Professional Documents
Culture Documents
2/10/14 1:41 PM
TRANSFORMERS
HANDBOOK
Published by
InterNational Electrical Testing Association
#1
IN CUSTOMER SUPPORT
Raytech offers:
Toll free 888 484 3779 | Phone: 267 404 2676 | Fax: 267 404 2685
118 South 2nd St., Perkasie, PA, 18944
www.raytechusa.com
Published by
InterNational Electrical Testing Association
3050 Old Centre Avenue, Suite 102, Portage, Michigan 49024
269.488.6382
www.netaworld.org
Copyright © 2013 by InterNational Electrical Testing Association, all rights reserved. No part of this publication may
be reproduced in any form or by any means, electronic or mechanical, without permission in writing from the publisher.
TRANSFORMERS
HANDBOOK
TABLE OF CONTENTS
SFRA: The Basics of Swept Frequency Response Testing and Analysis .................... 21
Matt Kennedy and Mario Locarno, Doble Engineering Company
Published by
You have just come from your annual physical checkup. The produces water. This is caused by the molecular breakdown of the
doctor has ordered a blood test, and a few of the results have come cellulose which is high in hydrogen and oxygen molecules. The
back out of the normal range. He scheduled you for a few more original bonds are broken by what is call depolymerization and
diagnostic tests such as x-ray, treadmill, and EKG. Those test re- the loose hydrogen and oxygen molecules reunite to form H2O,
sults are inconclusive. Further tests are required to provide a com- hence water.
ductivity of the oil which will increase with age. The quality of di-
electric response analyzers is not primarily given by the accuracy
of the measurement device but rather by the built-in knowledge of
the analysis software.
One is often faced with the question of “What do these results
mean?” Whether the moisture in oil tests (with equilibrium charts)
or advanced dielectric response methods are performed, each test
technique should lead to some conclusion about the condition of
the transformer. Much study and work has been performed in eval-
uating what to do with moisture results. In some cases, a wet trans-
former may be vacuum processed, reducing the moisture content
to an acceptable level. In cases where the transformer is very old
and there is concern that exposing the insulation system to vacuum
processing may do more harm than good (further reducing the me-
chanical strength of the insulation), this information can be used
to assist in an assessment as well. In general, dielectric frequency
response methods are more accurate than traditional oil sample
analysis. Because of this increased accuracy, better decisions can
be made and useful life extension solutions can be provided to the
end user.
So the next time you test transformer oil and still have questions,
ask yourself if a more advanced test is needed to completely diag-
nose the condition of the transformer.
__________________________________________________
Outline:
• What is DFR? • 1990’s
• When does DFR testing apply in practice?
• What does DFR measure?
• DFR analysis and modeling software • 1990-2004
• Power Transformer moisture measurements – Method & technology of DFR developed further
• PF temperature correction • 2004-2009
– CIGRE
• , ”Dielectric Response Methods for
Diagnostics of Power Transformers” is published
– Certain materials will behave a particular way when an
• reported at CIGRE
• “Dielectric response diagnoses
– Apply a voltage to insulation and study how it reacts over
various frequencies
• 2009
– IEEE Transformer Committee presentations
– Another name for DFR
• 2010
– IEEE
• Moisture • Chemicals
Permittivity is material’s ability to transmit (or “permit”) an
• Aging • Contaminants
electric field through polarization of dipoles in the material.
• Heat • Etc……
• Measures
• Measures
• Measures MOISTURE % in insulation
10 Transformers Handbook
• Cellulose
– Barriers
– Spacers
• Oil
– Corrosive Sulfur
– Carbon Tracking
– Semi-Conductive sludge deposited in ducts
between windings
– Aging paper as it breaks down
– Incorrect shield connections
– Ultimately, it leads to a condition assessment of the
electrical insulation inside a transformer!
Transformers Handbook 11
Oil Cellulose
Transformers Handbook 17
– In short:
A measurement at e.g. 60 Hz, 20C corresponds to a
measurement at higher frequency at higher temperature
• Various material have different activation energy (W above)
– Non-impregnated paper typically around 1.0 eV
– Oil-impregnated paper typically 0.9 – 1.0 eV
– Mineral transformer oil typically 0.4 – 0.5 eV
20 Transformers Handbook
INTRODUCTION
In the past several years, SFRA testing has evolved from a design The international community has widely accepted SFRA and is
tool to a mainstream test used by hundreds of utilities, industries, now developing guidelines for its use. Doble Engineering has been
and testing companies around the world. This paper introduces the active in both the IEEE and IEC organizations in preparing guides
basics of SFRA testing and highlights some interesting cases to and worldwide standards for test methods and analysis of SFRA
illustrate practical application and analysis techniques. test results. The following guides will soon be available:
SFRA is a diagnostic tool that provides information about the • The IEEE C57.149 Working Group is preparing the “Guide
mechanical integrity of a transformer core, windings, and connections for the Application and Interpretation of Frequency Response
without requiring a technician to climb inside the transformer. It is Analysis for Oil Immersed Transformers.”
often used before and after a transformer is moved from one location • Members of the International Electrotechnical Commission
to another. The premise of SFRA testing is that changes in the (IEC) are preparing a similar FRA standard, “Measurement of
frequency response of a winding may indicate winding movement. Frequency Response” under the Power Transformer Technical
The SFRA test process is as follows: Committee TC14/PT 60076-18.
1. Inject a voltage at one end of a winding. These documents will lead to greater acceptance of SFRA test
2. See what comes out the other end. techniques and further signify worldwide acceptance.
3. Repeat at a variety of different frequencies.
4. Plot the results.
5. Investigate unexpected variations. When SFRA testing is performed on a transformer winding, a signal
is injected at one end of the winding and the response is measured at
PROBLEMS SFRA HAS DETECTED the other end of the same winding. The signal is a sine wave voltage
• Radial deformation (hoop buckling) which is swept through a range of 20 Hz to 2 MHz. The response
• Telescoped windings at each frequency is dependent on the complex arrangement of
• Turn-to-turn short circuits in the winding inductance, capacitance, and resistance of the winding. The input and
• Open-circuited winding output voltages are measured with reference to ground; this makes
• High-resistance connections the SFRA test a true two-port network, with the need for a ground
• Defects in the core reference. Usually the shield of the coax test leads is grounded at the
• Bulk and local movement base of the bushings. See Figure 1.
