17

Standard No.

GENERAL RULES FOR INSTRUMENT JERSD-J-0080

STUDY & INSTALLATION Folio Rev.

a 0A
COVER PAGE
Format Date

A4 07/2008

REFINING STANDARD

*******

GENERAL RULES FOR INSTRUMENT STUDY & INSTALLATION

This document is the property of JER COMPANY. It must not be stored, reproduced or disclosed to others without written authorization of JER COMPANY.
Standard No.

JERSD-J-0080
GENERAL RULES FOR INSTRUMENT
page Rev.
STUDY & INSTALLATION
b 0A

REVISION SUMMARY TABLE Format Date

A4 07/2008

page Description Rev. Date

0 07/2008
page a
Cover page

0 07/2008
page b
Revision summary table

0 07/2008
page c
Revision summary table

Spare

Spare

0 07/2008
page 1
Local instrument label

0 07/2008
page 2
Local instrument label (example)

0 07/2008
page 3
Cabinets label

0 07/2008
page 4
Cabinets label

0 07/2008
page 5
Local panel label

0 07/2008
page 6
Dangerous product label

page 7
Spare

0 07/2008
page 8
Mounting bracket instrument on ground to simple sensor

0 07/2008
page 9
Mounting bracket instrument on ground to double sensor

0 07/2008
page 10
Mounting bracket instrument on plateform to simple instrument

0 07/2008
page 11
Mounting bracket instrument on plateform to double instrument

0 07/2008
page 12
Typical of supporting instruments equiped of direct manifold blocs

0 07/2008
page 13
Supporting sensor without manifold bloc

page 14
Reserve

page 15
Reserve

0 07/2008
page 16
Installing capillary on delta P mounting

This document is the property of JER COMPANY. It must not be stored, reproduced or disclosed to others without written authorization of JER COMPANY.
Standard No.

JERSD-J-0080
GENERAL RULES FOR INSTRUMENT
page Rev.
STUDY & INSTALLATION
c 0A

REVISION SUMMARY TABLE Format Date

A4 07/2008

page Description Rev. Date

page 17
Reserve

page 18
Reserve

page 19 0 03/2007
Capilary protection

page 20 0 03/2007
Capilary slack loop protection

page 21
spare

page 22
spare

page 23
spare

page 24
spare

page 25
spare

page 26
spare

page 27
spare

page 28
spare

page 29
spare

page 30
spare

page 31
spare

page 32
spare

page 33
spare

page 34
spare

page 35
spare

page 36
spare

page 37
spare

This document is the property of JER COMPANY. It must not be stored, reproduced or disclosed to others without written authorization of JER COMPANY.
Standard No.

JERSD-J-0080
GENERAL RULES FOR INSTRUMENT
Folio Rev.
STUDY & INSTALLATION
1 0A
LOCAL INSTRUMENTS LABEL
Format Date

A4 07/2008

150
Eyelet brass 06.5mm
16
16
16
50

Unit number
(3 caracters)
65

Thickness 3mm; letter width


~12mm

Instrument tag
(12 caracters maxi)
20

Thickness 3mm; letter width


~12mm
12

Instrument service line 1


16

(18 caracters maxi, point and space


included)
Thickness 1mm; letter width ~12mm
8
32

16

Instrument service line 2


8

(18 caracters maxi, point and space


2 included)
Thickness 1mm; letter width ~8mm

Vue de dessus
Top view or IFS marking
Thickness 3mm; letter width ~12mm
Height 20mm

Matter :
Plate realised in plastic laminate (GRAVOPLY type) fixed by gluing on aluminium plate
(thickness 1mm)
Colors :
-Safety sensors and actuators : white letters on red background
-Other sensors and actuators : white letters on blue backgro
und
-IFS sensors and actuators : an red insert with IFS indication in white frame
Fixing :
By collar or by bolting can be used but bolting is recommended.
Utilization :
Marking transmitters, valves, solenoide valves, local regulators, thermoco
uples.

This document is the property of JER COMPANY. It must not be stored, reproduced or disclosed to others without written authorization of JER COMPANY.
Standard No.

GENERAL RULES FOR INSTRUMENT JERSD-J-0080

STUDY & INSTALLATION Folio Rev.

