TEMP. RISE Ө= 0.5000 INITIAL TEMP. Ө₀= 0.

5000

FLC SETTING Iᵣ= 0.3 FLC SETTING Iᵣ= 0.3


TIME CONST T 600 TIME CONST T 600
O.L.F k= 1.05 O.L.F k= 1.05
N. SEQ. F K₂= 4.9 N. SEQ. F K₂= 4.9

INJECTION Imax= 1 INJECTION Imax= 1.8


INJECTION I₂= 0.1 INJECTION I₂= 0
ELAPSED TIME t(sec)= 2
TRIP TIME t(sec)= 23.4372 TEMP RISE ӨA= 0.1342
WITH INITIAL TEMP 50 %
FOR I > 1.05 x Iᵣ

CONSIDER AMBIENT TEMP 50 ⁰C COOLING CONST 7200


INITIAL TEMP 1.00
FINAL TEMP 0.74
REQUIRED TIME 36.1326 MIN
INITIAL TEMP. Ө₀= 0.5000 INITIAL TEMP. Ө₀=

FLC SETTING Iᵣ= 0.3 FLC SETTING Iᵣ=


TIME CONST T 600 TIME CONST T
O.L.F k= 1.05 O.L.F k=
N. SEQ. F K₂= 4.9 N. SEQ. F K₂=

INJECTION Imax= 1.8 INJECTION Imax=


INJECTION I₂= 0 INJECTION I₂=
STARTING TIME t(sec)= 2 ELAPSED TIME t(sec)=
TEMP RISE ӨB= 0.0537 TEMP RISE ӨB=

BACKGROUN CALCULATION FOR I < 1.05 x Iᵣ


DURING STARTING DURING NORMAL

TEMPERATURE AFTER 600 sec = 0.7830


WITH INITIAL TEMP & 50 %
STARTING TIME 2 sec
0.5000

0.3
600
1.05
4.9

0.27
0
600
0.2293