Table 2: Short-Circuit Test Configurations for CASE STUDY #1: AUTOTRANSFORMER TRANS-
Delta Wye Transformer PORTATION DAMAGE FOUND USING SFRA
• Results can vary between units, depending on size and type of unit.
• Results can be different because of magnetization and
grounding effects.
• Variations occur with tap changer positions. The standard is
16R, nominal.
• Change occurs based on the oil level.
Figure 8: Y1 Lead Lies on Top of the Core Figure 11: Board on Top of Core
CONCLUSION
SFRA is a useful addition to your toolset. It should be used with
other tests such as power factor, excitation current, TTR, and so
on. Used correctly, it will assist you to spot various failure modes
Figure 14: Short Circuit Test Results – Series Winding and help your transformer assessment process.
100%
Still Supported Still Supported Still Supported
Toll free 888 484 3779 | Phone: 267 404 2676 | Fax: 267 404 2685
118 South 2nd St., Perkasie, PA, 18944
www.raytechusa.com
26 Transformers Handbook
Figure 5: Dry-Type Transformer in the Field Figure 6: Average Sound Levels for Dry-Type Transformers
(Shermco Industries Photo) (Courtesy of General Electric)
Also, the audible sound produced by fan-assist cooled (FAC)
transformers is partially due to the energizing of the core by the any sound that is
alternating voltage applied to the windings and also by the fans forcing undesired or interferes with one’s hearing of something.
air through the coils. The noise generated by the core, and whose So who is to say what sound is undesired or interferes with
fundamental frequency is twice the frequency of the applied voltage, something? What may be a calming sound of transformer
will create audible sound that will be present even under no load (humming to some), may be a nuisance to others.
conditions. The vibrations producing audible sound can occur in the
Just as rock concerts may be annoying to some, and the loud
core, coil, mounting, housing, and in the conduit. The transmission of
music and rhythm may be stimulating and desirable to others.
sound from the transformer can be by various media such as air, metal,
concrete, wood or any combination. And since different people have different opinions as to what is
acceptable and what is not, and how annoying a transformer has
become is different in different situations, the best tactic is to try
Transformer hum also arises through the vibration caused when
and mitigate the problem on the front end through proper placement
the load current passes through the windings, interacting with the
and design, and when initially tested and commissioned make sure
you carefully inspect the shipping bolts, packing materials, and
the size of the load current.
resilient mounts so sound is kept at a minimum.
CONTROL OF TRANSFORMER SOUND TRANSMISSION Removal or loosening of the shipping bolts will allow for a smooth
transfer of vibration and should reduce the overall noise generated
by the unit.
Ssshhh! I need to listen to the hum, it’s just getting to the good part.
a mass as possible. Vibration pads or properly designed isolation
mounts under the transformer will reduce transmittal of sound. Ron. A. Widup, Executive Vice President/
The neoprene rubber isolation pads (Figure 2) provided with the General Manager of Shermco Industries,
unit should be installed between the transformer and its mounting
surface. This will reduce case vibration and compensate for slight the low-, medium-, and high-voltage
unevenness of the mount. Care must be taken to ensure proper and switchgear and substation market. He is
tight installation of conduit. Flexible conduit is recommended. a principal member of NFPA Technical
A normal conversation is typically 60-70 dB. OSHA has an
actionable level to sound exposure at 85 decibels whenever noise Safety in the Workplace and a member of
levels equal or exceed an eight-hour time-weighted average sound NEC Code Panel 11. He is past president
of NETA and currently a member of the
Handling transformer oil is a challenge as well due to the viscosity Table 1-2: High Side Winding Resistance Correction Factors
of the oil becoming so low that the oil cannot be moved. The oil
actually looks more like thick maple syrup. In these cases heated
tankers are required to warm the oil to the point where transferring
it becomes possible. If the oil is already in the transformer tank,
the radiators can be shut off and the oil circulated through heaters
to bring the transformer up to temperature for testing.
Most test equipment does not function properly at extremely low Table 1-3: Low Side Winding Resistance Correction Factors
temperatures. Test equipment is often required to be set up in the warm
vehicle and the test leads run out through the window. It is important
to understand why some testing should not be performed, nor is it
recommended when the temperature reaches below freezing point,
unless certain heaters and insulated tarps with support structure can
be provided to help keep heat in and around apparatus. For example, INSULATION RESISTANCE
if a company were to test a transformer in -40ºC temperature, how
accurate will the test results be? Are the powerfactor results going to Looking at the table from the ANSI NETA MTS-2011, it can be seen
capture all the moisture present in the oil, windings, and insulation? that at 20°C the temperature correction factor equals one. For every
Is the test set screen going to freeze up? Are the results going to 10°C increase in temperature the correction factor approximately
accurately compare with summer test records? Can the drain valve be doubles and vice versa for decreasing temperature by 10°C.
accessed to take an oil sample? These are just some of the questions Table 1: Insulation-Resistance Correction Factors (20ºC)
you will have to ask yourself before maintenance is performed on NETA Table 100.14.1
outdoor transformers and a service report is developed.
OIL SAMPLING
Gathering an oil sample from the top and bottom drain valves at
below operating temperatures will give the greatest insight on the
oil quality. As the temperature decreases closer to freezing point,
the moisture present in the oil will escape, thus affecting high
voltage testing. When the moisture is becoming extracted from
Illustration 2: 1000 Volt Secondary to Primary and the oil, it will sit closer to the bottom of the transformer tank.