2 0A
LOCAL INSTRUMENTS LABEL Format Date

(EXAMPLE)
A4 07/2008

This document is the property of JER COMPANY. It must not be stored, reproduced or disclosed to others without written authorization of JER COMPANY.
Standard No.

JERSD-J-0080
GENERAL RULES FOR INSTRUMENT
Folio Rev.
STUDY & INSTALLATION
1 0A
CABINETS LABEL
Format Date

A4 07/2008

-Plate realized in plastic laminate


(GRAVOPLY TYPE)
-Fastening by rivet nylon 03mm

FOR DCS CABINETS


160

-Blue label
60

-White text
-Height text : 30mm

10

FOR ESD CABINETS


160

-Red label
60

-White text
-Height text : 30mm

10

FOR SUPPLY CABINETS


160

-White label
60

-Black text
-Height text : 30mm

10

FOR MARSHALLING CABINETS


160

-Red label for safety


-Blue label for other
60

-Height text : 30mm

10

This document is the property of JER COMPANY. It must not be stored, reproduced or disclosed to others without written authorization of JER COMPANY.
Standard No.

JERSD-J-0080

GENERAL RULES FOR INSTRUMENT


Folio Rev.
STUDY & INSTALLATION
4 0
CABINETS LABEL
Format Date

A4 07/2008

FOR TERMINALS LIST IN MARSHALLING CABINETS


160

10
-White label
-Black text
-Height text : 10mm
20
80 *
1

* Can be extended in according to the number of


terminal

10

FOR CABINETS WITH INTRINSIC


SAFETY 160

-Blue label
-White text : INTRINSIC SAFETY
20

-Height text : 10mm

10

This document is the property of JER COMPANY. It must not be stored, reproduced or disclosed to others without written authorization of JER COMPANY.
Standard No.

JERSD-J-0080
GENERAL RULES FOR INSTRUMENT
Folio Rev.
STUDY & INSTALLATION
5 0

LOCAL PANEL LABEL Format Date

A4 07/2008

-Plate realized in plastic laminate (type


GRAVOPLY)
-Fastening by rivet nylon 03mm

LOCAL PANEL MARK

160
60

-White label
-Black text
-Height text : 30mm

10

REPERE APPAREIL SUR TABLEAU LOCAL


INTRUMENT MARK ON LOCAL PANEL

The marking plate must have 2


lines
-Instrument tag
-Instrument service

60
20

5 -White label
10 -Black text
-Height text : 8mm

This document is the property of JER COMPANY. It must not be stored, reproduced or disclosed to others without written authorization of JER COMPANY.
Standard No.

JERSD-J-0080
GENERAL RULES FOR INSTRUMENT
Folio Rev.
STUDY & INSTALLATION
6 0A
DANGEROUS PRODUCT LABEL
Format Date

A4 07/2008

150

Eyelet brass 06.5mm

16

Background orange
Text black
16
16

Obligatory text: WARNING


50

Background yellow
Symbol black Thickness 1mm; letter width
8mm
! WARNING
Background white
Text black
Text mentioning the type of
product with safety message
HIGT Thickness 1mm; letter width
5mm
Background yellow
CONCENTRATION H25
80

Symbol black TO FOLLOW


! PROCEDURE

Matter :
Plate realised in plastic laminate (GRAVOPLY type) fixed by gluing on
aluminium plate (thickness 1mm)
Color, symbol :
ISO3864-1
ISO3864-2
ISO3864-3

This document is the property of JER COMPANY. It must not be stored, reproduced or disclosed to others without written authorization of JER COMPANY.
Standard No.

JERSD-J-0080

GENERAL RULES FOR INSTRUMENT


Folio Rev.
STUDY & INSTALLATION
8 0A
MOUNTING BRACKET INSTRUMENT ON GROUND
Format Date
TO SIMPLE SENSOR
A4 07/2008

Cap thickness 5mm to block the pipe

Pipe 2" Sch40

Note 1
Earthing plate
300
1

900

Note 2

Thickness 10mm 2 holes 05mm

4 holes 018mm

25
25
1
70
70
1
22 25 0
0 25 22

NOTE 1:
For earthing
See JERD-J-0010
NOTE 2:
Anticorrosive paint
See Progect spicification

This document is the property of JER COMPANY. It must not be stored, reproduced or disclosed to others without written authorization of JER COMPANY.
Standard No.

JERSD-J-0080
GENERAL RULES FOR INSTRUMENT
Folio Rev.
STUDY & INSTALLATION
9 0A
MOUNTING BRACKET INSTRUMENT ON GROUND
TO DOUBLE INSTRUMENT Format Date

A4 07/2008

Cap thickness 5mm to block the pipe

60
0
300
1

Earthing plate

Note 1

Pipe 2" Sch40


000

Note 2
1

900

Thickness 10mm 2 holes 05mm

4 holes 018mm

25
25
1
70
70
1
22 25 0
0 25 22

NOTE 1:
For earthing
See JERD-J-0010
NOTE 2:
Anticorrosive paint
See Progect spicification

This document is the property of JER COMPANY. It must not be stored, reproduced or disclosed to others without written authorization of JER COMPANY.
Standard No.

GENERAL RULES FOR INSTRUMENT JERSD-J-0080


STUDY & INSTALLATION
Folio Rev.
MOUNTING BRACKET INSTRUMENT ON PLATEFORM
10 0A
TO SIMPLE INSTRUMENT
Format Date

A4 07/2008

Cap thickness 5mm to block the pipe

Note 1
1300

Pipe 2" Sch40


900

Note 2

2 holes 05mm

i
n
i
m
0 0
20 15

NOTE 1:
For earthing
See JERD-J-0010
NOTE 2:
Anticorrosive paint
See Progect spicification

This document is the property of JER COMPANY. It must not be stored, reproduced or disclosed to others without written authorization of JER COMPANY.
Standard No.

JERSD-J-0080
GENERAL RULES FOR INSTRUMENT
STUDY & INSTALLATION Folio Rev.

MOUNTING BRACKET INSTRUMENT ON PLATFORM 11 0A


TO DOUBLE SENSOR Format Date

A4 07/2008

Cap thickness 5mm to block the pipe

60
0
300
1

Note 1

Pipe 2" Sch40


000

Note 2
1

900

2 holes 05mm

i
in
m
0
20 50
1

NOTE 1:
For earthing
See JERSD-J-0010
NOTE 2:
Anticorrosive paint
See Progect spicification
Standard No.

JERSD-J-0080
GENERAL RULES FOR INSTRUMENT

STUDY & INSTALLATION Folio Rev.

12 0A
TYPICAL OF SUPPORTING INSTRUMENTS EQUIPED OF
Format Date
DIRECT MANIFOLD BLOCS
A4 07/2008

Sensor

Manifold bloc

Support for horizontal


or vertical mounting

Mounting bracket

This document is the property of JER COMPANY. It must not be stored, reproduced or disclosed to others without written authorization of JER COMPANY.
Standard No.

JERSD-J-0080
GENERAL RULES FOR INSTRUMENT
STUDY & INSTALLATION Folio Rev.

INSTALLING CAPILLARY ON DELTA P MOUNTING 16 0A

Format Date

A4 07/2008

The northern hemisphere The northern hemisphere

South North South North

30cm

Advised setting
All fuild / All
pressure
Possible setting except
-Vacuum
-Capacity or line submissive to important
purge(>10bar)
-H2

FORBIDDEN
1 pitting each side

This document is the property of JER COMPANY. It must not be stored, reproduced or disclosed to others without written authorization of JER COMPANY.
Standard No.

JERSD-J-0080
GENERAL RULES FOR INSTRUMENT
Folio Rev.
STUDY & INSTALLATION
19 0A
CAPILARY PROTECTION
Format Date

A4 07/2008

Capillary descent protection


type iron in U galvanized cover

No
te
1
d

Capillary

Housing of protection for loop of the capillary

No
te
1
d

NOTE 1:
If d>10cm put a protection type
iron in U
For capilary tracing see
STD115

This document is the property of JER COMPANY. It must not be stored, reproduced or disclosed to others without written authorization of JER COMPANY.
Standard No.

JERSD-J-0080
GENERAL RULES FOR INSTRUMENT
Folio Rev.
STUDY & INSTALLATION
20 0A
CAPILARY SLACK LOOP PROTECTION
Format Date

A4 07/2008

200

Hole for flowing

1
00
Joint

Note 1
d

0
20

Capillary

Wing nut

NOTE 1:
If d>10cm put a protection type
iron in U

This document is the property of JER COMPANY. It must not be stored, reproduced or disclosed to others without written authorization of JER COMPANY.