Ground PI Test
The fact that the transformer tested poorly outside and good
inside shows how crucial it is to consider the entire transformer’s
temperature during testing. By placing a higher voltage on the
windings, more results are revealed, but testing at a nonoperating,
freezing temperature will not give acceptable data as clearly shown
RECOMMENDATIONS
Move to Florida! There are many challenges involved with
winter work especially when dealing with transformers and
transformer oil. Special precautions and extra effort are required to
get the equipment up to temperature so certain tasks can be done.
It can be seen how such a drastic change in results are affected by
temperature. Therefore, having an accurate test sheet temperature
correction-factor database is crucial in order to have comparable
results from season to season. In today’s world, digital test sets
perform the majority of the testing and should, therefore, be kept
in a warm environment where results can be accurately processed.
If need be, bring the test set inside a vehicle or indoors and run
the test leads outside to the equipment under test. When tarps and
heaters are used to heat the transformer, ensure that all proper
clearances are kept around bushing and test connections. Having
scaffolding or any support structure too close to the bushings will
also pose a threat to accurate test results.
IMPORTANCE OF ANALYZING
EXCITATION TEST RESULTS
NETA World, Fall 2011 Issue
by Keith Hill, Doble Engineering Company
Often times an indication of a problem is overlooked by testing in the tap-changing device. These conditions result in a change of
personnel. Fortunately for the owner of this transformer, the the effective reluctance of the magnetic circuit which consequently
Table 2 records the exciting current test results attained by Doble Doble Transformer Turns Ratio
personnel before the demagnetizing procedure was performed.
Exciting Current Tests before Demagnetization
magnetic circuit.
Although the overall power-factor test results were within
the recommended limits, the single-phase exciting-current tests Figure 5: Low Voltage
combined with irregularities observed when performing the TTR Phase 2
Phase 3
and SFRA tests provides substantial evidence there is a problem Layer 16
36 Transformers Handbook
with the small blister was not detected by routine test. After the
temperature rise test, the blister in the conductor developed an
increased contact between adjacent conductors. This condition
resulted in an increase in the damage and the fault current but
was not detected since no other tests were performed after the
temperature rise test.
It should be noted that the factory took immediate corrective
actions in their test process/laboratory and in the winding process
to prevent recurrence of this problem. It was noted in the factory’s
Layer 11 diagnostic report that some testing will be performed at the factory
after the heat rise test.
CONCLUSION
current pattern, this unit could have failed when placed into service.
When an odd exciting current pattern is obtained, the tester should
not take for granted that the core is magnetized, as this odd pattern
may indicate a problem with the core or windings. It should also
Layer 16 be noted that the low voltage TTR tests did not reveal a problem
with the turn’s ratio on this transformer. Use of the TTR capacitor,
at a higher test voltage, revealed a problem with the turns ratio
when the voltage applied was above 2.6 kV. The TTR capacitor
REFERENCES
Toll free 888 484 3779 | Phone: 267 404 2676 | Fax: 267 404 2685
118 South 2nd St., Perkasie, PA, 18944
www.raytechusa.com
Transformers Handbook 37
MODERN METHODS IN
CURRENT TRANSFORMER TESTING
NETA World, Fall 2011 Issue
by Peter Fong, OMICRON electronics Corp. USA
Different test devices and methods are used in the market to Several ways of conventional testing are possible:
verify the performance of current transformers during development, 1. The traditional way of testing a current transformer is to apply a high
production, installation and maintenance. This article describes current to the primary side and read the signals on the secondary
an innovative solution to test current transformers at all lifecycle side. By using different burdens or injecting overcurrents, various
stages by using a revolutionary testing method called “the modeling situations can be simulated and the signals on the secondary side
concept.” can be measured and analyzed. However, this method is time-
Current transformers are used in electrical power systems for consuming and requires a lot of equipment. Sometimes it is not
relaying and metering purposes. Depending on the application for even feasible as very high currents are required, e.g., for on-site
which they are used, the current transformers are designed differently. testing of a bushing current transformer inside a power transformer
or a shunt reactor.
APPLICATIONS AREAS
2. Another common testing scenario for current transformers is
The current transformers for metering and protection applications
work basically the same way – transforming high power primary the reverse transformed value on the primary side. Unfortunately,
signals to lower secondary values. However, while current using this scenario, some parameters like accuracy and knee point
transformers used for protection applications operate to well above (excitation curve), can only be tested with limitations. This is due
the load current, the current transformers for metering purposes must to the scenario’s restrictions in accuracy caused by the very low
go into saturation directly above the load current level to protect the signals in use and the maximum voltage of approximately two kV
connected meter. which can be applied to the secondary side of current transformers.
Other important parameters like the transient dimensioning factor,
Current transformers play an important role in the protection of the accuracy limit factor, the safety factor, composite errors, time
electrical power systems. They provide the protection relay with a constancies, and many others cannot be tested at all.
replication of the primary current so that it can operate according to As both methods have limitations, OMICRON has developed an
its settings. The transformation of the current values from primary innovative method of testing CTs.
to secondary must be accurate during normal load conditions and
especially during fault conditions on the primary side (when currents MODELING CONCEPT
up to 30-times the nominal current can be expected). OMICRON developed a CT analyzer test device which uses a
revolutionary testing concept. The concept of modeling a current
Today, energy is supplied by many different sources including transformer allows for a detailed view of the transformer’s design and
alternative energy sources like solar and wind power. To guarantee its physical behavior. The test device builds up a model of the current
accurate billing in this competitive electricity market, additional transformer by using initial data, measured automatically during the
metering points are necessary. It is, therefore, important to have the test. Based on this model the test device is able to calculate parameters
entire metering circuit calibrated, as the meter is only as accurate as like the secondary terminal voltage, Vb,the accuracy limiting factor
the instrument transformers sourcing it. This makes the testing and (ALF), and the safety factor (FS), and simulate the CT’s behavior
calibration of current transformers up to the 0.15 accuracy class under different burdens or with various primary currents.
essential. However, on-site testing of CTs of the 0.15 accuracy class The analyzer measures the transformer’s copper and iron losses
according to its equivalent circuit diagram. While copper losses are
the measurement results. described as the winding resistance, RCT, iron losses are described
as the eddy losses or eddy resistance Reddy, and hysteresis losses as
TESTING OF CURRENT TRANSFORMERS hysteresis resistance RH. With this detailed information about the
Conventional testing methods apply a signal on one side and read core’s total losses, the CT analyzer is capable of modeling the current
the output signal on the other side. transformer and calculating the current ratio error as well as the phase
displacement for any primary current and secondary burden.
38 Transformers Handbook
Therefore, all operating points described in the relevant standards the current which caused the remanence. In a second step, the current
for current transformers can be determined. The model also allows transformer is demagnetized by reducing the voltage gradually to zero.
important parameters such as the residual magnetism, the saturated
and unsaturated inductance, the symmetrical short-current factor
(overcurrent factor) and even the transient dimensioning factor
(according to the IEC 60044-6 standard for transient fault current
calculations) to be assessed.
Within seconds a test report, including an automatic assessment
according to IEEE C57.13 or C57.13.6 (Standard for High Accuracy
Instrument Transformers) is generated. The CT analyzer offers a
very high testing accuracy of 0.05% (0.02% typical) for current Figure 5 and 6: Demagnetization principle of iron cores
ratio and 3 minutes of angle (1 min typical) for phase displacement.
The CT analyzer performs the residual magnetism measurements
prior to the usual CT testing cycle as it automatically removes
residual magnetism after testing. In order to determine the residual
magnetism the CT analyzer drives the core into positive and negative
saturation alternately until a stable symmetric hysteresis loop is
reached. The CT analyzer then calculates the initial remanence
condition to determine whether the core was affected by residual
magnetism. The results are displayed as absolute values in voltage
Figure 1: Equivalent circuit diagram of a real current transformer
RESIDUAL MAGNETISM
Additionally, the remanence factor Kr is shown on the test card.
A new measurement function for the CT nalyzer allows current
transformers to be tested for residual magnetism. Residual magnetism
may occur if a current transformer is driven into saturation. This can
happen as a consequence of high fault currents containing transient
components, or direct currents applied to the current transformer during
winding resistance tests or during a polarity check (wiring check).
CONCLUSION
After installation, current transformers are typically used for 30 years.
In order to guarantee a reliable and safe operation over the life time of the
CTs, a high level of quality during design phase, manufacturing process,
and installation is essential. Therefore, several quality tests are performed
from development to installation. After installation, CTs should be tested
Figure 4: Hysteresis curve at the max. saturation point on a regular basis to ensure correct functioning over the entire life time.
showing the possible area for residual magnetism
Since remanence effects in protective current transformers are not Peter Fong received a BS in Electrical
predictable and barely recognizable during normal operation, these Engineering from the University of British
effects are even more critical. Unwanted operation of the differential Columbia in 1988. He joined OMICRON in
protection may be caused. Protective relays also may show a failure
to operate in case of real overcurrent as the current transformer’s of Application Engineer. Prior to joining
signal is distorted due to the residual magnetism in the CT core.
Once the current transformer is magnetized, a demagnetization Hydro and two years at a relay manufacturer in
process is necessary in order to remove residual magnetism. This can the US. Peter Fong is a Professional Engineer
be achieved, e.g., by applying an ac current with similar strength as (APEGBC) and a member of IEEE.
Transformers Handbook 39
Figure 2: Equivalent circuit for insulation materials and Figure 3: PDC Wave Shape and Interpretation
corresponding vector diagram
Transformers Handbook 41
0.01 Hz – 1 Hz. Dissolved conductive aging by-products increase Figure 5: Combined PDC and FDS Measurement
Using Transformation
polarization (insulation geometry, ratio of oil to pressboard)
determines the local maximum or “hump” in the 0.003 Hz range. the combining of time and frequency domain measurements. A
The higher the ratio of oil to pressboard, the more dominating is transformation is applied to the time domain measurement and the
this effect. Finally, the moisture effects within the cellulose appear
again at the frequencies below 0.5 mHz [1].
The Power Factor Tip-Up method monitors the behavior
of insulation as a function of test voltage. The test voltage is
generally increased at predetermined levels and the power
factor is recorded. Healthy insulation systems in transformers
and bushings should not produce the “Tip-Up effect”, whereby
the percent power factor increases with an increase in voltage.
Sensitivity to Tip-Up can be caused by aging, localized defects
that result in partial discharges, and defective connections in
series with a given insulation path.
For practical purposes the “value” of Tip-Up is the difference
between the 10 kV Power Factor and the 2 kV Power Factor for
insulation systems rated at 15 kV and above. It is not the terminal
Figure 6a: Power Factor Tip-Up Figure 7: Superposition of Cellulose and Oil
test protocols exist. Table 1, shown below, lists a few common types.
REFERENCES
[1] M. Koch, M. Krueger, M. Puetter. “Advanced Insulation Diagnostic
Figure 11, shown below, illustrates the CHL power factor
behavior from two similar transformers. The 60 Hz power factors [2] E. Nemeth. “Measuring the Voltage Response, a Diagnostic
are identical (0.22%); however the overall responses are different. Test Method of Insulation.” Proceedings of the VII International
These results would be an indication that T2 has a slightly higher Symposium on High Voltage Engineering, ISH, Dresden, 1991;
moisture content. [3] M. Koch, M. Kruger, S. Tenbohlen. “Comparing Various Moisture
Determination Methods for Power Transformers.” South Africa
Regional Conference, CIGRE 2009;
[4] V.D. Houhanessian. “Measurement and Analysis of Dielectric
Response in Oil-Paper Insulation Systems.” Ph.D. Dissertation, Swiss
Federal Institute of Technology Zurich, ETHZ, 1998;
[5] R. Niemanis, T.K. Saha, R. Eriksson. “Determination of Moisture
Content in Mass Impregnated Cable Insulation Using Low Frequency
Dielectric Spectroscopy.” IEEE Power Engineering Society Summer
Meetings, p 463-468, vol. 1, Seattle, USA, July 16-20, 2000;
[6] M. Koch, M. Krüger. “Moisture Determination by Improved
PowerTest 2012
by Rick Youngblood, Doble Engineering
It is common knowledge that transformer cost comprises any- the failure modes must be known and tested for on a regular basis.
where from 40-60% of the price of a substation. The cost has spi- -
raled out of control, up 40% from last year. These price increases ing categories: mechanical, electrical and dielectric. Each of these
have dried up the inventory of the used market and new transform- categories should be further divided into internal and external test-
ers are averaging 50-56 weeks from order to arrival. All rewind ing. The last two divisions are what separate mediocre from the
shops are swamped and their time lines are growing as well. Un- complete testing programs.
fortunately, the majority of the U.S. transformer population is also
at the end of the baby boom era and requires special care and test- EXTERNAL FAILURE MODES
ing if they are to continue to serve until the market can catch up. In Mechanical failures are typically broken into LTC drive systems
some of the more progressive industries and utilities, transformer and cooling.
testing is nothing more than a walk around to look for leaks, nitro- It is imperative the LTC make a full tap change at a speed where
gen and oil levels, LTC count, and the temperature recorded by the
internal arcing damage is minimized. Items such as weak motor
hot spot and top oil gages. Some company maintenance and test starting capacitors (Pictures 1 and 2) and low source voltage will
personnel have implemented DGA testing but many still have no cause the motor to labor; pull abnormally high currents, and even-
clue of its value. tually burn up if not protected by a safety of some sort. Motor
The companies that do regularly test transformers are many voltage should not drop more than 10% during tap change from 1
times still guilty of only testing what is inside the tank and totally L to 1 R. Low voltage means high current and overheating. Bad
overlook many of the obvious other transformer failure producing source wiring or corroded connections to the LTC can also be a
indicators on the outside. To truly test a transformer 100%, all of culprit of low voltage.
Picture 1: Motor mounted Required Torque = Source Voltage X Current Picture 2: Externally mounted
capacitor Voltage Down = Current Up capacitor
Transformers Handbook 45
Stiff rusty chains (Picture 3), weak drive springs, dry gear boxes
and poor shaft alignment all contribute to tap changer and trans-
former failure and have nothing to do with the internal workings
of LTC or windings. Many transformer failures can be attributed
to the failure of the dynamic braking system that stops the LTC on
tap rather than partially on tap as can be seen below in (Picture 4.)
COOLING
Cooling is essential for long transformer life. Most trans-
formers are designed for 55C or 65C rise. Using newer in-
sulations such as Nomex®, temperatures of 95C and higher
can be achieved. These temperatures can only be maintained if
the transformer operating conditions do not exceed the design
limitations.
Unfortunately in today’s operating environment, most end
users are pushing loads well past nameplate design limitations
resulting in increased winding temperatures. These tempera-
tures are primarily due to increased losses such as I2R. In-
creased heating plays a major effect on the degradation of in-
sulation quality and drastically diminishes its life expectancy.
Here the standard 10 rule of thumb still applies for insulation
Picture 4: Contact failure due to faulty drive mechanism on half life.
a 550B
46 Transformers Handbook
Bottom mount fans blow air across the total length of the
cooler or radiator but have higher motor failure due to water
entrance around the shaft seal. The use of totally enclosed, non
vented motors with high quality shaft seals do however in-
crease motor life. Inspection of these motors should be made
Picture 5: ONAN naturally cooled through oil convection monthly. Side mounted fans have a longer life expectancy but
cooling no external fans tend to blow only across the section of the cooler or radia-
tor where placed. Side mounted fans are also very susceptible
to prevalent wind direction which can help or defeat the air
movement across the heat transfer surface. Open frame motors
are not recommended in any case due to higher failure rates
due to environmental considerations.
Transformers Handbook 47
Picture 8
Picture 9
problem.
Picture 10
Pump flow rate is hard to measure and typically
uses a small vane gage located in the piping
indicating pump ON or OFF activity. Flow
indicators are not always accurate. Many times
48
during maintenance a gage isTransformers found to be Handbook
stuck
and not truly indicate flow. A simple test can be
Forced oil pumping systems FOA/ FOW (Picture 11) provide
performed by turning the pump off and look at
the indicators
maximum to determine if they read correctly.
heat transfer.
Pumps, themselves create their own set of failure
#11 modes in located
a transformer;
vane gage in the piping built to pump
indicating tightONtolerances
or OFF ac-
dotivity.
notFlow
tolerate loose
indicators bearings
are not or bushings.
always accurate. Many timesAs dur-
ing maintenance a gage is found to be
they age, bearings, bushings or thrust washers stuck and not truly indicate
wear and can cause impeller drag on the pump
look at the indicators to determine if they read correctly. Pumps,
housings
themselves (Pictures 12set
create their own &of13).
failureThis
modescauses large
in a transformer;
deposits oftolerances
built to tight metal filings to beloose
do not tolerate deposited
bearings orin the
bushings.
transformer windings and eventually causes can
As they age, bearings, bushings or thrust washers wear and
cause impeller
insulation drag onas
failure thethey
pumpvibrate
housings (Pictures 12 and 13).
at operating
frequency and wear in.
transformer windings and eventually causes insulation failure as
Ultrasonic
they vibrate atinspection for bearing
operating frequency wear
and wear in. is aninspec-
Ultrasonic
Picture 11 excellent
tion for bearing wear is an excellent test and can be performed atas
test and can be performed at anytime
long
anytimeas as
the
longpump is running
as the pump is runningasas shown below.
shown below.
#12
Stages of thrust washer wear New/Failed
Picture 17
Oil level gages (seen above) can become stuck in one position
after many years without movement. Most are magnetically cou-
pled through the tank wall and can fail without notice. Oil leaks
and multiple oil samples can all lead to low oil levels. Care should
be taken to insure these gages work properly and if connected to
alarms or trip circuits, provide the correct outputs. Magnetically
coupled gages can be removed without the loss of oil and can be
tested using a continuity check and rotating the gage to indicate
low oil level.
BUSHINGS
Picture 15: Standard winding temperature gage made
by “Orto”. Bushing integrity is paramount. Bushings should be tested dur-
required to determine both insulating oil and paper health. Typical oil
tests are Dissolved Gas Analysis Dielectric Breakdown, Power Fac-
tor, Acidity, IFT, Color, and Karl Fisher. Other tests such as Degree
of Polymerization and Furnanic Compounds can be useful in deter-
mining the condition and remaining life of the insulation and should
be done sparingly as the transformer ages or in cases of overloaded,
overheated units. All can be done with the transformer in service.
CONCLUSIONS
Transformer testing whether internal or external is paramount
in providing the maximum life expectancy of our equipment
-
ure modes are addressed can we be certain to provide our custom-
Picture 19: Internal overheating due to overload
ers with a level of certainty that we have done everything pos-
High resistance on top connection to a bushing (Picture 18) can sible to insure the integrity of their transformers. There is nothing
cause conductor failure and/or internal bushing pressurization and worse to a test technician than a call form a customer asking why
ultimately bushing failure. Complete overheating (Picture 19) oc-
curs due to high resistance internal to the bushing or in many cases caught the problem and prevented the failure. It is the difference
today, overloading of the bushing beyond design limits. between a mediocre and an excellent testing program.
Are you missing the test point?
NETA has been connecting engineers, architects, facility managers, and users of electrical power equipment and systems
with NETA Accredited Companies since1972.
42 Electrical Testing, Inc. 49 Electrical Maintenance & Testing Inc. 57 Tidal Power Services, LLC
2671 Cedartown Hwy. 12342 Hancock St. 8184 Hwy. 44, Suite 105
Rome, GA 3016-6791 Carmel, IN 46032 Gonzales, LA 70737
(706) 234-7623 Fax: (706) 236-9028 (317) 853-6795 Fax: (317) 853-6799 (225) 644-8170 Fax: (225) 644-8215
info@emtesting.com darryn.kimbrough@tidalpowerservices.com
steve@electricaltestinginc.com www.emtesting.com
www.electricaltestinginc.com www.tidalpowerservices.com
Brian K. Borst Darryn Kimbrough
43 Nationwide Electrical Testing, Inc. 50 High Voltage Maintenance Corp. 58 Tidal Power Services, LLC
6050 Southard Trace 8320 Brookville Rd., #E
1056 Mosswood Dr.
Cumming, GA 30040 Indianapolis, IN 46239
Sulphur, LA 70663
(770) 667-1875 Fax: (770) 667-6578 (317) 322-2055 Fax: (317) 322-2056
(337) 558-5457 Fax: (337) 558-5305
shashi@n-e-t-inc.com www.hvmcorp.com steve.drake@tidalpowerservices.com
www.n-e-t-inc.com www.tidalpowerservices.com
Shashikant B. Bagle IOWA Steve Drake
Shermco Industries
ILLINOIS 51
2100 Dixon St., Suite C
MAINE
44 Dude Electrical Testing, LLC Des Moines, IA 50316 59 Electric Power Systems, Inc.
145 Tower Dr., Suite 9 (515) 263-8482 56 Bibber Pkwy., #1
Burr Ridge, IL 60527 lhamrick@shermco.com Brunswick, ME 04011
(815) 293-3388 Fax: (815) 293-3386 www.shermco.com (207) 837-6527
Lynn Hamrick www.eps-international.com
scott.dude@dudetesting.com
www.dudetesting.com 52 Shermco Industries 60 Three-C Electrical Co., Inc.
Scott Dude
796 11th St. 72 Sanford Drive
Marion, IA 52302 Gorham, ME 04038
45 Electric Power Systems, Inc.
(319) 377-3377 Fax: (319) 377-3399 (800) 649-6314 Fax: (207) 782-0162
23823 Andrew Rd.
lhamrick@shermco.com jim@three-c.com
Plainfield, IL 60585
www.shermco.com www.three-c.com
(815) 577-9515 Fax: (815) 577-9516
Lynn Hamrick Jim Cialdea
www.eps-international.com
86 Electrical Reliability Services 93 Longo Electrical-Mechanical, Inc. 100 A&F Electrical Testing, Inc.
1380 Greg St., Suite 217 One Harry Shupe Blvd., Box 511 80 Broad St., 5th Floor
Sparks, NV 89431 Wharton, NJ 07855 New York, NY 10004
(775) 746-8484 Fax: (775) 356-5488 (973) 537-0400 Fax: (973) 537-0404 (631) 584-5625 Fax: (631) 584-5720
www.electricalreliability.com jmlongo@elongo.com afelectricaltesting@afelectricaltesting.com
www.elongo.com www.afelectricaltesting.com
87 Hampton Tedder Technical Services Joe Longo Florence Chilton
4920 Alto Ave.
Las Vegas, NV 89115 94 M&L Power Systems, Inc. 101 American Electrical Testing Co., Inc.
(702) 452-9200 Fax: (702) 453-5412 109 White Oak Ln., Suite 82 76 Cain Dr.
www.hamptontedder.com Old Bridge, NJ 08857 Brentwood, NY 11717
Roger Cates (732) 679-1800 Fax: (732) 679-9326 (631) 617-5330 Fax: (631) 630-2292
milind@mlpower.com mschacker@aetco.us
NEW HAMPSHIRE www.mlpower.com www.99aetco.com
Milind Bagle Michael Schacker
88 Electric Power Systems, Inc.
915 Holt Ave., Unit 9 95 Scott Testing Inc. 102 Elemco Services, Inc.
Manchester, NH 03109 1698 5th St. 228 Merrick Rd.
(603) 657-7371 Fax: (603) 657-7370 Ewing, NJ 08638 Lynbrook, NY 11563
www.eps-international.com (609) 882-2400 Fax: (609) 882-5660 (631) 589-6343 Fax: (631) 589-6670
rsorbello@scotttesting.com courtney@elemco.com
NEW JERSEY www.scotttesting.com
Russ Sorbello
www.elemco.com
Courtney O’Brien
American Electrical Testing Co., Inc.
89
Trace Electrical Services 103 High Voltage Maintenance Corp.
50 Intervale Rd., Suite 1 96
Boonton, NJ 07005 & Testing, LLC 1250 Broadway, Suite 2300
(973) 316-1180 Fax: (781) 316-1181 293 Whitehead Rd. New York, NY 10001
jsomol@aetco.us Hamilton, NJ 08619 (718) 239-0359
www.99aetco.com (609) 588-8666 Fax: (609) 588-8667 www.hvmcorp.com
Jeff Somol jvasta@tracetesting.com
www.tracetesting.com 104 HMT, Inc.
Joseph Vasta 6268 Route 31
90
Eastern High Voltage Cicero, NY 13039
11A South Gold Dr. (315) 699-5563 Fax: (315) 699-5911
Robbinsville, NJ 08691-1606 NEW MEXICO jpertgen@hmt-electric.com
(609) 890-8300 Fax: (609) 588-8090 www.hmt-electric.com
joewilson@easternhighvoltage.com 97 Electric Power Systems, Inc.
8515 Cella Alameda NE, Suite A John Pertgen
www.easternhighvoltage.com
Joseph Wilson Albuquerque, NM 87113
(505) 792-7761 NORTH CAROLINA
High Energy Electrical Testing, Inc. www.eps-international.com ABM Electrical Power Solutions
91 105
515 S. Ocean Ave. 3600 Woodpark Blvd., Suite G
Seaside Park, NJ 08752
98 Electrical Reliability Services Charlotte, NC 28206
(732) 938-2275 Fax: (732) 938-2277 8500 Washington Pl. NE, Suite A-6 (704) 273-6257 Fax: (704) 598-9812
hinrg@comcast.net Albuquerque, NM 87113 ernest.goins@abm.com
www.highenergyelectric.com (505) 822-0237 Fax: (505) 822-0217 www.abm.com
Charles Blanchard www.electricalreliability.com Ernest Goins
92 Longo Electrical-Mechanical, Inc. NEW YORK 106 ABM Electrical Power Solutions
1625 Pennsylvania Ave. 5805 G Departure Dr.
Linden, NJ 07036 99 A&F Electrical Testing, Inc. Raleigh, NC 27616
(908) 925-2900 Fax: (908) 925-9427 80 Lake Ave. S., Suite 10 (919) 877-1008 Fax: (919) 501-7492
jmlongo@elongo.com Nesconset, NY 11767 www.abm.com
www.elongo.com (631) 584-5625 Fax: (631) 584-5720 Rob Parton
Joe Longo kchilton@afelectricaltesting.com
www.afelectricaltesting.com
Kevin Chilton
107 ELECT, P.C. 115 Electrical Reliability Services 123 Taurus Power & Controls, Inc.
7400-G Siemens Rd. 610 Executive Campus Dr. 9999 SW Avery St.
PO Box 2080 Westerville, OH 43082 Tualatin, OR 97062-9517
Wendell, NC 27591 (877) 468-6384 Fax: (614) 410-8420 (503) 692-9004 Fax: (503) 692-9273
(919) 365-9775 Fax: (919) 365-9789 info@electricalreliability.com robtaurus@tauruspower.com
btyndall@elect-pc.com www.electricalreliability.com www.tauruspower.com
www.elect-pc.com Rob Bulfinch
Barry W. Tyndall 116 High Voltage Maintenance Corp.
5100 Energy Dr. PENNSYLVANIA
108 Electric Power Systems, Inc. Dayton, OH 45414
(937) 278-0811 Fax: (937) 278-7791 124 ABM Electrical Power Solutions
319 US Hwy. 70 E, Unit E
www.hvmcorp.com 710 Thomson Park Dr.
Garner, NC 27529
Cranberry Township, PA 16066-6427
(919) 322-2670 (724) 772-4638 Fax: (724) 772-6003
www.eps-international.com 117 High Voltage Maintenance Corp.
7200 Industrial Park Blvd. william.mckenzie@abm.com
www.abm.com
109 Electrical Reliability Services Mentor, OH 44060
William (Pete) McKenzie
6135 Lakeview Road, Suite 500 (440) 951-2706 Fax: (440) 951-6798
Charlotte, NC 28269 www.hvmcorp.com 125 American Electrical Testing Co., Inc.
(704) 441-1497 Green Hills Commerce Center
www.electricalreliability.com
118 Power Services, LLC 5925 Tilghman St., Suite 200
998 Dimco Way, PO Box 750066 Allentown, PA 18104
110 Power Products & Solutions, Inc. Centerville, OH 45475 (215) 219-6800
12465 Grey Commercial Rd. (937) 439-9660 Fax: (937) 439-9611 jmunley@aetco.us
Midland, NC 28107 mkbeucler@aol.com www.99aetco.com
(704) 573-0420 x12 Mark Beucler Jonathan Munley
Fax: (704) 573-3693
119 Power Solutions Group, Ltd. 126 Burlington Electrical Testing Co., Inc.
ralph.patterson@powerproducts.biz 300 Cedar Ave.
670 Lakeview Plaza Blvd.
www.powerproducts.biz Croydon, PA 19021-6051
Columbus, OH 43085
Ralph Patterson (215) 826-9400 x221
(614) 310-8018
sspohn@powersolutionsgroup.com Fax: (215) 826-0964
111 Power Test, Inc. waltc@betest.com
2200 Hwy. 49 www.powersolutionsgroup.com
www.betest.com
Harrisburg, NC 28075 Stuart Spohn
Walter P. Cleary
(704) 200-8311 Fax: (704) 455-7909
rich@powertestinc.com 120 Power Solutions Group, Ltd. 127 Electric Power Systems, Inc.
425 W. Kerr Rd. 1090 Montour West Industrial Blvd.
www.powertestinc.com
Richard Walker Tipp City, OH 45371 Coraopolis, PA 15108
(937) 506-8444 Fax: (937) 506-8434 (412) 276-4559
bwilloughby@powersolutionsgroup.com
OHIO www.powersolutionsgroup.com
www.eps-international.com
112 CE Power Solutions, LLC Barry Willoughby 128 Electric Power Systems, Inc.
4500 W. Mitchell Ave. 2495 Boulevard of the Generals
Cincinnati, OH 45232 OKLAHOMA Norristown, PA 19403
(513) 563-6150 Fax: (513) 563-6120 (610) 630-0286
121 Shermco Industries
info@cepowersol.net www.eps-international.com
1357 N. 108th E. Ave.
Rhonda Harris
Tulsa, OK 74116 EnerG Test
129
(918) 234-2300
113 DYMAX Service, Inc. 204 Gale Lane, Bldg. 2 – 2nd Floor
jharrison@shermco.com Kennett Square, PA 19348
4213 Kropf Ave.
www.shermco.com
Canton, OH 44706 (484) 731-0200 Fax: (484) 713-0209
Jim Harrison
(330) 484-6801 Fax: (740) 333-1271 kbleiler@energtest.com
www.dymaxservice.com www.energtest.com
Gary Swank OREGON Katie Bleiler
122 Electrical Reliability Services
114 Electric Power Systems, Inc. 130 High Voltage Maintenance Corp.
4099 SE International Way, Suite 201
2601 Center Rd., #101 355 Vista Park Dr.
Milwaukie, OR 97222-8853
Hinckley, OH 44233 Pittsburgh, PA 15205-1206
(503) 653-6781 Fax: (503) 659-9733
(330) 460-3706 Fax: (330) 460-3708 (412) 747-0550 Fax: (412) 747-0554
www.electricalreliability.com
www.eps-international.com www.hvmcorp.com
131 Longo Electrical-Mechanical, Inc. 138 Power & Generation Testing, Inc. 146 Saber Power Systems
1400 F Adams Road 480 Cave Rd. 9841 Saber Power Lane
Bensalem, PA 19020 Nashville, TN 37210 Rosharon, TX 77583
(215) 638-1333 Fax: (215) 638-1366 (615) 882-9455 Fax: (615) 882-9591 (713) 222-9102
jmlongo@elongo.com mose@pgti.net info@saberpower.com
www.elongo.com www.pgti.net www.saberpower.com
Joe Longo Mose Ramieh Ron Taylor
VIRGINIA 162 Taurus Power & Controls, Inc. 168 Energis High Voltage
6617 S. 193rd Pl., Suite P104 Resources, Inc.
154 ABM Electrical Power Solutions Kent, WA 98032 1361 Glory Rd.
814 Greenbrier Cir., Suite E (425) 656-4170 Fax: (425) 656-4172 Green Bay, WI 54304
Chesapeake, VA 23320 jiml@tauruspower.com (920) 632-7929 Fax: (920) 632-7928
(757) 548-5690 Fax: (757) 548-5417 www.tauruspower.com info@energisinc.com
www.abm.com Jim Lightner www.energisinc.com
Mark Anthony Gaughan, III Mick Petzold
163 Western Electrical Services, Inc.
155 Electric Power Systems, Inc. 14311 29th St. East 169 High Voltage Maintenance Corp.
827 Union St. Sumner, WA 98390 3000 S. Calhoun Rd.
Salem, VA 24153 (253) 891-1995 Fax: (253) 891-1511 New Berlin, WI 53151
(540) 375-0084 Fax: (540) 375-0094 dhook@westernelectricalservices.com (262) 784-3660 Fax: (262) 784-5124
www.eps-international.com www.westernelectricalservices.com www.hvmcorp.com
156 Potomac Testing, Inc. Dan Hook
11179 Hopson Rd., Suite 5
Ashland, VA 23005 164 Western Electrical Services, Inc.
(804) 798-7334 Fax: (804) 798-7456 4510 NE 68th Dr., Suite 122
www.potomactesting.com Vancouver, WA 98661
(888) 395-2021 Fax: (253) 891-1511
157 Reuter & Hanney, Inc. tasciutto@westernelectricalservices.com
4270-I Henninger Ct. www.westernelectricalservices.com
Chantilly, VA 20151 Tony Asciutto
(703) 263-7163 Fax: (703) 263-1478
www.reuterhanney.com WISCONSIN
WASHINGTON 165 CE Power Solutions of
Wisconsin, LLC
158 Electrical Reliability Services 3100 East Enterprise Ave.
2222 West Valley Hwy. N., Suite 160 Appleton, WI 54913
Auburn, WA 98001 (920) 968-0281 Fax: (920) 968-0282
(253) 736-6010 Fax: (253) 736-6015 rob.fulton@cepower.net
www.electricalreliability.com Rob Fulton
procedures, testing, and requirements, not only for commissioning new equipment but for testing the reliability and performance of
existing equipment.
CERTIFICATION
serviceability is the prerequisite that individuals performing the tests be capable of conducting the tests in a safe manner and with com-
plete knowledge of the hazards involved. They must also evaluate the test data and make an informed judgment on the continued ser-
recognition of four levels of competency within the electrical testing industry in accordance with ANSI/NETA ETT-2000 Standard for
An independent overview is the only method of determining the long-term usage of electrical apparatus and its suitability for the
intended purpose. NETA Accredited Companies best support the interest of the owner, as the objectivity and competency of the testing
electrical testing associa-tion dedicated to setting world standards in electrical maintenance and acceptance testing. Hiring a NETA Ac-
credited Company assures the customer that:
• The NETA Technician has broad-based knowledge — this person is trained to inspect, test, maintain, and calibrate all types of
electrical equipment in all types of industries.
• NETA Technicians meet stringent educational and experience requirements in accordance with ANSI/NETA ETT-2000 Standard for